Professional Documents
Culture Documents
0 - Script Very Important For Lecture
0 - Script Very Important For Lecture
Course of studies
Electrical Engineering and Information Technology
VGU 2017/EMA1/Lä1-Titel
Contents of the Lecture Fundamentals of Power Engineering
Chapter - Electrical Machines
___________________________________________________________
2 D.C. Machines
2.1 Design and Principle of Operation of D.C. Machines
2.2 Air-Gap Field
2.3 Commutation
2.4 Balance of Power, Torque Creation and Induced Voltage
2.5 Circuits of D.C. Machines and Terminal Markings
2.6 Operational Performance of D.C. Machines
2.6.1 Generating Operation
2.6.2 Motor Operation
2.6.2.1 Speed Control of D.C. Machines
2.6.2.2 Starting of D.C. Machines
2.6.2.3 Braking of D.C. Machines
3 Transformers
3.1 Single-Phase Transformers
3.1.1 Design and Principle of Operation of Single-Phase Transformers
3.1.2 Ideal and Real Transformer
3.1.3 Equivalent Circuit and Phasor Diagram of Single-Phase Transformers
3.2 Operating Conditions of Single-Phase Transformers
3.2.1 The Transformer in No-Load Operation
3.2.2 The Transformer in Short-Circuit Operation
3.2.3 The Change of Voltage under Rated Operation
3.2.4 Losses, Balancing of Power and Efficiency
3.2.5 Parallel Operation of Single-Phase Transformers
3.3 Autotransformers
3.4 Three-Phase Transformers
3.4.1 Design of Three-Phase Transformers
3.4.2 Circuits and Markings of Three-Phase Transformers
3.4.3 Vector Groups of Three-Phase Transformers
3.4.4 Parallel Operation of Three-Phase Transformers
Fitzgerald, A. E.
Electric Machinery, 2002
ISBN 0-07-366009-4
Dale R. Patrick
Rotating Electrical Machines and Power Systems, 1996
ISBN 0-88173-239-7
Rajput, R. K.
A Textbook of Electrical Machines, 2006
ISBNM-10: 8170088593
References (German)
Fundamentals:
Fischer, R. Elektrische Maschinen, Carl Hanser Verlag München
Application:
Stölting, H.-D. Handbuch elektrischer Kleinantriebe,
Kallenbach, E. Carl Hanser Verlag München
Mechanical Energy
GENERATOR
MOTOR
Mechanical Energy
Important relations:
B H Vs/m² - material equation of the magnetic field
flux tube
VGU 2021/EMA1/Lä4_General_Fundamentals
B ferromagnetic: iron, alloys;
0 Nonlinear
and of
technical
relevance
ferrimagnetic: ferrite;0
partielle Hysteresekurve -
- partiel hysteresis loop
Coils were applicated for reactors in power transmission, in transformers and electric
machines, smoothing reactors in power electronics, in relays and filters, ...
Standards exist for transformers, reactors and electric machines (e. g. in Germany DIN VDE
standards 0530 and 0532 or international standards EU and IEC)
VGU 2017/EMA1/Lä5_magnetic_materials
Field Distribution (examples)
VGU 2017/EMA1/Lä6_field_analogies
1.3 Ampere´s law
Hds
s
current linkage
Examples of current linkages:
a) picture above: = I1 + I2 – I3 + I4
=I*N
c) transformer:
(I N I N )
B H 1 1 2 2
l
m
A( I N I N )
Φ BA 1 1 2 2 Θ
l R
m m
B B
Θ IN H FelFe H lll lFe ll
length of the air gap – ll Fe l
IN
B with lFe >ll and Fe>>l
lFe ll
Fe l
IN A Θ
Φ BA l
l R
l m
VGU 2021/EMA1/Lä7_amperes_law
1.4 The Faraday´s Law and the Origin of Force
The Faraday´s law describes the relation between a time–dependent magnetic field and the elec-
tric field. (induction, induced voltage)
e N dΦ
dt
e (v B)dl
l
F I (dl B)
l
di 1
C
u Ri uL u idt
dt
VGU 2021/EMA1/Lä8_induction_force
Circuit Generator - Load :
Erzeuger: UI 0 Verbraucher: UI 0
= Pab / Pzu
VGU 2021/EMA1/Lä9_arrows
1.6 Phasor Diagram and Locus Diagram
The phasor diagram is the symbolic representation of sinusiodal quantities of the same
frequency. Therefore the use of nonrotating phasor is sufficient.
Rotating phasor
The character of a phasor is an underlined
letter to destinguish from r.m.s. value.
e. g. I = Ie ji
Example:
VGU 2021/EMA1/Lä10_phasors
Locus Diagram
The locus diagram shows the movement of the phasor in the complex plane as function of
another parameter.
VGU 2011/EMA1/Lä11_locus_diagram
1.7 Classification of Electric Machines
TRANSFORMERS --- D.C. MACHINES--- A.C. - AND THREE-PHASE MACHINES LINEAR MOTORS
1832 Pixii, development of a generator for a two-pulse direct current with permanent
magnet
1850 First separately excited d.c. machine
1860 Pacinotti, application of a ring winding for the rotor of a d.c. machine
1872 v. Hefener-Alteneck, invention of the drum-type armature, which is used in
modern d.c. machines until now
1882/1884 The first power- station generators in New York and Berlin with d.c. machines
1890 The predominance of the d.c. machine was finished by the increasing
application of three-phase systems.
currently Application
- performance less than 1W up to 30MW;
- range of high performance operation with higher voltage (e. g. 3kV);
- application mostly as motor;
- generator application nonsignificant
Examples
- trains and further electrical vehicles and cranes
- machine tools
- mill motors and transport equipment
- inside cars as wipers, blowers and positioners up to 100W
(permanent excited)
- spezial design as servo motor with disc-type rotor or bell-shaped rotor
VGU 2017/EMA1/Lä13_history_state
Principle of the D.C. Generator
Principle of
Drum-Type Armature
VGU 2017/EMA1/Lä14_d.c._drum_type_armature
d.c. machine
with the number of pole pairs
p = 1 (two-pole)
Pole Pitch:
d.c. machine
with the number of pole pairs
p = 2 (four-pole)
remark: In reality the brushes are arranged under the pole shoes. But
they are connected with the turns inside the commutating zone
between the pole shoes.
VGU 2021/EMA1/Lä15_poles
Longitudinal and cross section of a four-pole, fully laminated d.c. machine ( P = 38kW,
U = 400V, n = 1460min-1 – Franz Kessler KG, Bad Buchenau)
VGU 2017/EMA1/Lä16_cross_section
a) Armature Winding as Lap Winding
(S) (N)
Commutator Brushes
(S) (N)
Commutator Brushes
VGU 2017/EMA1/Lä17_winding_kind
2.2 Air-Gap Fields
a) Magnetic Field of the Main Poles (Exciting Field)
IE x x IE
Maximum of flux IE NE
density in the air gap BEmax 0
2 min
pole-pitch factor
BEm
0,65...0,7
BEmax
armature ampere
conductor
I Stab z A
A
dA π
field excitation
curve
x
VA Adx
0
field distribution
curve
VA
BA 0
x
VGU 2021/EMA1/Lä18_air_gap_fields
c) armature reaction
unsaturated machine
saturated machine
Impacts:
BE BEmax
2. By saturation the flux intensity is less increased, but another parts are fully
weakened. A field weakening results in the sum.
0
3. The zero crossing of the flux intensity is shifted in the commutating zone.
= x
Therefore the function of the d.c. machine will be influenced. The armature reaction is
eliminated by the compensation of the armature ampere-turns.
VGU 2021/EMA1/Lä19_armature_reaction
Commutating-Field and Compensating Winding
a) Commutating Field
VW(air) x
BW μ0
W
VGU 2017/EMA1/Lä20_commutating_field
Commutating-Field and Compensating Winding
b) field of armature compensation
The commutating-field winding are not able to influence the field under the
pole shoes of the excitation winding (main poles). The weakness of the flux
under the main poles would be unchanged.
The compensation winding is inserted in the surface of the main poles and
leading the armature current.
VW(air)
BW μ 0
W
VWr(air)
BWr μ 0
W x
VGU 2021/EMA1/Lä21_compensating_field
2.3 commutation
over
-commutation
bB
tk
vk
tk – time of commutation
bB – brush width
vk - peripheral speed of the
commutator
VGU 2017/EMA1/Lä22_commutation
2.4 Balance of Power, Torque Creation and Induced Voltage
Balance of Power
PA PE
PA, PE – active power absorbed by the armature
P resp. by the excitation winding
Efficiency
Torque Creation
The basic relation is the equation describing the force at a current-carrying conductor in the
magnetic field.
F I (dl B)
l
VGU 2017/EMA1/Lä23_balance_of_power
Because of rectangular conditions between the quantities in an electric machine the relation
will be much easier. Finally the absolute value is only from interest. Therefore results:
M F r IlBr.
IA
M ( x) lB( x)r.
2a
After calculation of the mean value of B(x) for the total torque of all z conductors of the arma-
ture results:
r
p
I rz
M A
πr B( x)ldx.
2a 0
p
zp
M ΦP I A cΦP I A M i . intrinsic moment
2 πa
zp
Thereby is c a machine constant andP the pole flux.
2 πa
U q (v B)dl U q cΦP.
generator voltage (counter-voltage of the motor)
b) Series Machine
Design:
- armature and excitation winding in series
- excitation, pole flux Φ = f(IA)
- winding with few turns and relatively big
diameter
Application:
- universal motors for a.c. and d.c.
- traction drives (e.g. electric cars)
c) Shunt Machine
Design:
- shunt winding as excitation winding of the
separately-excited machine
- armature winding just as well
- IE << IA ; RE >> RA
- non-dependent voltages UA, UE
Application:
- if only one voltage supply is available
(e.g. accumulator)
- characteristics as separately-excited machine
d) Compound Machine
- compound winding (combination separately
and series)
- intensified separately excitation
- indirect compensation of armature reaction
(cheaper than compensation winding)
- reversing polarity of excitation winding
means reversing polarity of series winding,
too
A - armature winding, excitation windings: D – series,
B - commutating winding, E – shunt,
C - compensating winding F – separately excited
IA = 0; UA = cΦPω = Uq
UA = f(ΦP) ist nichtlinear
A1
F1
UA
U A
F2
A2
Uq
IIEE
IA = ILoad
UA = Uq - IA RA - UBK
UBK
UA
UA0
UAN Kurzschlussstrom:
IARA ANKERRÜCKWIRKUNG
IN IA
VGU 2021/EMA1/Lä26_gen_separately
c) Self-Excited Shunt Generator in No-Load Operation
Leerlauf:
IE0
Because of IE IA results:
IA ILoad
and therefore
IARA
IARA
IA
cP UA IAK
Remark: Series and compound machines are also able to operate as generator.
VGU 2017/EMA1/Lä28_gen_shunt_load
2.6.2 Motor Operation
2.6.2.1 Speed Control of D.C. Machines
The d.c. machine operates at a grid with constant voltage. A transition in the generator
operation is possible.
UA = cΦPω + IARA !
exciting circuit
UE = IERE
= f(M)!
IA = f(M)!
VGU 2021/EMA1/Lä29_mot_separately_excited
With both relations = f(M) and IA = f(M) the characteristics of the operational performance
of the separately-excited d.c. machine can be represented.
UA RA M
= f(M) M IA = f(M) IA
cΦ P (cΦ P ) 2 cΦP
IA
0
The armature voltage UA and the angular velocity resp. the speed n have the same direction
both in generator and motor operation.
The same neglects as in case a) are used. Friction losses , losses by magnetic reversal and
voltage drop over the brushes are again zero.
Interval I Interval II
P
P = k1IA P = k2 IA, IE
VGU 2021/EMA1/Lä30_mot_series
The armature equation is unessentialy changed according to the series connection of armature
and exciting winding.
Interval I Interval II
P = k1IA P = k2
With
M = cPIA = ck1IA2
results
M M
IA . IA = f(M)! IA
ck1 ck 2
UA R RE
A M
ck1 I A (ck1 I A ) 2
UA R RE U A RA RE
A = f(M)! M
ck 1 M ck 1 ck 2 (ck 2 ) 2
IA
M M
VGU 2021/EMA1/Lä31_mot_series
c) Speed Control (Example: Separately- Excited D.C. Machine)
Three possibilities of speed control exist. We can show the results by the characteristics of
angular velocity and armature current versus machine torque.
IA
The speed control of the series excited d.c. machine is possible in an analogical way. Because
of the serial connectien of armature and exciting winding the realization is made by other
methods.
VGU 2021/EMA1/Lä32_mot_speed_control
2.6.2.2 Starting of D.C. Machine
- A d.c. machine with small performance (less than 1kW) can be directly connected with
the d.c. grid .
- A d.c. machine with higher performance can be started by two methods to prevent an
overload of the grid.
3. Counter-Current Braking
VGU 2021/EMA1/Lä33_braking
3 Transformers
1831 Faraday; experiments with two coupled coils for the evidence of the
induction law (Faraday´s Law)
today Integrated system over the most parts of Europe with high transmission
voltages (transmission performance S U²). Transformers are important
equipment in this system (380kV, 220kV, 110kV … 400V).
e. g. Europe 220kV/380kV, Canada, Russia 750kV
Application of Transformers
VGU 2011/EMA1/Lä34_history_state
3.1 Single-Phase Transformers
The statements made for the single-phase transformer are also valid for one phase of the
three-phase transformer. The specialities of the three-phase transformer are presented in chap-
ter 3.4.
principle of operation:
Joch
Schenkel
a
Lower-voltage winding 2
a
Higher-voltage winding
The higher- and the lower-voltage winding can be arranged on both limbs in the case of core
type.
Windings:
b) Time-variable voltages are induced in the windings by the time-variable magnetic fields
floating trough the windings (Faraday´s law).
VGU 2021/EMA1/Lä35_single_design
There are two kinds of the design of windings:
Iron Core:
The iron core consists of iron sheets isolated of each other. The sheets are especially rolled to
a thickness of 0,23 to 0,35mm . The insulation is either an enamel coat or a thin silica-
phosphat layer.
The eddy-current losses are decreased by means of the lower electric conductivity of the iron
sheets and the arrangement of the sheets in direction of the flux.
For transformers with low or medium performance the cross section of the core is squared (a).
Graded cores are used to adapt the cross section to the shape of the winding (b).
A special construction is the involute core (c).
The geometric space factor increases from the left to the right.
a) b1) b2) c)
VGU 2017/EMA1/Lä36_iron_core
3.1.2 Ideal and Real Transformer
- - Der
The elektrische Widerstand
electric resistance deswinding
of the Wick- is
gleich null
zero ( conductivity Cu ).
(Cu ).
- - - Der
The magnetische Widerstand
magnetic resistance desiron-
of the Eisen-core
kreises ist gleich null ).
is zero (permeability
(Fe ). Fe
- - Der
The elektrische Widerstandofdes
magnetic resistance theEisenkrei-
iron core
ses ist unendlich groß
is zero (permeability Fe ).
(Fe = 0 ).
- - Der
Themagnetische Widerstand
magnetic resistance of thedes Umge-
environment
bungsmediums ist unendlich
is infinite (permeability air Luft = 0).
of thegroß
(Luft = 0 ). Luft
That means, there is no leakage flux under ideal conditions (Fe ; Luft = 0 ) or the
whole magnetic flux is inside the iron core. Therefore the magnetic flux must be the
same in both windings (useful flux).
According to Faraday´s law for both windings results:
dΦ dΦ
u1 N1 N2 u2
dt dt
Therefore the identity follows for the voltage ratio of the ideal transformer with the turn ra-
tio.
U 1 N1
ü
U2 N2
The magnetic resistance of the iron core is zero. Therefore with the Ampere´s law follows that
the magnetic voltage drop is zero, too:
ds 0 I 1 N 1 I 2 N 2
H
For the current ratio of the ideal transformer consequently results:
I1 N 2 1
I 2 N1 ü
VGU 2021/EMA1/Lä37_tr_ideal
The real transformer
The real transformer only few differs from the ideal transformer in comparison to other elec-
tric machines. Two distinctions are essential for the function of a transformer.
b) The ideal transformer might have no magnetic flux outside the iron core.
In reality leakage fluxes exist. They are closed outside the iron core and don´t
achieve the other winding.
The deviations from the ideal transformer are very low. The real transformer has losses from
0.5 to 3% and efficiencies from 97 to 99.5%.
Cancellation of Ideal Conditions:i
- endlichen Widerstand R.
2. For the material of the iron core is valid Fe und Fe > 0.
-- Permeability Fe means, the iron core has the magnetic resistance Rm0.
- Therefore ampere turns are required.
.
-
-
-- Conductivity Fe > 0 means, eddy currents and eddy-current losses results
- inside the iron core. In addition hysteresis losses arise by means of the
- magnetic reversal of the core with 50Hz.
-
- Magnetizing Fe Ibedeutet,
Permeabilitätcurrent dass der
and leakage Eisenkreis
current einen
IFe have magnetischen
a phase displacement
- of Beide Ströme
90° and result sind zueinander
in the um 90° Iphasenverschoben
no-load current . und bilden den Leer-
0
laufstrom I0.
magnetizing I
UU101
I 0 I μ I Fe
II10
0
No-load I
VGU 2021/EMA1/Lä38_tr_real
Leakage I 0 IFe
IuI Fe
of the
magnetic
-reversal losses
3. For the permeability of the iron core is valid Fe and for the environment Luft > 0.
1
Useful flux h (main flux)
Index 1: primary winding
Index 2: secondary winding
h
The goals are:
a) The realization of an integrative electric equivalent circuit summarizing primary and
secondary winding of the transformer.
b) The construction of the phasor diagram out of this equivalent circuit.
The transmission ratio of the transformer must be reduced to ü =1(unity turns-ratio, N1=N2).
All quantities of the secondary winding are related to the primary winding (symbol e.g. U´).
The answer for the secondary voltage is:
U2 = (N2 /N1)U1
U2´= U2ü .
Finally the resistance, inductivity, reactance and impedance can be calculated according to:
VGU 2021/EMA1/Lä39_tr_reduction
3.1.3 Equivalent Circuit and Phasor of Single-Phase Transformers
Under consideration of the preconditions 1 and 3 of the transition from the ideal to the real
transformer and the reduction of the transformation ratio to ü =1 the following equivalent
circuit is valid. leakeage flux ~ inductor
** **
jN2h´=
' jN2 (N1/N2)h = jN1h .
That means, both of the voltage drops (left and right of the main inductivity) are always
identical and therefore both signed points, too ( * -> ** ) .
(
For the component in the cross circuit is valid
jN1h = jLhI .
According to Ampere´s law and under consideration of the no-load current results
VGU 2017/EMA1/Lä40_tr_circuit
Phasor Diagram of the Transformer
3. I1 - I2´= I0 4. I0 = I + IFe
I1jL1
U1
I1R1
-I2´jL2´
Uh -I2´R2 ´ I2´
I1
U2
IFe
I0
h
I
-I2´
-Uh
VGU 2017/EMA1/Lä41_tr_phasor
3.2 Operating Conditions of Single-Phase Transformers
3.2.1 The Transformer in No-Load Operation (open)
b) The no-load current flows through the primary winding (I10 I1N).
Therefore the voltage drops over jL1 und R1 are negligible, too.
Both components can be neglected.
U10
I0 0
0 IFe
I
3. open-circuit test I0 P0
A W
V U10
to d) P0
cos 10
U10 I10
U 10 Xh
Xh resp. Lh
Iμ
The open-circuit test is connected with the test of the iron core. The crest value of the flux in
the iron circuit can be determined by the transformer formula.
2π ˆ
UN fΦ 4,44 NfΦˆ
2
The transformers have much influence on the short-circuit behaviour of the transmission
grids. They care for the limitation of the short-circuit current which is many times of the nom-
inal current.
Because I1NI10 (current in the cross circuit) is valid again and in addition also U1N Uk
(voltage during the short-circuit test) the cross circuit (Xh, RFe) can be neglected.
Then I1 = I2´ is valid.
I1NjL
k
Uk
I1NRk
I1N= I2´
VGU 2021/EMA1/Lä43_tr_short_circuit
I1N
3. short-circuit test
A Pk W
U1=Uk V Uk
goals: determination of
to c) U 1N
I k U 1N
Ik I1N
I1N U kN U kN
to e)
Pk P U kN U k
cos k kN with
Zk
U k I1 U kN I1N I1N I1
to f)
U kN
Rk R1 R2 ´ cos k
I1N
U kN
Lk Lσ1 Lσ2 ´ sin k
I1N
VGU 2021/EMA1/Lä44_tr_short_circuit
3.2.3 The Change of Voltage under Rated Operation
The cross circuit is neglected under rated operation, too (I1NI0). The difference to the previ-
ous test is U2´ 0.
U2N´
U1= I1NRk + I1NjXk + U2N I1N = I2N´
Under rated operation the voltage (UN) and the current (IN) must have their nominal values
depending of the performance and the design of the transformer. Only the phase angle (Load)
of the load can be changed.
U2
blue – inductive
decreasing voltage
U1
red – capazitive
increasing voltage U2
green – ohmic
decreasing voltage
U2 I1= I2
Last
I1 Last I1
VGU 2021/EMA1
/Lä45_tr_load
According to VDE 0532 for changing of voltage is valid :
Rk I 1N X I
u UX u cos k 1N sin
U 1N U 1N
U1
UR
U2´
3.2.4 Losses, Balance of Power and Efficiency
Possible losses in transformers are:
c) additional losses in parts of the construction auxiliaries service (e.g. fans for cooling)
The losses of the transformers are very low (0.5 to 3% of the nominal active power). The
determination is impossible during nominal operation .
Therefore the determination by means of the segregated-loss method is useful (see chapters
3.2.1 and 3.2.2).
P1 U1 I1 cos 1
b) Determination of the copper losses Pcu by means of the short-circuit test
at nominal current:
2
2 I1
at any desired current: PCuN Rk I1N
1N
I
VGU 2021/EMA1/Lä46_tr_balance
by means of the definition of
the load factor:
c) Determination of the load-independent iron losses PFe by means of the open-circuit test
is const for all losses condition
d) Total losses PV of a transformer
Under consideration only of the copper and the iron losses results:
Active input
power P1
PCu
Active output
power PFe
P2
2
I PFe
Therewith for the load factor and the maximal efficiency in this point results
VGU 2021/EMA1/Lä47_tr_balance
3.2.5 Parallel Operation of Single-Phase Transformers
The secondary terminals of transformers in parallel must have the same potential for avoiding
circulating currents between the transformers.
This will be fulfilled if: - the voltage ratios (U1N/U2N) and therewith the rated
voltages are equal
grid 1 - the short-circuit voltages u % at different rated
k
currents are equal and
- the short-circuit power factors cos k are equal.
tr1 tr2
In the case of transformers in parallel operation for the determination of
the apparent power is valid:
S1 S1N u k2 %
grid 2
S 2 S 2 N u k1 %
3.2 Autotransformers
Beim Spartransformator
At autotransformers werden
parts of the Wicklungsteile sowohl
coil are used both fürprimary
for the die
Primär- als auch für die Sekundärseite
winding and for the secondary winding. verwendet.
Autotransformers arewerden
Spartransformatoren used if eingesetzt,
an electrical
woisolation between Tren-
eine galvanische
nung
higher-voltage
zwischen and
Ober-
lower-voltage
und Unterspannungsseite
side is not necessary.
nicht erforderlich
ist.
In opposite to the separate-winding transformer autotransformers
Gegenüber
have lowerdem
costsVolltransformator führt
for the construction der and
(core Spartransformator zu
winding material)
geringeren Kosten bei der Herstellung
and operation (lower losses). (Kern- und Wicklungsmate-
rial) und beim Betrieb (geringere Verluste).
Autotransformers
Der are able
Spartransformator kanntoinoperate in both directions.
beide Richtungen betrieben werden
S T U R I1 (U 1 U 2 ) I1 U 1 I1 (1
U2 U
) S D (1 2 ) ST SD
U1 U1
VGU 2021/EMA1/Lä48_tr_auto
3.4 Three-PhaseTransformers
3.4.1 Design of Three-Phase Transformers
At units of very high performance the power is transmitted by means of three single-phase
transformers (three-phase transformer bank). The problem is the transport to the operation
place.
L1
L2 grid 1
L3
L1´
L2´ grid 2
L3´
The three transformers are only electrically coupled, but not magnetically.
u + v + w = 0
By means of the phase shift of the fluxes of 120° the value of the flux through the middle
limb is zero. On this way the „temple type“ comes into beeing.
a) core-type transformers
a1) symmetrical (very seldom) a2) unsymmetrical three-limb transformer (usual)
iron core
iron core
lower-voltage winding
higher-voltage winding
VGU 2021/EMA1/Lä49_3tr_design
b) shell-type transformers
b1) five-limb transformer b2) three-phase shell-type transformer
(very seldom)
iron core iron core
The behaviour of a three-phase transformer and of 3 single-phase transformers for each phase
is equal under symmetrical load. This is only valid for the fundamental wave, but not for the
third harmonic wave (e.g.). By means of tertiary windings (delta connection over three limbs)
asymmetries can be balanced.
1U
1U 1V
1V 1W
1W Here the star connection is chosen as higher-voltage
system. (The delta connection would be possible,
too.)
N1 1
N
Transformers with zigzag connection are insensitive against unsymmetric load in the phases.
This is normal near the consumer. In transformers with other combinations (star, delta or zig-
zag - vector groups) tertiary windings are used to prevent the saturation of the iron core.
VGU 2021/EMA1/Lä51_3tr_yd
The kind of connection of windings is indicated by identification symbols.
- Dreieckschaltung (D - Oberspannungswicklung,
d - Mittel- oder Unterspannungswicklung)
-- star connection
Sternschaltung (Y,y)
(Y,y)
-- zigzag connection
Zick-Zack-Schaltung (Z,z)
(Z,z)
-- Offene Schaltung
brought-out neutral or star point(III,
(N,iii)
n)
-- Herausgeführter
open connection Sternpunkt (N, n)
(III, iii)
12 vector groups are determined by standard (VDE 0532, part 4). Transformer producer have
to use these vector groups only. The vector group shows:
- - die
theZusammenschaltung
lagging of the phasorder
of Wicklungsstränge
the lower-voltage connection
against the same phasor in the higher-voltage connection
- die Phasenlage zuordenbarer Spannungszeiger
- - das
the Spannungsübersetzungsverhältnis.
kind of connections of the higher and the lower-voltage windings and
e. g.:
- the capital letter (the connection with the highest voltage) must be the first part of the symbol
- connections with the same voltage are classified according to the nominal power
D: delta
- at the same nominal power the classification follows the order D, Y, Z, I Y: Star
Z: Zigzag
- N resp. n is the last letter at brought-out neutral point I: Innerconnection
- the final numerical index of vector group multiplied by 30° represented the phase lagging of
the corresponding phasors of the l.v. connection against the h.v. connection.
There are 4 preferred vector groups under the 12 groups fixed by standard:
1. Yy0 step-down
step-downtransformer for for
transformer the the
interconnection of grids
interconnection resp.
of grids in distribution
resp.
grids.
in distribution grids
VGU 2021/EMA1/Lä52_3tr_vector_groups
2. Yd5 generator transformer in power stations; delta connection to the generator
a) Determination of the numerical index resp. the lagging between the phasors of the
higher-voltage and lower-voltage connection
U2v´ U2w´
U
a3) phasor diagram
U2v´´ -U2w´ U2v´
VGU 2021/EMA1/Lä53_3tr_theory_group
W V
b) Determination of the voltage ratio
The modification of the amplitude of the voltage happens on the way from the higher-voltage
terminals to the lower-voltage terminals by two reasons.
- by circuit-logic reasons ( e.g. transition from line to phase quantities) and
- the reason of voltage ratio (Faraday´s Law).
The product of all modifications, analog to amplifiers in series, results in the voltage ratio.
For the transformer with the vector group Yd5 therefore results:
Yz5
U 1uv U 1uv U 1u U 2u N 1 2 N1
3 1
U 2uv
U 2uv U 1u U 2u N2 3 3N 2
2
keep in mind:
Bei Drehstromtransformatoren kann das Spannungsübersetzungsverhältnis
vom Windungszahlverhältnis abweichen!
2. Gemessen wurden:
3.1 triangle of the line voltages of the higher-voltage terminals (length corresponding to 600V)
3.2 Circle around 1U - because of wired connection identical with 2U (radius corresponding to 400V).
At this circle are located the potentials of the terminals 2V and 2W.
3.3 Determination of the final potentials of the terminals 2V und 2W circles around 1V and 1W.
(radius 1V – 2V corresponding to 320V; radius 1W – 2V coresponding to 720V).
(720V um 1W)
phasor diagram:
2U
(400V um 1U)
1U
2V
(320V um 1V) For the determination of the
phase angle resp. the numeri-
cal index the phasor U2UV
must be turned anticlockwise
until it has the same direction
2W
as the phasor U1UV
1W 1V
Uq {PFe = 0} Uq {PFe ≠ 0}
P (at shaft)
cɸp {PFe = 0} cɸp {PFe ≠ 0}
Mi {PFe ≠ 0}
cɸp IA {PFe = 0} - PFe /2πn Legend of Indices:
A - armature
+Mrbg -Mrbg P - pole
q - source
i - intrinsic
Fe - iron
M (at shaft) rbg - friction
GENERATOR MOTOR
M
P Prbg
M i cΦP I A M + M rbg
= 2πn 2πn
Motor: intrinsic torque at the air gap induced counter voltage in the armature
(> load torque of the driven machine) (< voltage of the grid)
Generator: induced voltage in the armature counter torque at the air gap
(> voltage of the grid) (< driven torque of the turbine)
- A d.c. machine with small performance (less than 1kW) can be directly connected with the d.c. grid .
- A d.c. machine with higher performance can be started by two methods to prevent an overload of the grid.
Breaking of DC Machines
U1
U2
I1
I2
N1 /N2 = 1
I IFe
FHF 2003/EMA1/Lä40_tr_ersatz
1. Circuit
Delta Connection Star Connection
W1 U2
V2 V1 W1 V1
U UV
U WU
I StrU I StrW
I3
I StrW I StrU U UV
I StrV
U StrU
U VW U WU
I StrV
U StrW U StrV
I2
I StrW
U VW
3. Power
V v U V W u v w
Yz11 w 2N1/√3N2
U W u
with P = M𝜔 = M2𝜋n
1.3 Torque
Mi = M + Mrbg (PFe ≠ 0)
shunt machine: I = IA + IE
with M = cΦpIA
= UA / cΦp - [RA / (cΦp)2]M
cΦp = Uq /2𝜋n = M / IA
b) series machine:
R RE M
UA
A IA
ck1M ck1 ck1
U A RA RE M
M IA
ck 2 (ck2 ) 2 ck 2
2 Transformers
Single-Phase Transformer
U1 / U2 = N1 / N2 = ü; I1 / I2 = N2 / N1 = 1/ü
S1 = S2 = U1 I1 = U2 I2
Three-Phase Transformer
2.10 Vector groups: are different combinations of star, delta and/or zigzag connections
2.11 Phase shift: Different vector groups cause different phase shifts between
equivalent primary and always lagging secondary voltages. The
determination is possible by mesh equations and phasor diagrams.