Data sheet

Geometry:
          Length of north and south facade: 12.5 m
          Length of west and east facade: 10.0 m
          Height (without roof): 10.0 m
          Number of floors: 2
          Height of roof: 2.0
          Roof ridge: in north-south-direction
          Deviation from south direction (west positive): 0.0 °

          Ground area: 125.0 m²


          Useful area: 225.0 m²
          Volume total: 1250.0 m³
          Air volume: 1100.0 m³
          Facade north resp. south: 125.0 m²
          Facade east resp. west: 100.0 m²
          Surface-to-volume value: 0.5 1/m

Insulation:
          U values of the walls:
                    north: 0.51 W/(m² K)
                    south: 0.30 W/(m² K)
                    east: 0.20 W/(m² K)
                    west: 0.32 W/(m² K)
          Absorption coefficient of the walls: 0.50
          Roof:
                    Towards: outside air
                    U value: 0.20 W/(m² K)
          Lower floor:
                    Towards: soil (with border insulation)
                    U value: 0.63 W/(m² K)
          Door (north facade):
                    Area: 0.7 m²
                    U value: 1.50 W/(m² K)
          Wärmebrücken: ignore heat bridges

Building:
          Interior temperature: 19.0 °C
          Limit of overheating: 26.0 °C
          Ventilation:
                    Natural ventilation (infiltration): 0.60 1/h
                    Mechanical ventilation: 0.20 1/h
                    Heat recovery (only mech. ventilation): 50 %
          efficiency factor of air conditioning: 2.5 kWhcool / kWhelectr
          Internal gains: 25.0 kWh/(m² a)
          Kind of indoor walls: heavy construction
          Kind of outdoor walls: light construction

Climate:
          Climate station: Budapest (Magyarország)

Windows:
          North:
                    Windows area: 68.8 m²
                    Fraction of windows area at the facade: 55.0 %
                    Kind of windows: heat protection triple glazing (U = 0.7 W/(m² K))
                    U value glazing: 0.70 W/(m² K)
                    U value frame: 0.70 W/(m² K)
                    g value glazing: 0.51
                    Fraction of frame: 20.0 %
                    Shading: 20.0 %
          South:
                    Window area: 50.0 m²
                    Fraction of windows area at the facade: 40.0 %
                    Kind of windows: heat protection triple glazing (U = 0.7 W/(m² K))
                    U value glazing: 0.70 W/(m² K)
                    U value frame: 0.70 W/(m² K)
                    g value glazing: 0.51
                    Fraction of frame: 20.0 %
                    Shading: 20.0 %
          East:
                    Window area: 22.0 m²
                    Fraction of windows area at the facade: 22.0 %
                    Kind of windows: heat protection triple glazing (U = 0.7 W/(m² K))
                    U value glazing: 0.70 W/(m² K)
                    U value frame: 0.70 W/(m² K)
                    g value glazing: 0.51
                    Fraction of frame: 20.0 %
                    Shading: 20.0 %
          West:
                    Window area: 5.0 m²
                    Fraction of windows area at the facade: 5.0 %
                    Kind of windows: heat protection triple glazing (U = 0.7 W/(m² K))
                    U value glazing: 0.70 W/(m² K)
                    U value frame: 0.70 W/(m² K)
                    g value glazing: 0.51
                    Fraction of frame: 20.0 %
                    Shading: 20.0 %

Energy:
          Heating system: soil heat pump, buffer storage and distribution
      inside the thermal zone
          Heat transfer / system temperature: radiators (outside walls), thermostatic valves
      (layout temperature: 1K), system temperature:
      55/45°C
          Source of energy: electricity
CASAnova
________________________________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________

Output: Overview

Heat energy and cooling demand:


Heat energy demand Cooling demand
in kWh/m² in kWh/m²
          ______________________________________________________________________________

          January 26.3 0.0


          February 18.8 0.0
          March 10.4 0.0
          April 2.9 0.2
          May 0.2 2.8
          June 0.0 5.2
          July 0.0 7.6
          August 0.0 6.8
          September 0.1 1.3
          October 4.6 0.5
          November 17.1 0.0
          December 24.8 0.0
          ______________________________________________________________________________

          Yearly sum 105.0 24.5

Heating and cooling hours:


Heating hours Zero energy hours Cooling hours
in hours in hours in hours
          ______________________________________________________________________________

          January 744 0 0
          February 672 0 0
          March 710 34 0
          April 437 273 10
          May 143 371 230
          June 25 354 341
          July 0 127 617
          August 5 299 440
          September 59 522 139
          October 484 226 34
          November 691 29 0
          December 744 0 0
          ______________________________________________________________________________

          Sum (in hours) 4714 2235 1811


          Sum (in %) 53.8 25.5 20.7
CASAnova
________________________________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________

Output: Climate and building data

Climate data:
Mean temperature Maximum temperature Minimum temperature
in °C in °C in °C
          ______________________________________________________________________________

          January -0.6 13.4 -16.2


          February 1.1 15.6 -8.7
          March 6.1 19.3 -4.5
          April 10.6 23.7 -2.7
          May 15.6 30.8 0.7
          June 18.9 32.6 6.6
          July 20.6 31.9 9.9
          August 20.6 34.3 7.6
          September 16.7 25.3 7.2
          October 10.6 27.2 -2.5
          November 3.9 19.4 -9.1
          December 1.1 11.4 -11.5
          ______________________________________________________________________________

          Yearly mean 10.5

Building data:
          Mean U value: 0.43 W/(m² K)
          Specific transmission losses: 315.0 W/K
          Specific ventilation losses: 275.9 W/K
          Sum specific losses: 579.6 W/K
          Thermal inertia: 25.2 hours
          Maximum heating load: 18.6 kW
          Maximum specific heating load: 82.7 W/m²
          Maximum cooling load: 16.0 kW
          Maximum specific cooling load: 71.0 W/m²
          Limit temperature for heating: 17.8°C
          Effective heating days: 276 Tage
CASAnova
________________________________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________

Output: Heat balance

Specific (per m² useful area):

Transm. Ventil. Internal Solar Usability Heat energy


losses losses Gains Gains factor demand
in kWh/m² in kWh/m² in kWh/m² in kWh/m² in kWh/m²
          ______________________________________________________________________________

          January 16.6 17.9 2.1 6.1 0.98 26.3


          February 13.7 14.7 1.8 7.8 0.95 18.8
          March 10.9 11.8 1.8 10.5 0.86 10.4
          April 6.9 7.4 1.3 10.1 0.63 2.9
          May 2.9 3.1 0.6 5.2 0.28 0.2
          June 0.1 0.1 0.0 0.1 0.01 0.0
          July 0.0 0.0 0.0 0.0 0.00 0.0
          August 0.0 0.0 0.0 0.0 0.00 0.0
          September 1.9 2.0 0.5 3.4 0.23 0.1
          October 7.1 7.7 1.6 8.6 0.75 4.6
          November 12.4 13.3 2.0 6.7 0.95 17.1
          December 15.2 16.3 2.1 4.7 0.98 24.8
          ______________________________________________________________________________

          Yearly sum 87.5 94.4 13.8 63.2 105.0

Absolute (total building):


Transm. Ventil. Internal Solar Usability Heat energy
losses losses Gains Gains factor demand
in kWh in kWh in kWh in kWh in kWh
          ______________________________________________________________________________

          January 3732 4023 468 1377 0.98 5910


          February 3076 3316 412 1744 0.95 4237
          March 2458 2650 411 2367 0.86 2330
          April 1548 1669 293 2272 0.63 651
          May 646 697 132 1173 0.28 38
          June 17 18 3 32 0.01 0
          July 0 0 0 0 0.00 0
          August 0 0 0 0 0.00 0
          September 425 459 106 762 0.23 16
          October 1597 1721 359 1926 0.75 1033
          November 2786 3003 441 1508 0.95 3840
          December 3411 3677 470 1049 0.98 5569
          ______________________________________________________________________________
          Yearly sum 19698 21233 3096 14210 23625
CASAnova
________________________________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________

Output: Cooling balance

Cooling demand and overheating:

Cooling demand Cooling demand Mean Cooling degree


specific absolute overheating hours
in kWh/m² in kWh in hours/day in Kh
          ______________________________________________________________________________

          January 0.0 0 0.0 0.0


          February 0.0 0 0.0 0.0
          March 0.0 0 0.0 0.0
          April 0.2 34 0.3 11.9
          May 2.8 637 7.4 746.8
          June 5.2 1173 11.4 1639.2
          July 7.6 1721 19.9 2456.5
          August 6.8 1540 14.2 2401.5
          September 1.3 290 4.6 157.2
          October 0.5 107 1.1 38.7
          November 0.0 0 0.0 0.0
          December 0.0 0 0.0 0.0
          ______________________________________________________________________________

          Yearly sum 24.5 5502 7451.8


CASAnova
________________________________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________

Output: Primary and end energy demand for heating

Energy demand of the heating system:

          Heat:
                    Heat energy demand: 105.0 kWh/(m² a)
                    Losses of the heat storage: 0.2 kWh/(m² a)
                    Heat losses from the distribution: 1.6 kWh/(m² a)
                    Looses at the transmission to the rooms: 1.1 kWh/(m² a)
                    Expense number of heat generation: 0.27

                    End energy demand electricity: 29.1 kWh/(m² a)

          Auxiliary energy (electricity):


                    Auxiliary energy for heat generation: 1.1 kWh/(m² a)
                    Auxiliary energy for heat storage: 0.3 kWh/(m² a)
                    Auxiliary energy for heat distribution: 1.0 kWh/(m² a)

                    End energy demand auxiliary energy (electricity): 2.4 kWh/(m² a)

          Primary energy factor electricity: 3.0


          Primary energy demand electricity: 94.6 kWh/(m² a)

End energy demand Primary energy demand


electricity electricity
in kWh/m² in kWh/m²
          ______________________________________________________________________________

          January 7.9 23.7


          February 5.7 17.0
          March 3.1 9.3
          April 0.9 2.6
          May 0.1 0.2
          June 0.0 0.0
          July 0.0 0.0
          August 0.0 0.0
          September 0.0 0.1
          October 1.4 4.1
          November 5.1 15.4
          December 7.4 22.3
          ______________________________________________________________________________

          Yearly sum 31.5 94.6


CASAnova
________________________________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________

Output: Primary and end energy demand for cooling

Energy demand of the cooling system:

          Efficiency factor of the air conditioning: 2.5 kWh cooling/ kWh electricity

Cooling demand End energy demand for cooling Primary energy demand
in kWh/m² in kWh/m² in kWh/m²
          ______________________________________________________________________________

          January 0.0 0.0 0.0


          February 0.0 0.0 0.0
          March 0.0 0.0 0.0
          April 0.2 0.1 0.2
          May 2.8 1.1 3.4
          June 5.2 2.1 6.3
          July 7.6 3.1 9.2
          August 6.8 2.7 8.2
          September 1.3 0.5 1.5
          October 0.5 0.2 0.6
          November 0.0 0.0 0.0
          December 0.0 0.0 0.0
          ______________________________________________________________________________

          Yearly sum 24.5 9.8 29.3