Data sheet
Geometry:
Length of north and south facade: 12.5 m
Length of west and east facade: 10.0 m
Height (without roof): 10.0 m
Number of floors: 2
Height of roof: 2.0
Roof ridge: in north-south-direction
Deviation from south direction (west positive): 0.0 °
Insulation:
U values of the walls:
north: 0.51 W/(m² K)
south: 0.30 W/(m² K)
east: 0.20 W/(m² K)
west: 0.32 W/(m² K)
Absorption coefficient of the walls: 0.50
Roof:
Towards: outside air
U value: 0.20 W/(m² K)
Lower floor:
Towards: soil (with border insulation)
U value: 0.63 W/(m² K)
Door (north facade):
Area: 0.7 m²
U value: 1.50 W/(m² K)
Wärmebrücken: ignore heat bridges
Building:
Interior temperature: 19.0 °C
Limit of overheating: 26.0 °C
Ventilation:
Natural ventilation (infiltration): 0.60 1/h
Mechanical ventilation: 0.20 1/h
Heat recovery (only mech. ventilation): 50 %
efficiency factor of air conditioning: 2.5 kWhcool / kWhelectr
Internal gains: 25.0 kWh/(m² a)
Kind of indoor walls: heavy construction
Kind of outdoor walls: light construction
Climate:
Climate station: Budapest (Magyarország)
Windows:
North:
Windows area: 68.8 m²
Fraction of windows area at the facade: 55.0 %
Kind of windows: heat protection triple glazing (U = 0.7 W/(m² K))
U value glazing: 0.70 W/(m² K)
U value frame: 0.70 W/(m² K)
g value glazing: 0.51
Fraction of frame: 20.0 %
Shading: 20.0 %
South:
Window area: 50.0 m²
Fraction of windows area at the facade: 40.0 %
Kind of windows: heat protection triple glazing (U = 0.7 W/(m² K))
U value glazing: 0.70 W/(m² K)
U value frame: 0.70 W/(m² K)
g value glazing: 0.51
Fraction of frame: 20.0 %
Shading: 20.0 %
East:
Window area: 22.0 m²
Fraction of windows area at the facade: 22.0 %
Kind of windows: heat protection triple glazing (U = 0.7 W/(m² K))
U value glazing: 0.70 W/(m² K)
U value frame: 0.70 W/(m² K)
g value glazing: 0.51
Fraction of frame: 20.0 %
Shading: 20.0 %
West:
Window area: 5.0 m²
Fraction of windows area at the facade: 5.0 %
Kind of windows: heat protection triple glazing (U = 0.7 W/(m² K))
U value glazing: 0.70 W/(m² K)
U value frame: 0.70 W/(m² K)
g value glazing: 0.51
Fraction of frame: 20.0 %
Shading: 20.0 %
Energy:
Heating system: soil heat pump, buffer storage and distribution
inside the thermal zone
Heat transfer / system temperature: radiators (outside walls), thermostatic valves
(layout temperature: 1K), system temperature:
55/45°C
Source of energy: electricity
CASAnova
________________________________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________
Output: Overview
January 744 0 0
February 672 0 0
March 710 34 0
April 437 273 10
May 143 371 230
June 25 354 341
July 0 127 617
August 5 299 440
September 59 522 139
October 484 226 34
November 691 29 0
December 744 0 0
______________________________________________________________________________
Climate data:
Mean temperature Maximum temperature Minimum temperature
in °C in °C in °C
______________________________________________________________________________
Building data:
Mean U value: 0.43 W/(m² K)
Specific transmission losses: 315.0 W/K
Specific ventilation losses: 275.9 W/K
Sum specific losses: 579.6 W/K
Thermal inertia: 25.2 hours
Maximum heating load: 18.6 kW
Maximum specific heating load: 82.7 W/m²
Maximum cooling load: 16.0 kW
Maximum specific cooling load: 71.0 W/m²
Limit temperature for heating: 17.8°C
Effective heating days: 276 Tage
CASAnova
________________________________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________
Heat:
Heat energy demand: 105.0 kWh/(m² a)
Losses of the heat storage: 0.2 kWh/(m² a)
Heat losses from the distribution: 1.6 kWh/(m² a)
Looses at the transmission to the rooms: 1.1 kWh/(m² a)
Expense number of heat generation: 0.27
Efficiency factor of the air conditioning: 2.5 kWh cooling/ kWh electricity
Cooling demand End energy demand for cooling Primary energy demand
in kWh/m² in kWh/m² in kWh/m²
______________________________________________________________________________