Professional Documents
Culture Documents
Iom1206 Agz
Iom1206 Agz
Trailblazer®
Air-Cooled Scroll Compressor Chillers
With High Efficiency Variable Speed Fan Technology
Model AGZ, E Vintage
30 to 241 Tons (100 to 840 kW)
HFC-410A Refrigerant
50/60 Hz
Table of Contents
Table of Contents
©2019 Daikin Applied. Illustrations and data cover the Daikin Applied product at the time of publication and we reserve the right to
make changes in design and construction at any time without notice.
This manual provides installation, operation, and maintenance information for Daikin Trailblazer model AGZ-E air-cooled scroll
chillers with the MicroTech® III controller and using R-410A. Packaged unit configurations and optional heat recovery installations
are covered in this manual. Information for units with either the pump package or remote evaporator options can be found at www.
DaikinApplied.com.
DANGER
Disconnect, lockout and tag all power to the unit before servicing condenser fan motors or compressors. Failure to do so can cause
bodily injury or death.
WARNING
Electric shock hazard. Improper handling of this equipment can cause personal injury or equipment damage. This equipment must
be properly grounded. Connections to and service of the MicroTech® III control panel must be performed only by personnel that are
knowledgeable in the operation of the equipment being controlled.
CAUTION
Static sensitive components. A static discharge while handling electronic circuit boards can cause damage to the components. Use
a static strap before performing any service work. Never unplug any cables, circuit board terminal blocks, or power plugs while
power is applied to the panel.
CAUTION
When moving refrigerant to/from the chiller using an auxiliary tank, a grounding strap must be used. An electrical charge builds
when halo-carbon refrigerant travels in a rubber hose. A grounding strap must be used between the auxiliary refrigerant tank and
the chiller’s end sheet (earth ground), which will safely take the charge to the ground. Damage to sensitive electronic components
could occur if this procedure is not followed.
WARNING
Escaping refrigerant can displace air and cause suffocation. Immediately evacuate and ventilate the equipment area. If the unit
is damaged, follow Environmental Protection Agency (EPA) requirements. Do not expose sparks, arcing equipment, open flame
or other ignition source to the refrigerant.
DANGER
Dangers indicate a hazardous situation, which will result in death or serious injury if not avoided.
WARNING
Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not
avoided.
CAUTION
Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.
General Description
Daikin Trailblazer® air-cooled water chillers are complete, self- The electrical control center includes all equipment protection
contained, automatic chillers designed for outdoor installation. and operating controls necessary for dependable automatic
Packaged units are completely assembled, factory wired, operation. Components housed in a centrally located, weather
charged, and tested. resistant control panel with hinged and tool-locked doors.
NOMENCLATURE
A G Z XXX E D SE
Air-Cooled Application, Efficiency, Unit Type
Global Design
Scroll Compressor
Nominal Tons # of Compressors
D = Tandem per Circuit
Design Vintage
T = Trio per Circuit
Nameplates Inspection
Identification nameplates on the chiller: Check all items carefully against the bill of lading. Inspect
all units for damage upon arrival. Report shipping damage
• The unit nameplate is located on the exterior of the Unit
and file a claim with the carrier. Check the unit nameplate
Power Panel. Both the Model No. and Serial No. are
located on the unit nameplate; the Serial No. is unique to before unloading, making certain it agrees with the power
the unit. These numbers should be used to identify the supply available. Daikin Applied is not responsible for physical
unit for service, parts, or warranty questions. This plate damage after the unit leaves the factory.
also has the unit refrigerant charge and electrical ratings.
• Evaporator data plate is under insulation and contains Handling
the serial number.
Be careful to avoid rough handling of the unit. Do not push or
• Compressor nameplate is located on each compressor pull the unit from anything other than the base while sitting on
and gives pertinent electrical information. appropriately-sized roller dollies.
WARNING To lift the unit, 2-1/2” (64mm) diameter lifting eyes are provided
Installation is to be performed by qualified personnel who are on the base of the unit. Arrange spreader bars and cables to
familiar with local codes and regulations. prevent damage to condenser coils or cabinet (see Figure 1).
CAUTION CAUTION
Sharp edges and coil surfaces are a potential injury hazard. All lifting locations must be used to prevent damage to unit.
Avoid contact with them.
DANGER access to the sides or ends of the unit with piping or conduit.
These areas must be open for service access.
Improper rigging, lifting, or moving of a unit can result in
property damage, severe personal injury or death. Follow Minimum service clearance is as follows:
rigging and moving instructions carefully. Do not stand Sides
beneath the unit while it is lifted or being installed.
• 030-070 Ton Models: Minimum of 4 feet (1.2 meters)
• 075-241 Ton Models: It is highly recommended to
Figure 1: Required Lifting Arrangement
provide a minimum of 8 feet (2.4 meters) on one side to
NOTE: Number
of fans and allow for coil replacement. Coils can be removed from
rigging holes may the top, allowing a minimum of 4 feet (1.2 meters) of
vary from this side clearance; however, the unit performance may be
diagram. derated.
The lifting
method will CAUTION
remain the same.
Unit performance may be impacted if the operational
clearance is not sufficient.
Minimum = 4 ft (1.2 m)
075-241 Ton Models: 8ft (2.4 m) recommended on one side
Unit Placement
Minimum = 7.5 ft (2.3 m) Minimum = 4 ft
Trailblazer® units are for outdoor applications and can be for 030-070 Ton Models
Control Panel
(1.2 m)
mounted either on a roof or at ground level. For roof mounted
applications, install the unit on a steel channel or I-beam frame Minimum = 4 ft (1.2 m)
to support the unit above the roof. Spring isolators for roof for 075-241 Ton Models
applications are recommended. For ground level applications,
install the unit on a substantial base that will not settle. Use a
one-piece concrete slab with footings extended below the frost Minimum = 4 ft (1.2 m)
line. Be sure the foundation is level within 0.5” (13 mm) over
its length and width. The foundation must be strong enough
to support the unit weight - see “Dimensions and Weights -
Packaged Units” on page 24. Operational Spacing Requirements
The addition of neoprene waffle pads (supplied by customer) Sufficient clearance must be maintained between the unit
under the unit may allow water to drain from inside the frame, and adjacent walls or other units to allow the required unit air
which can act as a dam. Installation of optional spring or flow to reach the coils. Failure to do so will result in a capacity
rubber-in-shear isolators can also assist with drainage, see reduction and an increase in power consumption. No solid
page 39 for information. obstructions are allowed above the unit at any height, see page
10 for details.
Mounting Hole Access The clearance requirements shown are a general guideline
The inside of the base rail is open to allow access for securing and cannot account for all scenarios. Such factors as prevailing
mounting bolts, etc. Mounting location dimensions are given in winds, additional equipment within the space, design outdoor
Dimensional Drawings beginning on page 24 air temperature, and numerous other factors may require more
clearance than what is shown. Additional clearances may be
required under certain circumstances.
Service Clearance
The control panels are located on the end of the chiller and Graphs on the following pages give the minimum clearance for
require a minimum of four feet of clearance in front of the different types of installations and also capacity reduction and
panels. Compressors, filter-driers, and liquid line shutoff valves power increase if closer spacing is used. The graphs are based
are accessible on each side or end of the unit. Do not block on individual cases and should not be combined with other
scenarios.
Case 1: Building or Wall on One Side of Unit Case 2: Two Units, Side-by-Side
NOTE: Assumes a solid height wall taller than unit. Refer to For models 030-180, there must be a minimum of 4 feet
Case 4 for partial wall openings. between two units placed side-by-side; however, performance
For models AGZ030-101E, maintain a 4 feet minimum from a may be affected at this distance. For models 191-241,
wall of any height. the minimum is 6 feet as closing spacing may cause air
recirculation and elevated condenser pressure. Assuming
For models AGZ110-130E, maintain a 6 feet minimum from a the requirement of one side having at least 8 feet of
wall of any height. service clearance is met, Case 2 figures show performance
For models AGZ140-241E, maintain a 8 feet minimum from a adjustments as the distance between two units increases.
wall of any height.
Figure 4: Two Units, Side-by-Side
Figure 3: Building or Wall on One Side of Unit
Height Distance
of Between
Wall Wall
and
Unit
Figure 5: Case 2 - Full Load Capacity Reduction
3.0
% Capacity Reduction
2.5
2.0
1.5
1.0
0.5
0.0
4 5 6 8
Distance Between Units (ft)
AGZ030-070E AGZ075-101E
AGZ110-130E AGZ140-180E
AGZ191-211E AGZ226-241E
4.0
3.5
% Power Increase
3.0
2.5
2.0
1.5
1.0
0.5
0.0
4 5 6 8
Distance Between Units (ft)
AGZ030-070E AGZ075-101E
AGZ110-130E AGZ140-180E
AGZ191-211E AGZ226-241E
7.0
4.0
5.0
% Capacity Reduction
3.0
4.0
0 10 20 30 40 50
% Open Wall Area
3.0 AGZ030-070E AGZ075-101E
AGZ110-130E AGZ140-180E
AGZ191-241E
2.0
1.0
0.0
4 5 6 8
Distance Between Units
AGZ030-035E AGZ040-070E AGZ075-101E
AGZ0110-130E AGZ140-180E AGZ191-211E
AGZ226-241E
7.0
% Power Increase
6.0
5.0
4.0
3.0
2.0
1.0
0.0
4 5 6 8
Distance Between Units (ft)
AGZ030-035E AGZ040-070E AGZ075-101E
AGZ0110-130E AGZ140-180E AGZ191-211E
AGZ226-241E
Models AGZ030-070E:
Models AGZ075-130E:
The Case 5 figures for models AGZ030-070E show adjustment
The Case 5 figures for models AGZ075-130E show adjustment
factors for pit/wall heights of 4 feet, 5 feet, and 6 feet.
factors for pit/wall heights of 5 feet, 6 feet, and 8 feet.
Figure 11: Case 5 - Full Load Capacity Reduction Figure 14: Case 5 - Full Load Capacity Reduction
(AGZ030E-070E) (AGZ075-130E)
Full Load Capacity Reduction (AGZ030-070E) Full Load Capacity Reduction (AGZ075-130E)
6.0 6.0
5.0 5.0
% Capacity Reduction
% Capacity Reduction
4.0 4.0
3.0 3.0
2.0 2.0
1.0 1.0
0.0 0.0
0 8 10 12 13 14 0 8 10 12 13 14
Depth of Pit / Wall Height (ft) Depth of Pit / Wall Height ft)
Distance = 4 f t Distance = 5 f t Distance = 6 f t Distance = 5 f t Distance = 6 f t Distance = 8 f t
Figure 12: Case 5 - Power Increase (AGZ030-070E) Figure 15: Case 5 - Power Increase (AGZ075-130E)
Power Increase (AGZ030-070E) Power Increase (AGZ075-130E)
9.0 9.0
8.0 8.0
7.0 7.0
% Power Increase
6.0
% Power Increase
6.0
5.0 5.0
4.0 4.0
3.0 3.0
2.0 2.0
1.0 1.0
0.0 0.0
0 8 10 12 13 14 0 8 10 12 13 14
Depth of Pit / Wall Height (ft) Depth of Pit / Wall Height (ft)
Distance = 4 f t Distance = 5 f t Distance = 6 f t Distance = 5 f t Distance = 6 f t Distance = 8 f t
Models AGZ140-241E:
The Case 5 figures for models AGZ140-241E show adjustment
factors for pit/wall heights of 6 feet, 8 feet, and 10 feet.
Figure 16: Case 5 - Full Load Capacity Reduction Figure 18: Case 5 - Power Increase
(AGZ140-180E) (AGZ140-211E)
Full Load Capacity Reduction (AGZ140-180E) Power Increase (AGZ140-211E)
6.0 9.0
8.0
5.0
7.0
% Capacity Reduction
% Power Increase
4.0 6.0
3.0 5.0
4.0
2.0
3.0
1.0 2.0
0.0 1.0
0 8 10 12 13 14
0.0
Depth of Pit / Wall Height (ft) 0 8 10 12 13 14
Distance = 6 ft Distance = 8 ft Distance = 10 ft Depth of Pit / Wall Height (ft)
Distance = 6 f t Distance = 8 f t Distance = 10 f t
Figure 17: Case 5 - Full Load Capacity Reduction Figure 19: Case 5 - Power Increase
(AGZ191-241E) (AGZ226-241E)
5.0 8.0
% Power Increase
7.0
4.0
6.0
3.0 5.0
4.0
2.0
3.0
1.0 2.0
1.0
0.0
0 8 10 12 13 14 0.0
Depth of Pit / Wall Height (ft) 0 8 10 12 13 14
Depth of Pit / Wall Height (ft)
Distance = 6 ft Distance = 8 ft Distance = 10 ft
Distance = 6 ft Distance = 8 ft Distance = 10 ft
Air
Vent
Strainer
Inlet
Isolation
P Vibration
Valves
Eliminators
Outlet
Flow
Switch
Drain
WELDED PIPE CONNECTIONS ARE NOT ALLOWED
BETWEEN THE STRAINER AND EVAPORATOR DUE
TO THE CHANCE OF SLAG ENTERING THE EVAPORATOR
3.0 in
2.0 in. 2.5 in
4.0 in can occur. See Variable Evaporator Flow on page 76 for set
10.0 point information.
6.0 in.
System Water Considerations
8.0 in.
All chilled water systems need adequate time to recognize
a load change, respond to the change and stabilize to avoid
undesirable short cycling of the compressors or loss of
1.0
temperature control. In air conditioning systems, the potential
for short cycling usually exists when the building load falls
below the minimum chiller plant capacity or on close-coupled
systems with very small water volumes. Some of the things
the designer should consider when looking at water volume
0.1
are the minimum cooling load, the minimum chiller plant
10.0 100.0 1000.0 capacity during the low load period and the desired cycle time
Flow Rate (gpm) for the compressors. Assuming that there are no sudden load
changes and that the chiller plant has reasonable turndown, 2. Add a glycol solution to the chilled water system. Burst
a rule of thumb of “gallons of water volume equal to two to protection should be approximately 10°F below minimum
three times the chilled water gpm flow rate” is often used. A design ambient temperature.
storage tank may have to be added to the system to reach the 3. Insulate the exposed piping.
recommended system volume. Refer to AG 31-003 for method
of calculating “Minimum Chilled Water Volume”. 4. Add thermostatically controlled heat by wrapping the
lines with heat tape.
The water quality provided by the owner/occupant/operator/
5. When glycol is added to the water system for freeze
user to a chiller system should minimize corrosion, scale
protection, the refrigerant suction pressure will be lower,
buildup, erosion, and biological growth for optimum efficiency
cooling performance less, and water side pressure drop
of HVAC equipment without creating a hazard to operating
greater. See “Table 4: Glycol Performance Factors” on
personnel or the environment. Strainers must be used to
page 15 for flow rate and pressure drop adjustment
protect the chiller systems from water-borne debris. Daikin will
factors.
not be responsible for any water-borne debris damage or water
side damage to the chiller heat exchangers due to improperly
treated water. Chilled Water Pump
Water systems should be cleaned and flushed prior to chiller It is important that the chilled water pumps be wired to, and
installation. Water testing and treatment should be verified controlled by, the chiller’s microprocessor. When equipped
during initial chiller installation/commissioning and maintained with optional dual pump output, the chiller controller has the
on a continuous basis by water treatment professionals (see capability to selectively send the signal to a pump relay (by
Limited Product Warranty). others) to start pump A or B or automatically alternate pump
selection and also has standby operation capability. The
CAUTION controller will energize the pump whenever at least one circuit
The improper use of detergents, chemicals, and additives on the chiller is enabled to run, whether there is a call for
in the chiller system water may adversely affect chiller cooling or not. This helps ensure proper unit start-up sequence.
performance and potentially lead to repair costs not covered The pump will also be turned on when the water temperature
by warranty. Any decision to use these products is at the goes below the Freeze Setpoint for longer than a specified time
discretion of the owner/occupant/operator/user as such they
to help prevent evaporator freeze-up. Connection points are
assume full liability/responsibility for any damage that may
occur due to their use. shown in the Field Wiring Diagram beginning on page 48.
CAUTION
Evaporator Freeze Protection Adding glycol or draining the system is the recommended
Evaporator freeze-up can be a concern in the application of method of freeze protection. If the chiller does not have
air-cooled water chillers in areas experiencing below freezing the ability to control the pumps and the water system is not
temperatures. To protect against freeze-up, insulation and an drained or does not have adequate glycol in temperatures
electric heater are furnished with the evaporator. Models 030 below freezing, catastrophic evaporator failure may occur.
to 241 have an external plate heater and thermostat. These Failure to allow pump control by the chiller may cause the
heaters help protect the evaporator down to -20°F (-29°C) following problems:
ambient air temperature. The evaporator heater cable is factory
1. If the chiller attempts to start without first starting the
wired to the 115 volt control circuit transformer in the control
pump, the chiller will lock out on the No Flow alarm and
box. A 115V power source for the heater and controls may
require manual reset.
also be supplied from a separate power feed to maximize unit
protection if desired. Refer to the field wiring diagram on page 2. If the chiller evaporator water temperature drops below
48 for additional information on supplying a separate 115V the “Freeze setpoint” the chiller will attempt to start the
power feed. water pumps to avoid evaporator freeze. If the chiller
does not have the ability to start the pumps, the chiller
Operation of the heaters is automatic through the sensing
will alarm due to lack of water flow.
thermostat that energizes the evaporator heaters for protection
against freeze-up. Unless the evaporator is drained in the 3. If the chiller does not have the ability to control the
winter or contains an adequate concentration of anti-freeze, the pumps and the water system is not to be drained in
disconnect switch to the evaporator heater must not be open. temperatures below freezing or contain glycol, the chiller
may be subject to catastrophic evaporator failure due to
Although the evaporator is equipped with freeze protection,
freezing. The freeze rating of the evaporator is based on
it does not protect water piping external to the unit or the
the evaporator heater and pump operation. The external
evaporator itself if there is a power failure or heater burnout, or
brazed plate heater itself may not be able to properly
if the chiller is unable to control the chilled water pumps. Use
protect the evaporator from freezing without circulation
one of the following recommendations for additional freeze
of water.
protection:
1. If the unit will not be operated during the winter, drain the
evaporator and chilled water piping and flush with glycol.
Partial Heat Recovery It is recommended that the field installed heat recovery water
piping include:
Partial heat recovery for Trailblazer® chillers is achieved by
adding an auxiliary heat exchanger in each unit refrigerant • a field-installed safety or relief valve and expansion
circuit between the compressors and the condenser coils. tank on the water side to prevent risks in case the water
The heat exchangers transfer the heat from the compressor temperature thermostat should fail.
discharge gas to a separate water loop which can be used • a water tank and an additional water heater in the heat
for various heating applications. The heating recovery cycle recovery piping loop for initial water temperature control
is only available when the chiller is running. The partial and better loop stability. Typical loop sizing guidance
heat recovery auxiliary heat exchanger can return water up is water volume (in gallons) be greater than or equal to
to 155°F; however, this value cannot be set. The amount approximately two to three times the heat recovery water
of heat produced can be up to 50% of the nominal cooling flow rate (in gallons/minute).
capacity and is dependent on the requested cooling load, the
operating temperatures, and the water flow rate through the Partial Heat Recovery Freeze Avoidance
auxiliary heat exchangers. Contact a local Daikin Applied sales The heat recovery condenser is insulated; a factory-installed
representative for information on specific applications. heater will protect the heat exchanger from freezing in
ambient temperatures down to -20°F (-29°C). When the
WARNING ambient temperature drops to approximately 39°F (3.9°C) the
Potable water cannot be used in the partial heat recovery thermostat energizes the heaters. The inlet and outlet piping
system due to the single wall construction of the heat should be protected against freezing by one of the following
exchangers. methods:
Partial heat recovery components that are factory-supplied: • Install heat tape on all field-installed water piping
• Brazed plate heat exchangers - one in each circuit with • Add freeze-inhibiting fluid to the partial heat recovery
the water piped together in parallel for one inlet and one water loop. If adequate amounts of glycol are supplied, it
outlet water connection, see Figure 50 for pressure drops. is not required to power the heater.
• Insulation of heat exchangers and water piping at the unit.
• Separate temperature sensors for inlet and outlet water
piping at the heat exchangers.
• Connections for air vent at the outlet water piping and
drain at the inlet water piping.
• Immersion heater for each auxiliary heat exchanger for
freeze protection.
Required partial heat recovery field piping (see next page) and
connections are listed below.
• an external 3-way valve or a variable speed pump in the
auxiliary heat exchanger water piping for modulation of
flow through the heat exchangers by the unit controller.
Heat recovery water loop pump must also be controlled
by the chiller controller.
• a cleanable strainer with perforations no larger than
0.063” (1.6 mm) diameter must be installed within 5 feet
(1500 mm) of pipe length from the heat exchanger inlet
and downstream of any welded connections, see Figure
21 for pressure drop.
• water piping and other portions of the heat recovery water
loop must be insulated to prevent heat loss and possible
injury due to hot surfaces.
• separate 120 volt power supply for immersion heaters. A
junction box for a 120 Volt power connection is provided.
NOTE: If the partial heat exchanger is drained, the heater
must be turned off to avoid damaging the heat
exchanger. The heater should only be on when the
heat recovery heat exchanger has water in it.
THERMOMETER VIBRATION
(USER OPTION) ELIMINATOR
VIBRATION
ELIMINATOR
INLET WATER
STRAINER
1,2
ELECTRONIC
3-WAY VALVE
HEAT 1,2
RECOVERY FIELD INSTALLED
HEAT LOAD WATER PUMP
NOTES:
1. A VFD CONTROLLED WATER PUMP OR AN ELECTRONIC 3-WAY VALVE IS REQUIRED AND MUST BE CONTROLLED BY THE CHILLER.
2. FIELD INSTALLED 3-WAY VALVE OR WATER PUMP VFD TO BE CONTROLLED BY 0-10 DCV OR 4-20 mA OUTPUT FROM
THE CHILLER UNIT CONTROLLER.
3. GALLONS OF WATER VOLUME FOR THE HEAT RECOVERY PIPING LOOP SHOULD EQUAL 2 TO 3 TIMES THE
HEAT RECOVERY LOOP GPM FLOW RATE.
4. FOR POTABLE WATER USE - A SECONDARY HEAT EXCHANGER IN A SEPARATE LOOP IS REQUIRED.
5. WATER PIPING CONNECTIONS AT THE UNIT ARE 2.0" VICTAULIC.
CONDENSER AIR
ASSEMBLY FLOW
SCHRADER
VALVE
CHARGING
DISCHARGE VALVE
DISCHARGE HIGH PRESSURE SUCTION SUCTION
AIR
SHUT-OFF SWITCH TRANSDUCER TEMP. SENSOR
FLOW DISCHARGE SUCTION SHUT-OFF
VALVE (WL1, WL2) (ST1, ST2)
AIR (OPTIONAL) TRANSDUCER BALL VALVE
FLOW (WH1, WH2) (OPTIONAL)
DISCHARGE SCHRADER
TUBING VALVE
COMPRESSOR SUCTION
(WAA) (TANDEM) TUBING
LOCATED BEHIND
THE CONTROL BOX
EXPANSION VALVE
SENSING BULB
LIQUID WYE STRAINER REQUIRED
TUBING (FACTORY OR FIELD
INSTALLED)
HOT GAS SOLENOID HGBP
ACCESS BYPASS TUBING VALVE VALVE
FITTING
(OPTIONAL) WATER
IN
SCHRADER
VALVE
LEAVING WATER
LIQUID TEMP. SENSOR
SHUT-OFF
VALVE
(OPTIONAL) WATER
OUT
FILTER SCHRADER SOLENOID SIGHT SCHRADER THERMAL FLOW SENSOR PLATE TYPE
DRIER VALVE VALVE GLASS VALVE EXPANSION VALVE (OPTIONAL) EVAPORATOR
(REPLACEABLE (EXV – OPTIONAL)
CORE OR SEALED)
18 www.DaikinApplied.com
Refrigerant Schematics
Refrigerant Schematics
AGZ075-101E PACKAGE CHILLER
NOTE: PIPING SHOWN FOR ONE SYSTEM OF UNIT. UNITS MICROCHANNEL ALUMINUM COIL
HAVE TWO INDEPENDENT SYSTEMS.
334549802 0D
www.DaikinApplied.com 19
OIL SIGHT OIL
GLASS HEATER FUSIBLE
CHARGING
PLUG
VALVE
ENTERING WATER
TEMPERATURE
LIQUID SENSOR WYE STRAINER REQUIRED
TUBING (FACTORY OR FIELD
INSTALLED)
HOT GAS SOLENOID HGBP
ACCESS BYPASS TUBING VALVE VALVE
FITTING
(OPTIONAL) WATER
SCHRADER IN
VALVE
LEAVING WATER
LIQUID TEMP. SENSOR
SHUT-OFF
VALVE
WATER
OUT
FILTER SCHRADER SOLENOID SCHRADER SIGHT ELECTRICAL FLOW SENSOR PLATE TYPE
DRIER VALVE VALVE VALVE GLASS EXPANSION VALVE (OPTIONAL) EVAPORATOR
(REPLACEABLE CORE)
SCHRADER
AIR VALVE AIR
FLOW FLOW
SUCTION
TRANSDUCER
(WL1, WL2)
HOTGAS CHARGING
SHUT-OFF VALVE
SUCTION SHUT-OFF
SCHRADER VALVE SUCTION BALL VALVE WITH
AIR AIR
VALVE TEMP. SENSOR SCHRADER VALVE
FLOW FLOW DISCHARGE
(ST1, ST2) (OPTION)
DISCHARGE HIGH PRESSURE
DISCHARGE TRANSDUCER SWITCH
DISCHARGE (WH1, WH2)
SHUT-OFF VALVE
SOLENOID
WITH SCHRADER
VALVE
VALVE
ENTERING WATER
TEMPERATURE
LIQUID SENSOR WYE STRAINER REQUIRED
TUBING (FACTORY OR FIELD
INSTALLED)
HOT GAS SOLENOID HGBP
ACCESS BYPASS TUBING VALVE VALVE
FITTING
(OPTIONAL) WATER
SCHRADER IN
VALVE
LEAVING WATER
LIQUID TEMP. SENSOR
SHUT-OFF
VALVE
WATER
OUT
FILTER SCHRADER SOLENOID SCHRADER SIGHT ELECTRICAL FLOW SENSOR PLATE TYPE
DRIER VALVE VALVE VALVE GLASS EXPANSION VALVE (OPTIONAL) EVAPORATOR
(REPLACEABLE CORE)
20 www.DaikinApplied.com
Refrigerant Schematics
NOTE: PIPING SHOWN FOR ONE SYSTEM OF UNIT. UNITS AGZ140-180E PACKAGE CHILLER
HAVE TWO INDEPENDENT SYSTEMS. MICROCHANNEL ALUMINUM COIL
CONDENSER 334549802 0D
ASSEMBLY
HOTGAS CHARGING
SHUT-OFF VALVE
AIR AIR SUCTION SHUT-OFF
FLOW FLOW VALVE SUCTION BALL VALVE WITH
TEMP. SENSOR SCHRADER VALVE
DISCHARGE
(ST1, ST2) (OPTION)
DISCHARGE HIGH PRESSURE
DISCHARGE
TRANSDUCER SWITCH
SOLENOID
SCHRADER (WH1, WH2)
VALVE
VALVE
LIQUID LINE
CHECK VALVE
SCROLL
DISCHARGE OUTSIDE AIR COMPRESSOR SUCTION
SHUT-OFF VALVE TEMPERATURE (TANDEM OR TRIO)
WITH SCHRADER
TUBING
(WAA) DISCHARGE
Figure 28: AGZ140-180E Package Chiller with Microchannel
VALVE LOCATED ON
www.DaikinApplied.com 21
CONDENSER RAIL TUBING
ENTERING WATER
TEMPERATURE
LIQUID SENSOR WYE STRAINER REQUIRED
TUBING (FACTORY OR FIELD
INSTALLED)
HOT GAS SOLENOID HGBP
ACCESS BYPASS TUBING VALVE VALVE
FITTING
(OPTIONAL) WATER
SCHRADER IN
VALVE
LEAVING WATER
LIQUID TEMP. SENSOR
SHUT-OFF
VALVE
WATER
OUT
FILTER SCHRADER SOLENOID SCHRADER SIGHT ELECTRICAL FLOW SENSOR PLATE TYPE
DRIER VALVE VALVE VALVE GLASS EXPANSION VALVE (OPTIONAL) EVAPORATOR
(REPLACEABLE CORE)
DISCHARGE
AIR SOLENOID AIR AIR AIR
SCHRADER SCHRADER
FLOW VALVE FLOW FLOW FLOW
VALVE VALVE
HOTGAS
AIR AIR SHUT-OFF SUCTION
VALVE SUCTION
FLOW FLOW TEMP. SENSOR
PRESSURE
TRANSDUCER (ST1, ST2)
DISCHARGE (WL1, WL2)
PRESSURE
SCHRADER TRANSDUCER DISCHARGE
DISCHARGE VALVE (WH1, WH2) HIGH PRESSURE
SWITCH
TUBING
22 www.DaikinApplied.com
Refrigerant Schematics
CONDENSER ASSEMBLY
(10 FAN CONFIGURATION SHOWN)
NOTES:
AIR FLOW AIR FLOW SCHRADER AIR FLOW
VALVE 1. PIPING SHOWN FOR ONE SYSTEM OF UNIT.
AGZ075-241E PACKAGE CHILLER UNITS HAVE TWO INDEPENDENT SYSTEMS.
WITH HEAT RECOVERY 2. HEAT RECOVERY WATER INLET/OUTLET FROM FIELD
INSTALLED REMOTE PUMP AND WATER CIRCUIT.
MICROCHANNEL ALUMINUM COIL 3. DISCHARGE GAS FROM THE COMPRESSOR ALWAYS
PASSES THROUGH THE HEAT EXCHANGER BEFORE
GOING TO THE CONDENSER COILS.
AIR FLOW HEAT FROM THE HEAT EXCHANGER GAS FLOW IS
AIR FLOW
TRANSFERRED TO THE REMOTE WATER CIRCUIT
WHEN THE REMOTE PUMP IS TURNED ON.
4. LOCATION OF CHARGING VALVE ON SUCTION TUBING
DISCHARGE DEPENDS ON UNIT CONFIGURATION. REFERENCE FLAG
SOLENOID
VALVE OUTSIDE AIR TEMP. SENSOR NOTE 4 FOR PROPER LOCATION (2 PLACES).
(WAA)
LOCATED ON 334549812 0A
CONDENSER RAIL
HEAT RECOVERY
DESUPERHEATERS
HEAT EXCHANGERS DISCHARGE
ASSEMBLY TUBING
LEAVING WATER (HX-COND.) SUCTION TEMP. SENSOR
TEMP. SENSOR LIQUID LINE (ST1, ST2)
CHECK VALVE HOT GAS
SHUT-OFF SUCTION
VALVE TRANSDUCER SUCTION
WATER (WL1, WL2) SHUT-OFF VALVE
DISCHARGE DISCHARGE WITH SCHRADER VALVE
OUTLET HIGH PRESSURE
TRANSDUCER (OPTIONAL)
2 (WH1, WH2) SWITCH
DISCHARGE
www.DaikinApplied.com 23
TUBING SCHRADER
ENTERING WATER (CMPR-HX) VALVE
TEMP. SENSOR CHARGING
VALVE CHARGING
*ALL UNITS EXCEPT VALVE
191, 211, 226 & 241 *191, 211, 226 & 241
DISCHARGE 4 UNITS ONLY
4
WATER SHUT-OFF VALVE
INLET WITH SCHRADER
*WYE STRAINER VALVE SUCTION
REQUIRED SCROLL TUBING
(FIELD INSTALLED) DISCHARGE COMPRESSOR
2 SHUT-OFF VALVE (TANDEM OR TRIO)
WITH SCHRADER FUSIBLE
VALVE OIL PLUG
OIL SIGHT HEATER
Figure 30: AGZ75-241E Package Chiller with Microchannel and Heat Recovery
GLASS
LIQUID HOT GAS
TUBING BYPASS
TUBING ENTERING WATER
(OPTIONAL) TEMPERATURE
SENSOR WYE STRAINER REQUIRED
CHARGING (FACTORY OR FIELD INSTALLED)
VALVE HGBP SCHRADER
SOLENOID VALVE
VALVE VALVE
WATER
IN
ACCESS
FITTING
LEAVING WATER
TEMP. SENSOR
SCHRADER SIGHT PLATE TYPE
LIQUID SCHRADER VALVE GLASS EVAPORATOR
SHUT-OFF VALVE WATER
VALVE OUT
FLOW SENSOR
SOLENOID (OPTIONAL)
VALVE ELECTRICAL
EXPANSION VALVE
FILTER DRIER
(REPLACEABLE CORE)
209
L4 L2 1822
8.2
M4 M2 71.8
REF.
BLANK PANELS ARE
USED ON UNIT SIDES. CONTROL
BOX
51 497
2.0 19.6 64
[22] 22 2X 2.5
Ø.875 KNOCKOUTS 80 127 .875 KNOCKOUTS
POWER ENTRY KNOCKOUTS 165 370
3.2 5.0 FIELD CONTROL
ARE ON THE OPPOSITE 6.5 14.6 2546
CONNECTIONS
SIDE OF CONTROL BOX QTY. 3 100.2
[22] 2389
152 A Ø.875
EVAP. 94.1
WATER 6.0 B POWER ENTRY
INLET KNOCKOUTS
FRONT OR
1094 RIGHT SIDE Y
43.1 153
635 6.0 EVAP.
L1 - L4, 25.0
LIFTING 266
LOCATIONS 10.5
L3 L1
506 L4 EVAP. L2 506 WYE-STRAINER
19.9 WATER 19.9 FRONT LEFT REQUIRED X
OUTLET 797 CORNER POST (FACTORY OR FIELD
PURPOSELY INSTALLED OPTION) 2235
31.4 HIDDEN
Z 88.0
2396 DIMENSION DOES NOT INCLUDE
94.3 LIFTING BRACKETS
24 www.DaikinApplied.com
Dimensions and Weights - Packaged Units
Dimensions and Weights - Packaged Units
AGZ035E 2873 (1303) 2887 (1310) 1051 (477) 861 (391) 528 (240) 433 (196) 1005 (456) 824 (374) 581 (264) 476 (216)
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE PACKAGE UNITS WITH MICROCHANNEL COILS
M3 M1 CG LOCATION, IN (MM)
337 1721 337 UNIT MODEL
13.3 67.8 13.3 X Y Z
L3 L1
AGZ040E 39.8 (1011) 45.9 (1166) 38.4 (975)
52 AGZ045E 38.9 (988) 44.5 (1130) 41.2 (1047)
2.0 AGZ050E 39.1 (993) 44.9 (1141) 41.2 (1047)
COMPRESSORS
CIRCUIT #2 AGZ055E 39.1 (993) 44.8 (1138) 41.2 (1047)
COMPRESSORS
CIRCUIT #1 AGZ060E 39.2 (996) 44.6 (1133) 41.1 (1044)
AGZ065E 39.2 (996) 44.6 (1133) 41.1 (1044)
AGZ070E 36.8 (935) 41.8 (1062) 42.6 (1082)
TOP VIEW WITH
COILS AND
FANS REMOVED EVAP. DIMENSIONS IN (MM) CONNECTION SIZE
UNIT MODEL
A B (VICTAULIC)
AGZ040E 22.8 (579) 1.5 (38) 2.5 (64)
AGZ045E 21.4 (544) 0.11 (3) 2.5 (64)
AGZ050E 20 (508) 2.7 (69) 2.5 (64)
AGZ055E 19.3 (490) 2.0 (51) 2.5 (64)
19 AGZ060E 17.6 (447) 0.3 (8) 2.5 (64)
.750
QTY. 4 52 AGZ065E 17.6 (447) 0.3 (8) 2.5 (64)
2.0 AGZ070E 17.6 (447) 0.3 (8) 2.5 (64)
L4 L2 208
1822
8.2
M4 M2 71.8
REF.
CONTROL
Figure 32: AGZ040E - AGZ070E, 4 Fan Models
BOX
497
19.6
51
2.0 64
22 2X 2.5
[22]
.875 KNOCKOUTS
www.DaikinApplied.com 25
Ø.875 KNOCKOUTS 80 127
POWER ENTRY KNOCKOUTS FIELD CONTROL 165 370
3.2 5.0 CONNECTIONS 6.5 14.6
ARE ON THE OPPOSITE 2546
SIDE OF CONTROL BOX QTY. 3 100.2
2.0
M6 L4 M4 L2 M2
www.DaikinApplied.com 27
CONTROL
BOX
2506
98.6
WYE-STRAINER
REQUIRED 22 X
(FACTORY OR .875 KNOCKOUTS 2355
FIELD INSTALLED FIELD CONTROL 92.7
OPTION) CONNECTIONS
51 QTY. 3
2.0 64
80 2.5
153 127
3.1 213 Y
858 6.0 5.0 64
305 8.4
33.8 2.5
12.0
290
11.4
L3 L1 1
L4 EVAP. EVAP. L2 609 22 292 165
996 WATER WATER .875 KNOCKOUTS
1
L1 - L4, 24.0 11.5 6.5 [22]
LIFTING 39.2 OUTLET INLET POWER ENTRY KNOCKOUTS .875 POWER ENTRY
LOCATIONS Z ARE ONTHE OPPOSITE SIDE 175 KNOCKOUTS
OF THE CONTROL BOX 2235 6.9 FRONT OR RIGHT SIDE
88.0
4879 37 DIMENSION DOES NOT INCLUDE
LIFTING BRACKETS 334547121 0A
192.1 1.5
AGZ-E 8 FANS
UNIT SHIPPING WEIGHT OPERATING WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER, LBS (KG) MOUNTING (OPERATING) WEIGHT, LBS (KG)
MODEL LBS (KG) LBS (KG) L1 L2 L3 L4 M1 M2 M3 M4 M5 M6
AGZ110E 5437 (2466) 5528 (2508) 1762 (799) 1769 (802) 951 (431) 955 (433) 1424 (646) 1430 (649) 845 (383) 849 (385) 489 (222) 491 (223)
AGZ120E 5696 (2584) 5796 (2629) 1907 (865) 1915 (869) 935 (424) 939 (426) 1548 (702) 1555 (705) 878 (398) 882 (400) 465 (211) 467 (212)
AGZ130E 5792 (2627) 5903 (2678) 1941 (880) 1863 (845) 1015 (460) 974 (442) 1575 (714) 1511 (685) 920 (417) 883 (401) 517 (235) 496 (225)
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
M1
M5 M3 UNIT CG LOCATION, IN (MM) EVAP. DIMENSIONS, IN (MM) CONNECTION
1711 1564 2433 315
67.4 61.6 95.8 12.4 MODEL X Y Z A B SIZE, IN.
L3 L1 AGZ140E 44.1 (1120) 42.6 (1083) 83.3 (2117) 122.1 (3102) 67.51 (1715)
AGZ150E 43.9 (1116) 42.4 (1077) 83.3 (2115) 120.5 (3062) 65.9 (1674) 4.0 (102)
52 AGZ161E 43.5 (1105) 42.3 (1074) 83.4 (2117) 120.5 (3062) 65.9 (1674)
19 2.0
.750 NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
TOP VIEW WITH QTY. 6 MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
COILS AND FANS SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
COMPR.
REMOVED CIR. 2 NOTE:
1. IT IS RECOMMENDED THAT THE SIDE LOCATIONS BE USED
FOR POWER ENTRY WIRE SIZES LARGER THAN 350 MCM.
COMPR.
1118 CIR. 1
44.0
52
2.0
M6 L4 M4 L2 M2
Figure 35: AGZ140E - AGZ161E, 10 Fan Models
CONTROL
BOX X 2355
92.7
51
2.0 64
2.5 Y
80 127
210 3.1 64 213
858 5.0
8.3 2.5 8.4
33.8
22
290 305 .875 KNOCKOUTS
11.4 12.0 FIELD CONTROL
L3 L1 CONNECTIONS
1919 L4 EVAP. L2 609 QTY. 3 292 165
EVAP. [22] 1
75.5 WATER WATER 24.0 22 1 11.5 6.5 175
L1 - L4 .875
OUTLET INLET 2235 6.9 POWER ENTRY
LIFTING WYE-STRAINER .875 KNOCKOUTS
37 88.0 KNOCKOUTS FRONT
LOCATIONS REQUIRED POWER ENTRY KNOCKOUTS
(FACTORY OR FIELD 1.5 DIMENSION DOES NOT INCLUDE OR RIGHT SIDE
Z ARE ON THE OPPOSITE SIDE
INSTALLED OPTION) LIFTING BRACKETS
6025 OF THE CONTROL BOX
334547131 0B
237.2 AGZ-E 10 FANS
UNIT SHIPPING WEIGHT OPERATING WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER, LBS (KG) MOUNTING (OPERATING) WEIGHT, LBS (KG)
MODEL LBS (KG) LBS (KG) L1 L2 L3 L4 M1 M2 M3 M4 M5 M6
AGZ140E 6555 (2973) 6674 (3027) 1862 (845) 1868 (847) 1410 (640) 1415 (642) 1411 (640) 1416 (642) 1070 (485) 1074 (487) 850 (386) 853 (387)
AGZ150E 6617 (3001) 6745 (3059) 1888 (856) 1881 (853) 1426 (647) 1421 (645) 1433 (650) 1428 (648) 1085 (492) 1081 (490) 861 (391) 858 (389)
AGZ161E 6668 (3025) 6802 (3085) 1917 (870) 1876 (851) 1453 (659) 1422 (645) 1456 (660) 1425 (646) 1104 (501) 1080 (490) 878 (398) 859 (390)
28 www.DaikinApplied.com
Dimensions and Weights - Packaged Units
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE.
M1
M5 M3
1711 1564 2433 315
67.4 61.6 95.8 12.4
UNIT CG LOCATION, IN (MM) EVAP. DIMENSIONS, IN (MM) CONNECTION
L3 L1 MODEL X Y Z A B SIZE, IN.
52
2.0 AGZ170E 43.2 (1096) 40.4 (1025) 83.6 (2123) 119 (3022) 64.3 (1634)
4.0 (102)
AGZ180E 44.1 (1119) 39.4 (1000) 82.8 (2103) 117 (2971) 62.4 (1584)
TOP VIEW WITH COMPR. NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
COILS AND FANS CIR. 2 MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
REMOVED SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
NOTE:
1. IT IS RECOMMENDED THAT THE SIDE LOCATIONS BE USED
FOR POWER ENTRY WIRE SIZES LARGER THAN 350 MCM.
COMPR.
1118 CIR. 1
44.0 19
.750
Figure 36: AGZ170E - AGZ180E, 10 Fan Models
QTY. 6 52
2.0
M6 L4 M4 L2 M2
www.DaikinApplied.com 29
2506
98.6
CONTROL 2355
BOX X 92.7
51
2.0 64
2.5 Y
81 127
210 3.2 5.0 64 213
858
8.3 2.5 8.4
33.8
22
290 305 .875 KNOCKOUTS
11.4 12.0 FIELD CONTROL
L3 L1 CONNECTIONS
1919 L4 L2 QTY. 3
EVAP. EVAP. 609 22 1 292 165 [22]
75.5 .875 1
L1 - L4 WATER WATER 24.0 .875 KNOCKOUTS 11.5 6.5
WYE-STRAINER OUTLET INLET 37 175 POWER ENTRY
LIFTING REQUIRED POWER ENTRY KNOCKOUTS 2235 6.9 KNOCKOUTS FRONT
LOCATIONS 1.5
(FACTORY OR FIELD ARE ON THE OPPOSITE SIDE 88.0 OR RIGHT SIDE
INSTALLED OPTION) Z OF THE CONTROL BOX DIMENSION DOES NOT INCLUDE
6025 LIFTING BRACKETS 334547131 0B
237.2
AGZ-E 10 FANS
UNIT SHIPPING WEIGHT OPERATING WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER, LBS (KG) MOUNTING (OPERATING) WEIGHT, LBS (KG)
MODEL LBS (KG) LBS (KG) L1 L2 L3 L4 M1 M2 M3 M4 M5 M6
AGZ170E 7170 (3252) 7307 (3314) 2072 (940) 1995 (905) 1581 (717) 1522 (690) 1571 (713) 1512 (686) 1197 (543) 1152 (523) 956 (434) 920 (417)
AGZ180E 7412 (3362) 7560 (3429) 2121 (962) 2127 (965) 1580 (717) 1584 (718) 1613 (732) 1617 (733) 1210 (549) 1214 (551) 951 (431) 954 (433)
M8 L6 M6 L4 M4 L2 M2 22 1
2241 52 .875 KNOCKOUTS
88.2 2.0 POWER ENTRY POINTS
3577
140.8 w/o STRAINER OPTION FRONT & RIGHT SIDE
2506
37 CONTROL 98.6
22 1
CG 1.5 BOX
51 .875 KNOCKOUTS
2.0 POWER ENTRY POINTS CG 2355
WATER ARE ON OPPOSITE 92.7
INLET EVAP
SIDE OF CONTROL BOX
Y 923 WATER Y
OUTLET
36.3
305 127
12.0 5.0
L5 L3 L1 64 165
L6 308 L4 L2 80 213
2.5 6.5
12.1 3.1 64 175 8.4
1919 2436 2207 609 2.5 6.9
292
75.5 95.9 86.9 24.0 X
334547153 11.5
3167
Z 2235
124.7
7171 88.0
282.3 DIMENSION DOES NOT
INCLUDE LIFTING BRACKETS
NOTE:
1. IT IS RECOMMENDED THAT THE SIDE LOCATIONS BE USED
FOR POWER ENTRY WIRE SIZES LARGER THAN 350 MCM.
SHIP WEIGHT OPER. WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER MOUNTING (OPERATING) WEIGHT
UNIT
L1 L2 L3 L4 L5 L6 M1 M2 M3 M4 M5 M6 M7 M8
MODEL LBS KG LBS KG
LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG
AGZ191E 8635 3917 8785 3985 1759 798 1738 788 1458 661 1441 654 1127 511 1113 505 1578 716 1560 708 1164 528 1150 522 974 442 963 437 702 318 694 315
AGZ211E 8669 3932 8819 4000 1766 801 1753 795 1461 663 1450 658 1124 510 1116 506 1585 719 1573 713 1166 529 1158 525 975 442 968 439 700 318 695 315
30 www.DaikinApplied.com
Dimensions and Weights - Packaged Units
ISOLATOR MOUNTING HOLE LOCATIONS ARE ON BOTTOM SURFACE OF UNIT.
M1
M7 M5 M3
1711 2743 1114 2433 315
67.4 108.0 43.8 95.8 12.4 CG LOCATION
UNIT
L7 L5 L3 L1 X Y Z
MODEL
52 IN. MM IN. MM IN. MM
2.0 AGZ226E 43.8 1113 41.9 1064 113.8 2891
TOP VIEW 19 AGZ241E 43.8 1113 41.9 1064 113.2 2875
WITH COILS .75
AND FANS
REMOVED QTY 8
COMPRESSORS NOTE:
CIRCUIT #2 LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS. MOUNTING
[152] WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR
Ø6.0 COMPRESSORS WATER INCLUDED. SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE
1118 VICTAULIC CIRCUIT #1 THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
44.0 CONN. TYP.
52
2.0
M8 L8 L6 M6 L4 M4 L2 M2
Figure 38: AGZ226E - AGZ241E, 14 Fan Models
3281 [22] 1
129.2 .875 KNOCKOUTS
4617 POWER ENTRY POINTS
181.8 w/o STRAINER OPTION FRONT AND RIGHT SIDE
[22]
.875 KNOCKOUTS
www.DaikinApplied.com 31
FIELD CONTROL
CONNECTIONS
CONTROL 2506
37 22 1 BOX 98.6
CG 1.5 .875 KNOCKOUTS
51 POWER ENTRY POINTS CG
2.0 2355
WATER EVAP ARE ON OPPOSITE
INLET 92.7
SIDE OF CONTROL BOX
Y 923 WATER Y
OUTLET
36.3
305 127
12.0 5.0
L7 L5 L3 L1
L8 308 L6 L4 L2 64 165
80 213
12.1 2.5 6.5
3.1 8.4
64 175
1919 2207 1375 2207 609 2.5 6.9
75.5 86.9 54.1 86.9 24.0 292
11.5 X
4207 Z
165.6 2235
8317 88.0
327.4 DIMENSION DOES NOT
INCLUDE LIFTING BRACKETS
NOTE:
1. IT IS RECOMMENDED THAT THE SIDE LOCATIONS BE USED
FOR POWER ENTRY WIRE SIZES LARGER THAN 350 MCM.
SHIP WEIGHT OPER. WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER MOUNTING (OPERATING) WEIGHT
UNIT 334547143
L1 L2 L3 L4 L5 L6 L7 L8 M1 M2 M3 M4 M5 M6 M7 M8
MODEL LBS KG LBS KG
LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG
AGZ226E 9413 4270 9600 4354 1659 753 1640 744 1296 588 1282 582 1070 485 1058 480 708 321 700 318 1564 709 1546 701 1281 581 1266 574 1151 522 1138 516 832 377 822 373
AGZ241E 9501 4310 9688 4394 1683 763 1671 758 1309 594 1299 589 1075 488 1068 484 701 318 696 316 1586 719 1574 714 1292 586 1283 582 1158 525 1149 521 826 375 820 372
50
www.DaikinApplied.com 33
2.0
519 22 X 98.6
20.4 .875 KNOCKOUTS 2355
FIELD CONTROL 92.7
CONNECTIONS
HEAT RECOVERY QTY. 3
WATER INLET 51
1 2.0
64 334547122
1196 80 127 2.5
153 3.1
47.1 5.0 64 213 Y
858 6.0 305
33.8 2.5 8.4
12.0
290
11.4
22 2
L3 EVAP. EVAP. L1 165
996 L4 L2 609 .875 KNOCKOUTS 292 [22] 2
WATER WATER POWER ENTRY KNOCKOUTS 6.5
L1 - L4, 39.2 OUTLET INLET 24.0 11.5 175 .875 POWER ENTRY
LIFTING ARE ONTHE OPPOSITE SIDE 2235 KNOCKOUTS
OF THE CONTROL BOX
6.9
LOCATIONS Z 88.0 FRONT OR RIGHT SIDE
DIMENSION DOES NOT INCLUDE
4879 37 LIFTING BRACKETS
192.1 1.5
DISCH. 519
OUT
TYP. 20.4 REF.
1118 19
44.0 .750 COMPR.
C/L FOR QTY. 6 CIR. 1
ALL WATER
CONNECTIONS 52 1196
2.0 47.1 REF.
HEAT M6 L4 M4 L2 M2
RECOVERY
CIRCUIT 1 B
WYE-STRAINER BACK OF UNIT (HEAT RECOVERY DETAIL) JUNCTION BOX
A (w/o STRAINER OPTION) REQUIRED HEAT RECOVERY
HEAT RECOVERY (FACTORY OR FIELD FREEZE PROTECTION
FRONT OF UNIT
HEAT RECOVERY
WATER INLET 51
1 2.0 64
2.5
1196 80 127
210 64 213 Y
47.1 3.1 5.0
858 8.3 2.5 8.4
33.8 22
290 305 .875 KNOCKOUTS
11.4 12.0 FIELD CONTROL
L1 CONNECTIONS
L3
1919 L4 EVAP. L2 22 2 QTY. 3 165
EVAP. 609 292 [22] 2
75.5 WATER .875 KNOCKOUTS 6.5 .875
WATER INLET 24.0 11.5 2235 175
OUTLET POWER ENTRY KNOCKOUTS 6.9 POWER ENTRY
L1 - L4 37 88.0 KNOCKOUTS
LIFTING ARE ON THE OPPOSITE SIDE
1.5 OF THE CONTROL BOX DIMENSION DOES NOT INCLUDE FRONT OR
LOCATIONS LIFTING BRACKETS RIGHT SIDE
Z
6025 NOTE:
237.2 1. HEAT RECOVERY WATER CONNECTIONS FOR CIRCUIT 1 & 2 ARE CONNECTED WITH A TEE AND HAVE ONE INLET &
ONE OUTLET. CONNECTION SIZES ARE 2.0 NOMINAL VICTAULIC.
2. IT IS RECOMMENDED THAT THE SIDE LOCATIONS BE USED FOR MAIN POWER ENTRY AT THE CONTROL BOX FOR
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS. WIRE SIZES LARGER THAN 350 MCM.
MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED. 3. POWER SUPPLIED FROM FIELD INSTALLED CIRCUIT FOR HEAT RECOVERY TO BE 120V 15A SERVICE.
SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES. JUNCTION BOX HAS A 1/2" FPT THREADED ENTRY PORT.
SHIP WEIGHT OPER. WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER MOUNTING (OPERATING) WEIGHT
UNIT
L1 L2 L3 L4 M1 M2 M3 M4 M5 M6 334547132
MODEL LBS KG LBS KG
LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG
AGZ140E 6805 3087 6948 3152 1781 808 1810 821 1594 723 1620 735 1328 602 1349 612 1125 510 1143 518 994 451 1010 458
AGZ150E 6880 3121 7036 3191 1804 818 1820 826 1620 735 1635 742 1346 611 1359 616 1143 518 1154 523 1013 459 1022 464
AGZ161E 6968 3161 7130 3234 1826 828 1855 841 1631 740 1656 751 1365 619 1386 629 1154 523 1172 532 1019 462 1035 469
34 www.DaikinApplied.com
Dimensions and Weights - Heat recovery Units
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE. CG LOCATION EVAP DIM'S
UNIT NOM. VICTAULIC
X Y Z A B CONN. SIZE
M1 MODEL
M5 M3 IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM
1711 1564 2433 315 43.5 1105 40.6 1031 89.7 2278 119 3023 64.3 1633
AGZ170E
67.4 61.6 95.8 12.4 4.0 102
AGZ180E 44.3 1125 39.9 1013 90.0 2286 117 2972 62.4 1585
TOP VIEW WITH L3 L1
COILS AND FANS 52 1118
REMOVED 44.0 REF.
2.0
WATER
HR OUTLET
HEAT CIR 2
RECOVERY COMPR. 1
CIRCUIT 2 CIR. 2 DISCH. HR WATER
IN TYP. CIR 1 INLET
DISCH. 519
OUT
TYP. 20.4 REF.
1118 19
44.0 .750 COMPR.
C/L FOR QTY. 6 CIR. 1
ALL WATER
CONNECTIONS 52 1196
2.0 47.1 REF.
M6 L4 M4 L2 M2
HEAT
RECOVERY B
CIRCUIT 1 JUNCTION BOX
BACK OF UNIT (HEAT RECOVERY DETAIL)
A (w/o STRAINER OPTION) WYE-STRAINER HEAT RECOVERY
HEAT RECOVERY REQUIRED FREEZE PROTECTION
FREEZE PROTECTION (FACTORY OR FIELD FRONT OF UNIT
FIELD POWER ENTRY INSTALLED OPTION)
3
50
2.0
www.DaikinApplied.com 35
HEAT RECOVERY 2506
WATER OUTLET 98.6
1
519 CONTROL
20.4 BOX 2355
X
Figure 42: AGZ170E - AGZ180E, Heat Recovery Units, 10 Fan Models
92.7
HEAT RECOVERY
WATER INLET 51
1 2.0 64
2.5
1196 80
127 64 Y
47.1 210 3.1 213
858 5.0 2.5
33.8 8.3 22 8.4
.875 KNOCKOUTS
290 305
FIELD CONTROL
11.4 12.0 CONNECTIONS
L3 L1 QTY. 3
1919 L4 EVAP. L2 165 [22]
EVAP. WATER 609 22 2 292 .875 2
75.5 6.5 175
L1 - L4 WATER INLET 24.0 .875 KNOCKOUTS 11.5 POWER ENTRY
37 2235 6.9
LIFTING OUTLET POWER ENTRY KNOCKOUTS KNOCKOUTS
1.5 88.0 FRONT OR
LOCATIONS ARE ON THE OPPOSITE SIDE
DIMENSION DOES NOT INCLUDE RIGHT SIDE
Z OF THE CONTROL BOX
LIFTING BRACKETS
6025
237.2 NOTE:
1. HEAT RECOVERY WATER CONNECTIONS FOR CIRCUIT 1 & 2 ARE CONNECTED WITH A TEE AND HAVE ONE INLET & 334547132
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS. ONE OUTLET. CONNECTION SIZES ARE 2.0 NOMINAL VICTAULIC.
MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED. 2. IT IS RECOMMENDED THAT THE SIDE LOCATIONS BE USED FOR MAIN POWER ENTRY AT THE CONTROL BOX FOR
SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES. WIRE SIZES LARGER THAN 350 MCM.
3. POWER SUPPLIED FROM FIELD INSTALLED CIRCUIT FOR HEAT RECOVERY TO BE 120V 15A SERVICE.
JUNCTION BOX HAS A 1/2" FPT THREADED ENTRY PORT.
SHIP WEIGHT OPER. WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER MOUNTING (OPERATING) WEIGHT
UNIT
L1 L2 L3 L4 M1 M2 M3 M4 M5 M6
MODEL LBS KG LBS KG
LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG
AGZ170E 7525 3413 7696 3491 1991 903 1942 881 1818 825 1773 804 1483 673 1446 656 1274 578 1242 563 1139 517 1111 504
AGZ180E 7789 3533 7971 3616 2016 914 2042 926 1854 841 1878 852 1501 681 1520 689 1296 588 1312 595 1164 528 1179 535
19
.75 [152]
Ø6.0 DISCH 519
QTY 8 OUT
HEAT RECOVERY VICTAULIC 20.4 REF.
TYP.
CIRCUIT 2 CONN. TYP.
HEAT RECOVERY
CIRCUIT 1 COMPRESSORS
1118 CIRCUIT #2
44.0 1196
1118
C/L FOR COMPRESSORS
44.0 47.1 REF.
WATER CIRCUIT #1
CONNECTIONS
M8 L6 M6 L4 M4 L2 M2 JUNCTION BOX
HEAT RECOVERY 2241 2
FREEZE PROTECTION 52 22 HEAT RECOVERY
FIELD POWER ENTRY 88.2 FREEZE PROTECTION
2.0 .875 KNOCKOUTS
3 3577 POWER ENTRY POINTS
140.8 w/o STRAINER OPTION FRONT & RIGHT SIDE FRONT OF UNIT
HEAT RECOVERY
WATER OUTLET
1 22
.875 KNOCKOUTS 2506
FIELD CONTROL 98.6
519 CONNECTIONS
20.4
Figure 43: AGZ191E - AGZ211E with Heat Recovery, 12 Fan Models
2355
37 CONTROL 92.7
22 2 BOX
HEAT CG 1.5
RECOVERY 51 .875 KNOCKOUTS
WATER 2.0 POWER ENTRY POINTS CG
INLET WATER EVAP ARE ON OPPOSITE
1 INLET
SIDE OF CONTROL BOX
1196 923 WATER
Y
47.1 OUTLET
36.3
305 127
12.0 5.0
L5 L3 L1 64 165
L6 308 L4 L2 80 2.5 6.5 213
12.1 3.1 64 175 8.4
1919 2436 2207 609 2.5 6.9
292
75.5 95.9 86.9 24.0 X
11.5
3167 2235
124.7 Z 88.0
7171 DIMENSION DOES NOT
282.3 INCLUDE LIFTING BRACKETS
CG LOCATION NOTE:
NOTE: 1. HEAT RECOVERY WATER CONNECTIONS FOR CIRCUIT 1 & 2 ARE CONNECTED WITH A TEE
UNIT AND HAVE ONE INLET & ONE OUTLET. CONNECTION SIZES ARE 2.0 NOMINAL VICTAULIC.
X Y Z LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS. MOUNTING
MODEL 2. IT IS RECOMMENDED THAT THE SIDE LOCATIONS BE USED FOR MAIN POWER ENTRY AT THE
WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR CONTROL BOX FOR WIRE SIZES LARGER THAN 350 MCM.
IN. MM IN. MM IN. MM WATER INCLUDED. SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE 3. POWER SUPPLIED FROM FIELD INSTALLED CIRCUIT FOR HEAT RECOVERY TO BE 120V 15A SERVICE.
AGZ191E 43.8 1113 40.8 1036 106.6 2708 THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES. JUNCTION BOX HAS A 1/2" FPT THREADED ENTRY PORT.
AGZ211E 43.9 1115 40.8 1036 106.4 2703
SHIP WEIGHT OPER. WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER MOUNTING (OPERATING) WEIGHT 334547154
UNIT
L1 L2 L3 L4 L5 L6 M1 M2 M3 M4 M5 M6 M7 M8
MODEL LBS KG LBS KG
LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG
AGZ191E 8970 4069 9154 4152 1676 760 1664 755 1506 683 1495 678 1319 598 1310 594 1500 680 1490 676 1192 541 1184 537 1052 477 1044 474 849 385 843 382
AGZ211E 9005 4085 9189 4168 1684 764 1679 762 1509 684 1505 683 1316 597 1313 596 1507 684 1503 682 1195 542 1192 541 1052 477 1049 476 847 384 844 383
36 www.DaikinApplied.com
Dimensions and Weights - Heat recovery Units
ISOLATOR MOUNTING HOLE LOCATIONS ARE ON BOTTOM SURFACE OF UNIT. BACK OF UNIT 1118
M1 (HEAT RECOVERY DETAIL) 44.0 REF
M7 M5 M3
1711 2743 1114 2433 315
67.4 108.0 43.8 95.8 12.4 WATER
TOP VIEW
L7 L5 L3 L1 OUTLET
WITH COILS HR
AND FANS CIR 2 1
REMOVED 52 HR WATER
DISCH CIR 1
IN TYP. INLET
2.0
19 DISCH 519
[152] OUT
.75 Ø6.0 TYP. 20.4 REF
HEAT RECOVERY QTY 8 VICTAULIC
CIRCUIT 2 CONN. TYP.
COMPRESSORS
HEAT RECOVERY CIRCUIT #2
CIRCUIT 1
1118 1118 1196
44.0 COMPRESSORS
44.0 CIRCUIT #1 47.1 REF
C/L FOR
WATER
CONNECTIONS 52
2.0
JUNCTION BOX
HEAT RECOVERY
M8 L8 L6 M6 L4 M4 L2 M2 FREEZE PROTECTION
HEAT RECOVERY
FREEZE PROTECTION 3281
FIELD POWER ENTRY
129.2 2
3 4617 [22]
.875 KNOCKOUTS
181.8 w/o STRAINER OPTION POWER ENTRY POINTS FRONT OF UNIT
FRONT AND RIGHT SIDE
50
2.0
[22]
HEAT RECOVERY .875 KNOCKOUTS
WATER OUTLET
www.DaikinApplied.com 37
FIELD CONTROL
1 CONNECTIONS
519
20.4
CONTROL 2506
Figure 44: AGZ226E - AGZ241E with Heat Recovery, 14 Fan Models
37 2 98.6
22 BOX
HEAT CG 1.5
51 .875 KNOCKOUTS
RECOVERY POWER ENTRY POINTS
WATER 2.0 CG 2355
INLET WATER ARE ON OPPOSITE
INLET SIDE OF CONTROL BOX
92.7
1196 1 EVAP
47.1 923 WATER Y
OUTLET
36.3
305 127
12.0 5.0
L7 L5 L3 L1 80 64 165
L8 308 L6 L4 L2
3.1 2.5 6.5 213
12.1
1919 2207 1375 2207 609 64 175 8.4
75.5 86.9 54.1 86.9 24.0 2.5 6.9
292
4207 11.5 X
Z
165.6
2235
8317 88.0
327.4 DIMENSION DOES NOT
INCLUDE LIFTING BRACKETS
CG LOCATION
UNIT NOTE: NOTE:
X Y Z LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS. MOUNTING 1. HEAT RECOVERY WATER CONNECTIONS FOR CIRCUIT 1 & 2 ARE CONNECTED WITH A TEE
MODEL WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR AND HAVE ONE INLET & ONE OUTLET. CONNECTION SIZES ARE 2.0 NOMINAL VICTAULIC.
IN. MM IN. MM IN. MM 2. IT IS RECOMMENDED THAT THE SIDE LOCATIONS BE USED FOR MAIN POWER ENTRY AT THE
WATER INCLUDED. SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE CONTROL BOX FOR WIRE SIZES LARGER THAN 350 MCM.
AGZ226E 43.9 1115 42.1 1069 121.0 3073 THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES. 3. POWER SUPPLIED FROM FIELD INSTALLED CIRCUIT FOR HEAT RECOVERY TO BE 120V 15A SERVICE.
JUNCTION BOX HAS A 1/2" FPT THREADED ENTRY PORT.
AGZ241E 44.0 1118 42.2 1072 120.3 3056
SHIP WEIGHT OPER. WEIGHT LIFTING (SHIPPING) WEIGHT BY CORNER MOUNTING (OPERATING) WEIGHT 334547144
UNIT
L1 L2 L3 L4 L5 L6 L7 L8 M1 M2 M3 M4 M5 M6 M7 M8
MODEL LBS KG LBS KG
LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG
AGZ226E 9784 4438 10012 4541 1573 713 1563 709 1309 594 1301 590 1145 519 1138 516 881 400 875 397 1489 675 1479 671 1304 591 1295 587 1219 553 1211 549 1011 459 1004 455
AGZ241E 9873 4478 10101 4582 1597 724 1593 723 1321 599 1318 598 1150 522 1147 520 874 396 872 396 1511 685 1507 684 1315 596 1312 595 1226 556 1223 555 1005 456 1003 455
Refrigerant Charge
(BASE PLATE)
3/4 [19] DIA HOLE FOR
ATTACHMENT TO
2 1/4 [57]
STEEL (4 TYP)
6 1/4 [159] (VIEW CUT AWAY FOR CLARITY)
2 7/8 [73]
2 7/8 [73]
7/8 [22]
5 1/8
[130]
1 1/2 7 1/4
[38] [184]
5 3/4
3/4 [19] REMOVABLE [146]
ADJUSTING BOLT
STEEL SHIM
(REMOVE AFTER
SPRING ADJUSTMENT)
3/4 [19] STD.WASHER
(BY OTHERS)
3/8 [10] GAP
1/2 [13]
6 1/8 [156]
ELASTOMERIC
FREE &
SNUBBER LIMIT STOPS
OPERATING
HEIGHT SHIPPING SPACER (NOT SHOWN
ASSY STRAP IN TOP VIEW
(NOT SHOWN FOR CLARITY)
IN OTHER VIEWS
FOR CLARITY) 3/8 [10]
10 1/4 8
[260] [203]
Figure 48: Seismic Neoprene Isolation Pads Table 11: Seismic Isolator Kit Numbers
8.00 AGZ-E Packaged Unit - Microchannel Fins
203.2 Model Neoprene Pads Spring Isolators
030-065 334549001 334548801
070 334549001 334548802
50
I
C H
F
40 B
Differential Pressure (ft)
G
D
30
A M
K
L
20
J
10
0
10 60 110 160 210 260 310 360 410
40
O P Q R S T U V W X Y Z AA BB CC
35
W
X
30 U
O
V CC
AA
S
Differential Pressure (ft)
T Z
25
BB
Q
R
P
20
15
10
0
10 110 210 310 410 510 610 710 810 910
Minimum Flow Rate2 Minimum Flow Rate1 Nominal Flow Rate Maximum Flow Rate
Curve IP SI IP SI IP SI IP SI
Model
Ref. GPM DP ft. lps DP kpa GPM DP ft. lps DP kpa GPM DP ft. lps DP kpa GPM DP ft. lps DP kpa
A 030E 29.4 2.0 1.9 6.0 45.9 4.7 2.9 14.1 73.4 11.6 4.6 34.5 122.4 30.6 7.7 91.5
B 035E 35.1 2.6 2.2 7.8 54.9 6.1 3.5 18.3 87.8 15.0 5.5 44.8 146.4 39.9 9.2 119.0
C 040E 39.2 2.7 2.5 8.2 61.2 6.4 3.9 19.2 97.9 15.8 6.2 47.2 163.2 41.9 10.3 125.2
D 045E 42.9 2.5 2.7 7.4 67.1 5.8 4.2 17.3 107.3 14.2 6.8 43.2 178.8 37.7 11.3 112.6
E 050E 49.9 3.1 3.1 9.1 78.0 7.1 4.9 21.3 124.8 17.4 7.9 52.1 208.0 46.1 13.1 137.6
F 055E 53.6 2.7 3.4 8.0 83.7 6.3 5.3 18.8 133.9 15.5 8.4 46.1 223.2 41.0 14.1 122.4
G 060E 57.7 2.6 3.6 7.8 90.2 6.1 5.7 18.3 144.2 14.9 9.1 44.6 240.4 39.4 15.2 117.7
H 065E 59.3 2.8 3.7 8.2 92.7 6.4 5.8 19.3 148.3 15.7 9.4 47.0 247.2 41.6 15.6 124.1
I 070E 65.9 3.4 4.2 10.1 102.9 7.9 6.5 23.5 164.6 19.2 10.4 57.3 274.4 50.7 17.3 151.3
J 075E 71.2 1.3 4.5 3.8 111.3 3.0 7.0 8.9 178.1 7.3 11.2 21.8 296.9 19.3 18.7 57.8
K 076E 72.3 1.8 4.6 5.4 113.0 4.2 7.1 12.7 180.7 10.5 11.4 31.4 301.3 28.5 19.0 85.1
L 080E 75.5 1.1 4.8 3.2 117.9 3.0 7.4 8.9 188.6 7.7 11.9 23.0 314.5 21.1 19.8 63.1
M 081E 76.8 2.2 4.8 6.7 120.0 4.6 7.6 13.8 192.0 10.2 12.1 30.5 320.1 25.3 20.2 75.5
N 090E 83.3 1.4 5.3 4.1 130.2 3.6 8.2 10.9 208.3 9.4 13.1 28.1 347.3 25.6 21.9 76.6
O 091E 84.2 2.6 5.3 7.8 131.6 5.4 8.3 16.0 210.5 12.0 13.3 35.7 350.9 29.9 22.1 89.2
P 100E 97.4 1.9 6.1 5.7 152.3 3.9 9.6 11.5 243.6 8.5 15.4 25.4 406.1 20.8 25.6 62.3
Q 101E 97.4 2.3 6.1 7.0 152.3 5.3 9.6 15.9 243.6 11.6 15.4 34.7 356.0 23.0 22.5 68.7
R 110E 107.1 1.6 6.8 4.8 167.4 3.7 10.6 10.9 267.8 8.7 16.9 26.0 446.5 22.6 28.2 67.6
S 120E 118.8 1.7 7.5 5.1 185.6 4.0 11.7 12.0 296.9 9.8 18.7 29.4 494.9 26.4 31.2 78.8
T 130E 125.7 1.6 7.9 4.9 196.4 3.9 12.4 11.6 314.2 9.5 19.8 28.3 523.7 25.2 33.0 75.4
U 140E 137.1 1.9 8.6 5.8 214.2 4.6 13.5 13.7 342.7 11.2 21.6 33.6 571.3 30.0 36.0 89.7
V 150E 143.8 1.8 9.1 5.5 224.7 4.4 14.2 13.2 359.5 10.9 22.7 32.6 599.3 29.4 37.8 87.8
W 161E 150.0 2.0 9.5 6.0 234.3 4.8 14.8 14.3 374.9 11.8 23.7 35.3 624.9 31.9 39.4 95.2
X 170E 156.6 1.9 9.9 5.8 244.7 4.6 15.4 13.9 391.4 11.5 24.7 34.4 652.5 31.1 41.2 92.9
Y 180E 174.6 2.6 11.0 7.7 272.9 6.0 17.2 17.9 436.6 14.3 27.5 42.9 727.7 37.6 45.9 112.3
Z 191E 183.1 2.5 11.6 7.5 286.1 4.8 18.0 14.4 457.7 10.3 28.9 30.8 763.0 25.2 48.1 75.3
AA 211E 189.5 2.6 12.0 7.9 296.1 5.1 18.7 15.2 473.8 10.9 29.9 32.7 789.8 26.8 49.8 80.1
BB 226E 203.6 2.0 12.8 5.9 318.2 4.1 20.1 12.3 509.0 9.4 32.1 28.1 848.6 24.2 53.5 72.4
CC 241E 220.8 2.3 13.9 6.7 345.0 4.7 21.8 14.1 552.0 10.9 34.8 32.6 920.2 28.2 58.1 84.3
NOTE: 1 Full load flow minimum is the minimum allowable flow at full load conditions, and/or for a constant flow system.
2 Part load flow minimum is the minimum allowable flow for a partially loaded unit, which is only applicable in a variable flow system.
Flow may only be reduced proportionally to load, i.e. a flow reduction of 25% from the design flow rate is only allowable if the chiller
load is reduced by 25%.
Figure 50: Pressure Drop Curves- Heat Recovery Auxilliary Heat Exchangers (refer to data in Table 14)
20.0
1 2 3 4 5 6
18.0
16.0
14.0
Differential Pressure (ft)
12.0
10.0
8.0
6.0
4.0
2.0
1 6
2 3 4 5
0.0
0.0 50.0 100.0 150.0 200.0 250.0
Figure 51: Typical Packaged Unit Field Wiring Diagram (Single-Point Connection)
FIELD WIRING DIAGRAM
WITH MICROTECH CONTROLLER
PANEL
L1 T1
3 PHASE TO
POWER L2 T2 COMPRESSOR(S)
SOURCE AND FAN MOTORS
L3 T3
EARTH
FU4 FU5
GROUND
T1
TB1
35 120 VAC
CHWR1 301 120 299
FU6 DISCONNECT
PUMP NO.1 RELAY VAC
CONTROL (BY OTHERS)
(BY OTHERS) TB1
120VAC @ 1.0AMP MAX TB1 CIRCUIT
FUSE 22 N
33 N OPTIONAL
SEE NOTE 2
TB1 FIELD SUPPLIED
301A FU
TB1 CONTROL POWER
1A 120 VAC
P2+ 120 VAC 15A for 1.5 KVA
CHWR2 30A for 3.0KVA
PUMP NO.2 RELAY (BY OTHERS)
(BY OTHERS)
120VAC @ 1.0AMP MAX TB1
31 N
TB1
34 120 VAC
ALARM
BELL OPTION ALARM BELL RELAY
120VAC @ 1.0AMP MAX TB1
32A
ABR GND
OFF
** TIME CLOCK TB2
52
AUTO IF REMOTE STOP
REMOTE CONTROL IS USED
STOP SWITCH ON 585 REMOVE LEAD 585
(BY OTHERS) FROM TERM
TB2 TB2-52 TO TB2-72
MANUAL **
72
OFF
**TIME CLOCK TB2
54 ALARM BELL **
AUTO TB2 RELAY
DOUBLE SET POINT/MODE
SWITCH ON 24 VAC 43
COM NO
(BY OTHERS) ABR
TB2
MANUAL ** UNIT ALARM
74
TB2 BELL
1 2
N 83
TB2
Flow Switch Contacts 24VAC @ 0.4AMP MAX.
44 M
Use dry contacts only. DO NOT
supply Field Power to this circuit
NOTE: For Factory Supplied Thermal
Dispersion Flow Switch wiring, TB2
see wiring instruction kit. TB2
61 DI2
IF EXTERNAL 45
To UC DI2
ALARM/EVENT
EXTERNAL
IS USED 555A ALARM/
REMOVE LEAD 555A
EVENT
FROM TERM TB2 **
TB2-45 TO TB2-67 67
TB2
+ 68
4-20MA FOR
EVAP. - LWT RESET TB2
(BY OTHERS) _
69
TB2
+ 70
4-20MA FOR
DEMAND LIMIT TB2
(BY OTHERS) _
71
(+) TO/FROM BAS
BACNET-MSTP (-) (CUSTOMER
REF CONNECTION)
Notes:
1.) ALL FIELD WIRING TO BE INSTALLED AS
NEC CLASS 1 WIRING SYSTEM WITH
CONDUCTOR RATED 600 VOLTS.
2.) IF FIELD SUPPLIED, CONTROL POWER USER
MUST REMOVE FU6, AND WIRE NUMBERS
299, 301A INSIDE CONTROL PANEL
3.) ** = USE 'DRY CONTACTS' ONLY. DO NOT
SUPPLY FIELD POWER TO THIS CIRCUIT
4.) DO NOT SUPPLY FIELD POWER TO
24VAC OR 120VAC CONTROL CIRCUITS.
Figure 52: Typical Packaged Unit Field Wiring Diagram (Multi-Point Connection)
FIELD WIRING DIAGRAM
WITH MICROTECH CONTROLLER
PANEL
L1 T1
3 PHASE TO CIRCUIT 1
POWER L2 T2 COMPRESSOR(S)
SOURCE AND FAN MOTORS
L3 T3
FU4 FU5
T1
EARTH
GROUND
FU6 301 120 299
Note: Separate grounding is CONTROL CIRCUIT VAC
DISCONNECT
(BY OTHERS)
FUSE
required if fed from different SEE NOTE 2
TB1
22 N
transformers. Otherwise a OPTIONAL
301A FIELD SUPPLIED
single ground is acceptable. DISCONNECT SWITCH
TB1 FU
CONTROL POWER
CIRCUIT BREAKER 2 1A 120 VAC
(BY OTHERS) OR
15A for 1.5 KVA
POWER BLOCK
30A for 3.0KVA
(BY OTHERS)
L1 T1
3 PHASE TO CIRCUIT 2
POWER L2 T2 COMPRESSOR(S)
SOURCE AND FAN MOTORS
L3 T3
TB1
35 120 VAC
CHWR1
PUMP NO.1 RELAY
(BY OTHERS)
120VAC @ 1.0AMP MAX TB1
33 N
TB1
P2+ 120 VAC
CHWR2
PUMP NO.2 RELAY
(BY OTHERS)
120VAC @ 1.0AMP MAX TB1
31 N
TB1
34 120 VAC
ALARM
BELL OPTION ALARM BELL RELAY
120VAC @ 1.0AMP MAX TB1
32A
ABR GND
OFF
** TIME CLOCK TB2
52
AUTO IF REMOTE STOP
REMOTE CONTROL IS USED
STOP SWITCH ON 585 REMOVE LEAD 585
(BY OTHERS) FROM TERM
TB2
MANUAL ** TB2-52 TO TB2-72
72
OFF
** TIME CLOCK TB2
54
AUTO
DOUBLE SET POINT/MODE
SWITCH ON
(BY OTHERS)
TB2
MANUAL **
74
TB2
Flow Switch Contacts 44 M
Use dry contacts only. DO NOT ALARM BELL**
supply Field Power to this circuit TB2 RELAY
NOTE: For Factory Supplied Thermal 24 VAC 43
Dispersion Flow Switch wiring, TB2
see wiring instruction kit.
COM NO
61 DI2 ABR
ALARM BELL
To UC DI2 OPTION
TB2 BELL
1 2
N 83
24VAC @ 0.4AMP MAX.
TB2
IF EXTERNAL 45
ALARM/EVENT
EXTERNAL
IS USED 555A ALARM/
REMOVE LEAD 555A
** EVENT
FROM TERM TB2
TB2-45 TO TB2-67 67
TB2
+ 68
4-20MA FOR
EVAP. - LWT RESET TB2
(+) TO/FROM BAS
(BY OTHERS) _ 69
BACNET-MSTP (-) (CUSTOMER
TB2 REF CONNECTION)
+ 70
4-20MA FOR GND CONNECT TO GROUND
AT ONE END ONLY.
DEMAND LIMIT TB2
(BY OTHERS) _ 71
Notes:
1.) ALL FIELD WIRING TO BE INSTALLED AS
NEC CLASS 1 WIRING SYSTEM WITH
CONDUCTOR RATED 600 VOLTS.
2.) IF FIELD SUPPLIED, CONTROL POWER USER
MUST REMOVE FU6, AND WIRE NUMBERS
299, 301A INSIDE CONTROL PANEL
3.) ** = USE 'DRY CONTACTS' ONLY. DO NOT
SUPPLY FIELD POWER TO THIS CIRCUIT
4.) DO NOT SUPPLY FIELD POWER TO
24VAC OR 120VAC CONTROL CIRCUITS.
Figure 53: Typical Heat Recovery Unit Field Wiring Diagram (Single-Point Connection with all options shown)
FIELD WIRING DIAGRAM
WITH MICROTECH CONTROLLER
PANEL
L1 T1
Note: Separate grounding is 3 PHASE
POWER L2 T2
TO
COMPRESSOR(S)
required if fed from different SOURCE AND FAN MOTORS
L3 T3
transformers. Otherwise a
single ground is acceptable. EARTH
GROUND
FU4 FU5
T1
TB1
35 120 VAC
CHWR1 301 120 299
FU6 DISCONNECT
PUMP NO.1 RELAY VAC
CONTROL (BY OTHERS)
(BY OTHERS) TB1
120VAC @ 1.0AMP MAX TB1 CIRCUIT
FUSE 22 N
33 N OPTIONAL
/ SEE NOTE 2
TB1 FIELD SUPPLIED
301A FU
TB1 CONTROL POWER
1A 120 VAC
P2+ 120 VAC 15A for 1.5 KVA
CHWR2 30A for 3.0KVA
PUMP NO.2 RELAY (BY OTHERS)
TB2
(BY OTHERS)
IF EXTERNAL 45
120VAC @ 1.0AMP MAX TB1
ALARM/EVENT
31 N EXTERNAL
IS USED 555A
/ ALARM/
REMOVE LEAD 555A
EVENT
FROM TERM TB2 **
TB2-45 TO TB2-67 67
TB1
/
34 120 VAC
ALARM BELL **
ALARM TB2 RELAY
ALARM BELL RELAY /
BELL OPTION 24 VAC 43
120VAC @ 1.0AMP MAX TB1 COM NO
32A ABR
/ GND UNIT ALARM
ABR OFF
(317) TB2 BELL
** TIME CLOCK TB2 1 2
N 83
52 /
AUTO IF REMOTE STOP 24VAC @ 0.4AMP MAX.
REMOTE CONTROL IS USED
STOP SWITCH ON 585 REMOVE LEAD 585
(BY OTHERS) FROM TERM TB7
TB2 TB2-52 TO TB2-72
MANUAL ** 3
72
/
**Heat Recovery
OFF Request Switch
**TIME CLOCK TB2 TB7
54 5
AUTO
DOUBLE SET POINT/MODE TB7
SWITCH ON
8
(BY OTHERS)
TB2
MANUAL **
74 HEAT RECOVERY Heat Recovery
/ PUMP RELAY Pump Relay
120VAC @ 1.0 AMP MAX
TB2 N
Flow Switch Contacts 44 M
TB7
Use dry contacts only. DO NOT **Flo HR
supply Field Power to this circuit 1
NOTE: For Factory Supplied Thermal
Dispersion Flow Switch wiring, TB2 Heat Recovery
see wiring instruction kit.
61 DI2 Flow Switch
TB2
To UC DI2 /
100B
TB7
2
Heat Recovery
0-10 V DC Pump VFD
or 3-Way Valve
TB7
5
TB7
4
Heat Recovery
4-20mA Pump VFD
TB2 or 3-Way Valve
TB7
+ 68
4-20MA FOR 5
EVAP. - LWT RESET TB2
(BY OTHERS) _
69 TB2
/
TB2 32
+ 70
4-20MA FOR
Heat Recovery
DEMAND LIMIT TB2 Pump
(BY OTHERS) _ SVHR1
71 TB2
/ 1 2
102
/
120VAC
Notes:
1.) ALL FIELD WIRING TO BE INSTALLED AS
NEC CLASS 1 WIRING SYSTEM WITH
HEAT RECOVERY JUNCTION BOX CONDUCTOR RATED 600 VOLTS.
2.) IF FIELD SUPPLIED, CONTROL POWER USER
MUST REMOVE FU6, AND WIRE NUMBERS
TBHR
299, 301A INSIDE CONTROL PANEL
FIELD POWER SUPPLY + 120+ 120V 3.) ** = USE 'DRY CONTACTS' ONLY. DO NOT
TO HEAT RECOVERY SUPPLY FIELD POWER TO THIS CIRCUIT
FREEZE PROTECTION TBHR 4.) DO NOT SUPPLY FIELD POWER TO
HEATERS (BY OTHERS) _ 24VAC OR 120VAC CONTROL CIRCUITS.
120- N
/
Figure 54: Typical Heat Recovery Unit Field Wiring Diagram (Multi-Point Connection)
FIELD WIRING DIAGRAM
WITH MICROTECH CONTROLLER
PANEL
L1 T1
3 PHASE TO CIRCUIT 1
POWER L2 T2 COMPRESSOR(S)
SOURCE AND FAN MOTORS
L3 T3
Note: Separate grounding is FU4 FU5
required if fed from different T1
transformers. Otherwise a
EARTH
single ground is acceptable. GROUND
FU6 301 120 299
DISCONNECT
CONTROL CIRCUIT VAC
(BY OTHERS)
FUSE TB1
SEE NOTE 2
22 N
OPTIONAL
301A FIELD SUPPLIED
TB1 FU
DISCONNECT SWITCH CONTROL POWER
CIRCUIT BREAKER 2 1A 120 VAC
(BY OTHERS) OR
15A for 1.5 KVA
POWER BLOCK
30A for 3.0KVA
(BY OTHERS)
L1 T1
3 PHASE TO CIRCUIT 2
POWER L2 T2 COMPRESSOR(S)
SOURCE AND FAN MOTORS
L3 T3
ALARM BELL**
TB1 TB2 RELAY
/
35 120 VAC 24 VAC 43
COM NO
CHWR1 ABR
PUMP NO.1 RELAY ALARM BELL
(BY OTHERS) OPTION
120VAC @ 1.0AMP MAX TB1 TB2 BELL
1 2
33 N N 83
/
/ TB1 24VAC @ 0.4AMP MAX.
TB2
P2+ 120 VAC
CHWR2 IF EXTERNAL 45
PUMP NO.2 RELAY ALARM/EVENT
EXTERNAL
(BY OTHERS) IS USED 555A ALARM/
120VAC @ 1.0AMP MAX TB1 REMOVE LEAD 555A
** EVENT
FROM TERM TB2
31 N
TB2-45 TO TB2-67 67
/
/
TB1
TB7
34 120 VAC
3
TB2
32
Heat Recovery
Pump
TB2 TB2 SVHR1
1 2
+ 68 102
4-20MA FOR /
120VAC
EVAP. - LWT RESET TB2
(BY OTHERS) _ 69
/ (+) TO/FROM BAS
TB2
BACNET-MSTP (-) (CUSTOMER
+ 70
REF CONNECTION)
4-20MA FOR
DEMAND LIMIT TB2
(BY OTHERS) _ GND CONNECT TO GROUND
71 AT ONE END ONLY.
(317)
/
Notes:
1.) ALL FIELD WIRING TO BE INSTALLED AS
NEC CLASS 1 WIRING SYSTEM WITH
HEAT RECOVERY JUNCTION BOX CONDUCTOR RATED 600 VOLTS.
2.) IF FIELD SUPPLIED, CONTROL POWER USER
MUST REMOVE FU6, AND WIRE NUMBERS
TBHR
299, 301A INSIDE CONTROL PANEL
FIELD POWER SUPPLY + 120+ 120V 3.) ** = USE 'DRY CONTACTS' ONLY. DO NOT
TO HEAT RECOVERY SUPPLY FIELD POWER TO THIS CIRCUIT
FREEZE PROTECTION TBHR 4.) DO NOT SUPPLY FIELD POWER TO
HEATERS (BY OTHERS) _ 24VAC OR 120VAC CONTROL CIRCUITS.
120- N
/
Table 22: Electrical Data - Single Point (60/50 Hz) Table 23: Electrical Data - Single Point (60/50 Hz)
Single Point Field Data Single Point Field Data
Model Voltage / Ratings Lug Range Model Voltage / Ratings Lug Range
Size Freq. Disconnect Size Freq. Disconnect
MCA RFS MFS Power Block MCA RFS MFS Power Block
Switch Switch
208V/60 149 175 175 (1) 2-600MCM (1) 6-350MCM 208V/60 268 300 300 (1) 2-600MCM (2) 3/0-500MCM
230V/60 149 175 175 (1) 2-600MCM (1) 6-350MCM 230V/60 268 300 300 (1) 2-600MCM (2) 3/0-500MCM
380V/60 87 100 100 (1) 2-600MCM (1) 12-1/0 380V/60 161 175 175 (1) 2-600MCM (1) 6-350MCM
030E 065E
460V/60 74 80 80 (1) 14-2/0 (1) 12-1/0 460V/60 129 150 150 (1) 2-600MCM (1) 4-300MCM
575V/60 64 70 70 (1) 14-2/0 (1) 12-1/0 575V/60 113 125 125 (1) 2-600MCM (1) 4-300MCM
400V/50 77 90 90 (1) 14-2/0 (1) 12-1/0 400V/50 129 150 150 (1) 2-600MCM (1) 4-300MCM
208V/60 163 175 175 (1) 2-600MCM (1) 6-350MCM 208V/60 306 350 350 (1) 2-600MCM (2) 3/0-500MCM
230V/60 163 175 175 (1) 2-600MCM (1) 6-350MCM 230V/60 306 350 350 (1) 2-600MCM (2) 3/0-500MCM
380V/60 96 110 110 (1) 2-600MCM (1) 4-300MCM 380V/60 164 200 200 (1) 2-600MCM (1) 6-350MCM
035E 070E
460V/60 77 90 90 (1) 14-2/0 (1) 12-1/0 460V/60 138 150 150 (1) 2-600MCM (1) 4-300MCM
575V/60 64 70 70 (1) 14-2/0 (1) 12-1/0 575V/60 117 125 125 (1) 2-600MCM (1) 4-300MCM
400V/50 80 90 90 (1) 14-2/0 (1) 12-1/0 400V/50 138 150 150 (1) 2-600MCM (1) 4-300MCM
208V/60 168 200 200 (1) 2-600MCM (1) 6-350MCM 208V/60 338 400 400 (1) 2-600MCM (2) 3/0-500MCM
230V/60 168 200 200 (1) 2-600MCM (1) 6-350MCM 230V/60 338 400 400 (1) 2-600MCM (2) 3/0-500MCM
380V/60 107 125 125 (1) 2-600MCM (1) 4-300MCM 075E / 380V/60 173 200 200 (1) 14-2/0 (1) 6-350MCM
040E
460V/60 80 90 90 (1) 14-2/0 (1) 12-1/0 076E 460V/60 149 175 175 (1) 14-2/0 (1) 6-350MCM
575V/60 67 80 80 (1) 14-2/0 (1) 12-1/0 575V/60 125 150 150 (1) 14-2/0 (1) 4-300MCM
400V/50 83 100 100 (1) 14-2/0 (1) 12-1/0 400V/50 149 175 175 (1) 14-2/0 (1) 6-350MCM
208V/60 228 250 250 (1) 2-600MCM (1) 6-350MCM 208V/60 355 400 400 (1) 2-600MCM (2) 3/0-500MCM
230V/60 228 250 250 (1) 2-600MCM (1) 6-350MCM 230V/60 355 400 400 (1) 2-600MCM (2) 3/0-500MCM
380V/60 117 125 125 (1) 2-600MCM (1) 4-300MCM 080E / 380V/60 187 225 225 (1) 2-600MCM (1) 6-350MCM
045E
460V/60 90 100 100 (1) 2-600MCM (1) 12-1/0 081E 460V/60 153 175 175 (1) 14-2/0 (1) 6-350MCM
575V/60 75 90 90 (1) 14-2/0 (1) 12-1/0 575V/60 126 150 150 (1) 14-2/0 (1) 4-300MCM
400V/50 94 110 110 (1) 2-600MCM (1) 4-300MCM 400V/50 153 175 175 (1) 14-2/0 (1) 6-350MCM
208V/60 241 250 250 (1) 2-600MCM (2) 3/0-500MCM 208V/60 384 450 450 (1) 2-600MCM (2) 3/0-500MCM
230V/60 241 250 250 (1) 2-600MCM (2) 3/0-500MCM 230V/60 384 450 450 (1) 2-600MCM (2) 3/0-500MCM
380V/60 131 150 150 (1) 2-600MCM (1) 4-300MCM 090E / 380V/60 218 250 250 (1) 2-600MCM (1) 6-350MCM
050E
460V/60 109 125 125 (1) 2-600MCM (1) 4-300MCM 091E 460V/60 168 200 200 (1) 14-2/0 (1) 6-350MCM
575V/60 97 110 110 (1) 2-600MCM (1) 4-300MCM 575V/60 147 175 175 (1) 14-2/0 (1) 6-350MCM
400V/50 107 125 125 (1) 2-600MCM (1) 4-300MCM 400V/50 168 200 200 (1) 14-2/0 (1) 6-350MCM
208V/60 251 300 300 (1) 2-600MCM (2) 3/0-500MCM 208V/60 442 500 500 (2) 6-500MCM (2) 3/0-500MCM
230V/60 251 300 300 (1) 2-600MCM (2) 3/0-500MCM 230V/60 442 500 500 (2) 6-500MCM (2) 3/0-500MCM
380V/60 147 175 175 (1) 2-600MCM (1) 6-350MCM 100E / 380V/60 268 300 300 (1) 2-600MCM (2) 3/0-500MCM
055E
460V/60 118 125 125 (1) 2-600MCM (1) 4-300MCM 101E 460V/60 203 250 250 (1) 2-600MCM (1) 6-350MCM
575V/60 105 125 125 (1) 2-600MCM (1) 4-300MCM 575V/60 184 225 225 (1) 2-600MCM (1) 6-350MCM
400V/50 119 125 125 (1) 2-600MCM (1) 4-300MCM 400V/50 203 250 250 (1) 2-600MCM (1) 6-350MCM
208V/60 260 300 300 (1) 2-600MCM (2) 3/0-500MCM 208V/60 490 600 600 (2) 6-500MCM (2) 3/0-500MCM
230V/60 260 300 300 (1) 2-600MCM (2) 3/0-500MCM 230V/60 490 600 600 (2) 6-500MCM (2) 3/0-500MCM
380V/60 161 175 175 (1) 2-600MCM (1) 6-350MCM 380V/60 294 350 350 (1) 2-600MCM (2) 3/0-500MCM
060E 110E
460V/60 126 150 150 (1) 2-600MCM (1) 4-300MCM 460V/60 227 250 250 (1) 2-600MCM (1) 6-350MCM
575V/60 113 125 125 (1) 2-600MCM (1) 4-300MCM 575V/60 204 250 250 (1) 2-600MCM (1) 6-350MCM
400V/50 129 150 150 (1) 2-600MCM (1) 4-300MCM 400V/50 227 250 250 (1) 2-600MCM (1) 6-350MCM
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
Table 24: Electrical Data - Single Point (60/50 Hz) Table 25: Electrical Data - Single Point (60/50 Hz)
Single Point Field Data Single Point Field Data
Model Voltage / Ratings Lug Range Model Voltage / Ratings Lug Range
Size Freq. Disconnect Size Freq. Disconnect
MCA RFS MFS Power Block MCA RFS MFS Power Block
Switch Switch
208V/60 534 600 600 (2) 6-500MCM (2) 3/0-500MCM 208V/60 848 1000 1000 (4) 2-600MCM (4) 4/0-500MCM
230V/60 534 600 600 (2) 6-500MCM (2) 3/0-500MCM 230V/60 848 1000 1000 (4) 2-600MCM (4) 4/0-500MCM
380V/60 330 400 400 (1) 2-600MCM (2) 3/0-500MCM 380V/60 508 600 600 (2) 6-500MCM (2) 3/0-500MCM
120E 191E
460V/60 261 300 300 (1) 2-600MCM (2) 3/0-500MCM 460V/60 424 500 500 (2) 6-500MCM (2) 3/0-500MCM
575V/60 234 250 250 (1) 2-600MCM (2) 3/0-500MCM 575V/60 348 400 400 (2) 6-500MCM (2) 3/0-500MCM
400V/50 261 300 300 (1) 2-600MCM (2) 3/0-500MCM 400V/50 424 500 500 (1) 2-600MCM (2) 3/0-500MCM
208V/60 569 700 700 (2) 6-500MCM (3) 2/0-400MCM 208V/60 890 1000 1000 (4) 2-600MCM (4) 4/0-500MCM
230V/60 569 700 700 (2) 6-500MCM (3) 2/0-400MCM 230V/60 890 1000 1000 (4) 2-600MCM (4) 4/0-500MCM
380V/60 358 400 450 (1) 2-600MCM (2) 3/0-500MCM 380V/60 525 600 600 (2) 6-500MCM (2) 3/0-500MCM
130E 211E
460V/60 284 350 350 (1) 2-600MCM (2) 3/0-500MCM 460V/60 443 500 500 (2) 6-500MCM (2) 3/0-500MCM
575V/60 239 250 250 (1) 2-600MCM (2) 3/0-500MCM 575V/60 351 400 400 (2) 6-500MCM (2) 3/0-500MCM
400V/50 284 350 350 (1) 2-600MCM (2) 3/0-500MCM 400V/50 443 500 500 (1) 2-600MCM (2) 3/0-500MCM
208V/60 612 700 700 (2) 6-500MCM (3) 2/0-400MCM 208V/60 943 1000 1000 (4) 2-600MCM (4) 4/0-500MCM
230V/60 612 700 700 (2) 6-500MCM (3) 2/0-400MCM 230V/60 943 1000 1000 (4) 2-600MCM (4) 4/0-500MCM
380V/60 388 450 450 (1) 2-600MCM (2) 3/0-500MCM 380V/60 551 600 600 (2) 6-500MCM (3) 2/0-400MCM
140E 226E
460V/60 309 350 350 (1) 2-600MCM (2) 3/0-500MCM 460V/60 469 500 500 (2) 6-500MCM (2) 3/0-500MCM
575V/60 248 300 300 (1) 2-600MCM (2) 3/0-500MCM 575V/60 359 400 400 (2) 6-500MCM (2) 3/0-500MCM
400V/50 309 350 350 (1) 2-600MCM (2) 3/0-500MCM 400V/50 469 500 500 (1) 2-600MCM (2) 3/0-500MCM
208V/60 640 700 700 (2) 6-500MCM (3) 2/0-400MCM 208V/60 1071 1200 1200 (4) 2-600MCM (4) 4/0-500MCM
230V/60 640 700 700 (2) 6-500MCM (3) 2/0-400MCM 230V/60 1071 1200 1200 (4) 2-600MCM (4) 4/0-500MCM
380V/60 410 500 500 (1) 2-600MCM (2) 3/0-500MCM 380V/60 602 700 700 (2) 6-500MCM (3) 2/0-400MCM
150E 241E
460V/60 328 400 400 (1) 2-600MCM (2) 3/0-500MCM 460V/60 525 600 600 (2) 6-500MCM (2) 3/0-500MCM
575V/60 252 300 300 (1) 2-600MCM (2) 3/0-500MCM 575V/60 367 400 400 (2) 6-500MCM (2) 3/0-500MCM
400V/50 328 400 400 (1) 2-600MCM (2) 3/0-500MCM 400V/50 525 600 600 (1) 2-600MCM (2) 3/0-500MCM
208V/60 668 800 800 (2) 6-500MCM (3) 2/0-400MCM
230V/60 668 800 800 (2) 6-500MCM (3) 2/0-400MCM
380V/60 432 500 500 (1) 2-600MCM (2) 3/0-500MCM
161E
460V/60 346 400 400 (1) 2-600MCM (2) 3/0-500MCM
575V/60 255 300 300 (1) 2-600MCM (2) 3/0-500MCM
400V/50 346 400 400 (1) 2-600MCM (2) 3/0-500MCM
208V/60 734 800 800 (2) 6-500MCM (4) 4/0-500MCM
230V/60 734 800 800 (2) 6-500MCM (4) 4/0-500MCM
380V/60 442 500 500 (2) 6-500MCM (2) 3/0-500MCM
170E
460V/60 355 400 400 (1) 2-600MCM (2) 3/0-500MCM
575V/60 309 350 350 (1) 2-600MCM (2) 3/0-500MCM
400V/50 355 400 400 (1) 2-600MCM (2) 3/0-500MCM
208V/60 875 1000 1000 -- (4) 4/0-500MCM
230V/60 875 1000 1000 -- (4) 4/0-500MCM
380V/60 479 500 500 (2) 6-500MCM (2) 3/0-500MCM
180E
460V/60 394 450 450 (1) 2-600MCM (2) 3/0-500MCM
575V/60 339 350 350 (1) 2-600MCM (2) 3/0-500MCM
400V/50 394 450 450 (1) 2-600MCM (2) 3/0-500MCM
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
075E / 380V/60 92 110 125 (1) 14-2/0 (1) 4-300MCM 91 110 125 (1) 14-2/0 (1) 4-300MCM
076E 460V/60 80 100 110 (1) 14-2/0 (1) 4-300MCM 76 100 100 (1) 14-2/0 (1) 4-300MCM
575V/60 66 80 90 (1) 14-2/0 (1) 12-1/0 65 80 90 (1) 14-2/0 (1) 12-1/0
400V/50 80 100 110 (1) 14-2/0 (1) 4-300MCM 76 100 100 (1) 14-2/0 (1) 4-300MCM
208V/60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 3/0-500MCM
230V/60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 3/0-500MCM
080E / 380V/60 98 125 125 (1) 14-2/0 (1) 4-300MCM 98 125 125 (1) 14-2/0 (1) 6-350MCM
081E 460V/60 80 100 110 (1) 14-2/0 (1) 4-300MCM 80 100 110 (1) 14-2/0 (1) 4-300MCM
575V/60 66 80 90 (1) 14-2/0 (1) 12-1/0 66 80 90 (1) 14-2/0 (1) 4-300MCM
400V/50 80 100 110 (1) 14-2/0 (1) 4-300MCM 80 100 110 (1) 14-2/0 (1) 4-300MCM
208V/60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 3/0-500MCM
230V/60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 3/0-500MCM
090E / 380V/60 115 150 150 (1) 14-2/0 (1) 4-300MCM 115 150 150 (1) 14-2/0 (1) 6-350MCM
091E 460V/60 89 110 125 (1) 14-2/0 (1) 4-300MCM 89 110 125 (1) 14-2/0 (1) 4-300MCM
575V/60 78 100 110 (1) 14-2/0 (1) 4-300MCM 78 100 110 (1) 14-2/0 (1) 4-300MCM
400V/50 89 110 125 (1) 14-2/0 (1) 4-300MCM 89 110 125 (1) 14-2/0 (1) 4-300MCM
208V/60 215 300 300 (1) 2-600MCM (2) 3/0-500MCM 248 300 350 (1) 2-600MCM (2) 3/0-500MCM
230V/60 215 300 300 (1) 2-600MCM (2) 3/0-500MCM 248 300 350 (1) 2-600MCM (2) 3/0-500MCM
100E / 380V/60 129 175 175 (1) 14-2/0 (1) 6-350MCM 152 200 200 (1) 14-2/0 (2) 3/0-500MCM
101E 460V/60 96 125 125 (1) 14-2/0 (1) 4-300MCM 117 150 150 (1) 14-2/0 (1) 6-350MCM
575V/60 87 110 110 (1) 14-2/0 (1) 4-300MCM 105 150 150 (1) 14-2/0 (1) 6-350MCM
400V/50 96 125 125 (1) 14-2/0 (1) 4-300MCM 117 150 150 (1) 14-2/0 (1) 6-350MCM
208V/60 259 350 350 (1) 2-600MCM (2) 3/0-500MCM 259 350 350 (1) 2-600MCM (2) 3/0-500MCM
230V/60 259 350 350 (1) 2-600MCM (2) 3/0-500MCM 259 350 350 (1) 2-600MCM (2) 3/0-500MCM
380V/60 156 200 225 (1) 14-2/0 (1) 6-350MCM 156 200 225 (1) 14-2/0 (2) 3/0-500MCM
110E
460V/60 120 150 175 (1) 14-2/0 (1) 6-350MCM 120 150 175 (1) 14-2/0 (1) 6-350MCM
575V/60 108 150 150 (1) 14-2/0 (1) 4-300MCM 108 150 150 (1) 14-2/0 (1) 6-350MCM
400V/50 120 150 175 (1) 14-2/0 (1) 6-350MCM 120 150 175 (1) 14-2/0 (1) 6-350MCM
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
General Description
The MicroTech® III controller’s design not only permits Security protection prevents unauthorized changing of the
the chiller to run more efficiently, but also can simplify setpoints and control parameters.
troubleshooting if a system failure occurs. Every MicroTech® MicroTech® III control continuously performs self-diagnostic
III controller is programmed and tested prior to shipment to checks, monitoring system temperatures, pressures and
facilitate start-up. protection devices, and will automatically shut down a
The controller menu structure is separated into three distinct compressor or the entire unit should a fault occur. The cause
categories that provide the operator or service technician with of the shutdown will be retained in memory and can be easily
a full description of: displayed in plain English for operator review. The MicroTech®
III chiller controller will also retain and display the date/time the
1. current unit status
fault occurred. In addition to displaying alarm diagnostics, the
2. control parameters MicroTech® III chiller controller also provides the operator with
3. alarms a warning of limit (pre-alarm) conditions.
System Architecture
The overall controls architecture uses the following:
• One MicroTech® III unit controller
• I/O extension modules as needed depending on the
configuration of the unit
• Communications interface(s) as needed based on
installed options
Communication interface modules will connect directly to the
left side of the unit controller. I/O extensions will connect via
peripheral bus using the connection on the right side of the
controller. All of the I/O extension modules can connect directly
or using a wiring harness.
Peripheral Bus
I/O Extension
I/O Extension
EEXV1
CC1
Table 33: Digital Outputs X2 Circuit 2 Evap Press Voltage 0.4 to 4.6 volts
X4 Circuit 2 Cond Press Voltage 0.4 to 4.6 volts
Description Output Off Output On
DO1 Evaporator Water Pump 1 Pump Off Pump On
Table 38: Digital Inputs
DO2 Alarm Indicator Alarm Not Active Alarm Active
Description Signal Off Signal On
DO3 Circuit 1 Fan Output 1 Fan(s) Off Fan(s) On
Heat Recovery Flow
DO4 Circuit 1 Fan Output 2 Fan(s) Off Fan(s) On X3 No Flow Flow
Switch
DO5 Circuit 1 Fan Output 3 Fan(s) Off Fan(s) On X6 Circuit 2 Switch Circuit Disable Circuit Enable
DO6 Circuit 1 Fan Output 4 Fan(s) Off Fan(s) On X7 Circuit 2 MHP Switch Fault No fault
DO7 Circuit 2 Fan Output 1 Fan(s) Off Fan(s) On Circuit 2 Motor
X8 Fault No fault
DO8 Circuit 2 Fan Output 2 Fan(s) Off Fan(s) On Protection
DO9 Circuit 2 Fan Output 3 Fan(s) Off Fan(s) On DI1 Circuit 2 PVM/GFP Fault No fault
DO10 Circuit 2 Fan Output 4 Fan(s) Off Fan(s) On NOTE: The Motor Protection and MHP input signal are wired
X7 Circuit 1 Condenser SV 1 Solenoid Closed Solenoid Open in series. If Motor Protection input is open, MHP
X8 Circuit 2 Condenser SV 1 Solenoid Closed Solenoid Open
Switch input will also be open.
Table 39: Digital Outputs
Compressor Module 1 Description Output Off Output On
DO1 Compressor #2 Compressor Off Compressor On
Table 34: Analog Inputs DO2 Compressor #4 Compressor Off Compressor On
Description Signal Type Expected Range DO3 Compressor #6 Compressor Off Compressor On
X1 Circuit 1 Suction Temp NTC 10k 340 to 300k Ω Circuit 2 Hot Gas Bypass
DO5 Solenoid Closed Solenoid Open
X2 Circuit 1 Evaporator Press Voltage 0.4 to 4.6 volts SV
X4 Circuit 1 Condenser Press Voltage 0.4 to 4.6 volts DO6 Circuit 2 Liquid Line SV Solenoid Closed Solenoid Open
X3 Heat Recovery EWT NTC 10k 340 to 300k Ω Heat Recovery Pump
X5 Pump Off Pump On
X5 Heat Recovery LWT NTC 10k 340 to 300k Ω Relay
RapidRestore®
This module will be used only when the unit is equipped with
the RapidRestore® option.
Sensor Information
Pressure
Pressure inputs will be read using 0 to 5 volt ratiometric
sensors. Nominal voltage range will be 0.5 to 4.5 volts.
Set Points
Set points are initially set to the values in the Default column, to make a change and then require rebooting the controller in
and can be adjusted to any value in the Range column. order to apply a change. If an option is not included on the unit,
Set points are stored in permanent memory. Basic unit the respective set point may not be visible.
configuration set points will require the unit to be off in order
Table 48: Unit Level Set Point Defaults and Ranges
Description Default Range
Basic Unit Configuration
Unit Model AGZ000 Based on Unit Model Configuration
Evaporator Configuration Not Set Not Set, Packaged, Remote
Condenser Type Not Set Not Set, Microchannel
Expansion Valve Type Not Set Not Set, Thermal, Electronic
Condenser Fan VFD Configuration None None, 1/cir, 2/cir
Power Connection Configuration Single Point Single Point, Multi Point
RapidRestore No No, Yes
Heat Recovery Control Type None None, Valve, VFD Pump
Mode/Enabling
Unit Enable Enable Disable, Enable
Control source Local Local, Network
Available Modes Cool Cool, Cool w/Glycol, Cool/Ice w/Glycol, Ice, Test
Staging and Capacity Control
Cool LWT 1 7°C (44.6°F) See Dynamic Set Point Ranges
Cool LWT 2 7°C (44.6°F) See Dynamic Set Point Ranges
Ice LWT 4.4°C (39.9°F) -9.5 to 4.4 °C (14.9 to 39.9 °F)
Startup Delta T 5.6°C (10.1°F) 0.6 to 8.3 °C (1.1 to 14.9 °F)
Shut Down Delta T 0.3°C (0.5°F) 0.3 to 1.7 °C (0.5 to 3.1 °F)
Stage Up Delay 240 sec 120 to 480 sec
Stage Down Delay 30 sec 20 to 60 sec
Stage Delay Clear No No, Yes
Max Pulldown Rate 0.6°C/min (1.1°F/min) 0.1 to 2.7°C/min (0.2 to 4.9°F/min)
Full Capacity Evap Delta T 8.9 °C (16°F) 3.3 to 8.9 °C (5.9 to 16 °F)
Variable Evaporator Flow No No, Yes
Ice TimeCycle Delay 12 1-23 hours
Clear Ice Timer No No,Yes
RapidRestore Disable Disable, Enable
Rapid Restore Max Power Off Time 15 seconds 15 to 180 seconds
Evaporator Pump Control
Evap Pump Control Configuration #1 Only #1 Only, #2 Only, Auto, #1 Primary, #2 Primary
Evap Recirc Timer 90 15 to 300 seconds
Evap Pump 1 Run Hours 0 0 to 999999 hours
Evap Pump 2 Run Hours 0 0 to 999999 hours
Power Conservation and Limits
LWT Reset Enable Disable Disable, Enable
Demand Limit Enable Disable Disable, Enable
High IPLV Mode Disable Disable, Enable
IPLV Condensing Target 23.89°C (75°F) 21.11 to 32.22°C (70 to 90°F)
Sound Reduction Mode
Sound Reduction Enable Disable Disable, Enable
Sound Reduction Priority Capacity Sound, Capacity
Sound Reduction Fan Speed Limit 50% 50%, 60%, 70%, 80%, 90%
Monday Start Time 22:00 00:00 to 23:00
Monday Duration 12 hrs 0 to 24 hrs
Tuesday Start Time 22:00 00:00 to 23:00
Tuesday Duration 12 hrs 0 to 24 hrs
Wednesday Start Time 22:00 00:00 to 23:00
Wednesday Duration 12 hrs 0 to 24 hrs
Thursday Start Time 22:00 00:00 to 23:00
Thursday Duration 12 hrs 0 to 24 hrs
Friday Start Time 22:00 00:00 to 23:00
Table 49: Unit Level Set Point Defaults and Ranges (continued)
Friday Duration 12 hrs 0 to 24 hrs
Saturday Start Time 22:00 00:00 to 23:00
Saturday Duration 12 hrs 0 to 24 hrs
Sunday Start Time 22:00 00:00 to 23:00
Sunday Duration 12 hrs 0 to 24 hrs
Heat Recovery Mode
Heat Recovery Control Offset 2.78°C(5°F) 1.11 to 8.33 °C (2 to 15 °F)
Heat Recovery Priority Heat Heat, Efficiency
Heat Recovery Min Valve Position 30.0% 10.0 to 40.0 %
Heat Recovery Min Pump VFD Speed 5.0% 5.0 to 25.0 %
Heat Recovery Recirculation Time 2 minutes 1 to 7 minutes
Heat Recovery Retry Delay 5 minutes 3 to 30 minutes
Heat Recovery Control Mode Auto Auto, Manual
Heat Recovery Manual Valve Position 0.0 to 100.0%
Heat Recovery Manual Pump Speed 0.0 to 100.0%
Heat Recovery PID Kp Value 2.0 0.0 to 1000
Heat Recovery PID Ti Value 10.0 0.0 to 1000
Heat Recovery PID Td Value 0.0 0.0 to 1000
Unit Sensor Offsets
Evap LWT Sensor Offset 0°C (0°F) -5.0 to 5.0 °C (-9.0 to 9.0 °F)
Evap EWT Sensor Offset 0°C (0°F) -5.0 to 5.0 °C (-9.0 to 9.0 °F)
Heat Recovery LWT sensor offset 0°C (0°F) -5.0 to 5.0 °C (-9.0 to 9.0 °F)
Heat Recovery EWT sensor offset 0°C (0°F) -5.0 to 5.0 °C (-9.0 to 9.0 °F)
OAT Sensor Offset 0°C (0°F) -5.0 to 5.0 °C (-9.0 to 9.0 °F)
Circuit Configuration Timers (applies to both circuits)
Compressor Start to Start Time Delay 15 min 10-60 minutes
Compressor Stop to Start Time Delay 5 min 3-20 minutes
Clear Cycle Timers No No, yes
Alarm and Limit Settings - Units
Evaporator Water Freeze 2.2°C (36°F) See Dynamic Set Point Ranges
Evaporator Flow Proof 5 sec 5 to 15 sec
Evaporator Recirculate Timeout 3 min 1 to 10 min
External Fault Configuration Event Event, Alarm
Low Ambient Lockout 1.7°C (35.1°F) See Dynamic Set Point Ranges
Low Ambient Lockout BAS Alert Off Off, On
Alarm and Limit Settings - Circuits
Low Evap Pressure Unload 689.5 KPA (100 PSI) See Dynamic Set Point Ranges
Low Evap Pressure Hold 696.4 KPA (101 PSI) See Dynamic Set Point Ranges
High Condenser Pressure 4240 KPA (615 PSI) 3310 to 4275 KPA (480 to 620 PSI)
High Condenser Pressure Unload 4137 KPA (600 PSI) 3241 to 4137 KPA (470 to 600 PSI)
Low OAT Start Time 165 sec 150 to 240 sec
BAS Control Inputs
Network Unit Enable Disable Disable, Enable
Network Mode Command Cool Cool, Ice
Network Cool Set Point 7°C (44.6°F) See Dynamic Set Point Ranges
Network Ice Set Point 4.4°C (39.9°F) -9.5 to 4.4 °C (14.9 to 39.9 °F)
Network Capacity Limit 100% 0 to 100%
Network Alarm Clear Command Normal Normal, Clear Alarm
Security
All set points are protected using passwords. A four-digit
password provides operator access to changeable parameters.
Service level passwords are reserved for authorized service
personnel. See Passwords on page 101 for various levels of
access.
Entering Passwords
Passwords are entered on the first screen on the unit
controller.
If the wrong password is entered, a message will temporarily
appear stating this. If no valid password is active the active
password level displays “none.”
Editing Setpoints
After a valid password has been entered at the unit controller,
set points may be changed. If the operator attempts to edit a
set point for which the necessary password level is not active,
no action will be taken.
Once a password has been entered, it remains valid for 10
minutes after the last key-press on the unit controller.
Sequence of Operation
Unit power up
Is unit enabled? If the unit switch is off, the unit status will be Off:Unit Switch. If the chiller is
Yes disabled due to network command, the unit status will be Off:BAS Disable. When
the remote switch is open, the unit status will be Off:Remote Switch. When a unit
alarm is active, the unit status will be Off:Unit Alarm. In cases where no circuits
Yes are enabled, the unit status will be Off:All Cir Disabled. If the unit is disabled via
the Chiller Enable set point, the unit status will be Off:Keypad Disable.
Low ambient lockout will prevent the chiller from starting even if it is otherwise
Is low ambient lockout
enabled. When this lockout is disabling the chiller, the unit status will be Off:Low
active?
OAT Lock.
No
If the chiller is enabled, then the unit will be in the Auto state and the evaporator
Evaporator pump output on
water pump output will be activated.
No
The chiller will then wait for the flow switch to close, during which time the unit
Is flow present? status will be Auto:Wait for flow.
Yes
After establishing flow, the chiller will wait some time to allow the chilled water
Wait for chilled water loop to
recirculate loop to recirculate for an accurate reading of the leaving water temperature.
The unit status during this time is Auto:Evap Recirculate.
Yes
Is Motor Protection If the chiller is waiting on the motor protection delay after powering up, the unit
delay active? status will be Off: Motor Protection Delay.
No
No
The chiller is now ready to start if enough load is present. If the LWT is not higher
than the start up temperature, the unit status will be Auto:Wait for load.
Is there enough load to
start chiller?
If the LWT is higher than the start up temperature, the unit status will become
Auto. A circuit can start at this time.
Yes
The first circuit to start is generally the available circuit with the least number of
Start first circuit.
starts. This circuit will go through its start sequence at this point.
No
Additional capacity The unit capacity can be increased if the LWT is above the stage up temperature.
needed to satisfy load?
No
Yes No
Yes
If the second circuit is not running, it will be started now. The unit will try to keep
the load balanced between circuits as the unit capacity is increased.
Increase unit capacity.
If both circuits are running, then additional compressors will start based on the
sequencing logic.
Yes
Yes
No
Yes
Yes
Decrease unit capacity Compressors will shut off as needed in the order determined by sequencing logic.
Is unit running at
minimum capacity?
Yes
No
When only one compressor is running, the load may drop off to the point where even
Is load satisfied? minimum unit capacity is too much. The load has been satisfied when the LWT
drops below the shutdown temperature. At this time the only running circuit can
shut down.
Yes
Shut down last circuit. The last circuit running now shuts down.
When last circuit has completed pumpdown, the unit will go back to waiting for
All circuits off.
enough load to start.
Unit power up
Is unit enabled? If the unit switch is off, the unit status will be Off:Unit Switch. If the chiller is
Yes disabled due to network command, the unit status will be Off:BAS Disable. When
the remote switch is open, the unit status will be Off:Remote Switch. When a unit
alarm is active, the unit status will be Off:Unit Alarm. In cases where no circuits
Yes are enabled, the unit status will be Off:All Cir Disabled. If the unit is disabled via
the Chiller Enable set point, the unit status will be Off:Keypad Disable.
No
Low ambient lockout will prevent the chiller from starting even if it is otherwise
Is low ambient lockout enabled. When this lockout is disabling the chiller, the unit status will be Off:Low
active?
OAT Lock.
No
Yes
If the chiller is enabled, then the unit will be in the Auto state and the evaporator
Evaporator pump output on
water pump output will be activated.
No
The chiller will then wait for the flow switch to close, during which time the unit
Is flow present? status will be Auto:Wait for flow.
Yes
After establishing flow, the chiller will wait some time to allow the chilled water loop
Wait for chilled water loop to
recirculate. to recirculate for an accurate reading of the leaving water temperature. The unit
status during this time is Auto:Evap Recirc.
Yes
Is Motor Protection If the chiller is waiting on the motor protection delay after powering up, the unit
delay active? status will be Off:Motor Protection Delay.
No
No
The chiller is now ready to start if enough load is present. If the LWT is not higher
than the startup temperature, the unit status will be Auto:Wait for load.
Is fluid temp high
enough to start?
If the LWT is higher than the startup temperature, the unit status will be Auto.
A circuit can start at this time.
Yes
The first circuit to start is generally the circuit which contains the compressor with
the least number of starts. This circuit will go through it’s start sequence at this
Maintain unit capacity. point.
No
Has the stage up time A minimum time must pass between the starting of circuits.
delay expired?
No
Yes
No
Yes
If the second circuit is not running, it will be started now. The unit will try to keep
the load balanced between circuits as the unit capacity is increased.
Increase unit capacity.
If both circuits are running, then additional compressors will start based on the
sequencing logic.
Yes
No
Yes
When all circuits have completed shutdown, the unit will remain in the off state until
All circuits off.
the start conditions are satisfied again.
Unit power up
When the circuit is in the Off state the EXV is in the closed position, compressors are
Circuit is in Off state off, solenoid valves are closed, and all condenser fans are off.
No
The circuit must be enabled before it can run. It might be disabled for several
reasons. When the circuit switch is off, the status will be Off:Circuit Switch.
Is circuit enabled to If the circuit has an active stop alarm then the status will be Off:Alarm. If the circuit
start?
has been disabled via the circuit mode set point, the status will be Off:Keypad
Yes
Disable. If all compressors are disabled via the settings, the circuit status will be
Off:All Comp Disable.
Yes
A minimum time must pass between the previous start and stop of a compressor
and the next start. If this time has not passed, a cycle timer will be active. If all
Are all compressor cycle
timers active? compressors on the circuit have active cycle timers the circuit status will be
Off:Cycle Timers.
No
Circuit is ready to start If the circuit is ready to start when needed, the circuit status will be
Off:Ready.
No
Capacity control logic at the unit level will determine when a circuit needs to start
Is circuit commanded to
start? and issue a start command to the next circuit to start based on sequencing rules.
Yes
Yes
No Before the first compressor on a circuit can start, the EXV performs a brief preopen.
Preopen EXV
The circuit status during this time will be Preopen.
The first compressor will be started and the fans, solenoid valves, and other
Run circuit
devices will be controlled as needed. The normal circuit status at this time will be
Run:Normal. Additional compressors will be started as needed per the unit level
capacity control.
No
Is last compressor Capacity control logic at the unit level will determine when a compressor needs to
commanded to shut down and issue a stop command to the next compressor to stop based on
shut down? sequencing rules. If this compressor is the last one on the circuit, the circuit will
need to shut down.
Yes
When the circuit needs to shut down, a pumpdown of the circuit will NOT be
Is condenser type performed if the condenser coil is Microchannel type. When the circuit needs to
tube and fin? shut down and the condenser is Microchannel type, everything will turn off on the
circuit at approximately the same time.
Yes
When the circuit needs to shut down, a pumpdown of the circuit will be performed
Pumpdown circuit if the condenser coil is tube and fin type. The circuit status during this time will be
Run:Pumpdown.
No
Unit Functions
The calculations in this section are used in unit level control means the flow that is needed for a 5.56°C (10°F) delta T at full
logic or in control logic across all circuits. unit capacity.
Unit Mode Selection Pumpdown – Units with microchannel coils will not do a
pumpdown. So if the conditions for the Auto to Pumpdown
The operating mode of the unit is determined by setpoints and transition occur, the unit state will transition from Auto to
inputs to the chiller. The Available Modes Set Point determines Pumpdown and then immediately to Off.
what modes of operation can be used. This set point also
Transitions between these states are shown in the following
determines whether the unit is configured for glycol use. The
diagram.
Control Source Set Point determines where a command to
change modes will come from. A digital input switches between
cool mode and ice mode if they are available and the control
source is set to ‘local.’ The BAS mode request switches
between cool mode and ice mode if they are both available and
the control source is set to ‘network.’
The Available Modes Set Point should only be changeable
when the unit switch is off. This is to avoid changing modes of
operation inadvertently while the chiller is running.
3
T1 - Off to Auto the Low OAT Lockout set point is configurable if the chiller has
condenser fan VFD’s. In that case, there are three options:
All of the following are required:
• Lockout and Stop – chiller will shut down and lockout
• Unit Enable = On
• No Unit Alarm active • Lockout only – chiller does not shut down running circuits,
will lock out circuits that are off
• A circuit is enabled to start
• If Unit Mode = Ice then Ice Delay not active • Disabled – chiller does not shut down or lock out
• Low Ambient Lockout is not active For chillers without condenser fan VFD’s, there is no
configuration and the chiller will always operate according to
• Unit configuration settings are valid
the first option shown above. Descriptions of the operation for
T2 - Auto to Pumpdown each option are in the following sections.
3
Unit State = Off and Unit Enable
8 Off: Keypad Disable
Set Point = Disable
Unit State = Off and Remote
9 Off: Remote Switch
Switch is open
Unit State = Off, Control Source
10 Off: BAS Disable = Network, and BAS Enable = RUN START
false 5
Unit State = Off and Unit Switch
11 Off: Unit Switch
= Disable
Unit State = Off and Unit Mode
12 Off: Test Mode T1 – Off to Start
= Test
Unit State = Auto, no circuits Requires any of the following
running, and LWT is less than • Unit state = Auto
13 Auto: Wait for load
the active set point + startup • Freeze protection started
delta
Unit Capacity Control compressor on each circuit shall be left on until each circuit has
only one compressor running.
Unit capacity control will be performed as described in this
section. All unit capacity limits described in following sections Next To Start
must be applied as described.
If both circuits have an equal number of compressors running
or a circuit has no compressors available to start:
Compressor Staging in Cool Mode
• the available compressor with the least starts will be next
The first compressor on the unit should be started when
to start
evaporator LWT is higher than the Startup Temperature.
• if starts are equal, the one with the least run hours will be
Additional compressors can be started when Evaporator LWT next to start
is higher than the Stage Up Temperature and the Stage Up
• if run hours are equal, the lowest numbered one will be
Delay is not active.
next to start
When multiple compressors are running, one should shut down If the circuits have an unequal number of compressors running,
if evaporator LWT is lower than the Stage Down Temperature the next compressor to start will be on the circuit with the least
and the Stage Down Delay is not active. compressors running if it has at least one compressor available
All running compressors should shut down when the to start. Within that circuit:
evaporator LWT is lower than the Shut Down Temperature. • the available compressor with the least starts will be next
to start
Stage Up Delay
• if starts are equal, the one with the least run hours will be
A minimum amount of time, defined by the Stage Up Delay set next to start
point, should pass between increases in the capacity stage. • if run hours are equal, the lowest numbered one will be
This delay should only apply when at least one compressor next to start
is running. If the first compressor starts and quickly shuts off
for some reason, another compressor may start without this Next to Stop
minimum time passing.
If both circuits have an equal number of compressors running:
Stage Down Delay • the running compressor with the most run hours will be
next to stop
A minimum amount of time, defined by the Stage Down Delay
set point, should pass between decreases in the capacity • if run hours are equal, the one with the least starts will be
stage. This delay should not apply when the LWT drops below next to stop
the Shut Down Temperature (unit should immediately shut • if starts are equal, the lowest numbered one will be next
down). to stop
If the circuits have an unequal number of compressors running,
Compressor Staging in Ice Mode the next compressor to stop will be on the circuit with the most
The first compressor on the unit should be started when compressors running. Within that circuit:
evaporator LWT is higher than the Startup Temperature. • the running compressor with the most run hours will be
All compressors should be operationg except during startup next to stop
or shut down. Additional compressors should be started as • if run hours are equal, the one with the least starts will be
quickly as possible with respect to the Stage Up Delay. next to stop
The unit should shut down when evaporator LWT is less than • if starts are equal, the lowest numbered one will be next
the LWT target. to stop
Stage Up Delay
Unit Capacity Overrides
A fixed stage up delay of one minute between compressor
Unit capacity limits can be used to limit total unit capacity in
starts should be used in this mode.
Cool or Cool with Glycol modes only. Multiple limits may be
active at any time, and the lowest limit is always used in the
Staging Sequence unit capacity control.
This section defines which compressor is the next one to start
or stop. In general, compressors with fewer starts will normally
start first, and compressors with more run hours will normally
stop first.
If possible circuits will be balanced in stage. If a circuit is
unavailable for any reason, the other circuit shall be allowed
to stage all compressors on. When staging down, one
Network Limit
The maximum unit capacity can be limited by a network signal.
This function is only enabled if the control source is set to
network. The maximum unit capacity stage is based on the
network limit value received from the BAS and is determined
as shown in the following tables:
RapidRestore® Option A longer delay for motor protection modules will still be used
for normal starts.
RapidRestore® is an option that can be added to Trailblazer™
chillers. The general purpose of the option is to allow the Fast Loading
capability to restart more quickly and to load faster than normal
operation. Fast loading will be performed while RapidRestore® is active.
Table 70: RapidRestore® Mode Response Times On – Heat Recovery is fully active
Maximum Time to Transitions between these states are shown in the following
# of compressors
Restart Time Fully Loaded diagram.
4 220 sec.
Power lost
125 sec.
and restored
6 280 sec.
Circuit Functions
T4
T2
T5
Condenser Approach = Condenser Saturated Temperature
- OAT
Stopping a Compressor
A compressor should be turned off if any of the following occur:
• Unit capacity control logic commands it off
• An unload alarm occurs and the sequencing requires this
compressor to be next off
• Circuit state is pumpdown and sequencing requires this
compressor to be next off
Cycle Timers Table 72: 2 Fans per Circuit - With 1 Fan VFD per Circuit
Circuit 1
A minimum time between starts of the compressor and a
Stage
minimum time between shutdown and start of the compressor Description Output Fans
1 2 3 4 5 6
shall be enforced. The time values are determined by the Start-
start Timer and Stop-start Timer setpoints. Speed Signal 1 UC X5 Fan 11 On On -- -- -- --
Fan Output 2 UC DO4 Fan 12 On -- -- -- --
These cycle timers should not be enforced through cycling of Circuit 2
power to the chiller. This means that if power is cycled, the
Stage
cycle timers should not be active. Description Output Fans
1 2 3 4 5 6
These timers may be cleared via a setting on the controller. Speed Signal 1 UC X6 Fan 21 On On -- -- -- --
Fan Output 2 UC DO8 Fan 22 On -- -- -- --
Condenser Fan Control
Figure 64: 3 Fans per Circuit - Unit Numbering Schematic
Condenser fan control should stage fans as needed any time
compressors are running on the circuit. All fans and solenoid 3-Fan Unit Locations and Numbering
valves will be off when the circuit is in the off and preopen
states. Condenser fan digital outputs will be turned on or off
immediately for condenser stage changes. Condenser solenoid Fan 11 Fan 13 Fan 22
Control Panel
valve outputs will turn on immediately when a stage up
requires the output to turn on, but will have a delay for turning
off during a stage down. This delay is 20 seconds. If the circuit Fan 12 Fan 23 Fan 21
shuts off then the condenser solenoid valve outputs will turn off
without a delay.
Condenser Staging
Table 73: 3 Fans per Circuit - Without Fan VFD
Condenser staging will use up to 5 digital outputs for control of
condenser fans and a digital output for control of a condenser Circuit 1
solenoid valve. When equipped with condenser fan VFDs, the Stage
Description Output Fans
speed signal(s) also starts and stops the fan that is connected 1 2 3 4 5 6
to the VFD. The total number of fans on shall be adjusted Fan Output 1 UC DO3 Fan 11 On On On -- -- --
with changes of one fan at a time. The tables below show the
Fan Output 2 UC DO4 Fan 12 On On -- -- --
outputs energized for each stage.
Fan Output 3 UC DO5 Fan 13 On
Figure 63: 2 Fans per Circuit - Unit Numbering Schematic Condenser SV UC X7 SV 11 On
2-Fan Unit Locations and Numbering Circuit 2
Stage
Description Output Fans
1 2 3 4 5 6
Fan 11 Fan 12 Fan Output 1 UC DO7 Fan 21 On On On -- -- --
Control Panel
Table 74: 3 Fans per Circuit - With 1 Fan VFD per Circuit Table 76: 4 Fans per Circuit - Without Fan VFD
Circuit 1 Circuit 1
Stage Stage
Description Output Fans Description Output Fans
1 2 3 4 5 6 1 2 3 4 5 6
Speed Signal 1 UC X5 Fan 11 On On On -- -- -- Fan Output 1 UC DO3 Fan 11 On On On On -- --
Fan Output 2 UC DO4 Fan 12 On On -- --
Fan Output 2 UC DO4 Fan 12 On On -- -- --
Fan Output 3 UC DO5 Fan 13 On On On -- --
Fan Output 3 UC DO5 Fan 13 On Fan Output 4 UC DO6 Fan 14 On -- --
Condenser SV UC X7 SV 11 On Condenser SV UC X7 SV 11 On On On -- --
Circuit 2 Circuit 2
Stage Stage
Description Output Fans Description Output Fans
1 2 3 4 5 6 1 2 3 4 5 6
Fan Output 1 UC DO7 Fan 21 On On On On -- --
Speed Signal 1 UC X6 Fan 21 On On On -- -- --
Fan Output 2 UC DO8 Fan 22 On On -- --
Fan Output 2 UC DO8 Fan 22 On On -- -- -- Fan Output 3 UC DO9 Fan 23 On On On -- --
Fan Output 3 UC DO9 Fan 23 On -- -- -- Fan Output 4 UC DO10 Fan 24 On -- --
Condenser SV UC X8 SV 21 On On On -- --
Condenser SV UC X8 SV 21 On -- -- --
Table 77: 4 Fans per Circuit - With 1 Fan VFD per Circuit
Table 75: 3 Fans per Circuit - With 2 Fan VFDs per Circuit
Circuit 1
Circuit 1
Stage
Stage Description Output Fans
Description Output Fans 1 2 3 4 5 6
1 2 3 4 5 6
Speed Signal 1 UC X5 Fan 11/13 On On On On -- --
Speed Signal 1 UC X5 Fan 11 On On -- -- -- Fan Output 2 UC DO4 Fan 12 On On -- --
Speed Signal 2 UC X2 Fan 12/13 On On -- -- -- Fan Output 4 UC DO6 Fan 14 On -- --
Condenser SV UC X7 SV 11 On On On -- --
Condenser SV UC X7 SV 11 On On
Circuit 2
Circuit 2
Stage
Stage Description Output Fans
Description Output Fans 1 2 3 4 5 6
1 2 3 4 5 6
Speed Signal 1 UC X6 Fan 21/23 On On On On -- --
Speed Signal 1 UC X6 Fan 21 On On -- -- -- Fan Output 2 UC DO8 Fan 22 On On -- --
Speed Signal 2 UC X3 Fan 22/23 On On -- -- -- Fan Output 4 UC DO10 Fan 24 On -- --
Condenser SV UC X8 SV 21 On On On -- --
Condenser SV UC X8 SV 21 On On --
Table 78: 4 Fans per Circuit - With 2 Fan VFDs per Circuit
Figure 65: 4 Fans per Circuit - Unit Numbering Schematic
Circuit 1
Stage
Description Output Fans
4-Fan Unit Locations and Numbering 1 2 3 4 5 6
Speed Signal 1 UC X5 Fan 11/13 On On On -- -- --
Speed Signal 2 UC X2 Fan 12/14 On -- -- --
Fan 11 Fan 13 Fan 24 Fan 22
Control Panel
Condenser SV UC X7 SV 11 On On
Circuit 2
Stage
Fan 12 Fan 14 Fan 23 Fan 21 Description Output Fans
1 2 3 4 5 6
Speed Signal 1 UC X6 Fan 21/23 On On On -- -- --
Speed Signal 2 UC X3 Fan 22/24 On -- -- --
Condenser SV UC X8 SV 21 On On --
Figure 66: 5 Fans per Circuit - Unit Numbering Schematic Table 81: 5 Fans per Circuit - With 2 Fan VFDs per Circuit
Circuit 1
5-Fan Locations and Numbering
Stage
Description Output Fans
1 2 3 4 5 6
Speed Signal 1 UC X5 Fan 11/13 On On On -- -- --
Fan 11 Fan 13 Fan 15 Fan 24 Fan 22
Control Panel
Circuit 2
Stage
Description Output Fans
1 2 3 4 5 6 Fan 12 Fan 14 Fan 16 Fan 25 Fan 23 Fan 21
Fan Output 1 UC DO7 Fan 21 On On On On On --
Fan Output 2 UC DO8 Fan 22 On On On --
Fan Output 3 UC DO9 Fan 23 On On On On --
Fan Output 4 UC DO10 Fan 24 On On --
Fan Output 5 EEXV2 DO1 Fan 25 On --
Condenser SV UC X8 SV 21 On -- Table 82: 6 Fans per Circuit - Without Fan VFD
Circuit 1
Table 80: 5 Fans per Circuit - With 1 Fan VFD per Circuit Stage
Description Output Fans
Circuit 1 1 2 3 4 5 6
Stage Fan Output 1 UC DO3 Fan 11 On On On On On On
Description Output Fans Fan Output 2 UC DO4 Fan 12 On On
1 2 3 4 5 6
Speed Signal 1 UC X5 Fan 11/13 On On On On -- -- Fan Output 3 UC DO5 Fan 13 On On On On On
Fan Output 2 UC DO4 Fan 12 On On On -- -- Fan Output 4 UC DO6 Fan 14/16 On On
Fan Output 4 UC DO6 Fan 14 On On -- -- Fan Output 5 EEXV1 DO1 Fan 15 On On On On
Fan Output 5 EEXV1 DO1 Fan 15 On -- -- Condenser SV UC X7 SV 11 On On On On
Condenser SV UC X7 SV 11 On -- -- Circuit 2
Circuit 2 Stage
Description Output Fans
Stage 1 2 3 4 5 6
Description Output Fans Fan Output 1 UC DO7 Fan 21 On On On On On On
1 2 3 4 5 6
Speed Signal 1 UC X6 Fan 21/23 On On On On -- -- Fan Output 2 UC DO8 Fan 22 On On
Fan Output 2 UC DO8 Fan 22 On On On -- -- Fan Output 3 UC DO9 Fan 23 On On On On On
Fan Output 4 UC DO10 Fan 24 On On -- -- Fan Output 4 UC DO10 Fan 24/26 On On
Fan Output 5 EEXV2 DO1 Fan 25 On -- -- Fan Output 5 EEXV2 DO1 Fan 25 On On On On
Condenser SV UC X8 SV 21 On -- -- Condenser SV UC X8 SV 21 On On On On
Table 83: 6 Fans per Circuit - With 1 Fan VFD per Circuit Circuit 2
Circuit 1 Stage
Description Output Fans
Stage 2 3 1 4 5 6
Description Output Fans
1 2 3 4 5 6 Fan Output 1 UC DO7 Fan 21/23 On On On On On On
Speed Signal 1 UC X5 Fan 11/13 On On On On On -- Fan Output 2 UC DO8 Fan 22 On On On
Fan Output 1 UC DO3 Fan 12 On On On -- Fan Output 3 UC DO9 Fan 24/26 On On On
Fan Output 2 UC DO4 Fan 14 On On -- Fan Output 4 UC DO10 Fan 25 On On On On On
Fan Output 3 UC DO5 Fan 15 On On On On -- Fan Output 5 EEXV2 DO1 Fan 27 On
Fan Output 4 UC DO6 Fan 16 On -- Condenser SV UC X8 SV 21 On
Condenser SV UC X7 SV 11 On On On On --
Circuit 2 Table 86: 7 Fans per Circuit - With 1 Fan VFD per Circuit
Stage Circuit 1
Description Output Fans
1 2 3 4 5 6 Stage
Description Output Fans
Speed Signal 1 UC X6 Fan 21/23 On On On On On -- 1 2 3 4 5 6
Fan Output 1 UC DO7 Fan 22 On On On -- Speed Signal 1 UC X5 Fan 11/13 On On On On On On
Fan Output 2 UC DO8 Fan 24 On On -- Fan Output 1 UC DO3 Fan 12 On On On On
Fan Output 3 UC DO9 Fan 25 On On On On -- Fan Output 2 UC DO4 Fan 14 On On On
Fan Output 4 UC DO10 Fan 26 On -- Fan Output 3 UC DO5 Fan 15 On On On On On
Condenser SV UC X8 SV 21 On On On On -- Fan Output 4 UC DO6 Fan 16 On On
Fan Output 5 EEXV1 DO1 Fan 17 On
Table 84: 6 Fans per Circuit - With 2 Fan VFDs per Circuit Condenser SV UC X7 SV 11 On
Circuit 1 Circuit 2
Stage Stage
Description Output Fans Description Output Fans
1 2 3 4 5 6 1 2 3 4 5 6
Speed Signal 1 UC X5 Fan 11/13 On On -- -- -- Speed Signal 1 UC X6 Fan 21/23 On On On On On On
Fan Output 1 UC DO7 Fan 22 On On On On
Speed Signal 2 UC X2 Fan 12/14/15/16 On On -- -- --
Fan Output 2 UC DO8 Fan 24 On On On
Condenser SV UC X7 SV 11 On On Fan Output 3 UC DO9 Fan 25 On On On On On
Circuit 2 Fan Output 4 UC DO10 Fan 26 On On
Stage Fan Output 5 EEXV2 DO1 Fan 27 On
Description Output Fans
1 2 3 4 5 6 Condenser SV UC X8 SV 21 On
Speed Signal 1 UC X6 Fan 21/23 On On -- -- --
Speed Signal 2 UC X3 Fan 22/24/25/26 On On -- -- --
Table 87: 7 Fans per Circuit - With 2 Fan VFDs per Circuit
Circuit 1
Condenser SV UC X8 SV 21 On On --
Stage
Description Output Fans
1 2 3 4 5 6
Figure 68: 7 Fans per Circuit - Unit Numbering Schematic
Speed Signal 1 UC X5 Fan 11/13 On On On -- --
7-Fan Unit Locations and Numbering Fan
Speed Signal 2 UC X2 On On On -- --
12/14/15/16
Fan 11 Fan 13 Fan 15 Fan 17 Fan 26 Fan 24 Fan 22 Fan Output 5 EEXV1 DO1 Fan 17 On
Control Panel
Condenser SV UC X7 SV 11 On
VFD’s within a circuit). If Heat Recovery Priority = Efficiency, the condenser target
settings should be used as is. If Heat Recovery Priority = Heat,
The speed will normally be controlled between the minimum
then the condenser target should have an additional 5.56°C
and maximum speed set points using a PID loop.
(10°F) added to the current selected target. In addition, when
Heat Recovery state is either Recirculate or On the condenser
VFD State
target should be filtered when the circuit is running. Whenever
The VFD speed signals should always be 0 when the fan stage the target is changing, it should only be allowed to change
is 0. 0.1°C every two seconds.
When the condenser fan staging requires the fans connected
to a VFD to run, the VFD speed signal should be enabled and
control the speed as needed. EXV Control
Stage Up Compensation
Control States
EXV control will always be in one of two states: Closed or
In order to create a smoother transition when another fan is
Superheat Control.
staged on, the VFD speed compensates by slowing down
initially. This is accomplished by adding the new fan stage up Transitions between these states are shown in Figure 69.
deadband to the VFD target. The higher target causes the VFD
logic to decrease fan speed. Then, every 2 seconds, 0.1°C Figure 69: EXV Control Transitions
(0.18°F) is subtracted from the VFD target until it is equal to
the saturated condenser temperature target set point.
compressors are running the SSH Target at 100% set Operation Considerations
point is used.
For all units - the expansion valve maximum position may
• If the circuit has three compressors and one is running, be increased if both the suction superheat is higher than the
the value used is the SSH Target at 33% set point. target and the expansion valve has been within 1% of its
If either two or three are running the SSH Target at current maximum position for a minute. The maximum should
66/100% set point is used. increase at a rate of 0.1% every six seconds up to a total of an
If no compressors are running the target is set to set point used additional 10%. This addition to the maximum position should
when one compressor is running (applies to EXV preopen). be reset when the EXV is no longer in the Superheat Control
state, or a compressor on the circuit stages.
Position Commands
In order to improve the reliability of the EXV positioning, the Manual Control
position commands that are issued to the stepper driver are
The EXV position can be set manually. Manual control can only
limited in two ways:
be selected when the circuit is in the run state. At any other
1. Position commands are filtered so that the minimum change time, the EXV control set point is forced to auto.
in position is 0.3%. Changes of less than this are ignored. This
When EXV control is set to manual, the EXV position is equal
avoids unnecessary movement of the EXV and lowers the
to the manual EXV position setting. If set to manual when the
chances of losing steps as a result.
circuit state transitions from run to another state, the control
2. The position commands are issued once per program cycle setting is automatically set back to auto. When in manual
with a maximum change of 0.7% each time. This allows the control, the EXV control state displayed will be ‘Manual’.
stepper to move the valve to the commanded position before
the next position command is issued. Issuing commands in this Liquid Line Solenoid Valve
way may also lower the chances of losing steps.
The liquid line solenoid output should be on when the circuit
state is either Pre-open or Run. This output should be off at all
EXV Position Range other times.
The minimum EXV position while the circuit is running will
always be 8%. The maximum position will change as the
number of compressors running on the circuit changes. These
Hot Gas Bypass Solenoid Valve
values are shown for each unit model in Table 88. This output will be on when circuit state is Run for at least
30 seconds and one compressor on the unit is running. The
Table 88: Maximum Position Range output should be off at all other times unless the unit is a model
# Compressors Running/Circuit 191-241. For these models, the hot gas bypass will also be
Model
1 2 3 activated for 10 minutes when a second or third compressor is
AGZ030E 50 100 n/a started on the circuit.
AGZ035E 50 100 n/a
AGZ040E 50 100 n/a
AGZ045E 50 100 n/a
AGZ050E 50 100 n/a
AGZ055E 50 100 n/a
AGZ060E 50 100 n/a
AGZ065E 50 100 n/a
AGZ070E 50 100 n/a
AGZ075E / 076E 60 100 n/a
AGZ080E / 081E 60 100 n/a
AGZ090E / 091E 60 100 n/a
AGZ100E / 101E 60 100 n/a
AGZ110E 50 80 n/a
AGZ120E 50 80 n/a
AGZ130E 50 80 n/a
AGZ140E 70 100 n/a
AGZ150E 70 100 n/a
AGZ161E 80 100 n/a
AGZ170E 60 80 100
AGZ180E 60 80 100
AGZ191E 60 80 100
AGZ211E 60 80 100
AGZ226E 60 80 100
AGZ241E 60 80 100
Alarms
The following conditions shall override automatic capacity 1: Evaporator Pump State = Run AND Evaporator Flow Digital
control as described. These overrides keep the circuit from Input = No Flow for time > Flow Proof Set Point AND at least
entering a condition in which it is not designed to run. one compressor running
2: Evaporator Pump State = Start for time greater than
Low Evaporator Pressure Recirc Timeout Set Point and all pumps have been tried and
Evaporator Flow Digital Input = No Flow
If the Low Evaporator Pressure Hold or Low Evaporator
Action Taken: Rapid stop all circuits
Pressure Unload alarms are triggered, the circuit capacity may
be limited or reduced. See the Circuit Events section for details - if an auto reset occurrence has triggered, keep unit enabled
on triggering, reset, and actions taken. and allow the evaporator recirculation sequence to proceed
- if a manu reset occurrence has been triggered, lock out unit
High Condenser Pressure from running
If the High Condenser Pressure Unload alarm is triggered, Reset: This alarm can be cleared at any time manually via the
the circuit capacity may be limited or reduced. See the Circuit keypad or via the BAS clear alarm command.
Events section for details on triggering, reset, and actions
If active via trigger condition 1:
taken.
When the alarm occurs due to this trigger, it can auto reset the
Situations may arise that require some action from the chiller
first two times each day with the third occurrence being manual
or that should be logged for future reference. Alarms are
reset.
classified in the following sections as Faults, Problems, or
Warnings. For the auto reset occurrences, the alarm will reset
automatically when the evaporator state is Run again. This
When any Unit Fault Alarm is active, the alarm digital output
means the alarm stays active while the unit waits for flow, then
should be turned on continuously. If both circuits have a Circuit
it goes through the recirculation process after flow is detected.
Fault Alarm active, the alarm digital output should be turned
Once the recirculation is complete, the evaporator goes to the
on continuously. If no Unit Fault Alarm is active and only one
Run state which will clear the alarm. After three occurrences,
circuit has a Circuit Fault Alarm is active, the alarm digital
the count of occurrences is reset and the cycle starts over if the
output should alternate five seconds on and five seconds off
manual reset flow loss alarm is cleared.
continuously.
If active via trigger condition 2:
All alarms appear in the active alarm list while active. All alarms
are added to the alarm log when triggered and when cleared. If the flow loss alarm has occurred due to this trigger, it is
Entries in the log representing the occurrence of an alarm will always a manual reset alarm.
be preceded by ‘+’ while entries representing the clearing of an
alarm will be preceded by ‘-‘. Evaporator Water Freeze Protect
Trigger: Evaporator LWT drops below evaporator freeze
Unit Fault Alarms protect set point and LWT sensor fault is not active for a time
longer than the evaporator recirculation time set point.
PVM/GFP Fault
Action Taken: Rapid shutdown all circuits and lockout unit
Trigger: Power Configuration = Single Point and PVM/GFP from running.
Input #1 is open for longer than one second.
Reset: This alarm can be cleared manually via the keypad, but
Action Taken: Rapid shutdown all circuits and lockout unit only if the alarm trigger conditions no longer exist.
from running.
Reset: Auto reset when input is closed for at least 5 seconds Evaporator LWT Sensor Fault
or if Power Configuration = Multi Point. Trigger: Sensor shorted or open for longer than one second.
• Resistance value is less than 340 Ω or more than 300 kΩ
• Reliability value reported for input is anything other than
‘No Fault’.
Action Taken: Normal stop all circuits and lock out unit from
running.
Reset: This alarm can be cleared manually via the keypad
or BAS command, but only if the sensor is back in range and
reliability value reported for input is ‘No Fault’ for at least five
seconds.
External Event Reset: Auto reset when input is closed for at least 5 seconds
or if Power Configuration = Single Point.
Trigger: External Alarm/Event input is open for at least 5
seconds and external fault is configured as an event.
Action Taken: None.
Reset: Auto clear when digital input is closed.
The keypad/display consists of a 5-line by 22-character include changeable data fields (setpoints).
display, three buttons (keys) and a “push and roll” navigation When the cursor is on a line the highlights will look like this:
wheel. There is an Alarm Button, Menu (Home) Button and a
Back Button. The wheel is used to navigate between lines on Evaporator Delta T= 10.0F
a screen (page) and to increase and decrease changeable If line contains a changeable value-
values when editing. Pushing the wheel acts as an Enter
Button and will jump from a link to the next set of parameters. Unit Status= Run
If the line contains status-only information-
Figure 71: Typical Screen Or a line in a menu may be a link to further menus. This
is often referred to as a jump line, meaning pushing the
•6 View/Set Unit 3
navigation wheel will cause a “jump” to a new menu. An arrow
Status/Settings > (>) is displayed to the far right of the line to indicate it is a
Set Up > “jump” line and the entire line is highlighted when the cursor is
on that line.
Temperature >
NOTE - Only menus and items that are applicable to the
Date/Time/Schedule >
specific unit configuration are displayed.
Generally, each line on the display contains a menu title, a
This manual includes information relative to the operator level
parameter (such as a value or a setpoint), or a link (which will
of parameters; data and setpoints necessary for the every
have an arrow in the right of the line) to a further menu.
day operation of the chiller. There are more extensive menus
The first line visible on each display includes the menu title and available for the use of service technicians.
the line number to which the cursor is currently “pointing.” In
the above screen, Temperature is highlighted. Navigating
The left most position of the title line includes an “up” arrow ▲ When power is applied to the control circuit, the controller
to indicate there are lines (parameters) “above” the currently screen will be active and display the Home screen, which can
displayed line; and/or a “down” arrow ▼ to indicate there are also be accessed by pressing the Menu Button The navigating
lines (parameters) “below” the currently displayed items or an wheel is the only navigating device necessary, although the
“up/down” arrow • to indicate there are lines “above and below” MENU, ALARM, and BACK buttons can provide shortcuts as
the currently displayed line. The selected line is highlighted. explained later.
Each line on a screen can contain status-only information or
VFD Interface
The VFD controller is located in the lower left-hand corner of
the unit control panel. It is used to view data including fault and
alarm information. No operator intervention on this control is
required for normal unit operation.
State Content
Illuminated When the drive detects an alarm or error
When an alarm occurs
Flashing When an oPE is detected
When a fault or error occurs during Auto-Tuning
Off Normal operation (no fault or alarm)
Flashing
LED Lit Flashing Quickly Off
Slowly
When the operator When a device other than
is selected for Run the operator is selected for
LO/RE command and -- -- Run command and frequency
frequency reference reference control (REMOTE)
control (LOCAL)
While the drive was set to LOCAL, a Run
command was entered to the input terminals
then the drive was switched to REMOTE.
During
A Run command was entered via the input
deceleration
terminals while the drive was not in the Drive
to stop
Mode.
When a Run During deceleration when a Fast Stop
RUN During run command was entered. During stop
command
is input and The drive output is shut of by the Safe Disable
frequency function.
reference is
The STOP key was pressed while drive was
0 Hz
running in REMOTE.
The drive was powered up with b1-17 = 0
(default) while the Run command was active.
Table 94: Fault Reset Methods Table 95: Periodic Inspection Checklist
After the Fault Occurs Procedure Inspection Area Inspection Points Corrective Action
Press RESET on the controller. Inspect equipment Replace damaged
including wiring, components.
terminals, resistors,
Fix the cause of the fault, capacitors, diode and
restart the drive, and reset General IGBT for discoloration
the fault from overheating or
deterioration.
Inspect for dirt or foreign Use dry air to clear
particles away.
Close then open the fault signal
digital input via terminal S4. S4 is Inspect contactors and Check for over or
set for “Fault Reset” as default relays for excessive undervoltage
(H1-04 = 14) noise.
Resetting via Fault Reset Relays and
Digital Input S4 Inspect for signs of Replace damaged
Contactors
overheating such as parts.
melted or cracked
insulation
Table 96: Pumpdown and System Switch Positions 8. If electrical power is off, make provisions to power the
evaporator heater (if chilled water system is not drained
Switch Position or is filled with suitable glycol). Tag all opened electrical
Switch
ON OFF disconnect switches to warn against startup before the
PS1, PS2, Circuits will operate Circuit will go refrigerant valves are in the correct operating position.
Pumpdown Switches in the normal, through the normal To start the chiller after an extended shutdown, follow the pre-
automatic mode pumpdown cycle and startup and startup instructions.
shut off.
S1, System Switch Unit will operate in Unit will shut off Flow Switch Installation and Calibration
the normal automatic immediately without
A thermal dispersion flow switch uses heat to determine
mode pumping down
flow and therefore must be calibrated during system startup.
(emergency stop)
A thermal dispersion flow switch can be an acceptable
replacement for paddle type flow switches and differential
Post Startup pressure switches but care must be taken regarding wiring.
After the chiller has been operating for a period of time and has The thermal dispersion flow switch supplied by Daikin Applied,
become stable, check the following: shown in Figure 1, comes as a 2 part unit consisting of a flow
• Compressor oil level. switch and an adapter labeled E40242 by the supplier.
• Refrigerant sight glass for flashing.
Figure 77: Thermal Dispersion Flow Switch and Adapter
• Rotation of condenser fans.
IMPORTANT: Flow switch
• Complete the “Equipment Warranty Registration Form,”
MUST be calibrated before
found at the end of this manual, within 10 days of start-
chiller operation. Failure to
up in order to comply with the terms of Daikin Limited
properly calibrate the switch
Product Warranty.
may result in severe chiller
damage and/or void warranty.
Shutdown
Temporary Shutdown
1. Put both circuit switches to the OFF position (Pumpdown
and Stop).
2. After compressors have stopped, put System Switch (S1)
to OFF (emergency stop).
3. Turn off chilled water pump. Chilled water pump to
operate while compressors are pumping down.
4. To start the chiller after a temporary shutdown, follow the
startup instructions.
Mounting
Extended Shutdown Figure 78 highlights the position of the electrical connector and
1. Front seat both condenser liquid line service valves. indentation ‘mark’ on flow switch.
2. Put both circuit switches to the OFF position (Pumpdown
and Stop position). Figure 78: Flow Switch Details
3. After the compressors have stopped, put System Switch
(S1) to the OFF position (emergency stop).
4. Front seat both refrigerant circuit discharge valves (if
applicable).
5. If chilled water system is not drained, maintain power to
the evaporator heater to prevent freezing. Maintain heat
tracing on the chilled water lines.
6. Drain evaporator and water piping to prevent freezing.
7. If electrical power to the unit is on, the compressor
crankcase heaters will keep the liquid refrigerant out of
the compressor oil. This will minimize startup time when
putting the unit back into service. The evaporator heater
will be able to function.
It is required that the flow switch be mounted such that the If needed, the adapter is threaded into the pipe using pipe
electrical connection and indentation ‘mark’ are pointed in the sealant appropriate for the application. The flow sensor is
direction of flow as shown in Figure 79. mounted onto the adapter using silicone grease. Carefully
apply lubricant to the inside threads and o-ring so temperature
If the flow sensor is to be mounted away from the unit, the
probe does not become coated with lubricant. Torque the
sensor should be mounted on the wall of the outlet pipe of
adapter/sensor connection to 18.5 ft/lbs.
evaporator and condenser, or in a run of straight pipe that
allows 5 to 10 pipe diameters prior to the sensor and 3 to 5
pipe diameters of straight pipe after the sensor. Flow switch Wiring
is placed in outlet pipe to reflect flow leaving the barrel. If Refer to wiring diagram in the unit control panel.
installation on the inlet pipe is necessary, contact Chiller Either AC or DC is used to power the flow switch. The unit
Technical Response at TechResponse@DaikinApplied.com to controller’s digital input is a DC signal which is supplied
review the jobsite details. through the switch output of the flow switch for flow indication.
It is required that the AC and DC commons of power be
Figure 79: Mount in Direction of Flow
separated. Contact Chiller Technical Response for alternate
wiring scenarios.
Step 3: After the ‘Teach’ function is completed and the outer pressing the ‘-’ button increases the flow set point. Each button
LEDs flashed, the flow switch will indicate a new set point press, ‘+’ or ‘-‘, changes the flow set point by 2.5 cm/s.
based upon the current flow which should still be at the steady Step 4: Press the ‘+’ button until LED ‘9’ begins to flash, as
state minimum desired operating flow. Figure 82 shows a shown in Figure 83. Opening of flow switch should now occur
typical display for this condition. All LEDs to the left of the at approximately 80% to 90% of minimum flow.
SP LED are lit green. The SP LED is lit RED (or may toggle
amber) which indicates that the flow switch is OPEN. Typically,
an increase in fluid flow is between 15% to 30% above the Figure 83: Upper Range of Minimum Flow
‘Teach’ function flow is required for the SP LED to turn AMBER
and the flow switch to CLOSE indicating acceptable flow.
Flow above display range: The SP LED will be lit amber, all
LEDs to the left and right of the SP LED with be green with the
rightmost LED flashing green. For example, if the SP was set
to 200 cm/s, the flashing LED labeled ‘9’ would indicate that
the flow was above 230 cm/s. This may be a normal display
depending on range by which flow varies through chiller.
Component Operation
VFD Low Ambient Control Code 2 – Open/Shorted Motor Thermistor: The module will
flash the red Alert LED two times indicating the motor PTC
(Optional) thermistor circuit has an open/shorted thermistor chain (see
Table 2). A Code 2 Alert will open the M2-M1 contacts. The
The optional VFD fan control is used for unit operation below Alert will reset after 30 minutes and the M2-M1 contacts will
32°F (0°C) down to a minimum of -10°F (-23.3°C). The control close if the resistance of the motor PTC circuit is back in the
looks at the saturated discharge temperature and varies normal range. The module will lockout the compressor and a
(pressure) at the “target” temperature. This temperature is power cycle or Modbus reset command will be required to clear
established as an input to a setpoint screen labeled “Sat the lockout.
Condenser Temp Target.”
Code 3 – Short Cycling: The module will flash the red Alert
LED three times indicating the compressor is locked out due to
Compressor Communications short cycling. Once locked out the compressor, a power cycle
or Modbus reset command will be required to clear the lockout.
The CoreSense™ compressor communication module
on model sizes 070-241 provides advanced diagnostics, Code 4 – Scroll High Temperature: The module will flash
protection, and communications that enhance compressor the red Alert LED four times indicating the over-temperature
performance and reliability. condition. A Code 4 Alert will open the M2-M1 contacts. The
Alert will reset after 30 minutes. Once the module has locked
Features include motor temperature protection, scroll out the compressor, a power cycle or Modbus reset command
temperature protection, missing phase protection, reverse will be required to clear the lockout.
phase protection, low control circuit voltage protection, short
cycling detection and alert, operational and fault history Code 5 – Reserved for Future Use
storage, and LED status display. Code 6 – Missing Phase: The module will flash the red Alert
LED six times indicating a missing phase. The Alert will reset
Crankcase Heaters
The scroll compressors are equipped with externally mounted
band heaters located at the oil sump level. The function of
the heater is to keep the temperature in the crankcase high
enough to prevent refrigerant from migrating to the crankcase
and condensing in the oil during off-cycle.
Power must be supplied to the heaters 8 hours before starting
the compressors.
Evaporator
The evaporators are of brazed plate design. Other than
cleaning and testing, no service work should be required on
the evaporator.
Compressor Maintenance
The scroll compressors are fully hermetic and require no
maintenance other than checking oil level.
Lubrication
No routine lubrication is required on AGZ units. The fan motor
bearings are permanently lubricated and no further lubrication
is required. Excessive fan motor bearing noise is an indication
of a potential bearing failure.
Cleaning Microchannel Aluminum Coils
Maintenance consists primarily of the routine removal of dirt
POE type oil is used for compressor lubrication. Further details
and debris from the outside surface of the fins.
are listed in the Unit Service section on page 120.
Periodic Clean Water Rinse application of this product. As in all surface preparation,
the best work yields the best results.
A monthly clean water rinse is recommended for coils that are
applied in coastal or industrial environments to help to remove 2. Apply CHLOR*RID DTS - Apply CHLOR*RID DTS
chlorides, dirt and debris. An elevated water temperature (not directly onto the substrate. Sufficient product must be
to exceed 130ºF) will reduce surface tension, increasing the applied uniformly across the substrate to thoroughly
ability to remove chlorides and dirt. Pressure washer PSI must wet out surface with no areas missed. This may
not exceed 900 psig and the nozzle should remain at least 1 be accomplished by use of a pump-up sprayer or
foot from the coil to avoid damaging fin edges. conventional spray gun. The method does not matter, as
long as the entire area to be cleaned is wetted. After the
Routine Quarterly Cleaning of Epoxy Coated substrate has been thoroughly wetted, the salts will be
Coil Surfaces soluble and is now only necessary to rinse them off.
Quarterly cleaning is essential to extend the life of an epoxy 3. Rinse - It is highly recommended that a hose be used
coated coil and is required to maintain warranty coverage. as a pressure washer will damage the fins. The water to
Coil cleaning shall be part of the unit’s regularly scheduled be used for the rinse is recommended to be of potable
maintenance procedures. Failure to clean epoxy coated coils quality, though a lesser quality of water may be used if a
will void the warranty and may result in reduced efficiency and small amount of CHLOR*RID DTS is added. Check with
durability in the environment. CHLOR*RID International, Inc. for recommendations on
lesser quality rinse water.
For routine quarterly cleaning, first clean the coil with an
approved coil cleaner (see approved products list in Table 98). Harsh Chemical and Acid Cleaners
After cleaning the coils with the approved cleaning agent, use
the approved chloride remover to remove soluble salts and Harsh chemicals, household bleach or acid cleaners should
revitalize the unit. not be used to clean outdoor or indoor epoxy coated coils.
These cleaners can be very difficult to rinse out of the coil and
Recommended Coil Cleaner can accelerate corrosion and attack the epoxy coating. If there
is dirt below the surface of the coil, use the recommended coil
The following cleaning agent, assuming it is used in cleaners as described above.
accordance with the manufacturer’s directions on the container
for proper mixing and cleaning, has been approved for use on High Velocity Water or Compressed Air
epoxy coated coils to remove mold, mildew, dust, soot, greasy
residue, lint and other particulate: High velocity water from a pressure washer or compressed air
should only be used at a very low pressure to prevent fin and/
or coil damages. The force of the water or air jet may bend the
Table 98: Epoxy Coated Coil Recommended Cleaning
fin edges and increase airside pressure drop. Reduced unit
Agents
performance or nuisance unit shutdowns may occur.
Cleaning Agent Reseller Part Number
Hydro-Balance Corp
DANGER
Enviro-Coil P.O. Box 730
H-EC01 Electric shock hazard. Turn off all power before continuing
Concentrate Prosper, TX 75078
800-527-5166 with following service.
Enviro-Coil
Home Depot H-EC01
Concentrate
High Ambient Control Panel
Chlor*Rid Int’l, Inc.
This option consists of an exhaust fan with rain hood, two inlet
Chloride P.O. Box 908
Chlor*Rid DTS screens with filters, necessary controls and wiring to allow
Remover Chandler, AZ 85244
operation to 125°F (52°C). The components can be factory or
800-422-3217
field installed as a kit.
• It must be supplied on units operating at ambient
CHLOR*RID DTS™ should be used to remove soluble salts temperatures of 105°F (40.6°C) and above.
from epoxy coated coils, but the directions must be followed • It is automatically included on units with fan VFD (low
closely. This product is not intended for use as a degreaser. ambient option).
Any grease or oil film should first be removed with the
• Check inlet filters periodically and clean as required.
approved cleaning agent.
Verify that the fan is operational.
1. Remove Barrier - Soluble salts adhere themselves
to the substrate. For the effective use of this product,
the product must be able to come in contact with the
salts. These salts may be beneath any soils, grease or
dirt; therefore, these barriers must be removed prior to
Expansion Valve
The expansion valve’s function is to keep the evaporator
supplied with the proper amount of refrigerant to satisfy the
load conditions.
Before adjusting superheat, check that unit charge is correct
and liquid line sight glass is full with no bubbles and that the
circuit is operating under stable, full load conditions.
Thermal Expansion Valve - The suction superheat for the
suction leaving the evaporator is set at the factory to 10
degrees F.
Electronic Expansion Valve - For suction superheat targets,
see “Circuit Level Set Points” on page 66
Monthly Annual
Operation Weekly
(Note 1) (Note 2)
General
Complete unit log and review (Note 3) X
Visually inspect unit for loose or damaged components X
Inspect thermal insulation for integrity X
Clean and paint as required X
Electrical
Check terminals for tightness, tighten as necessary X
Clean control panel interior X
Visually inspect components for signs of overheating X
Verify compressor heater operation X
Test and calibrate equipment protection and operating controls X
Megger compressor motor (Note 4) X
Refrigeration
Leak test X
Check sight glasses for clear flow X
Check filter-drier pressure drop (see manual for spec) X
Perform compressor vibration test X
Acid test oil sample X
Condenser (air-cooled)
Clean condenser coils (Note 5) X
Check fan blades for tightness on shaft (Note 6) X
Check fans for loose rivets and cracks X
Check coil fins for damage X
Notes:
1. Monthly operations include all weekly operations.
2. Annual (or spring start-up) operations includes all weekly
and monthly operations.
3. Log readings can be taken daily for a higher level of unit
observation.
4. Never Megger motors while they are in a vacuum to
avoid damage to the motor.
5. Coil cleaning can be required more frequently in areas
with a high level of airborne particles.
6. Be sure fan motors are electrically locked out.
Troubleshooting Chart
High Discharge 3. Optional discharge shutoff valve not open 3. Open valve.
Pressure 4. Condenser fan control wiring not correct 4. Correct wiring.
5. Fan not running 5. Check electrical circuit and fan motor.
6. Dirty condenser coil 6. Clean coil.
7. Air recirculation 7. Correct.
1. Rapid load swings 1. Stabilize load.
2. Lack of refrigerant 2. Check for leaks, repair, add charge. Check liquid sight glass.
3. Fouled liquid line filter drier 3. Check pressure drop across filter drier. Replace.
4. Expansion valve malfunctioning 4. Repair or replace and adjust for proper superheat.
Low Suction
5. Condensing temperature too low 5. Check means for regulating condenser temperature.
Pressure
6. Compressors not staging properly 6. See corrective steps - Compressor Staging Intervals Too Low.
7. Insufficient water flow 7. Correct flow.
8. Excess or wrong oil used 8. Recover or change oil
9. Evaporator dirty 9. Back flush or clean chemically.
Compressor Oil 5. Insufficient water flow - Level too high 5. Correct flow, verify superheat.
Level Too High Or 6. Excessive liquid in crankcase - Level too high 6. Check crankcase heater. Check liquid line solenoid valve operation.
Too Low 7. Short cycling 7. Stabilize load or correct control settings for application.
8. HGBP valve oversize or improperly set-up 8. replace or adjust HGBP valve
9. Expansion valve operation or selection 9. Confirm superheat at minimum and maximum load conditions
10. Compressor mechanical issues 10. Replace compressor
11. Wrong oil for application 11. Verify
1. Voltage imbalance or out of range 1. Correct power supply.
Motor Overload
2. Defective or grounded wiring in motor 2. Replace compressor.
Relays or Circuit
3. Loose power wiring or burnt contactors 3. Check all connections and tighten, replace contactors.
Breakers Open
4. High condenser temperature 4. See corrective steps for High Discharge Pressure.
1. Operating beyond design conditions 1. Correct so conditions are within allowable limits.
2. Discharge valve not open 2. Open valve.
Compressor Thermal
3. Short cycling 3. Stabilize load or correct control settings for application
Protection Switch
4. Voltage range or imbalance 4. Check and correct.
Open
5. High superheat 5. Adjust to correct superheat.
6. Compressor mechanical failure 6. Replace compressor.
Daikin G .O . No .: Daikin S .O . No .:
Pre Start-Up Checklist, All NO checks require an explanation under "Description". Please check yes or no.
YES NO
A. Is the unit free of visible shipping damage, corrosion or paint problems?
C. Does the unit meet all location, installation and service clearances per IM Bulletin?
I. Has a fused disconnect and fuses or breaker been sized per product manual and installed per local code?
6/12/15 MLP
Control # - SF99007 1
N. Water Strainer installed? Brazed Plate Evaporator 0.063" (1.6mm) or smaller perforations
P. Has the chill water circuit been cleaned, flushed, and water treatment confirmed?
Q. Does the chiller and condenser water piping conform to the IM manual?
T. Description of unit location with respect to building structures. Include measured distances.
Description:
D. Does piping to unit appear to be adequately sized and installed according to the IM bulletin?
F. Is level of oil in sightglass visible butnot more than 1/2 glass with compressors running?
A. CHILLER
Water Pressure Drop: psig(kPa) Ft. (kPa) gpm (lps)
Water Temperatures: Entering °F (°C) Leaving °F (°C)
B. CONDENSER
Water Pressure Drop: psig(kPa) Ft. (kPa) gpm (lps)
Water Temperatures: Entering °F (°C) Leaving °F (°C)
V. START-UP
YES NO
A. Does unit start and perform per sequence of operation as stated in the IM Manual?
MICROTECH STATUS CHECK-Each Reading Must be Verified with Field Provided Instruments of Known Accuracy?
MicroTech Verification
C. Water Temperatures: Leaving Evaporator ……………………………… °F (°C) °F (°C)
Entering Evaporator ……………………………… °F (°C) °F (°C)
Entering Condenser ……………………………… °F (°C) °F (°C)
Leaving Condenser ……………………………… °F (°C) °F (°C)
D. Circuit #1 Refrigerant Pressures:
Evaporator …………………………………………. psig (kPa) psig (kPa)
Liquid Line pressure …………………………………………………………….. psig (kPa)
Condenser Pressure ……………………………… psig (kPa) psig (kPa)
E. Circuit #2 Refrigerant Pressures:
Evaporator …………………………………………. psig (kPa) psig (kPa)
Liquid Line Pressure ……………………………………………………………. psig (kPa)
Condenser Pressure …………………………….. psig (kPa) psig (kPa)
F. Circuit #1 Refrigerant Temperatures:
Saturated Evaporator Temperature …………………… °F (°C) °F (°C)
Suction Line Temperature ………………………………. °F (°C) °F (°C)
Suction Superheat ………………………………………. °F (°C) °F (°C)
Saturated Condenser Temperature …………………… °F (°C)
Liquid Line Temperature ………………………………………………………….. °F (°C)
Subcooling ………………………………………………………………………….. °F (°C)
Discharge Temperature ………………………………………………………….. °F (°C)
G. Circuit #2 Refrigerant Temperatures:
Saturated Evaporator Temperature …………………… °F (°C) °F (°C)
Suction Line Temperature ………………………………. °F (°C) °F (°C)
Suction Superheat …………………………………….... °F (°C) °F (°C)
Saturated Condenser Temperature …………………… °F (°C)
Liquid Line Temperature …………………………………………………………… °F (°C)
Subcooling ………………………………………………………………………….. °F (°C)
Discharge Temperature …………………………………………………………… °F (°C)
NON-MICROTECH READINGS
I. Does the system contain glycol? Yes No
Percentage by weight or by volume Glycol Type
J. If the chilled water system include glycol, have the freezstats been adjusted lower to meet acutal job requirements?
Note: See operation manual for low temperature on ice bank applications . Yes No
6/12/15 MLP
Control # - SF99007 3
VII. FOR TGZ Templifier CHILLERS ONLY (Must Be Taken At Full Load)
A. Place Unit in heat recovery mode.
B. Condenser Pressure Drop: psig (kPa) Ft. (kPa) gpm (lps)
C. Condenser Temperatures: Inlet Outlet
D. Head Pressure: Circuit #1 psig (kPa) Circuit #2: psig (kPa)
E: Evaporator Pressure Drop: psig (kPa) Ft. (kPa) gpm (lps)
F: Evaporator Temperatures: Inlet Outlet
G. Suction Pressure: Circuit #1 psig (kPa) Circuit #2: psig (kPa)
F. Compressor Current Per Phase
Compressor #1 L1 AMPS L2 AMPS L3 AMPS
Compressor #2 L1 AMPS L2 AMPS L3 AMPS
Compressor #3 L1 AMPS L2 AMPS L3 AMPS
Compressor #4 L1 AMPS L2 AMPS L3 AMPS
Compressor #5 L1 AMPS L2 AMPS L3 AMPS
Compressor #6 L1 AMPS L2 AMPS L3 AMPS
VIII. GENERAL
YES NO
A. Are all control lines secure to prevent excess vibration and wear? ……………………………………….
B. Are all gauges shut off, valve caps, and packings tight after startup? ……………………………………
Refrigerant Leaks:
6/12/15 MLP
Control # - SF99007 4
Repairs Made
Company Name:
Address:
Modem Number:
Signature: Date:
Contractor's Signature
RETURN COMPLETED FORM TO: DAIKIN, WARRANTY DEPT., PO BOX 2510, STAUNTON, VA 24402
6/12/15 MLP
Control # - SF99007 5
Daikin Applied Americas Inc. dba Daikin Applied (“Company”) warrants to contractor, purchaser and any owner of the product
(collectively “Owner”) that Company, at it’s option, will repair or replace defective parts in the event any product manufactured by
Company, including products sold under the brand name Daikin and used in the United States or Canada, proves defective in material
or workmanship within twelve (12) months from initial startup or eighteen (18) months from the date shipped by Company, whichever
occurs first. Authorized replaced parts are warranted for the duration of the original warranty. All shipments of such parts will be
made FOB factory, freight prepaid and allowed. Company reserves the right to select carrier and method of shipment.
In addition, labor to repair or replace warranty parts is provided during Company normal working hours on products with rotary
screw compressors and centrifugal compressors. Warranty labor is not provided for any other products.
Company’s liability to Owner under this warranty shall not exceed the lesser of the cost of correcting defects in the products sold or the
original purchase price of the products.
PRODUCT STARTUP ON CENTRIFUGAL AND SCREW COMPRESSOR PRODUCTS IS MANDATORY and must be
performed by a Daikin Applied or a Company authorized service representative.
It is Owner’s responsibility to complete and return the Registration and Startup Forms accompanying the product to Company within
ten (10) days of original startup. If this is not done, the ship date and the startup date will be deemed the same for warranty period
determination, and this warranty shall expire twelve (12) months from that date.
EXCEPTIONS
1. If free warranty labor is available as set forth above, such free labor does not include diagnostic visits, inspections, travel time and
related expenses, or unusual access time or costs required by product location.
2. Refrigerants, fluids, oils and expendable items such as filters are not covered by this warranty.
3. This warranty shall not apply to products or parts which (a) have been opened, disassembled, repaired, or altered by anyone other
than Company or its authorized service representative; or (b) have been subjected to misuse, negligence, accidents, damage, or
abnormal use or service; or (c) have been operated, installed, or startup has been provided in a manner contrary to Company’s
printed instructions, or (d) were manufactured or furnished by others and which are not an integral part of a product manufactured
by Company; (e) have been exposed to contaminates, or corrosive agents, chemicals, or minerals, from the water supply source, or
(f) have not been fully paid for by Owner.
ASSISTANCE
To obtain assistance or information regarding this warranty, please contact your local sales representative or a Daikin Applied office.
SOLE REMEDY
THIS WARRANTY CONSTITUTES THE OWNER’S SOLE REMEDY. IT IS GIVEN IN LIEU OF ALL OTHER
WARRANTIES. THERE IS NO IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE. IN NO EVENT AND UNDER NO CIRCUMSTANCE SHALL COMPANY BE LIABLE FOR INCIDENTAL,
INDIRECT, SPECIAL, CONTINGENT OR CONSEQUENTIAL DAMAGES, WHETHER THE THEORY BE BREACH OF
THIS OR ANY OTHER WARRANTY, NEGLIGENCE OR STRICT LIABILITY IN TORT.
No person (including any agent, sales representative, dealer or distributor) has the authority to expand the Company’s obligation
beyond the terms of this express warranty or to state that the performance of the product is other than that published by Company.
For additional consideration, Company will provide an extended warranty(ies) on certain products or components thereof. The terms
of the extended warranty(ies) are shown on a separate extended warranty statement.
Warranty
All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale, including
Limited Product Warranty. Consult your local Daikin Applied representative for warranty details. To find
your local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.