RTU560

Connections and Settings


Communication Unit 560CMU02 R0001

Application, characteristics and technical data The connection to the RTU560 serial peripheral
have to be taken from the hardware data sheet: bus is done via 48 pole DIN-F socket connector
according to DIN 41612. The serial peripheral bus
is not available on the RJ45 connectors on the
560CMU02 R0001 1KGT 150 595 front plate.

CPA Interface
Operation The CPA interface is available on the RJ45
The communication unit 560CMU02 R0001 is one connector on the front plate. It can interface
of the CMU boards (CMU = communication unit) RS485 signals. The RS485 bus mit be terminated
of the remote terminal unit. The 560CMU02 on both sides by a 1 k resistor. The termination
R0001 controls process events and on the CMU side is already done on board.
communications with control centers and local
The settings have to be done by RTUtil560
MMI systems via up to three serial interfaces configuration tool. The signals are used according
(CP1, CP2, CPA) and the Ethernet
to Fig. 2:
10BaseT/100BaseT LAN interface (E).

CPA Interface RS485 Mode

Pin Signal

1 - Not used

2 TA Data -
RJ45

3 TB Data + 1

4 - Not used 8

5 GND Signal Ground


Jack
6 -

7 - Not used

8 -

Shield Connected with housing

Fig. 2: CPA interface RS485 Mode

CP1 and CP2 Interface


The CP1 and CP2 interfaces USART (universal
Fig. 1: Block diagram 560CMU02 R0001
synchronous/asynchronous receiver/transmitter)
are available on the RJ45 connectors on the front
The module has one jumper x_ETH (see Fig. 5
plate. They can interface RS232C signals. On
and 6), to force the IP-address of the Ethernet both interfaces different UART based protocol
interface to a default value. If the jumper is set to
types can be used.
Position 1-2 after a restart, the Ethernet interface
will be initialized with the IP-address 192.168.0.1 The signals are used according to Fig. 3:
(Subnet mask 255.255.255.0, Gateway
192.168.0.20).

Doc.-No.: 1KGT 150 596 V005 1 1


RTU560
Connections and Settings 560CMU02 R0001
Signalling
CP1 and CP2 Interface RS232C Mode
The LEDs of the 560CMU02 R0001 are under
software control (exception T and R). The
Pin Signal Input/Output definition and operation of the LED “ERR" must
be taken from the release specific function
1 DCD Input description. The LEDs “TxD” and “RxD” are
directly connected to the receiver / transmitter of
2 RxD Input RJ45
the communication line. The LEDs “A" and “L" are
1 directly connected to the Ethernet controller.
3 TxD Output
8
4 DTR Output LED Colour Meaning
Jack
Err red Warning / Error
5 GND -
TxD (3x) green Transmit data (CP1, 2, A)
7 RTS Output RxD (3x) green Receive data (CP1, 2, A)
A (1x) green Ethernet Activity
8 CTS Input
L (1x) green Ethernet Link
Shield Connected with housing Table 1: Meaning of LEDs
Fig. 3: CP1- and CP2 Interface RS232C Mode
Firmware Version
Ethernet Interface The actual firmware version will be delivered on a
CompactFlash memory card. A new firmware file
The Ethernet interfaces on the Front plate
can be loaded with the Web diagnostic tool into
supports different functions.
the removable CompactFlash memory card.
Webserver-diagnostic with download of
Changing of CompactFlash memory cards is
configuration files and firmware
possible.
Protocol IEC 60870-5-104, DNP3, …
Integrated HMI Settings
The signals are used according to Fig. 4. The settings of the hardware and for operation of
the communication interface of the 560CMU02
R0001 have to be taken with the RTUtil560
Ethernet Interface E configuration tool.
The settings of the communication parameters
Pin Signal Input/Output
can be done in the “Hardware Tree" of the
1 TD + Output RTUtil560.
For RTU I/O bus protocol the settings are
2 TD - Output RJ45 predefined. For other protocols the parameters
3 RD + Input
have to be defined according to the protocol type.
1

4 Not used 8

5
Jack
6 RD - Input

7 Not used

Shield Connected with housing

Fig. 4: Ethernet Interface E

Doc.-No.: 1KGT 150 596 V005 1 2


RTU560
Connections and Settings 560CMU02 R0001

The following parameters have to be defined for The settings of the Ethernet interface are
all protocols:
node name
Baudrate: 50 to 19 200 baud
IP address
Modem control:
Subnet mask
Direct link (TxD/RxD only)
Default gateway
WT link full duplex (RTS/CTS handshake)
connected stations
WT link half duplex (RTS/CTS
number of the host interface.
handshake)
WT link half duplex (RTS/DCD
handshake)
Dial up (external modem DCD
handshake)
Loop switch unit DSTC 3002 (RP570/71
Host interface only)
Link with collision avoidance (TxD, RxD,
DCD, without handshake (DNP 3 only)

Fig. 5: Jumper Position

Doc.-No.: 1KGT 150 596 V005 1 3


RTU560
Connections and Settings
Communication Unit 560CMU02 R0001

Fig. 6: Use of jumper x_ETH

Note:
We reserve the right to make technical changes or modify the contents
of this document without prior notice. With regard to purchase orders,
the agreed particulars shall prevail. ABB AG does not accept any
esponsibility whatsoever for potential errors or possible lack of
information in this document.

We reserve all rights in this document and in the subject matter and
illustrations contained therein. Any reproduction, disclosure to third
parties or utilization of its contents - in whole or in parts –is forbidden
without prior written consent of ABB AG.

Copyright© 2011 ABB


All rights reserved

Doc.-No.: 1KGT 150 596 V005 1 4

You might also like