Operation: Remote Terminal Unit Connections and Settings Switch 560NUS04

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

ABB RTU560

Remote Terminal Unit


Connections and Settings
Switch 560NUS04

Application, characteristics and technical data have Operation


to be taken from the hardware data sheet
The 560NUS04 is a 10/100 Mbps auto-
560NUS04 R0001 1KGT 150 630 negotiating unmanaged Ethernet switch.

The figure below illustrates the position of all


jumpers, which are described in the following
section.

Fig. 1: Board layout and setting positions 560NUS04

Jumper X210 is used to switch between internal


(backplane) and external power supply of the mod-
ule 560NUS04. The power supply voltage is 5 V. 1-2 2-3
For external power connection a power supply with X210 Power supply 5 V Power supply 5 V
galvanic isolation has to be used. 5 V from backplane from pin z22
Attention: For subrack type 560CSR01 X210 Table 1: Power Supply Source
must always be in 1-2 position. An ex-
ternal power supply connection is not
possible.

Doc.-No.: 1KGT 150 631 V001 1 1


ABB
Connections and Settings 560NUS04 RTU560

Mounting in rack 23ET24 and 560SFR02 Alarm Signaling


The connection of the alarm signal is done by row The 560NUS04 is equipped with an Alarm relay
22 up to row 32 of the DIN-F socket connector us- indicating a malfunction of the switch. Contacts
ing a 18-pole sub-connector with crimp snap-in con- MK and AK are connected in alarm state while
tacts. The position of the columns and rows is contacts MK and RK are connected during nor-
shown in Fig. 2. The connection is done according mal operation. In unpowered state MK and AK
to Table 3. are connected. Alarm Signaling can be disabled
by jumper X207.
d b z
22 Attention: For rack type 560CSR01 alarm sig-
naling is not possible and jumper
24
X207 must always be mounted in
26 2-3 position.
28
30
32 1-2 2-3
X207 Alarm signaling Alarm signaling
Fig. 2: 18-pole sub connector Alarm enabled disabled
Table 2: Alarm Signaling
Mounting in rack 23TP22 and 560MPR01/03
The 18 connection points of the DIN-F sub-
connector are routed through the backplane to plug-
in sockets. The connection is done according to
Table 3.

23TP22/560MPR01/03 23ET24/560SFR02 Identification Description


1 z32
2 b32
3 d32
4 z30
5 b30
6 d30 GND External power ground
7 z28 AK Alarm contact
8 b28 MK Alarm contact
9 d28 RK Alarm contact
10 z26
11 b26
12 d26
13 z24
14 b24
15 d24
16 z22 +5 V DC External power supply
17
18 b22
19 d22

Table 3: Rack terminal connection 560NUS04

2 Doc.-No.: 1KGT 150 631 V001 1


ABB
RTU560 Connections and Settings 560NUS04

Note:
We reserve the right to make technical changes or modify the con-tents of this document without prior notice.
With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsi-
bility whatsoever for potential errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any re-
production, disclosure to third parties or utilization of its contents - in whole or in parts - is forbidden without
prior written consent of ABB AG.

Copyright© 2011 ABB


All rights reserved

Doc. -No.: 1KGT 150 631 V001 1 3