PNGRB - Electrical Safety Audit Checklist

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 4

PNGRB_2018_Checklist

Annexure –IV
System Document for Electrical Safety Audit
SL. No. Item Observation
A. Deviation from laid down procedure:
Deviation from statutory Requirements as laid down.
1 in the law in force relating to electricity and
petroleum
Equipments enclosure mis- match with
1.1
correspondingzone of application
1.2 Clearances not maintained as per guideline
1.3 Material not as per respective Indian Standards
1.4 Inappropriate illumination levels
B. Insulation, Grounding and Lightning Protection:
Grounding and Lightning Protection Systems are not
2
as per IS-3043 and IS -2309
Electrical equipments are not earthed as per the
2.1
recommendation

2.2 Neutral point of transformer and DG set are not earthed

The lightning or surge arrestors are in not in place


2.3
and/or not connected to earth, or both

2.4 High Earth Resistance

2.5 Insulation resistance low, less than 1 Mega Ohm

All panel doors are not earthed with flexible braided


2.6
connection
The electrical room is not clean, and there is water
2.7
accumulation inside the room or cable trenches
C. Protection and Metering System:
3 Protection System is not operating
3.1 Emergency push button jammed

Under-voltage, over-voltage, phase unbalance protection


3.2
not working

3.3 Neutral snap, phase failure protection not working


3.4 Meters not indicating or recording properly
D. Loose connection and overheating:
4.1 Loose connection in cable termination

Equipments running in overload condition, heating and


4.2
burning smell

E. Safety:
Non-functioning of lighting fixtures, especially in
5.1 critical zones viz. near the dispenser, tank farm area,
front and rear of sales room, electrical room
Safety equipments, viz. rubber mat, CO2 fire
5.2 extinguisher, shock treatment chart, flameproof torch are
not in designated places
Repairing work being carried out without any authorized
5.3
work-permit
Components material used are of poor sub-standard
5.4
quality
Labels or tag-marking or ferruling on equipments,
5.5
cables, feeders, cable cores are missing

5.6 Drawing or documents not available in panels


F. Repair and Maintenance:
6.1 Dirt and dust accumulation inside panel
6.2 Spare holes in electrical panel
cklist
fety Audit
Action Needed

Immediate attention needed to rectify the


issue and comply with statutory
requirements
Equipment with appropriate enclosure,to
be installed.
Minimum clearance to be ensured.
Replaced with IS approved materials.
Modify to meet the recommendation.

“Earth” connection to be provided as per


recommendation
“Neutral” points have to be grounded as
per recommendation
Lightning or surge arrestor to be properly
placed and connected
Salt and water to be added to earth pit to
reduce earth resistance.
Damaged portion of insulation to be
repaired, insulation resistance to be
beyond 1 Mega Ohm.
Missing flexible earth links to be put at the
earliest.
Room to be cleaned, water wiped out, all
holes for water entry, to be blocked.

Push button to be replaced, safety


checked by simulation
Relay to be properly set and fault
condition to be simulated to check and
ensure healthiness of the protection
system.

Meter, its C.T. and P.T., as required, to be


replaced immediately.
Termination to be tightened properly
Load must be restricted within the design
limits, loose connection, if any, shall be
set right.

Lighting fixtures and its associated


circuits to be checked and rectified.

To be put at their designated places


immediately and persons trained on
procedure for shock treatment
Immediately work authorization procedure
to be implemented
Standard good quality components to be
used
Missing labels or tag- marks or ferrules to
be put as per drawing.
Drawing or documents to be kept in the
dedicated pockets in panels

Clean periodically.
Spare holes to be blocked.

You might also like