Professional Documents
Culture Documents
Ansi Ashrae 133-2015
Ansi Ashrae 133-2015
Method of Testing
Direct Evaporative
Air Coolers
Approved by ASH RAE on J anuary 3 0, 201 5 , and by the American N ational Standards I nstitute on February 2, 201 5 .
ASH RAE Standards are scheduled to be updated on a five-year cycle; the date foll owing the standard number is the year of
ASH RAE approval . The latest edition of an ASH RAE Standard may be purchased on the ASH RAE website (www. ashrae. org) or
from ASH RAE Customer Service, 1 791 Tull ie Circle, N E, Atlanta, GA 3 03 29-23 05 . E-mail: orders@ashrae. org. Fax: 678-5 3 9-
21 29. Telephone: 404-63 6-8400 (worldwide) or toll free 1 -800-5 27-4723 (for orders in U S and Canada). For reprint permission,
go to www. ashrae. org/permissions.
Facebook/4MechEngineer Linked-in/4MechEngineer
Instagram/4MechEngineer YouTube/4MechEngineer
Google+/4MechEngineer Twitter/4MechEngineer
© ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution,
or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
ASHRAE Standards Project Committee 1 33
Cognizant TC: TC 5.7, Evaporative Cooling
SPLS Liaison: Waller S. Clements
Patricia T. Graef, Chair* Gursaran D. M athur* H ofu Wu*
* Denotes members of voting status when the document was approved for publication
SPECIAL NOTE
This American N ational Standard (AN S) is a national vol untary consensus Standard devel oped under the auspices of ASH RAE. Consensus is defined
by the American N ational Standards I nstitute (AN SI ), of which ASH RAE is a member and which has approved this Standard as an AN S, as
“substantial agreement reached by directl y and material l y affected interest categories. This signifies the concurrence of more than a simpl e majority,
but not necessaril y unanimity. Consensus requires that all views and objections be considered, and that an effort be made toward their resolution. ”
Compliance with this Standard is voluntary until and unl ess a l egal jurisdiction makes compliance mandatory through l egisl ation.
ASH RAE obtains consensus through participation of its national and international members, associated societies, and publ ic review.
ASH RAE Standards are prepared by a Project Committee appointed specifical l y for the purpose of writing the Standard. The Project
Committee Chair and Vice-Chair must be members of ASH RAE; whil e other committee members may or may not be ASH RAE members, al l
must be technical l y qual ified in the subject area of the Standard. Every effort is made to balance the concerned interests on all Project Committees.
The Senior M anager of Standards of ASH RAE shoul d be contacted for
a. interpretation of the contents of this Standard,
b. participation in the next review of the Standard,
c. offering constructive criticism for improving the Standard, or
d. permission to reprint portions of the Standard.
DISCLAIMER
ASH RAE uses its best efforts to promul gate Standards and Guidel ines for the benefit of the publ ic in l ight of avail abl e information and accepted
industry practices. H owever, ASH RAE does not guarantee, certify, or assure the safety or performance of any products, components, or systems
tested, instal led, or operated in accordance with ASH RAE’s Standards or Guidel ines or that any tests conducted under its Standards or Guidelines
wil l be nonhazardous or free from risk.
CONTENTS
ANSI/ASHRAE Standard 1 33-201 5,
Method of Testing Direct Evaporative Air Coolers
SECTION PAGE
Foreword ..................................................................................................................................................................... 2
1 Purpose ............................................................................................................................................................. 2
2 Scope ................................................................................................................................................................ 2
3 Definitions ......................................................................................................................................................... 2
4 Symbols and Subscripts.................................................................................................................................... 3
5 Requirements.................................................................................................................................................... 4
6 Instruments and Methods of Measurement....................................................................................................... 4
7 Equipment and Setup........................................................................................................................................ 6
8 Data to Be Recorded......................................................................................................................................... 7
9 Calculations....................................................................................................................................................... 7
1 0 Performance Corrections to Nominal or Standard Airflow Rate and Speed...................................................... 9
1 1 Report and Results of Test................................................................................................................................ 9
1 2 References ...................................................................................................................................................... 1 0
Informative Annex A: Bibliography ........................................................................................................................ 1 1
Informative Annex B: Additional Figures ............................................................................................................... 1 2
NOTE
Approved addenda, errata, or interpretations for this standard can be downloaded free of charge from the ASHRAE
Web site at www.ashrae.org/technology.
© 201 5 ASHRAE
1 791 Tullie Circle NE · Atlanta, GA 30329 · www.ashrae.org · All rights reserved.
ASHRAE is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
ANSI is a registered trademark of the American National Standards Institute.
2.3 This standard requires that packaged and component ECU outlet area: the gross inside area measured in the
direct evaporative air coolers be simultaneously tested for air- plane(s) of the outlet opening(s).
flow, total power, and saturation effectiveness. ECU static pressure differential: the static pressure differen-
2.4 The ratings resulting from application of this standard are tial measured across the ECU and its appurtenances at each
intended for use by manufacturers, specifiers, installers, and point of operation.
users of evaporative air cooling apparatus for residential,
ECU total power: the sum of the power in watts supplied to
commercial, agricultural, and industrial ventilation; for air-
the electrical components of the evaporative cooler tested.
cooling applications; and for commercial, industrial, and agri-
This includes fan motors, pump motors, and other devices
cultural processing applications.
needed to produce the cooling effect. The power to control
3. DEFINITIONS AND ACRONYMS devices such as thermostats, transformers providing low volt-
age to control mechanisms, and freeze protection devices
adiabatic saturation: evaporating water into air without shall not be included in total power.
external gain or loss of heat. Sensible heat in both air and
water becomes latent heat in evaporated vapor. The air is ECU water flow rate: the water supplied to the ECU header.
cooled and humidified. evaporative air cooling: two methods using evaporating
appurtenance device power: the electric power to drive water to cool air: direct, which is adiabatic and humidifies the
accessories—not including fans, pumps, or rotary devices— air, and indirect, which is not adiabatic and cools the air being
supplied as a standard component of the production model of treated without adding moisture.
standard air: dry air with a density of 1 .204 kg/m3 (0.075 P pressure differential, Pa (in. wg)
lbm/ft3 ), a specific heat of 1 .006 kJ/kg·K (0.24 Btu/lbm·°F), PECU pressure differential across ECU, Pa (in. wg)
and a viscosity of 1 .82×1 0 –5 N·s/m2 (1 .22×1 0 –5 lbm/ft·s). Air Pelbow pressure differential of elbow, Pa (in. wg)
at 20°C (68°F), 0% relative humidity, and 1 01 .325 kPa (29.92
in. Hg) has these properties, approximately.
Pnozzle pressure differential of nozzle, Pa (in. wg)
Pstd pressure differential corrected to standard air,
test: a series of determinations for various points of operation. Pa (in. wg)
wet-bulb depression: the difference between the dry-bulb and µ air viscosity, Pa·s (lbm/ft·s)
wet-bulb temperatures of an airstream.
air density, kg/m3 (lbm/ft3 )
4. SYMBOLS AND SUBSCRIPTS x air density at plane x, kg/m3 (lbm/ft3 )
4.1 Symbols std density of air at standard air condition, kg/m3 (lbm/ft3 )
A area of cross section, m2 (ft2 ) summation sign
C nozzle discharge coefficient, dimensionless 4.2 Subscripts
D diameter and equivalent diameter, m (ft) x plane or station x, where x = 0, 1 , 2, etc., as appropriate
D pressure tap diameter, mm (in.) 0 plane 0 (ECU inlet)
E energy factor, dimensionless 1 plane 1 (pressure tap station)
L nozzle throat dimension, m (ft) 2 plane 2 (temperature measurement station)
M chamber diameter or equivalent diameter, m (ft) 3 plane 3 (nozzle inlet station)
Nn nominal or corrected fan speed, rpm 4 plane 4 (nozzle discharge station)
N ECU fan speed as measured, rpm n nominal
n number of readings, dimensionless std standard
FIGURE 2 Static pressure tap. Note: A 2 mm (0.07 in.) hole is the maximum size that will allow space for a smooth surface 20 D from
the hole when installed 38 mm (1 .5 in.) from a partition, as in Figures 3 and B-1 .
6.1.4 Calibration. Where an accuracy closer than ±0.30°C 6.3.1 Nozzle Apparatus. This airflow-measuring appara-
(0.50°F) is specified, the instruments shall be calibrated by tus is shown schematically in Figures 3 and B-1 . Each nozzle
comparison with a thermometer that has a National Institute station consists of a receiving chamber and a discharge cham-
of Standards and Technology (NIST) certification in the range ber separated by a partition in which one or more nozzles of
of use, or a thermometer with a NIST certification shall be equal or unequal size are located. A detailed description of
used. the nozzle apparatus is given in ASHRAE Standard 41 .2. 3
6.1.5 Practice 6.3.2 Calibration. The standard nozzle is considered a pri-
mary instrument and need not be calibrated if maintained in
6.1.5.1 Wet-Bulb Temperature. Wet-bulb temperatures
the specified condition. Reliable coefficients have been estab-
shall be read only under conditions that ensure an air velocity
lished for throat dimension L = 0.6 D. Throat dimension L =
of 3.5 to 1 0 m/s (700 to 2000 ft/min) over the wet-bulb, and
0.6 D is recommended for testing airflow of direct evaporative
only after sufficient time has been allowed for evaporative
cooling equipment.
equilibrium to be attained.
6.3.3 Practice. The throat velocity of any nozzle in use shall
6.1.5.2 Measurement Stations. The same measuring not be less than 1 5 m/s (3000 ft/min) nor greater than 35 m/s
methods and equipment shall be used at all measurement sta- (7000 ft/min). For detailed instructions on nozzle construction
tions. and use with the airflow-measuring apparatus, see ASHRAE
6.2 Pressure Measurement. Other than barometric pressure, 41 .2. 3
static pressure in ducts or chambers shall be measured with 6.4 Power. Power shall be measured using a wattmeter con-
special taps designed to eliminate velocity effects. Each loca- nected to the ECU. Wattmeters shall have an accuracy of
tion requiring a static pressure measurement shall use a mini- ±1 .0% of observed reading.
mum of four taps equidistant around the perimeter of the duct
or chamber. These taps shall be joined in a piezometer ring
6.5 Water Flow. Water flow shall be measured using a total-
izing water meter connected to the ECU and a timing device
and the ring used for measurement. Static pressure taps (Fig-
to determine the rate of water flow. Water meters shall have
ure 2) are required on both sides of the flow nozzles and
an accuracy of ±5.0% of observed reading.
downstream of the ECU.
6.2.1 Type. Pressure measurement shall be made in accor- 6.6 Speed. Speed shall be measured with a revolution coun-
ter and chronometer, a stroboscope counter and chronometer,
dance with ASHRAE Standard 41 .3. 2
a precision instantaneous tachometer, an electronic counter-
6.2.2 Accuracy. The accuracy of pressure-measuring timer, or any other device that has a demonstrated accuracy of
instruments shall permit measurements with ±1 % of the ±0.5% of the value being measured.
reading. Barometric pressure shall have accuracy of ±34 Pa
6.6.1 Strobe. A stroboscopic device triggered by the line
(0.01 in. Hg).
frequency of a public utility is considered a primary instru-
6.2.3 Scale. In no case shall the smallest scale division of ment and need not be calibrated if it is maintained in good
the pressure-measuring instrument exceed two times the spec- condition.
ified accuracy. 6.6.2 Chronometer. The chronometer used for all time
6.3 Airflow Measurement. The airflow rate shall be deter- measurements shall have a display in seconds and keep time
mined by measuring the pressure differential across elliptical accurately to within ±2 minutes per day.
flow nozzles in chambers as shown in Figure 3. Determina- 6.6.3 Other Devices. The combination of a line frequency
tions shall be in accordance with ASHRAE Standard 41 .2. 3 strobe and chronometer shall be used to calibrate all other
FIGURE 3 Airflow measuring apparatus from setup in Figure B-1 (shown without throat taps or air-sampling device).
Note: Dimension J shall be at least 1 .0 times the fan equivalent discharge diameter for ECUs having fans with axis of rotation perpendic-
ular to the discharge airflow and at least 2.0 times the fan equivalent discharge diameter for ECUs having fans with axis of rotation paral-
lel to the discharge airflow.
Note: The distance from the exit face of the largest nozzle to the downstream settling means shall be a minimum of 2.5 × D4, the throat
diameter of the largest nozzle.
speed-measuring devices. Friction-driven counters shall not 7.1.3 Component Direct Evaporative Cooler Testing.
be used when they influence the speed due to drag. Component ECU testing shall be performed using the same
6.7 Water Conductivity. Water conductivity shall be mea- techniques as packaged ECU testing.
sured using a conductivity meter having an accuracy ±1 0% of 7.1.4 Mixers. Mixing or other types of devices shall be
observed reading. The meter shall have a means for tempera- used to ensure uniform temperature profiles to the ECU and
ture compensation. measurement devices in accordance with ANSI/ASHRAE
6.7.1 Calibration. Conductivity meters shall be calibrated Standard 41 .1 . 1
using a certified calibration solution according to the manu- 7.2 Ducts. Short ducts that are used to simulate outlet duct
facturer’s instructions. work shall be between 2 and 3 equivalent diameters in length
and have an area ±0.5% of the outlet area and a uniform shape
7. EQUIPMENT AND SETUP to fit the outlet. If the ECU is tested without outlet ductwork,
7.1 Setup. The suggested setup is shown in Figure B-1 . it shall be mounted on the end of the chamber.
7.1.1 Down Discharge Coolers. Down discharge coolers 7.2.1 Leakage. The ducts, chambers, and other equipment
shall be tested with a uniform elbow of an area with ±0.5% of utilized shall be designed to withstand the pressure and other
the ECU outlet area and a shape to fit the ECU outlet. The forces to be encountered. All joints between the ECU and the
elbow shall connect the discharge of the ECU to the chamber. measuring station shall be sufficiently tight so that measure-
See Figure 4. ments are not affected by more than one-half the allowable
7.1.2 The elbow system effect factor (SEF) shall be consid- instrument error.
ered. To minimize SEF for downdraft ECUs having centrifu- 7.3 Chambers. A chamber shall be incorporated in a labora-
gal blowers, the blower shall be oriented such that the turn of tory setup to provide a measuring station, to simulate the con-
the elbow follows the rotation of the shaft (see Figure 4). ditions the ECU is expected to encounter in service, or both.
FIGURE 4 Details of orientation of elbows for downdraft ECUs from Figure B-1 .
Such a chamber shall have a circular or rectangular cross-sec- shall be checked against a drawing and a copy of the drawing
tional shape. The dimension M in the test setup diagram (Fig- attached to the data.
ure 3) is the inside diameter of a circular chamber or the
8.2 Test Setup. The description of the test setup, including
equivalent diameter of a rectangular chamber with inside
specific dimensions, shall be recorded. The instruments and
transverse dimensions a and b where
apparatus used in the test shall be listed. Names, model num-
bers, serial numbers, scale ranges, and calibration information
M= (4 ab ⁄ ) 1 ⁄2 (1 )
shall be recorded.
7.3.1 Airflow Settling Means. Airflow settling means 8.3 Test Data. Test data for each determination shall be
shall be installed in the chamber(s) where indicated on the
recorded. Readings shall be made simultaneously whenever
test setup as shown in Figures 3 and B-1 . Settling means pro-
possible.
vide a proper airflow pattern. Where a measuring plane is
For all tests, three readings of the following shall be
located downstream of the settling means, the settling means
recorded and averaged for each determination:
is provided to ensure a substantially uniform airflow ahead of
the measuring plane. In this case, the maximum velocity at a a. ECU inlet dry-bulb temperature (td0 )
distance 0.1 M downstream of the screen shall not exceed the b. ECU inlet wet-bulb temperature (tw0 )
average velocity by more than 25% unless the maximum c. ambient barometric pressure (pb)
velocity is less than 2 m/s (400 fpm). Where measuring d. ECU downstream dry-bulb temperature (td2 )
planes are located on both sides of the settling means within
e. ECU downstream wet-bulb temperature (tw2 )
the chamber, the requirements for each side as outlined above
f. Fan speed (N)
shall be met. A performance check shall be performed to ver-
g. Power input to fan (Wf)
ify that the airflow settling means are providing proper air-
flow patterns. h. Power input to pump or rotary device (Wp)
i. Power input to appurtenances (Wa)
7.3.2 Multiple Nozzles. Multiple nozzles shall be located
j. ECU static pressure differential (P ECU)
as symmetrically as possible. The centerline of each nozzle
shall be at least 1 .5 nozzle throat diameters from the chamber k. Nozzle pressure differential (Pnozzle)
wall. The minimum distance between centers of any two noz- l. Water conductivity
zles in simultaneous use shall be three times the throat diame- When the ECU is not supplied with a pump or rotary
ter of the larger nozzle. device, water flow to the ECU (QW) shall be recorded.
7.4 Point of Operation. A means of varying the point of 8.4 Personnel. The names of test personnel shall be listed
operation shall be provided in the laboratory setup. If auxil- with the data for which they are responsible.
iary fans are used to control the point of operation of the
ECU, they shall be designed to produce sufficient pressure at 9. CALCULATIONS
the desired airflow rate to overcome losses through the test
setup, including any necessary transitional ductwork or 9.1 Calibration Correction. Calibration corrections, when
elbows located between the ECU and test chamber. Auxiliary required, shall be applied to individual readings before aver-
fans shall not surge or pulsate during tests. aging or other calculations. Calibration corrections need not
be made if the correction is smaller than one-half the maxi-
8. DATA TO BE RECORDED mum allowable error as specified in Section 6.
8.1 Test ECU. The description of the test ECU shall be 9.2 Density and Viscosity ofAir
recorded. The nameplate data shall be copied. Dimensions 9.2.1 Air Density
t d 0 + 459.67 P sx + 1 3.63 p b
x = 0 (5 I-P) Re =
2
CD 4 Y P Nozzle 2 1 – E 4
1 2
tdx + 459.67 1 3.63 p b 2
(1 2 SI)
Q2 = 1 097 Y 4 2 P Nozzle 2
1 2
CA 4 (1 6 I-P) Qstd = QECU( 0⁄std) (22)
INFORMATIVE ANNEX B
ADDITIONAL FIGURES
FIGURE B-2a Typical performance curve format for packaged ECU reported at constant speed.
FIGURE B-2b Typical performance curve format for packaged ECU reported with varying speed.
INPUT DATA ___________ 1 ________ 2 _______ 3 _______ 4 _______ 5 _______ 6 ______ 7________8 _______
1. ECU Outlet Area: ____________________________________________________________________________________
2. Nozzles Used (_a, _b, _c): ______________________________________________________________________________
3. Nozzle P: __________________________________________________________________________________________
4. Static Pressure Differential of ECU: ______________________________________________________________________
PECU = Ps + ( Pelbow + SEF)( std 0 ) _______________________________________________________________
a) Ps = Ps1 – Ps0 __________________________________________________________________________________
b) Pelbow: _______________________________________________________________________________________
c) SEF ___________________________________________________________________________________________
5. Dry-Bulb Temp. in, td0: ________________________________________________________________________________
6. Dry-Bulb Temp. out, td2: _______________________________________________________________________________
7. Wet-Bulb Temp. in, tw0: ________________________________________________________________________________
8. Wet-Bulb Temp. out, tw2: _______________________________________________________________________________
9. Saturation Effectiveness: _______________________________________________________________________________
= (td0 – td2 ) (td0 – tw0 ): _____________________________________________________________________________
1 0. Barometric Pressure, Pb: _______________________________________________________________________________
1 1 . Air Density: _________________________________________________________________________________________
a) 0 : ____________________________________________________________________________________________
b) 2 : ____________________________________________________________________________________________
1 2. ECU W = Wf+Wp + Wa: ________________________________________________________________________________
a) Fan Power, Wf: __________________________________________________________________________________
b) Pump Power, Wp: ________________________________________________________________________________
c) Appurtenance Power, Wa: __________________________________________________________________________
1 3. Fan Rotation, N: ______________________________________________________________________________________
1 4. Sheave Setting: ______________________________________________________________________________________
1 5. Nozzle Coefficients, C: ________________________________________________________________________________
a) C, Nozzle ‘ a’ ___________________________________________________________________________________
b) C, Nozzle ‘ b’ ___________________________________________________________________________________
c) C, Nozzle ‘ c’ ___________________________________________________________________________________
1 6. Nozzle Area, A a + A b + A c ______________________________________________________________________________
a) Nozzle Area, A a: _________________________________________________________________________________
b) Nozzle Area, A b: _________________________________________________________________________________
c) Nozzle Area, A c: _________________________________________________________________________________
1 7. QECU = (Qa + Qb + Qc)( 2 0) __________________________________________________________________________
a) Airflow, Nozzle ‘ a’, Qa: ___________________________________________________________________________
b) Airflow, Nozzle ‘b’ , Qb ___________________________________________________________________________
c) Airflow, Nozzle ‘ c’, Qc ____________________________________________________________________________
FIGURE B-4 Typical report format for packaged ECU.
INPUT DATA ___________ 1 ________ 2 _______ 3 _______ 4 _______ 5 _______ 6 ______ 7________8 _______
1. ECU Outlet Area: ____________________________________________________________________________________
2. Nozzles Used (_a, _b, _c): ______________________________________________________________________________
3. Nozzle PNozzle: _____________________________________________________________________________________
4. Static Pressure Differential of ECU: ______________________________________________________________________
PECU = Ps + ( Pelbow + SEF)( std 0 ) _______________________________________________________________
a) Ps = Ps1 – Ps0 __________________________________________________________________________________
b) Pelbow: _______________________________________________________________________________________
c) SEF ___________________________________________________________________________________________
5. Dry-Bulb Temp. in, td0: ________________________________________________________________________________
6. Dry-Bulb Temp. out, td2: _______________________________________________________________________________
7. Wet-Bulb Temp. in, tw0: ________________________________________________________________________________
8. Wet-Bulb Temp. out, tw2: _______________________________________________________________________________
9. Saturation Effectiveness: _______________________________________________________________________________
= (td0 – td2 ) (td0 – tw0 ): _____________________________________________________________________________
1 0. Barometric Pressure, Pb: _______________________________________________________________________________
1 1 . Air Density, : _______________________________________________________________________________________
a) 0 : ____________________________________________________________________________________________
b) 2 : ____________________________________________________________________________________________
1 2. ECU W = Wf+ Wp + Wa: _______________________________________________________________________________
a) Pump Power, Wp: ________________________________________________________________________________
b) Appurtenance Power, Wa: __________________________________________________________________________
1 3. Nozzle Coefficients, C: ________________________________________________________________________________
a) C, Nozzle ‘ a’ ___________________________________________________________________________________
b) C, Nozzle ‘ b’ ___________________________________________________________________________________
c) C, Nozzle ‘ c’ ___________________________________________________________________________________
1 4. Nozzle Area, A a + A b + A c ______________________________________________________________________________
a) Nozzle Area, A a: _________________________________________________________________________________
b) Nozzle Area, A b: _________________________________________________________________________________
c) Nozzle Area, A c: _________________________________________________________________________________
1 5. Entrainment? (Y, N): __________________________________________________________________________________
1 6. ECU Water Flow Rate, Qw _____________________________________________________________________________
1 7. Water Conductivity ___________________________________________________________________________________
DENSITY CORRECTIONS______________1 ______2 ______ 3 ______ 4 ______ 5 ______6 ______7 _____ 8 _____
1 8. QECU = (Qa + Qb + Qc) ( 2 0)__________________________________________________________________________
a) Airflow, Nozzle ‘ a’, Qa: ___________________________________________________________________________
b) Airflow, Nozzle ‘b’ , Qb ___________________________________________________________________________
c) Airflow, Nozzle ‘ c’, Qc
1 9. std = 1 – (1 – ) (0std): _______________________________________________________________________________
20. Pstd = PECU (std 0): _______________________________________________________________________________
21 . Wstd = Wp + Wa: ______________________________________________________________________________________
FIGURE B-5 Typical report format for component ECU.
About ASHRAE
ASHRAE, founded in 1 894, is a global society advancing human well-being through sustainable technology for the
built environment. The Society and its members focus on building systems, energy efficiency, indoor air quality,
refrigeration, and sustainability. Through research, Standards writing, publishing, certification and continuing
education, ASHRAE shapes tomorrow’s built environment today.
To stay current with this and other ASHRAE Standards and Guidelines, visit www.ashrae.org/standards.