PANEL BOARD DESIGNATION : PB2 SYSTEM : 2P 230V 2W+G 60HZ LOCATION : GROUND FLOOR

Xref .\xr-a-paper.dwg

CONNECTED LOADS BREAKER RATING WIRING SCHEDULE SIZE OF CONDUIT


CIRCUIT
LOAD DESCRIPTION
NUMBER
Quantity
Volt- Amper
VA
Current in
Amperes
Phase
System
AT POLE KAIC
TAP
1 DRYER 1 500 2.17 1 20 2 10
2-3.5mm² Cu. Wire THHN +
1-2.0mm² Cu. Wire Ground
20mmØ PNS TO
2 WASHING MACHINE 1 500 2.17 1 20 2 10
2-3.5mm² Cu. Wire THHN +
1-2.0mm² Cu. Wire Ground
20mmØ PNS
PRIMARY
2-5.5mm² Cu. Wire THHN +
3 AIRCON OUTLET 2.0HP 1 2760 12.00 1 30 2 10 1-2.0mm² Cu. Wire Ground
20mmØ PNS

3760 16.35
ISOLATION BREAKER NEMA 3R
SIZE OF THE CONDUCTOR: I= 129.10 + 25%@22.5 = 134.72@80%DF= 107.78Amperes
USE: 2- 60mm² ²

2-125mm² Cu. Wire THW


1-30mm² Cu. Wire TW Grounding
in 1-65mmØ RSC conduit

IF DISTANCE FROM METER TO MDP 15<

GROUND
PANEL BOARD DESIGNATION : MDP SYSTEM : 1ɸ 230V 2W+G 60HZ LOCATION :

SIZE OF 2- 60mm² Cu. WIRE THW + 1-22mm² TW 2- 60mm² Cu. WIRE THW + 1-22mm² TW
CONNECTED LOADS BREAKER RATING WIRING SCHEDULE
CONDUIT grounding in 50mmø PVC PIPE CONDUIT grounding in 50mmø PVC PIPE CONDUIT
PANELBOARDS

Volt- Amper Current in Phase


System AT POLE KAIC
VA Amperes
250AT/2P
2-60mm² Cu. Wire THHN + 1- 22mm²
1 PB-1 3040 13.22 1 150 2 20 Cu. Wire TW
50mmØ RSC

150AT/2P 150AT/2P
2-60mm² Cu. Wire THHN + 1- 22mm²
2 PB-2 3760 16.35 1 150 2 20 Cu. Wire TW
50mmØ RSC

60AT/2P 60AT/2P

6800.00 29.57

SIZE OF THE CONDUCTOR: I= 259.06 + 25%@22.5 = 264.69@80%DF= 211.75Amperes


USE: 2- 125mm² ²

GROUND

150AT/2P 150AT/2P
PB1 PB2
20AT/2P 20AT/2P 30AT/2P 30AT/2P

LIGHTING OUTLET LIGHTING OUTLET DRYER OUTLET WASHING MACHINE OUTLET


20AT/2P 30AT/2P

LIGHTING OUTLET SPARE AIRCON OUTLET SPARE

GROUND GROUND

THE SITE
BRGY.,INDANGAN ,DAVAO CITY

ARCHITECTURAL FIRM PROJECT TITLE PROJECT OWNER sheet contents REVISIONS RA 9266 ARTICLE 4 SECTION 33 SHEET NO.

Drawings and specifications and other contract documents duly signed,


Electrical Engineer stamped or sealed, as instruments of service, are the intellectual property
PROPOSED 2 - STOREY RESIDENTIAL BUILDING

PRC NO.: TIN. NO.:


and documents of the architect, whether thE object for which they are made
is executed or not. It shall be unlawful for any person to duplicate or to make
copies of said documents for use in the repetition of and for other projects or
E-2
DATE ISSUED: buildings, whether executed partly or in whole, without the written consent of
DATE VALID:
architect or author of said documents.