1. The number of turns on the primary and secondary windings of a 1-f


transformer are 350 and 35 respectively. If the primary is connected to a 2.2
kV, 50-Hz supply, determine the secondary voltage on no-load. [220 V]

GIVEN:
N1 = 350 turns E1 = 2.2 kV / 2200 V
N2 = 35 turns E2 = ?
f = 50 Hz

SOLUTION:
𝑁 35 1
𝐾= 1= =
𝑁2 350 10

𝐸1
𝐾= ; 𝐸2 = 𝐸1 𝐾
𝐸2
1
𝐸2 = 2200 𝑉( )
10
𝐸2 = 220 𝑉

2. A 3000/200-V, 50-Hz, 1-phase transformer is built on a core having an


effective cross-sectional area of 150 cm2 and has 80 turns in the low-
voltage winding. Calculate
(a) the value of the maximum flux density in the core
(b) the number of turns in the high-voltage winding.
[(a) 0.75 Wb/m2 (b) 1200]

GIVEN:
E1 = 3000 V a = 150 cm2
E2 = 200 V Bmax = ?
N2 = 80 turns N1 = ?
f = 50 Hz

SOLUTION:
𝐸2 = 4.44 ∅𝑚𝑎𝑥 𝑓 𝑁2
200 𝑉 = 4.44 ∅𝑚𝑎𝑥 (50 𝐻𝑧)(80)
∅𝑚𝑎𝑥 = 0.0112 𝑊𝑏

This study source was downloaded by 100000863775449 from CourseHero.com on 03-13-2023 07:49:48 GMT -05:00

https://www.coursehero.com/file/60537203/AC-DC-LEC-TRANSFORMER-convertedpdf/
∅𝑚𝑎𝑥
a. 𝐵𝑚𝑎𝑥 =
𝑎
0.0112 𝑊𝑏
𝐵𝑚𝑎𝑥 =
150 𝑐𝑚2
𝑊𝑏
𝐵𝑚𝑎𝑥 = 0.000075
𝑐𝑚2
𝑊𝑏
𝐵𝑚𝑎𝑥 = 0.75
𝑚2

𝐸1
b. 𝑁1 = 𝑥𝑁2
𝐸2
3000 𝑉
𝑁1 = (80)
200 𝑉
𝑁1 = 1200 𝑡𝑢𝑟𝑛𝑠

3. A 3,300/230-V, 50-Hz, 1-phase transformer is to be worked at a maximum


flux density of 1.2 Wb/m2 in the core. The effective cross-sectional area of
the transformer core is 150 cm2. Calculate suitable values of primary and
secondary turns. [830; 58]

GIVEN:
E1 = 3300 V a = 150 cm2 / 1.5 m2
E2 = 230 V N1 = ?
f = 50 Hz N2 = ?
Bmax = 1.2 Wb/m2

SOLUTION:

• 𝐵𝑚𝑎𝑥 = 𝑚𝑎𝑥
𝑎
𝑊𝑏 ∅𝑚𝑎𝑥
1.2 2 =
𝑚 1.5 𝑚2
∅𝑚𝑎𝑥 = 1.8 𝑊𝑏

• 𝐸1 = 4.44 ∅𝑚𝑎𝑥 𝑓 𝑁1
3300 𝑉 = 4.44 (1.8) (50 𝐻𝑧 𝑥 10−3 )(𝑁1 )
𝑁1 = 825.83 𝑡𝑢𝑟𝑛𝑠

• 𝐸2 = 4.44 ∅𝑚𝑎𝑥 𝑓 𝑁2
230 𝑉 = 4.44 (1.8) (50 𝐻𝑧 𝑥 10−3 )(𝑁2 )
𝑁2 = 57.56 𝑡𝑢𝑟𝑛𝑠

4. A 40-kVA, 3,300/240-V, 50 Hz, 1-phase transformer has 660 turns on the


primary. Determine
This study source was downloaded by 100000863775449 from CourseHero.com on 03-13-2023 07:49:48 GMT -05:00

https://www.coursehero.com/file/60537203/AC-DC-LEC-TRANSFORMER-convertedpdf/
(a) the number of turns on the secondary
(b) the maximum value of flux in the core
(c) the approximate value of primary and secondary full-load currents.
Internal drops in the windings are to be ignored.
[(a) 48 (b) 22.5 mWb (c) 12.1 A; 166.7 A]

GIVEN:
V1 = 3300 V N2 = ?
V2 = 240 V ∅max = ?
f = 50 Hz Ip = ?
VA = 40 Kva Is =?
N1 = 660 turns

SOLUTION:

𝑁1 𝑉1
a. =
𝑁2 𝑉2
660 3300
=
𝑁2 240
𝑁2 = 48 𝑡𝑢𝑟𝑛𝑠

b. 𝐸2 = 4.44 ∅𝑚𝑎𝑥 𝑓 𝑁2
240 𝑉 = 4.44 ∅𝑚𝑎𝑥 (50 𝐻𝑧)(48)
∅𝑚𝑎𝑥 = 22.5 𝑚𝑊𝑏

𝑉𝐴
c. 𝐼𝑝 =
𝑉1
40 𝑥 103
𝐼𝑝 =
3300
𝐼𝑝 = 12.1 𝐴

𝑉𝐴
𝐼𝑝 =
𝑉2
40 𝑥 103
𝐼𝑝 =
240
𝐼𝑝 = 166.7 𝐴

5. A double-wound, 1-phase transformer is required to step down from 1900 V


to 240 V, 50-Hz. It is to have 1.5 V per turn. Calculate the required number
of turns on the primary and secondary windings respectively.

This study source was downloaded by 100000863775449 from CourseHero.com on 03-13-2023 07:49:48 GMT -05:00

https://www.coursehero.com/file/60537203/AC-DC-LEC-TRANSFORMER-convertedpdf/
The peak value of flux density is required to be not more than 1.2 Wb/m2.
Calculate the required cross-sectional area of the steel core. If the output
is 10 kVA, calculate the secondary current.
[1,267; 160; 56.4 cm2; 41.75 A]

GIVEN:

This study source was downloaded by 100000863775449 from CourseHero.com on 03-13-2023 07:49:48 GMT -05:00

https://www.coursehero.com/file/60537203/AC-DC-LEC-TRANSFORMER-convertedpdf/
6. The no-load voltage ratio in a 1-phase, 50-Hz, core-type transformer is
1,200/440. Find the number of turns in each winding if the maximum flux is
to be 0.075 Wb. [24 and 74 turns]

GIVEN:
E1 = 1200 V ∅max = 0.075 Wb
E2 = 440 V N1 = ?
f = 50 Hz N2 = ?

SOLUTION:
• 𝐸1 = 4.44 ∅𝑚𝑎𝑥 𝑓 𝑁1
1200 𝑉 = 4.44 (0.075)(50 𝐻𝑧)(𝑁1 )
𝑁1 = 72 𝑡𝑢𝑟𝑛𝑠

• 𝐸2 = 4.44 ∅𝑚𝑎𝑥 𝑓 𝑁2
440 𝑉 = 4.44 (0.075)(50 𝐻𝑧)(𝑁2 )
𝑁2 = 26 𝑡𝑢𝑟𝑛𝑠

7. A 1-phase transformer has 500 primary and 1200 secondary turns. The net
cross-sectional area of the core is 75 cm2. If the primary winding be
connected to a 400-V, 50 Hz supply, calculate.
(i) the peak value of flux density in the core and (ii) voltage induced in the
secondary winding. [0.48 Wb/m2; 60 V]

GIVEN:
N1 = 500 turns a = 75 cm2
N2 = 1200 turns Bmax = ?
f = 50 Hz V2 = ?
V1 = 400 V

SOLUTION:
𝑉1
i. 𝐵𝑚𝑎𝑥 =
4.44 𝑓 𝑁1 𝑎
400 𝑉
𝐵𝑚𝑎𝑥 =
4.44 (50𝑥10−2 ) (1200) (0.75)
𝑊𝑏
𝐵𝑚𝑎𝑥 = 0.48
𝑚2

This study source was downloaded by 100000863775449 from CourseHero.com on 03-13-2023 07:49:48 GMT -05:00

https://www.coursehero.com/file/60537203/AC-DC-LEC-TRANSFORMER-convertedpdf/
𝑁1 𝑉1
ii. =
𝑁2 𝑉2
500 400 𝑉
=
1200 𝑉2
𝑉2 = 960 𝑉

8. A 10-kVA, 1-phase transformer has a turn ratio of 300/23. The primary is


connected to a 1500-V, 60 Hz supply. Find the secondary volts on open-
circuit and the approximate values of the currents in the two windings on
full-load. Find also the maximum value of the flux.
[115 V; 6.67 A; 87 A; 11.75 mWb]

GIVEN:

This study source was downloaded by 100000863775449 from CourseHero.com on 03-13-2023 07:49:48 GMT -05:00

https://www.coursehero.com/file/60537203/AC-DC-LEC-TRANSFORMER-convertedpdf/
9. A 100-kVA, 3300/400-V, 50 Hz, 1 phase transformer has 110 turns on the
secondary. Calculate the approximate values of the primary and
secondary full-load currents, the maximum value of flux in the core and the
number of primary turns. [30.3 A; 250 A; 16.4 mWb; 907]

GIVEN:
VA = 100 kVA Ip = ?
V1 = 3300 V Is = ?
V2 = 400 V ∅max = ?
f = 50 Hz N1 = ?
N2 = 110 turns

SOLUTION:
𝑉𝐴
• 𝐼𝑝 =
𝑉1
100 𝑥 103
𝐼𝑝 =
3300 𝑉
𝐼𝑝 = 30.3 𝐴

𝑉𝐴
• 𝐼𝑠 =
𝑉2
100 𝑥 103
𝐼𝑠 =
400 𝑉
𝐼𝑠 = 250 𝐴

𝑉1 𝑁1
• =
𝑉2 𝑁2
3300 𝑁1
=
400 110
𝑁2 = 907 𝑡𝑢𝑟𝑛𝑠

10. The no-load current of a transformer is 5.0 A at 0.3 power factor when
supplied at 230-V, 50-Hz. The number of turns on the primary winding is 200.
Calculate (i) the maximum value of flux in the core (ii) the core loss (iii) the
magnetising current. [5.18 mWb; 345 W; 4.77 A]

GIVEN:
Io = 5.0 A f = 50 Hz Im = ?
cos∅o = 0.3 N1 = 200 turns Ic = ?
∅o = cos-1(0.3) = 72.54o ∅max = ?
V = 230 V
This study source was downloaded by 100000863775449 from CourseHero.com on 03-13-2023 07:49:48 GMT -05:00

https://www.coursehero.com/file/60537203/AC-DC-LEC-TRANSFORMER-convertedpdf/
SOLUTION:

i. 𝐸1 = 4.44 ∅𝑚𝑎𝑥 𝑓 𝑁1
230 𝑉 = 4.44 ∅𝑚𝑎𝑥 (50𝑥10−3 )(200)
∅𝑚𝑎𝑥 = 5.18 𝑚𝑊𝑏

ii. 𝐼𝑚 = 𝐼𝑜 sin(𝜃𝑜 )
𝐼𝑚 = 5.0 sin(72.54°)
𝐼𝑚 = 4.77 𝐴

iii. 𝐼𝑐 = 𝐼𝑜 cos(𝜃𝑜 )
𝐼𝑐 = 5.0 cos(72.54°)
𝐼𝑐 = 1.5002 𝐴

𝑊 = 𝐼𝑐 𝑉
𝑊 = (1.5002 𝐴)(230 𝑉)
𝑊 = 345 𝑊𝑎𝑡𝑡𝑠

11. The no-load current of a transformer is 15 at a power factor of 0.2 when


connected to a 460-V, 50-Hz supply. If the primary winding has 550 turns,
calculate:
(a) the magnetising component of no-load current
(b) the iron loss
(c) the maximum value of the flux in the core.
[(a) 14.7 A (b) 1,380 W (c) 3.77 mWb]

GIVEN:
Io = 15 A N1 = 550 turns
cos∅o = 0.2 Im = ?
∅o = cos-1(0.2) = 78.46o Ic = ?
V = 460 V ∅max = ?
f = 50 Hz

SOLUTION:

a. 𝐼𝑚 = 𝐼𝑜 sin(𝜃𝑜 )
𝐼𝑚 = 15 sin(78.46°)
𝐼𝑚 = 14.7 𝐴
b. 𝐼𝑐 = 𝐼𝑜 cos(𝜃𝑜 )
This study source was downloaded by 100000863775449 from CourseHero.com on 03-13-2023 07:49:48 GMT -05:00

https://www.coursehero.com/file/60537203/AC-DC-LEC-TRANSFORMER-convertedpdf/
𝐼𝑐 = 15 cos(78.46°)
𝐼𝑐 = 3 𝐴

𝑊 = 𝐼𝑐 𝑉
𝑊 = (3 𝐴)(460 𝑉)
𝑊 = 1380 𝑊𝑎𝑡𝑡𝑠

c. 𝐸1 = 4.44 ∅𝑚𝑎𝑥 𝑓 𝑁1
230 𝑉 = 4.44 ∅𝑚𝑎𝑥 (50𝑥10−3 )(550)
∅𝑚𝑎𝑥 = 3.77 𝑚𝑊𝑏