Daikin Altherma low

temperature monobloc
Technical data book
EBLA09-16D(3)W1 /
EBLA09-16D(3)V3 /
EDLA09-16D(3)W1 /
EBLA09DAW1
EBLA11DAW1
EDLA09-16D(3)V3
EBLA14DAW1
EBLA16DAW1
EBLA09DAV3
EBLA11DAV3
EBLA14DAV3
EBLA16DAV3
EBLA09DA3W1
EBLA11DA3W1
EBLA14DA3W1
EBLA16DA3W1
EBLA09DA3V3
EBLA11DA3V3
EBLA14DA3V3
EBLA16DA3V3
EDLA09DAW1
EDLA11DAW1
EDLA14DAW1
EDLA16DAW1
EDLA09DAV3
EDLA11DAV3
EDLA14DAV3
EDLA16DAV3
EDLA09DA3W1
EDLA11DA3W1
EDLA14DA3W1
EDLA16DA3W1
EDLA09DA3V3
EDLA11DA3V3
EDLA14DA3V3
EDLA16DA3V3

EEDEN21
TABLE OF CONTENTS
EBLA09-16DW1 / EBLA09-16DV3 /
EBLA09-16D3W1 / EBLA09-16D3V3 /
EDLA09-16DW1 / EDLA09-16DV3 /
EDLA09-16D3W1 / EDLA09-16D3V3
1 Features 5
EBLA09-16DW1, EBLA09-16DV3 5
EDLA09-16DW1, EDLA09-16DV3 6
EBLA09-16D3W1, EBLA09-16D3V3 7
EDLA09-16D3W1, EDLA09-16D3V3 8

2 Specifications 9

3 Electrical data 57

4 Combination table 58

5 Capacity graphs 59
Cooling Capacity Graphs 59
Heating Capacity Graphs 60

6 Capacity tables 61
Certification Programs 61

7 Dimensional drawings 62

8 Centre of gravity 64

9 Piping diagrams 65

10 Wiring diagrams 67
Notes & Legend 67
Control Circuit 68
Compressor - Notes & Legend 69
Compressor - Single phase 70
Compressor - Three phase 71
Hydro Module - Notes & Legend 72
Hydro Module - Power Supply, Back-up Heater 73
Hydro Module - Control Circuit 74
External back-up heater - Option Circuit 75

11 External connection diagrams 76

3
12 Installation 77
Installation Method 77

13 Operation range 78

14 Hydraulic performance 80
Static Pressure Drop Unit 80

4
Daikin Altherma low temperature monobloc

1 Features
1 - 1 EBLA09-16DW1, EBLA09-16DV3

Reversible air to water monobloc system, ideal when indoor space is limited

›› Monobloc all-in-one concept including hydraulic parts ›› Energy efficient heating and cooling system based on air to water 1
›› W-LAN cartridge connection (optional) heat pump technology
›› Possible to combine with domestic hot water ›› Separate back-up heater kit

Daikin Online
Residential controller
Controller

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 5
Daikin Altherma low temperature monobloc

1 Features
1 - 2 EDLA09-16DW1, EDLA09-16DV3

Heating only air to water monobloc system, ideal when indoor space is limited

1 ›› Monobloc all-in-one concept including hydraulic parts ›› Energy efficient heating only system based on air to water heat
›› W-LAN cartridge connection (optional) pump technology
›› Possible to combine with domestic hot water ›› Separate back-up heater kit

Daikin Online
Residential controller
Controller

6 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

1 Features
1 - 3 EBLA09-16D3W1, EBLA09-16D3V3

Reversible air to water monobloc system, ideal when indoor space is limited

›› Monobloc all-in-one concept including hydraulic parts ›› Energy efficient heating and cooling system based on air to water 1
›› W-LAN cartridge connection (optional) heat pump technology
›› Possible to combine with domestic hot water ›› Built-in electric back-up heater as additional heating during
extremely cold outdoor temperature

Daikin Online
Residential controller
Controller

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 7
Daikin Altherma low temperature monobloc

1 Features
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Heating only air to water monobloc system, ideal when indoor space is limited

1 ›› Monobloc all-in-one concept including hydraulic parts ›› Energy efficient heating only system based on air to water heat
›› W-LAN cartridge connection (optional) pump technology
›› Possible to combine with domestic hot water ›› Built-in electric back-up heater as additional heating during
extremely cold outdoor temperature

Daikin Online
Residential controller
Controller

8 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09DW1 EBLA11DW1 EBLA14DW1 EBLA16DW1
Heating capacity Nom. kW 9.37 (1) / 9.00 (2) 10.6 (1) / 9.82 (2) 12.0 (1) / 12.5 (2) 16.0 (1) / 16.0 (2)
Cooling capacity Nom. kW 9.35 (3) / 9.10 (4) 11.6 (3) / 11.5 (4) 12.8 (3) / 12.7 (4) 14.0 (3) / 15.3 (4)
Power input Cooling
Heating
Nom.
Nom.
kW
kW
2.79 (3) / 1.71 (4)
1.91 (1) / 2.43 (2)
3.56 (3) / 2.17 (4)
2.18 (1) / 2.68 (2)
4.06 (3) / 2.51 (4)
2.46 (1) / 3.42 (2)
4.58 (3) / 3.24 (4)
3.53 (1) / 4.56 (2)
2
COP 4.91 (1) / 3.71 (2) 4.83 (1) / 3.66 (2) 4.87 (1) / 3.64 (2) 4.53 (1) / 3.51 (2)
EER 3.35 (3) / 5.34 (4) 3.26 (3) / 5.31 (4) 3.16 (3) / 5.04 (4) 3.06 (3) / 4.74 (4)
SEER 5.62 (5) 5.79 (5) 5.71 (5) 5.59 (5)
Casing Colour Silver
Material Polyester painted galvanised steel plate
Dimensions Unit Height mm 870
Width mm 1,380
Depth mm 460
Packed Height mm 1,053
unit Width mm 1,520
Depth mm 650
Weight Unit kg 147
Packed unit kg 164
Packing Material PE wrapping foil / Carton / Wood (pallet)
Weight kg 17
Heat exchanger Length mm 1,136 /1,166 /1,195
Rows Quantity 3
Fin pitch mm 1.4
Passes Quantity 13
Face area m² 0.950 /0.970 /1.00
Stages Quantity 38
Empty Quantity 2
tubeplate
hole
Tube type 7.0 Hi-XD
Fin Type WF fin
Treatment Anti-corrosion treatment
Fan Type Propeller fan
Quantity 1
Discharge direction Horizontal
Air flow Heating High m³/min 48.0 55.8 70.4 85.0
rate Cooling High m³/min 63.1 70.4 85.0
Fan motor Quantity 1
Model Brushless DC motor
Fan motor Speed Steps 8
Heating Nom. rpm 400 450 550 650
Cooling Nom. rpm 500 550 650
Output W 234
Drive Direct drive
Compressor Quantity 1
Model 2Y350BPAY1P#C
Type Hermetically sealed swing compressor
PED Category Category II
Most Name Accumulator
critical Ps*V Bar*l 159
part
Operation range Heating Ambient Min. °CDB -25
Max. °CDB 25 (6)
Water Min. °C 9 (6)
side Max. °C 60 (6)
Cooling Ambient Min. °CDB 10
Max. °CDB 43
Water Min. °C 5
side Max. °C 22
Domestic Ambient Min. °CDB -25
hot water Max. °CDB 35
Water Min. °C 25
side Max. °C 55 (6)
Refrigerant Type R-32
GWP 675.0
Charge kg 3.80
Charge TCO2Eq 2.57
Control Expansion valve
Circuits Quantity 1
Refrigerant oil Type FW68DA
Charged volume l 1.35
Defrost method Reversed cycle
Defrost control Sensor for outdoor heat exchanger temperature
Capacity control Method Inverter controlled

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 9
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09DW1 EBLA11DW1 EBLA14DW1 EBLA16DW1
Safety devices Item 01 High pressure switch
02 Low pressure switch
2 Safety devices Item
03
04
Fan driver overload protector
Fuse
05 Compressor motor thermal protector
Pump Quantity 1
Nr of speeds PWM
Nominal Heating kPa 106.5 102.9 97.6 76.7
ESP unit Cooling kPa 106.6 99.2 94.1 88.4
Power input W 180
Water side Heat Type Plate heat exchanger
exchanger Quantity 1
Water volume l 2.16
Water Heating Nom. l/min 26.9 (1) / 25.8 (2) 30.3 (1) / 28.2 (2) 34.4 (1) / 35.7 (2) 45.9 (1) / 45.9 (2)
flow rate Cooling Nom. l/min 26.8 (3) / 26.1 (4) 33.2 (3) / 33.0 (4) 36.8 (3) / 36.3 (4) 40.2 (3) / 43.9 (4)
Insulation material EPDM type
Heater W 50.0
Expansion vessel Volume l 8
Max. water pressure bar 4
Pre pressure bar 1
Heater W 65
Water filter Diameter perforations mm 0.8
Material Stainless steel
Water circuit Piping connections diameter inch G 1" (male)
Piping inch 1-1/4"
Piping Max. OU - Tank m 10
length
Level dif- Max. m 5
ference
Safety valve bar 3
Drain valve / fill valve Yes
Shut off valve Yes
Air purge valve Yes (Manually)
Minimum water volume in the system l 50 (7)
Heater W 66.0
General Supplier/ Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Manu- Name or trademark Daikin Europe N.V.
facturer
details
Product Air-to-water heat pump Yes
descrip- Brine-to-water heat pump No
tion Heat pump combination heater No
Low-temperature heat pump No
Supplementary heater integrated No
General Product Water-to-water heat pump No
descrip-
tion
LW(A) Sound power level (according to EN14825) dB(A) 62.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating Air to Rated airflow (outdoor) m³/h 2,880 3,350 4,220 5,100
general water
unit
Other Capacity control Inverter
Pck (Crankcase heater mode) kW 0.000
Poff (Off mode) kW 0.023
Psb (Standby mode) kW 0.023
Pto (Thermostat off) kW 0.023

10 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09DW1 EBLA11DW1 EBLA14DW1 EBLA16DW1
Space heating Average General Annual energy kWh 5,404 6,134 6,651 7,359
climate consumption
water
outlet
ηs (Seasonal
space heating
% 135 132 134 132
2
55°C efficiency)
Prated at -10°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 19 22 24 26
gy consumption
(GCV)
SCOP 3.44 3.37 3.42 3.37
Seasonal space heating A++
eff. class
A Condition Cdh (Degradation heating) 1.0
(-7°CDB/-8°CWB) COPd 2.09 1.90 2.02 1.95
Pdh kW 8.5 9.3 9.4
PERd % 83.6 76.0 80.8 78.0
B Con- Cdh (Degradation heating) 1.0
dition COPd 3.28 3.25 3.28 3.27
(2°CD- Pdh kW 5.0 5.4 6.2 6.9
B/1°CWB) PERd % 131.2 130.0 131.2 130.8
C Con- Cdh (Degradation heating) 1.0
dition COPd 4.80 4.81 4.88 4.93
(7°CD- Pdh kW 4.4
B/6°CWB) PERd % 192.0 192.4 195.2 197.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 6.45 6.41 6.58 6.60
Pdh kW 5.3
PERd % 258.0 256.4 263.2 264.0
Tol (tem- COPd 1.70 1.6 4 1.70 1.67
perature Pdh kW 6.8 7.6 7.8 8.0
operat- PERd % 68.0 65.6 68.0 66.8
ing limit) TOL °C -10
WTOL °C 55
Rated Psup (at Tdesign kW 2.2 2.4 3.2 4.1
heat -10°C)
output
supple-
mentary
capacity

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 11
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09DW1 EBLA11DW1 EBLA14DW1 EBLA16DW1
Space heating Average Tbiv COPd 1.92 1.90 2.09 2.13
climate (bivalent Pdh kW 8.8 9.3 9.4 10.1
2 water
outlet
tempera-
ture)
PERd
Tbiv
%
°C
76.8
-8
76.0
-7
83.6
-6
85.2
-5
55°C
Cold General Annual energy kWh 7,092 7,848 8,808 9,510
climate consumption
water ηs (Seasonal % 122 123 120 121
outlet space heating
55°C efficiency)
Prated at -22°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 26 28 32 34
gy consumption
(GCV)
Warm General Annual energy kWh 2,820 3,083 3,690
climate consumption
water ηs (Seasonal % 168 170 172
outlet space heating
55°C efficiency)
Prated at 2°C kW 9.0 10.0 12.1
Qhe Annual ener- Gj 10 11 13
gy consumption
(GCV)
B Con- Cdh (Degradation heating) 1.0
dition COPd 2.12 2.18 2.17
(2°CD- Pdh kW 9.0 9.8
B/1°CWB) PERd % 84.8 87.2 86.8
C Con- Cdh (Degradation heating) 1.0
dition COPd 3.65 3.74 3.83
(7°CD- Pdh kW 6.2 7.6
B/6°CWB) PERd % 146.0 149.6 153.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 5.68 5.69
Pdh kW 5.0
PERd % 227.2 227.6
Tbiv COPd 2.12 2.18 2.40
(bivalent Pdh kW 9.0 9.8 11.0
tempera- PERd % 84.8 87.2 96.0
ture) Tbiv °C 2 3
Average General Annual energy kWh 3,854 4,371 4,838 5,281
climate consumption
water ηs (Seasonal % 190 186 185
outlet space heating
35°C efficiency)
Prated at -10°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 14 16 17 19
gy consumption
(GCV)
SCOP 4.82 4.73 4.70 4.69
Seasonal space heating A+++
eff. class
A Condition COPd 3.07 3.03 2.95 2.87
(-7°CDB/-8°CWB) Pdh kW 8.5 9.2 10.1 11.2
PERd % 122.8 121.2 118.0 114.8

12 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09DW1 EBLA11DW1 EBLA14DW1 EBLA16DW1
Space heating Average B Con- Cdh (Degradation heating) 1.0
climate dition COPd 4.52 4.37 4.35 4.33
water
outlet
(2°CD-
B/1°CWB)
Pdh
PERd
kW
% 180.8
5.5
174.8
6.1
174.0
6.7
173.2
2
35°C C Con- Cdh (Degradation heating) 1.0
dition COPd 6.78 6.74 6.70 6.83
(7°CD- Pdh kW 4.7 4.6 4.7
B/6°CWB) PERd % 271.2 269.6 268.0 273.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 8.75 8.54 8.65 8.82
Pdh kW 5.5 5.4 5.5
PERd % 350.0 341.6 346.0 352.8
Tol (tem- COPd 2.64 2.58 2.51 2.48
perature Pdh kW 8.3 10.1 11.2 11.8
operat- PERd % 105.6 103.2 100.4 99.2
ing limit) TOL °C -10
WTOL °C 35
Tbiv COPd 2.75 2.58 2.51 2.48
(bivalent Pdh kW 8.7 10.1 11.2 11.8
tempera- PERd % 110.0 103.2 100.4 99.2
ture) Tbiv °C -9 -10
Rated Psup (at Tdesign kW 0.7 0.0
heat -10°C)
output
supple-
mentary
capacity
Cold General Annual energy kWh 4,980 5,732 6,266 7,245
climate consumption
water ηs (Seasonal % 175 169 170 160
outlet space heating
35°C efficiency)
Prated at -22°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 18 21 23 26
gy consumption
(GCV)
Warm General Annual energy kWh 1,938 2,128 2,333 2,573
climate consumption
water ηs (Seasonal % 243 248 249 246
outlet space heating
35°C efficiency)
Prated at 2°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 7 8 9
gy consumption
(GCV)
B Con- Cdh (Degradation heating) 1.0
dition COPd 3.36 3.30 3.45 3.30
(2°CD- Pdh kW 9.0 10.3 10.8 11.9
B/1°CWB) PERd % 134.4 132.0 138.0 132.0
C Con- Cdh (Degradation heating) 1.0
dition COPd 5.59 5.70 5.77 5.64
(7°CD- Pdh kW 5.9 6.7 7.4 8.1
Space heating Warm C Con- PERd % 223.6 228.0 230.8 225.6
climate dition
water (7°CD-
outlet B/6°CWB)
35°C D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 7.87 7.73
Pdh kW 5.2
PERd % 314.8 309.2
Tbiv COPd 3.36 3.30 3.45 3.30
(bivalent Pdh kW 9.0 10.3 10.8 11.9
tempera- PERd % 134.4 132.0 138.0 132.0
ture) Tbiv °C 2
Control systems Class of temperature control VI
Contribution to seasonal space heating % 4
efficiency

Electrical specifications EBLA09DW1 EBLA11DW1 EBLA14DW1 EBLA16DW1


Compressor Starting method Inverter
Pump Type PWM

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 13
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Electrical specifications EBLA09DW1 EBLA11DW1 EBLA14DW1 EBLA16DW1
Compressor com- Main Phase 3N~
ponent power Voltage V 400
2 supply
Voltage Min. % -10
range Max. % 10
Power supply Name W1
Phase 3~
Frequency Hz 50
Voltage V 400
Voltage range Min. % -10
Max. % 10
Current Maxi- Heating A 14.0
mum
running
current
Recommended fuses A 16
Wiring connec- Optional Quantity 3G
tions domestic Type of wires Minimum 2.5 mm²
hot water
tank +
Q2L
R5T Quantity 2
Type of wires Wire included in option EKHWS*
For con- Quantity 2
nection Remark Minimum 0.75 mm²
with R6T
A3P Quantity 4
Type of wires Select diameter and type according to national and local regulations
M2S Quantity 2
Type of wires Select diameter and type according to national and local regulations
M3S Quantity 3
Type of wires Select diameter and type according to national and local regulations
Quantity 2
Type of wires Wire included in option EKFLSW1
For Quantity 4G
power Remark See installation manual outdoor unit
supply
For con- Quantity 4
nection Remark O.75 mm² till 1.25 mm² (max length 200 m)
with user Type of wires 0,75 ~1,25 mm² (P1P2)
interface
Prefer- Quantity Power: 2
ential Remark Power 6.3A
kWh rate
power
supply
Domestic Quantity 3
hot water
pump
Wiring connec- Domestic Remark Minimum 0.75 mm²
tions hot water
pump
Cable require- Cooling/ Maximum running current A 0.3
ments Heating
output
(1)Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) |
(2)Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) |
(3)Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB |
(4)Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB |
(5)According to EN14825 |
(6)For more details, see operation range drawing |
(7)Depends on operation mode, refer to installation manual.

Technical specifications EBLA09DV3 EBLA11DV3 EBLA14DV3 EBLA16DV3


Heating capacity Nom. kW 9.37 (1) / 9.00 (2) 10.6 (1) / 9.82 (2) 12.0 (1) / 12.5 (2) 16.0 (1) / 16.0 (2)
Cooling capacity Nom. kW 9.35 (3) / 9.10 (4) 11.6 (3) / 11.5 (4) 12.8 (3) / 12.7 (4) 14.0 (3) / 15.3 (4)
Power input Cooling Nom. kW 2.79 (3) / 1.71 (4) 3.56 (3) / 2.17 (4) 4.06 (3) / 2.51 (4) 4.58 (3) / 3.24 (4)
Heating Nom. kW 1.91 (1) / 2.43 (2) 2.18 (1) / 2.68 (2) 2.46 (1) / 3.42 (2) 3.53 (1) / 4.56 (2)
COP 4.91 (1) / 3.71 (2) 4.83 (1) / 3.66 (2) 4.87 (1) / 3.64 (2) 4.53 (1) / 3.51 (2)
EER 3.35 (3) / 5.34 (4) 3.26 (3) / 5.31 (4) 3.16 (3) / 5.04 (4) 3.06 (3) / 4.74 (4)
SEER 5.62 (5) 5.79 (5) 5.71 (5) 5.59 (5)
Casing Colour Silver
Material Polyester painted galvanised steel plate

14 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09DV3 EBLA11DV3 EBLA14DV3 EBLA16DV3
Dimensions Unit Height mm 870
Width mm 1,380

Packed
Depth
Height
mm
mm
460
1,053
2
unit Width mm 1,520
Depth mm 650
Weight Unit kg 147
Packed unit kg 164
Packing Material PE wrapping foil / Carton / Wood (pallet)
Weight kg 17
Heat exchanger Length mm 1,136 /1,166 /1,195
Rows Quantity 3
Fin pitch mm 1.4
Passes Quantity 14
Face area m² 0.950 /0.970 /1.00
Stages Quantity 38
Tube type 7.0 Hi-XD
Fin Type WF fin
Treatment Anti-corrosion treatment
Fan Type Propeller fan
Quantity 1
Discharge direction Horizontal
Air flow Heating High m³/min 48.0 55.8 70.4 85.0
rate Cooling High m³/min 63.1 70.4 85.0
Fan motor Quantity 1
Model Brushless DC motor
Speed Steps 8
Fan motor Speed Heating Nom. rpm 400 450 550 650
Cooling Nom. rpm 500 550 650
Output W 230
Drive Direct drive
Compressor Quantity 1
Model 2Y350BPAX1P#C
Type Hermetically sealed swing compressor
PED Category Category II
Most Name Accumulator
critical Ps*V Bar*l 159
part
Operation range Heating Ambient Min. °CDB -25
Max. °CDB 25 (6)
Water Min. °C 9 (6)
side Max. °C 60 (6)
Cooling Ambient Min. °CDB 10
Max. °CDB 43
Water Min. °C 5
side Max. °C 22
Domestic Ambient Min. °CDB -25
hot water Max. °CDB 35
Water Min. °C 25
side Max. °C 55 (6)
Refrigerant Type R-32
GWP 675.0
Charge kg 3.80
Charge TCO2Eq 2.57
Control Expansion valve
Circuits Quantity 1
Refrigerant oil Type FW68DA
Charged volume l 1.35
Defrost method Reversed cycle
Defrost control Sensor for outdoor heat exchanger temperature
Capacity control Method Inverter controlled
Safety devices Item 01 High pressure switch
02 Low pressure switch
03 Fan driver overload protector
04 Fuse
Safety devices Item 05 Compressor motor thermal protector
Pump Quantity 1
Nr of speeds PWM
Nominal Heating kPa 106.5 102.9 97.6 76.7
ESP unit Cooling kPa 106.6 99.2 94.1 88.4
Power input W 180

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 15
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09DV3 EBLA11DV3 EBLA14DV3 EBLA16DV3
Water side Heat Type Plate heat exchanger
exchanger Quantity 1
2 Water volume
Water Heating Nom.
l
l/min 26.9 (1) / 25.8 (2) 30.3 (1) / 28.2 (2)
2.16
34.4 (1) / 35.7 (2) 45.9 (1) / 45.9 (2)
flow rate Cooling Nom. l/min 26.8 (3) / 26.1 (4) 33.2 (3) / 33.0 (4) 36.8 (3) / 36.3 (4) 40.2 (3) / 43.9 (4)
Insulation material EPDM type
Heater W 50.0
Expansion vessel Volume l 8
Max. water pressure bar 4
Pre pressure bar 1
Heater W 65
Water filter Diameter perforations mm 0.8
Material Stainless steel
Water circuit Piping connections diameter inch G 1" (male)
Piping inch 1-1/4"
Piping Max. OU - Tank m 10
length
Level dif- Max. m 5
ference
Safety valve bar 3
Drain valve / fill valve Yes
Shut off valve Yes
Air purge valve Yes (Manually)
Minimum water volume in the system l 50 (7)
Heater W 66.0
General Supplier/ Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Manu- Name or trademark Daikin Europe N.V.
facturer
details
Product Air-to-water heat pump Yes
descrip- Brine-to-water heat pump No
tion Heat pump combination heater No
Low-temperature heat pump No
Supplementary heater integrated No
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825) dB(A) 62.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating Air to Rated airflow (outdoor) m³/h 2,880 3,350 4,220 5,100
general water
unit
Other Capacity control Inverter
Pck (Crankcase heater mode) kW 0.000
Poff (Off mode) kW 0.023
Psb (Standby mode) kW 0.023
Pto (Thermostat off) kW 0.023

16 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09DV3 EBLA11DV3 EBLA14DV3 EBLA16DV3
Space heating Average General Annual energy kWh 5,404 6,134 6,651 7,359
climate consumption
water
outlet
ηs (Seasonal
space heating
% 135 132 134 132
2
55°C efficiency)
Prated at -10°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 19 22 24 26
gy consumption
(GCV)
SCOP 3.44 3.37 3.42 3.37
Seasonal space heating A++
eff. class
A Condition Cdh (Degradation heating) 1.0
(-7°CDB/-8°CWB) COPd 2.09 1.90 2.02 1.95
Pdh kW 8.5 9.3 9.4
PERd % 83.6 76.0 80.8 78.0
B Con- Cdh (Degradation heating) 1.0
dition COPd 3.28 3.25 3.28 3.27
(2°CD- Pdh kW 5.0 5.4 6.2 6.9
B/1°CWB) PERd % 131.2 130.0 131.2 130.8
C Con- Cdh (Degradation heating) 1.0
dition COPd 4.80 4.81 4.88 4.93
(7°CD- Pdh kW 4.4
B/6°CWB) PERd % 192.0 192.4 195.2 197.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 6.45 6.41 6.58 6.60
Pdh kW 5.3
PERd % 258.0 256.4 263.2 264.0
Tol (tem- COPd 1.70 1.6 4 1.70 1.67
perature Pdh kW 6.8 7.6 7.8 8.0
operat- PERd % 68.0 65.6 68.0 66.8
ing limit) TOL °C -10
WTOL °C 55
Rated Psup (at Tdesign kW 2.2 2.4 3.2 4.1
heat -10°C)
output
supple-
mentary
capacity
Tbiv COPd 1.92 1.90 2.09 2.13
(bivalent
tempera-
ture)

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 17
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09DV3 EBLA11DV3 EBLA14DV3 EBLA16DV3
Space heating Average Tbiv Pdh kW 8.8 9.3 9.4 10.1
climate (bivalent PERd % 76.8 76.0 83.6 85.2
2 water
outlet
tempera- Tbiv
ture)
°C -8 -7 -6 -5

55°C
Cold General Annual energy kWh 7,376 8,196 8,808 9,599
climate consumption
water ηs (Seasonal % 117 120
outlet space heating
55°C efficiency)
Prated at -22°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 27 30 32 35
gy consumption
(GCV)
Warm General Annual energy kWh 2,820 3,083 3,690
climate consumption
water ηs (Seasonal % 168 170 172
outlet space heating
55°C efficiency)
Prated at 2°C kW 9.0 10.0 12.1
Qhe Annual ener- Gj 10 11 13
gy consumption
(GCV)
B Con- Cdh (Degradation heating) 1.0
dition COPd 2.12 2.18 2.17
(2°CD- Pdh kW 9.0 9.8
B/1°CWB) PERd % 84.8 87.2 86.8
C Con- Cdh (Degradation heating) 1.0
dition COPd 3.65 3.74 3.83
(7°CD- Pdh kW 6.2 7.6
B/6°CWB) PERd % 146.0 149.6 153.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 5.68 5.69
Pdh kW 5.0
PERd % 227.2 227.6
Tbiv COPd 2.12 2.18 2.40
(bivalent Pdh kW 9.0 9.8 11.0
tempera- PERd % 84.8 87.2 96.0
ture) Tbiv °C 2 3
Average General Annual energy kWh 3,854 4,371 4,838 5,281
climate consumption
water ηs (Seasonal % 190 186 185
outlet space heating
35°C efficiency)
Prated at -10°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 14 16 17 19
gy consumption
(GCV)
SCOP 4.82 4.73 4.70 4.69
Seasonal space heating A+++
eff. class
A Condition COPd 3.07 3.03 2.95 2.87
(-7°CDB/-8°CWB) Pdh kW 8.5 9.2 10.1 11.2
PERd % 122.8 121.2 118.0 114.8
B Con- Cdh (Degradation heating) 1.0
dition
(2°CD-
B/1°CWB)

18 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09DV3 EBLA11DV3 EBLA14DV3 EBLA16DV3
Space heating Average B Con- COPd 4.52 4.37 4.35 4.33
climate dition Pdh kW 5.5 6.1 6.7
water
outlet
(2°CD-
B/1°CWB)
PERd % 180.8 174.8 174.0 173.2
2
35°C C Con- Cdh (Degradation heating) 1.0
dition COPd 6.78 6.74 6.70 6.83
(7°CD- Pdh kW 4.7 4.6 4.7
B/6°CWB) PERd % 271.2 269.6 268.0 273.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 8.75 8.54 8.65 8.82
Pdh kW 5.5 5.4 5.5
PERd % 350.0 341.6 346.0 352.8
Tol (tem- COPd 2.64 2.58 2.51 2.48
perature Pdh kW 8.3 10.1 11.2 11.8
operat- PERd % 105.6 103.2 100.4 99.2
ing limit) TOL °C -10
WTOL °C 35
Tbiv COPd 2.75 2.58 2.51 2.48
(bivalent Pdh kW 8.7 10.1 11.2 11.8
tempera- PERd % 110.0 103.2 100.4 99.2
ture) Tbiv °C -9 -10
Rated Psup (at Tdesign kW 0.7 0.0
heat -10°C)
output
supple-
mentary
capacity
Cold General Annual energy kWh 5,351 5,732 6,266 7,245
climate consumption
water ηs (Seasonal % 163 169 170 160
outlet space heating
35°C efficiency)
Prated at -22°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 19 21 23 26
gy consumption
(GCV)
Warm General Annual energy kWh 1,938 2,128 2,333 2,573
climate consumption
water ηs (Seasonal % 243 248 249 246
outlet space heating
35°C efficiency)
Prated at 2°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 7 8 9
gy consumption
(GCV)
B Con- Cdh (Degradation heating) 1.0
dition COPd 3.36 3.30 3.45 3.30
(2°CD- Pdh kW 9.0 10.3 10.8 11.9
B/1°CWB) PERd % 134.4 132.0 138.0 132.0
C Con- Cdh (Degradation heating) 1.0
dition COPd 5.59 5.70 5.77 5.64
(7°CD- Pdh kW 5.9 6.7 7.4 8.1
B/6°CWB) PERd % 223.6 228.0 230.8 225.6
Space heating Warm D Condition Cdh (Degradation heating) 1.0
climate (12°CDB/11°CWB) COPd 7.87 7.73
water Pdh kW 5.2
outlet PERd % 314.8 309.2
35°C Tbiv COPd 3.36 3.30 3.45 3.30
(bivalent Pdh kW 9.0 10.3 10.8 11.9
tempera- PERd % 134.4 132.0 138.0 132.0
ture) Tbiv °C 2
Control systems Class of temperature control VI
Contribution to seasonal space heating % 4
efficiency

Electrical specifications EBLA09DV3 EBLA11DV3 EBLA14DV3 EBLA16DV3


Compressor Starting method Inverter
Pump Type PWM
Compressor com- Main Phase 1~
ponent power Voltage V 230
supply
Voltage Min. % -10
range Max. % 10

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 19
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Electrical specifications EBLA09DV3 EBLA11DV3 EBLA14DV3 EBLA16DV3
Power supply Name V3
Phase 1~
2 Frequency
Voltage
Hz
V
50
230
Voltage range Min. % -10
Max. % 10
Current Maxi- Heating A 30.8
mum
running
current
Recommended fuses A 32
Wiring connec- Optional Quantity 3G
tions domestic Type of wires Minimum 2.5 mm²
hot water
tank +
Q2L
R5T Quantity 2
Type of wires Wire included in option EKHWS*
For con- Quantity 2
nection Remark Minimum 0.75 mm²
with R6T
A3P Quantity 4
Type of wires Select diameter and type according to national and local regulations
M2S Quantity 2
Type of wires Select diameter and type according to national and local regulations
M3S Quantity 3
Type of wires Select diameter and type according to national and local regulations
Quantity 2
Type of wires Wire included in option EKFLSW1
For Quantity 2G
power Remark See installation manual outdoor unit
supply
For con- Quantity 4
nection Remark O.75 mm² till 1.25 mm² (max length 200 m)
with user Type of wires 0,75 ~1,25 mm² (P1P2)
interface
Prefer- Quantity Power: 2
ential Remark Power 6.3A
kWh rate
power
supply
Domestic Quantity 3
hot water
pump
Wiring connec- Domestic Remark Minimum 0.75 mm²
tions hot water
pump
Cable require- Cooling/ Maximum running current A 0.3
ments Heating
output
(1)Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) |
(2)Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) |
(3)Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB |
(4)Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB |
(5)According to EN14825 |
(6)For more details, see operation range drawing |
(7)Depends on operation mode, refer to installation manual.

Technical specifications EBLA09D3W1 EBLA11D3W1 EBLA14D3W1 EBLA16D3W1


Heating capacity Nom. kW 9.37 (1) / 9.00 (2) 10.6 (1) / 9.82 (2) 12.0 (1) / 12.5 (2) 16.0 (1) / 16.0 (2)
Cooling capacity Nom. kW 9.35 (3) / 9.10 (4) 11.6 (3) / 11.5 (4) 12.8 (3) / 12.7 (4) 14.0 (3) / 15.3 (4)
Heater capacity Step 1 kW 3
Power input Cooling Nom. kW 2.79 (3) / 1.71 (4) 3.56 (3) / 2.17 (4) 4.06 (3) / 2.51 (4) 4.58 (3) / 3.24 (4)
Heating Nom. kW 1.91 (1) / 2.43 (2) 2.18 (1) / 2.68 (2) 2.46 (1) / 3.42 (2) 3.53 (1) / 4.56 (2)
COP 4.91 (1) / 3.71 (2) 4.83 (1) / 3.66 (2) 4.87 (1) / 3.64 (2) 4.53 (1) / 3.51 (2)
EER 3.35 (3) / 5.34 (4) 3.26 (3) / 5.31 (4) 3.16 (3) / 5.04 (4) 3.06 (3) / 4.74 (4)
SEER 5.62 (5) 5.79 (5) 5.71 (5) 5.59 (5)
Casing Colour Silver
Material Polyester painted galvanised steel plate
Dimensions Unit Height mm 870
Width mm 1,380
Depth mm 460
Packed Height mm 1,053
unit Width mm 1,520
Depth mm 650

20 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09D3W1 EBLA11D3W1 EBLA14D3W1 EBLA16D3W1
Weight Unit kg 149
Packed unit kg 166
Packing Material
Weight kg
PE wrapping foil / Carton / Wood (pallet)
17
2
Heat exchanger Length mm 1,136 /1,166 /1,195
Rows Quantity 3
Fin pitch mm 1.4
Passes Quantity 13
Face area m² 0.950 /0.970 /1.00
Stages Quantity 38
Empty Quantity 2
tubeplate
hole
Tube type 7.0 Hi-XD
Fin Type WF fin
Treatment Anti-corrosion treatment
Fan Type Propeller fan
Quantity 1
Discharge direction Horizontal
Air flow Heating High m³/min 48.0 55.8 70.4 85.0
rate Cooling High m³/min 63.1 70.4 85.0
Fan motor Quantity 1
Fan motor Model Brushless DC motor
Speed Steps 8
Heating Nom. rpm 400 450 550 650
Cooling Nom. rpm 500 550 650
Output W 234
Drive Direct drive
Compressor Quantity 1
Model 2Y350BPAY1P#C
Type Hermetically sealed swing compressor
PED Category Category II
Most Name Accumulator
critical Ps*V Bar*l 159
part
Operation range Heating Ambient Min. °CDB -25
Max. °CDB 35
Water Min. °C 15 (6)
side Max. °C 60 (6)
Cooling Ambient Min. °CDB 10
Max. °CDB 43
Water Min. °C 5
side Max. °C 22
Domestic Ambient Min. °CDB -25
hot water Max. °CDB 35
Water Min. °C 25
side Max. °C 55 (6)
Refrigerant Type R-32
GWP 675.0
Charge kg 3.80
Charge TCO2Eq 2.57
Control Expansion valve
Circuits Quantity 1
Refrigerant oil Type FW68DA
Charged volume l 1.35
Defrost method Reversed cycle
Defrost control Sensor for outdoor heat exchanger temperature
Capacity control Method Inverter controlled
Safety devices Item 01 High pressure switch
02 Low pressure switch
Safety devices Item 03 Fan driver overload protector
04 Fuse
05 Compressor motor thermal protector
Pump Quantity 1
Nr of speeds PWM
Nominal Heating kPa 106.9 102.7 96.5 71.4
ESP unit Cooling kPa 107.0 98.4 92.3 85.5
Power input W 180

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 21
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09D3W1 EBLA11D3W1 EBLA14D3W1 EBLA16D3W1
Water side Heat Type Plate heat exchanger
exchanger Quantity 1
2 Water volume
Water Heating Nom.
l
l/min 26.9 (1) / 25.8 (2) 30.3 (1) / 28.2 (2)
2.16
34.4 (1) / 35.7 (2) 45.9 (1) / 45.9 (2)
flow rate Cooling Nom. l/min 26.8 (3) / 26.1 (4) 33.2 (3) / 33.0 (4) 36.8 (3) / 36.3 (4) 40.2 (3) / 43.9 (4)
Insulation material EPDM type
Heater W 50.0
Expansion vessel Volume l 8
Max. water pressure bar 4
Pre pressure bar 1
Heater W 65
Water filter Diameter perforations mm 0.8
Material Stainless steel
Water circuit Piping connections diameter inch G 1" (male)
Piping inch 1-1/4"
Piping Max. OU - Tank m 10
length
Level dif- Max. m 5
ference
Safety valve bar 3
Drain valve / fill valve Yes
Shut off valve Yes
Air purge valve Yes
Minimum water volume in the system l 20 (7)
Heater W 66.0
General Supplier/ Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Manu- Name or trademark Daikin Europe N.V.
facturer
details
Product Air-to-water heat pump Yes
descrip- Brine-to-water heat pump No
tion Heat pump combination heater No
Low-temperature heat pump No
General Product Supplementary heater integrated Yes
descrip- Water-to-water heat pump No
tion
LW(A) Sound power level (according to EN14825) dB(A) 62.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating Air to Rated airflow (outdoor) m³/h 2,880 3,350 4,220 5,100
general water
unit
Other Capacity control Inverter
Pck (Crankcase heater mode) kW 0.000
Poff (Off mode) kW 0.023
Psb (Standby mode) kW 0.023
Pto (Thermostat off) kW 0.023
Inte- Type of energy input Electrical
grated
supple-
mentary
heater

22 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09D3W1 EBLA11D3W1 EBLA14D3W1 EBLA16D3W1
Space heating Average General Annual energy kWh 5,404 6,134 6,651 7,359
climate consumption
water
outlet
ηs (Seasonal
space heating
% 135 132 134 132
2
55°C efficiency)
Prated at -10°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 19 22 24 26
gy consumption
(GCV)
SCOP 3.44 3.37 3.42 3.37
Seasonal space heating A++
eff. class
A Condition Cdh (Degradation heating) 1.0
(-7°CDB/-8°CWB) COPd 2.09 1.90 2.02 1.95
Pdh kW 8.5 9.3 9.4
PERd % 83.6 76.0 80.8 78.0
B Con- Cdh (Degradation heating) 1.0
dition COPd 3.28 3.25 3.28 3.27
(2°CD- Pdh kW 5.0 5.4 6.2 6.9
B/1°CWB) PERd % 131.2 130.0 131.2 130.8
C Con- Cdh (Degradation heating) 1.0
dition COPd 4.80 4.81 4.88 4.93
(7°CD- Pdh kW 4.4
B/6°CWB) PERd % 192.0 192.4 195.2 197.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 6.45 6.41 6.58 6.60
Pdh kW 5.3
PERd % 258.0 256.4 263.2 264.0
Tol (tem- COPd 1.70 1.6 4 1.70 1.67
perature Pdh kW 6.8 7.6 7.8 8.0
operat- PERd % 68.0 65.6 68.0 66.8
ing limit) TOL °C -10

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 23
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09D3W1 EBLA11D3W1 EBLA14D3W1 EBLA16D3W1
Space heating Average Tol (tem- WTOL °C 55
climate perature
2 water
outlet
operat-
ing limit)
55°C Rated Psup (at Tdesign kW 2.2 2.4 3.2 4.1
heat -10°C)
output
supple-
mentary
capacity
Tbiv COPd 1.92 1.90 2.09 2.13
(bivalent Pdh kW 8.8 9.3 9.4 10.1
tempera- PERd % 76.8 76.0 83.6 85.2
ture) Tbiv °C -8 -7 -6 -5
Cold General Annual energy kWh 7,092 7,848 8,808 9,510
climate consumption
water ηs (Seasonal % 122 123 120 121
outlet space heating
55°C efficiency)
Prated at -22°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 26 28 32 34
gy consumption
(GCV)
Warm General Annual energy kWh 2,820 3,083 3,690
climate consumption
water ηs (Seasonal % 168 170 172
outlet space heating
55°C efficiency)
Prated at 2°C kW 9.0 10.0 12.1
Qhe Annual ener- Gj 10 11 13
gy consumption
(GCV)
B Con- Cdh (Degradation heating) 1.0
dition COPd 2.12 2.18 2.17
(2°CD- Pdh kW 9.0 9.8
B/1°CWB) PERd % 84.8 87.2 86.8
C Con- Cdh (Degradation heating) 1.0
dition COPd 3.65 3.74 3.83
(7°CD- Pdh kW 6.2 7.6
B/6°CWB) PERd % 146.0 149.6 153.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 5.68 5.69
Pdh kW 5.0
PERd % 227.2 227.6
Tbiv COPd 2.12 2.18 2.40
(bivalent Pdh kW 9.0 9.8 11.0
tempera- PERd % 84.8 87.2 96.0
ture) Tbiv °C 2 3
Average General Annual energy kWh 3,854 4,371 4,838 5,281
climate consumption
water ηs (Seasonal % 190 186 185
outlet space heating
35°C efficiency)
Prated at -10°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 14 16 17 19
gy consumption
(GCV)
SCOP 4.82 4.73 4.70 4.69
Seasonal space heating A+++
eff. class
A Condition COPd 3.07 3.03 2.95 2.87
(-7°CDB/-8°CWB)

24 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09D3W1 EBLA11D3W1 EBLA14D3W1 EBLA16D3W1
Space heating Average A Condition Pdh kW 8.5 9.2 10.1 11.2
climate (-7°CDB/-8°CWB) PERd % 122.8 121.2 118.0 114.8
water
outlet
B Con-
dition
Cdh (Degradation heating)
COPd 4.52 4.37
1.0
4.35 4.33
2
35°C (2°CD- Pdh kW 5.5 6.1 6.7
B/1°CWB) PERd % 180.8 174.8 174.0 173.2
C Con- Cdh (Degradation heating) 1.0
dition COPd 6.78 6.74 6.70 6.83
(7°CD- Pdh kW 4.7 4.6 4.7
B/6°CWB) PERd % 271.2 269.6 268.0 273.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 8.75 8.54 8.65 8.82
Pdh kW 5.5 5.4 5.5
PERd % 350.0 341.6 346.0 352.8
Tol (tem- COPd 2.64 2.58 2.51 2.48
perature Pdh kW 8.3 10.1 11.2 11.8
operat- PERd % 105.6 103.2 100.4 99.2
ing limit) TOL °C -10
WTOL °C 35
Tbiv COPd 2.75 2.58 2.51 2.48
(bivalent Pdh kW 8.7 10.1 11.2 11.8
tempera- PERd % 110.0 103.2 100.4 99.2
ture) Tbiv °C -9 -10
Rated Psup (at Tdesign kW 0.7 0.0
heat -10°C)
output
supple-
mentary
capacity
Cold General Annual energy kWh 4,980 5,732 6,266 7,245
climate consumption
water ηs (Seasonal % 175 169 170 160
outlet space heating
35°C efficiency)
Prated at -22°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 18 21 23 26
gy consumption
(GCV)
Warm General Annual energy kWh 1,938 2,128 2,333 2,573
climate consumption
water ηs (Seasonal % 243 248 249 246
outlet space heating
35°C efficiency)
Prated at 2°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 7 8 9
gy consumption
(GCV)
B Con- Cdh (Degradation heating) 1.0
dition COPd 3.36 3.30 3.45 3.30
(2°CD- Pdh kW 9.0 10.3 10.8 11.9
B/1°CWB) PERd % 134.4 132.0 138.0 132.0
C Con- Cdh (Degradation heating) 1.0
dition
(7°CD-
B/6°CWB)
Space heating Warm C Con- COPd 5.59 5.70 5.77 5.64
climate dition Pdh kW 5.9 6.7 7.4 8.1
water (7°CD- PERd % 223.6 228.0 230.8 225.6
outlet B/6°CWB)
35°C D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 7.87 7.73
Pdh kW 5.2
PERd % 314.8 309.2
Tbiv COPd 3.36 3.30 3.45 3.30
(bivalent Pdh kW 9.0 10.3 10.8 11.9
tempera- PERd % 134.4 132.0 138.0 132.0
ture) Tbiv °C 2
Control systems Class of temperature control VI
Contribution to seasonal space heating % 4
efficiency

Electrical specifications EBLA09D3W1 EBLA11D3W1 EBLA14D3W1 EBLA16D3W1


Compressor Starting method Inverter

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 25
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Electrical specifications EBLA09D3W1 EBLA11D3W1 EBLA14D3W1 EBLA16D3W1
Pump Type PWM
Compressor com- Main Phase 3N~
2 ponent power
supply
Voltage V 400

Voltage Min. % -10


range Max. % 10
Hydraulic compo- Back-up Type 3V3
nent heater Power Phase 1~
current supply Frequency Hz 50
Voltage V 230
Running Back-up heater A 13.0
current
Voltage Min. % -10
range Max. % 10
Wiring Type of wires Select diameter and type according to national and local regulations
connec-
tions
Power supply Name W1
Phase 3~
Frequency Hz 50
Voltage V 400
Voltage range Min. % -10
Max. % 10
Current Maxi- Heating A 14.0
mum
running
current
Recommended fuses A 16
Wiring connec- Optional Quantity 3G
tions domestic Type of wires Minimum 2.5 mm²
hot water
tank +
Q2L
R5T Quantity 2
Type of wires Wire included in option EKHWS*
For con- Quantity 2
nection Remark Minimum 0.75 mm²
with R6T
A3P Quantity 4
Type of wires Select diameter and type according to national and local regulations
M2S Quantity 2
Type of wires Select diameter and type according to national and local regulations
M3S Quantity 3
Type of wires Select diameter and type according to national and local regulations
Quantity 2
Type of wires Wire included in option EKFLSW1
Wiring connec- For Quantity 4G
tions power Remark See installation manual outdoor unit
supply
For con- Quantity 4
nection Remark O.75 mm² till 1.25 mm² (max length 200 m)
with user Type of wires 0,75 ~1,25 mm² (P1P2)
interface
Prefer- Quantity Power: 2
ential Remark Power 6.3A
kWh rate
power
supply
Domestic Quantity 3
hot water Remark Minimum 0.75 mm²
pump
Cable require- Cooling/ Maximum running current A 0.3
ments Heating
output
(1)Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) |
(2)Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) |
(3)Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB |
(4)Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB |
(5)According to EN14825 |
(6)For more details, see operation range drawing |
(7)Depends on operation mode, refer to installation manual.

Technical specifications EBLA09D3V3 EBLA11D3V3 EBLA14D3V3 EBLA16D3V3


Heating capacity Nom. kW 9.37 (1) / 9.00 (2) 10.6 (1) / 9.82 (2) 12.0 (1) / 12.5 (2) 16.0 (1) / 16.0 (2)
Cooling capacity Nom. kW 9.35 (3) / 9.10 (4) 11.6 (3) / 11.5 (4) 12.8 (3) / 12.7 (4) 14.0 (3) / 15.3 (4)

26 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09D3V3 EBLA11D3V3 EBLA14D3V3 EBLA16D3V3
Heater capacity Step 1 kW 3
Power input Cooling Nom. kW 2.79 (3) / 1.71 (4) 3.56 (3) / 2.17 (4) 4.06 (3) / 2.51 (4) 4.58 (3) / 3.24 (4)

COP
Heating Nom. kW 1.91 (1) / 2.43 (2)
4.91 (1) / 3.71 (2)
2.18 (1) / 2.68 (2)
4.83 (1) / 3.66 (2)
2.46 (1) / 3.42 (2)
4.87 (1) / 3.64 (2)
3.53 (1) / 4.56 (2)
4.53 (1) / 3.51 (2)
2
EER 3.35 (3) / 5.34 (4) 3.26 (3) / 5.31 (4) 3.16 (3) / 5.04 (4) 3.06 (3) / 4.74 (4)
SEER 5.62 (5) 5.79 (5) 5.71 (5) 5.59 (5)
Casing Colour Silver
Material Polyester painted galvanised steel plate
Dimensions Unit Height mm 870
Width mm 1,380
Depth mm 460
Packed Height mm 1,053
unit Width mm 1,520
Depth mm 650
Weight Unit kg 149
Packed unit kg 166
Packing Material PE wrapping foil / Carton / Wood (pallet)
Weight kg 17
Heat exchanger Length mm 1,136 /1,166 /1,195
Rows Quantity 3
Fin pitch mm 1.4
Passes Quantity 14
Face area m² 0.950 /0.970 /1.00
Stages Quantity 38
Tube type 7.0 Hi-XD
Fin Type WF fin
Treatment Anti-corrosion treatment
Fan Type Propeller fan
Quantity 1
Discharge direction Horizontal
Air flow Heating High m³/min 48.0 55.8 70.4 85.0
rate Cooling High m³/min 63.1 70.4 85.0
Fan motor Quantity 1
Model Brushless DC motor
Fan motor Speed Steps 8
Heating Nom. rpm 400 450 550 650
Cooling Nom. rpm 500 550 650
Output W 230
Drive Direct drive
Compressor Quantity 1
Model 2Y350BPAX1P#C
Type Hermetically sealed swing compressor
PED Category Category II
Most Name Accumulator
critical Ps*V Bar*l 159
part
Operation range Heating Ambient Min. °CDB -25
Max. °CDB 35
Water Min. °C 15 (6)
side Max. °C 60 (6)
Cooling Ambient Min. °CDB 10
Max. °CDB 43
Water Min. °C 5
side Max. °C 22
Domestic Ambient Min. °CDB -25
hot water Max. °CDB 35
Water Min. °C 25
side Max. °C 55 (6)
Refrigerant Type R-32
GWP 675.0
Charge kg 3.80
Charge TCO2Eq 2.57
Control Expansion valve
Circuits Quantity 1
Refrigerant oil Type FW68DA
Charged volume l 1.35
Defrost method Reversed cycle
Defrost control Sensor for outdoor heat exchanger temperature
Capacity control Method Inverter controlled
Safety devices Item 01 High pressure switch
02 Low pressure switch
03 Fan driver overload protector

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 27
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09D3V3 EBLA11D3V3 EBLA14D3V3 EBLA16D3V3
Safety devices Item 04 Fuse
05 Compressor motor thermal protector
2 Pump Quantity
Nr of speeds PWM
1

Nominal Heating kPa 106.9 102.7 96.5 71.4


ESP unit Cooling kPa 107.0 98.4 92.3 85.5
Power input W 180
Water side Heat Type Plate heat exchanger
exchanger Quantity 1
Water volume l 2.16
Water Heating Nom. l/min 26.9 (1) / 25.8 (2) 30.3 (1) / 28.2 (2) 34.4 (1) / 35.7 (2) 45.9 (1) / 45.9 (2)
flow rate Cooling Nom. l/min 26.8 (3) / 26.1 (4) 33.2 (3) / 33.0 (4) 36.8 (3) / 36.3 (4) 40.2 (3) / 43.9 (4)
Insulation material EPDM type
Heater W 50.0
Expansion vessel Volume l 8
Max. water pressure bar 4
Pre pressure bar 1
Heater W 65
Water filter Diameter perforations mm 0.8
Material Stainless steel
Water circuit Piping connections diameter inch G 1" (male)
Piping inch 1-1/4"
Piping Max. OU - Tank m 10
length
Level dif- Max. m 5
ference
Safety valve bar 3
Drain valve / fill valve Yes
Shut off valve Yes
Air purge valve Yes
Minimum water volume in the system l 20 (7)
Heater W 66.0
General Supplier/ Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Manu- Name or trademark Daikin Europe N.V.
facturer
details
Product Air-to-water heat pump Yes
descrip- Brine-to-water heat pump No
tion Heat pump combination heater No
Low-temperature heat pump No
Supplementary heater integrated Yes
General Product Water-to-water heat pump No
descrip-
tion
LW(A) Sound power level (according to EN14825) dB(A) 62.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating Air to Rated airflow (outdoor) m³/h 2,880 3,350 4,220 5,100
general water
unit
Other Capacity control Inverter
Pck (Crankcase heater mode) kW 0.000
Poff (Off mode) kW 0.023
Psb (Standby mode) kW 0.023
Pto (Thermostat off) kW 0.023
Inte- Type of energy input Electrical
grated
supple-
mentary
heater

28 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09D3V3 EBLA11D3V3 EBLA14D3V3 EBLA16D3V3
Space heating Average General Annual energy kWh 5,404 6,134 6,651 7,359
climate consumption
water
outlet
ηs (Seasonal
space heating
% 135 132 134 132
2
55°C efficiency)
Prated at -10°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 19 22 24 26
gy consumption
(GCV)
SCOP 3.44 3.37 3.42 3.37
Seasonal space heating A++
eff. class
A Condition Cdh (Degradation heating) 1.0
(-7°CDB/-8°CWB) COPd 2.09 1.90 2.02 1.95
Pdh kW 8.5 9.3 9.4
PERd % 83.6 76.0 80.8 78.0
B Con- Cdh (Degradation heating) 1.0
dition COPd 3.28 3.25 3.28 3.27
(2°CD- Pdh kW 5.0 5.4 6.2 6.9
B/1°CWB) PERd % 131.2 130.0 131.2 130.8
C Con- Cdh (Degradation heating) 1.0
dition COPd 4.80 4.81 4.88 4.93
(7°CD- Pdh kW 4.4
B/6°CWB) PERd % 192.0 192.4 195.2 197.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 6.45 6.41 6.58 6.60
Pdh kW 5.3
PERd % 258.0 256.4 263.2 264.0
Tol (tem- COPd 1.70 1.6 4 1.70 1.67
perature Pdh kW 6.8 7.6 7.8 8.0
operat- PERd % 68.0 65.6 68.0 66.8
ing limit) TOL °C -10
WTOL °C 55

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 29
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09D3V3 EBLA11D3V3 EBLA14D3V3 EBLA16D3V3
Space heating Average Rated Psup (at Tdesign kW 2.2 2.4 3.2 4.1
climate heat -10°C)
2 water
outlet
output
supple-
55°C mentary
capacity
Tbiv COPd 1.92 1.90 2.09 2.13
(bivalent Pdh kW 8.8 9.3 9.4 10.1
tempera- PERd % 76.8 76.0 83.6 85.2
ture) Tbiv °C -8 -7 -6 -5
Cold General Annual energy kWh 7,376 8,196 8,808 9,599
climate consumption
water ηs (Seasonal % 117 120
outlet space heating
55°C efficiency)
Prated at -22°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 27 30 32 35
gy consumption
(GCV)
Warm General Annual energy kWh 2,820 3,083 3,690
climate consumption
water ηs (Seasonal % 168 170 172
outlet space heating
55°C efficiency)
Prated at 2°C kW 9.0 10.0 12.1
Qhe Annual ener- Gj 10 11 13
gy consumption
(GCV)
B Con- Cdh (Degradation heating) 1.0
dition COPd 2.12 2.18 2.17
(2°CD- Pdh kW 9.0 9.8
B/1°CWB) PERd % 84.8 87.2 86.8
C Con- Cdh (Degradation heating) 1.0
dition COPd 3.65 3.74 3.83
(7°CD- Pdh kW 6.2 7.6
B/6°CWB) PERd % 146.0 149.6 153.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 5.68 5.69
Pdh kW 5.0
PERd % 227.2 227.6
Tbiv COPd 2.12 2.18 2.40
(bivalent Pdh kW 9.0 9.8 11.0
tempera- PERd % 84.8 87.2 96.0
ture) Tbiv °C 2 3
Average General Annual energy kWh 3,854 4,371 4,838 5,281
climate consumption
water ηs (Seasonal % 190 186 185
outlet space heating
35°C efficiency)
Prated at -10°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 14 16 17 19
gy consumption
(GCV)
SCOP 4.82 4.73 4.70 4.69
Seasonal space heating A+++
eff. class
A Condition COPd 3.07 3.03 2.95 2.87
(-7°CDB/-8°CWB) Pdh kW 8.5 9.2 10.1 11.2

30 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EBLA09D3V3 EBLA11D3V3 EBLA14D3V3 EBLA16D3V3
Space heating Average A Condition PERd % 122.8 121.2 118.0 114.8
climate (-7°CDB/-8°CWB)
water
outlet
B Con-
dition
Cdh (Degradation heating)
COPd 4.52 4.37
1.0
4.35 4.33
2
35°C (2°CD- Pdh kW 5.5 6.1 6.7
B/1°CWB) PERd % 180.8 174.8 174.0 173.2
C Con- Cdh (Degradation heating) 1.0
dition COPd 6.78 6.74 6.70 6.83
(7°CD- Pdh kW 4.7 4.6 4.7
B/6°CWB) PERd % 271.2 269.6 268.0 273.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 8.75 8.54 8.65 8.82
Pdh kW 5.5 5.4 5.5
PERd % 350.0 341.6 346.0 352.8
Tol (tem- COPd 2.64 2.58 2.51 2.48
perature Pdh kW 8.3 10.1 11.2 11.8
operat- PERd % 105.6 103.2 100.4 99.2
ing limit) TOL °C -10
WTOL °C 35
Tbiv COPd 2.75 2.58 2.51 2.48
(bivalent Pdh kW 8.7 10.1 11.2 11.8
tempera- PERd % 110.0 103.2 100.4 99.2
ture) Tbiv °C -9 -10
Rated Psup (at Tdesign kW 0.7 0.0
heat -10°C)
output
supple-
mentary
capacity
Cold General Annual energy kWh 5,351 5,732 6,266 7,245
climate consumption
water ηs (Seasonal % 163 169 170 160
outlet space heating
35°C efficiency)
Prated at -22°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 19 21 23 26
gy consumption
(GCV)
Warm General Annual energy kWh 1,938 2,128 2,333 2,573
climate consumption
water ηs (Seasonal % 243 248 249 246
outlet space heating
35°C efficiency)
Prated at 2°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 7 8 9
gy consumption
(GCV)
B Con- Cdh (Degradation heating) 1.0
dition COPd 3.36 3.30 3.45 3.30
(2°CD- Pdh kW 9.0 10.3 10.8 11.9
B/1°CWB) PERd % 134.4 132.0 138.0 132.0
C Con- Cdh (Degradation heating) 1.0
dition COPd 5.59 5.70 5.77 5.64
Space heating Warm C Con- Pdh kW 5.9 6.7 7.4 8.1
climate dition PERd % 223.6 228.0 230.8 225.6
water (7°CD-
outlet B/6°CWB)
35°C D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 7.87 7.73
Pdh kW 5.2
PERd % 314.8 309.2
Tbiv COPd 3.36 3.30 3.45 3.30
(bivalent Pdh kW 9.0 10.3 10.8 11.9
tempera- PERd % 134.4 132.0 138.0 132.0
ture) Tbiv °C 2
Control systems Class of temperature control VI
Contribution to seasonal space heating % 4
efficiency

Electrical specifications EBLA09D3V3 EBLA11D3V3 EBLA14D3V3 EBLA16D3V3


Compressor Starting method Inverter
Pump Type PWM

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 31
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Electrical specifications EBLA09D3V3 EBLA11D3V3 EBLA14D3V3 EBLA16D3V3
Compressor com- Main Phase 1~
ponent power Voltage V 230
2 supply
Voltage Min. % -10
range Max. % 10
Hydraulic compo- Back-up Type 3V3
nent heater Power Phase 1~
current supply Frequency Hz 50
Voltage V 230
Running Back-up heater A 13.0
current
Voltage Min. % -10
range Max. % 10
Wiring Type of wires Select diameter and type according to national and local regulations
connec-
tions
Power supply Name V3
Phase 1~
Frequency Hz 50
Voltage V 230
Voltage range Min. % -10
Max. % 10
Current Maxi- Heating A 30.8
mum
running
current
Recommended fuses A 32
Wiring connec- Optional Quantity 3G
tions domestic Type of wires Minimum 2.5 mm²
hot water
tank +
Q2L
R5T Quantity 2
Type of wires Wire included in option EKHWS*
For con- Quantity 2
nection Remark Minimum 0.75 mm²
with R6T
A3P Quantity 4
Type of wires Select diameter and type according to national and local regulations
M2S Quantity 2
Type of wires Select diameter and type according to national and local regulations
M3S Quantity 3
Type of wires Select diameter and type according to national and local regulations
Quantity 2
Type of wires Wire included in option EKFLSW1
Wiring connec- For Quantity 2G
tions power Remark See installation manual outdoor unit
supply
For con- Quantity 4
nection Remark O.75 mm² till 1.25 mm² (max length 200 m)
with user Type of wires 0,75 ~1,25 mm² (P1P2)
interface
Prefer- Quantity Power: 2
ential Remark Power 6.3A
kWh rate
power
supply
Domestic Quantity 3
hot water Remark Minimum 0.75 mm²
pump
Cable require- Cooling/ Maximum running current A 0.3
ments Heating
output
(1)Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) |
(2)Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) |
(3)Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB |
(4)Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB |
(5)According to EN14825 |
(6)For more details, see operation range drawing |
(7)Depends on operation mode, refer to installation manual.

Technical specifications EDLA09DW1 EDLA11DW1 EDLA14DW1 EDLA16DW1


Heating capacity Nom. kW 9.37 (1) / 9.00 (2) 10.6 (1) / 9.82 (2) 12.0 (1) / 12.5 (2) 16.0 (1) / 16.0 (2)
Power input Heating Nom. kW 1.91 (1) / 2.43 (2) 2.18 (1) / 2.68 (2) 2.46 (1) / 3.42 (2) 3.53 (1) / 4.56 (2)
COP 4.91 (1) / 3.71 (2) 4.83 (1) / 3.66 (2) 4.87 (1) / 3.64 (2) 4.53 (1) / 3.51 (2)

32 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09DW1 EDLA11DW1 EDLA14DW1 EDLA16DW1
Casing Colour Silver
Material Polyester painted galvanised steel plate
Dimensions Unit Height
Width
mm
mm
870
1,380
2
Depth mm 460
Packed Height mm 1,053
unit Width mm 1,520
Depth mm 650
Weight Unit kg 147
Packed unit kg 164
Packing Material PE wrapping foil / Carton / Wood (pallet)
Weight kg 17
Heat exchanger Length mm 1,136 /1,166 /1,195
Rows Quantity 3
Fin pitch mm 1.4
Passes Quantity 13
Face area m² 0.950 /0.970 /1.00
Stages Quantity 38
Empty Quantity 2
tubeplate
hole
Tube type 7.0 Hi-XD
Fin Type WF fin
Treatment Anti-corrosion treatment
Fan Type Propeller fan
Quantity 1
Discharge direction Horizontal
Air flow Heating High m³/min 48.0 55.8 70.4 85.0
rate
Fan motor Quantity 1
Model Brushless DC motor
Speed Steps 8
Heating Nom. rpm 400 450 550 650
Output W 234
Drive Direct drive
Compressor Quantity 1
Compressor Model 2Y350BPAY1P#C
Type Hermetically sealed swing compressor
PED Category Category II
Most Name Accumulator
critical Ps*V Bar*l 159
part
Operation range Heating Ambient Min. °CDB -25
Max. °CDB 25 (3)
Water Min. °C 9 (3)
side Max. °C 60 (3)
Domestic Ambient Min. °CDB -25
hot water Max. °CDB 35
Water Min. °C 25
side Max. °C 55 (3)
Refrigerant Type R-32
GWP 675.0
Charge kg 3.80
Charge TCO2Eq 2.57
Control Expansion valve
Circuits Quantity 1
Refrigerant oil Type FW68DA
Charged volume l 1.35
Defrost method Reversed cycle
Defrost control Sensor for outdoor heat exchanger temperature
Capacity control Method Inverter controlled
Safety devices Item 01 High pressure switch
02 Low pressure switch
03 Fan driver overload protector
04 Fuse
05 Compressor motor thermal protector
Pump Quantity 1
Nr of speeds PWM
Nominal Heating kPa 106.5 102.9 97.6 76.7
ESP unit
Power input W 180

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 33
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09DW1 EDLA11DW1 EDLA14DW1 EDLA16DW1
Water side Heat Type Plate heat exchanger
exchanger Quantity 1
2 Water volume
Water Heating Nom.
l
l/min 26.9 (1) / 25.8 (2) 30.3 (1) / 28.2 (2)
2.16
34.4 (1) / 35.7 (2) 45.9 (1) / 45.9 (2)
flow rate
Water side Heat Insulation material EPDM type
exchanger Heater W 50.0
Expansion vessel Volume l 8
Max. water pressure bar 4
Pre pressure bar 1
Heater W 65
Water filter Diameter perforations mm 0.8
Material Stainless steel
Water circuit Piping connections diameter inch G 1" (male)
Piping inch 1-1/4"
Piping Max. OU - Tank m 10
length
Level dif- Max. m 5
ference
Safety valve bar 3
Drain valve / fill valve Yes
Shut off valve Yes
Air purge valve Yes (Manually)
Minimum water volume in the system l 50 (4)
Heater W 66.0
General Supplier/ Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Manu- Name or trademark Daikin Europe N.V.
facturer
details
Product Air-to-water heat pump Yes
descrip- Brine-to-water heat pump No
tion Heat pump combination heater No
Low-temperature heat pump No
Supplementary heater integrated No
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825) dB(A) 62.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating Air to Rated airflow (outdoor) m³/h 2,880 3,350 4,220 5,100
general water
unit
Other Capacity control Inverter
Pck (Crankcase heater mode) kW 0.000
Poff (Off mode) kW 0.023
Psb (Standby mode) kW 0.023
Pto (Thermostat off) kW 0.023
Space heating Average General Annual energy kWh 5,488 6,218 6,735 7,444
climate consumption
water ηs (Seasonal % 133 130 132 130
outlet space heating
55°C efficiency)
Prated at -10°C kW 9.0 10.0 11.0 12.0

34 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09DW1 EDLA11DW1 EDLA14DW1 EDLA16DW1
Space heating Average General Qhe Annual ener- Gj 20 22 24 27
climate gy consumption
water
outlet
(GCV)
SCOP 3.39 3.32 3.37 3.33
2
55°C Seasonal space heating A++
eff. class
A Condition Cdh (Degradation heating) 1.0
(-7°CDB/-8°CWB) COPd 2.09 1.90 2.02 1.95
Pdh kW 8.5 9.3 9.4
PERd % 83.6 76.0 80.8 78.0
B Con- Cdh (Degradation heating) 1.0
dition COPd 3.28 3.25 3.28 3.27
(2°CD- Pdh kW 5.0 5.4 6.2 6.9
B/1°CWB) PERd % 131.2 130.0 131.2 130.8
C Con- Cdh (Degradation heating) 1.0
dition COPd 4.80 4.81 4.88 4.93
(7°CD- Pdh kW 4.4
B/6°CWB) PERd % 192.0 192.4 195.2 197.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 6.45 6.41 6.58 6.60
Pdh kW 5.3
PERd % 258.0 256.4 263.2 264.0
Tol (tem- COPd 1.70 1.6 4 1.70 1.67
perature Pdh kW 6.8 7.6 7.8 8.0
operat- PERd % 68.0 65.6 68.0 66.8
ing limit) TOL °C -10
WTOL °C 55
Rated Psup (at Tdesign kW 2.2 2.4 3.2 4.1
heat -10°C)
output
supple-
mentary
capacity
Tbiv COPd 1.92 1.90 2.09 2.13
(bivalent Pdh kW 8.8 9.3 9.4 10.1
tempera- PERd % 76.8 76.0 83.6 85.2
ture) Tbiv °C -8 -7 -6 -5
Cold General Annual energy kWh 7,142 7,899 8,858 9,561
climate consumption
water ηs (Seasonal % 121 122 119 121
outlet space heating
55°C efficiency)
Prated at -22°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 26 28 32 34
gy consumption
(GCV)
Warm General Annual energy kWh 2,921 3,184 3,792
climate consumption
water ηs (Seasonal % 162 165 168
outlet space heating
55°C efficiency)
Prated at 2°C kW 9.0 10.0 12.1
Qhe Annual ener- Gj 11 14
gy consumption
(GCV)

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 35
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09DW1 EDLA11DW1 EDLA14DW1 EDLA16DW1
Space heating Warm B Con- Cdh (Degradation heating) 1.0
climate dition COPd 2.12 2.18 2.17
2 water
outlet
(2°CD-
B/1°CWB)
Pdh
PERd
kW
%
9.0
84.8 87.2
9.8
86.8
55°C C Con- Cdh (Degradation heating) 1.0
dition COPd 3.65 3.74 3.83
(7°CD- Pdh kW 6.2 7.6
B/6°CWB) PERd % 146.0 149.6 153.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB)
COPd 5.68 5.69
Pdh kW 5.0
PERd % 227.2 227.6
Tbiv COPd 2.12 2.18 2.40
(bivalent Pdh kW 9.0 9.8 11.0
tempera- PERd % 84.8 87.2 96.0
ture) Tbiv °C 2 3
Average General Annual energy kWh 3,939 4,456 4,923 5,366
climate consumption
water ηs (Seasonal % 186 182
outlet space heating
35°C efficiency)
Prated at -10°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 14 16 18 19
gy consumption
(GCV)
SCOP 4.72 4.64 4.62
Seasonal space heating A+++
eff. class
A Condition COPd 3.07 3.03 2.95 2.87
(-7°CDB/-8°CWB) Pdh kW 8.5 9.2 10.1 11.2
PERd % 122.8 121.2 118.0 114.8
B Con- Cdh (Degradation heating) 1.0
dition COPd 4.52 4.37 4.35 4.33
(2°CD- Pdh kW 4.5 5.5 6.1 6.7
B/1°CWB) PERd % 180.8 174.8 174.0 173.2
C Con- Cdh (Degradation heating) 1.0
dition COPd 6.78 6.74 6.70 6.83
(7°CD- Pdh kW 4.7 4.6 4.7
B/6°CWB) PERd % 271.2 269.6 268.0 273.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 8.75 8.54 8.65 8.82
Pdh kW 5.5 5.4 5.5
PERd % 350.0 341.6 346.0 352.8

36 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09DW1 EDLA11DW1 EDLA14DW1 EDLA16DW1
Space heating Average Tol (tem- COPd 2.64 2.58 2.51 2.48
climate perature Pdh kW 8.3 10.1 11.2 11.8
water
outlet
operat-
ing limit)
PERd
TOL
%
°C
105.6 103.2
-10
100.4 99.2
2
35°C WTOL °C 35
Tbiv COPd 2.75 2.58 2.51 2.48
(bivalent Pdh kW 8.7 10.1 11.2 11.8
tempera- PERd % 110.0 103.2 100.4 99.2
ture) Tbiv °C -9 -10
Rated Psup (at Tdesign kW 0.7 0.0
heat -10°C)
output
supple-
mentary
capacity
Cold General Annual energy kWh 5,031 5,783 6,317 7,296
climate consumption
water ηs (Seasonal % 173 168 169 159
outlet space heating
35°C efficiency)
Prated at -22°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 18 21 23 26
gy consumption
(GCV)
Warm General Annual energy kWh 2,039 2,230 2,435 2,675
climate consumption
water ηs (Seasonal % 233 237 238 237
outlet space heating
35°C efficiency)
Prated at 2°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 7 8 9 10
gy consumption
(GCV)
B Con- Cdh (Degradation heating) 1.0
dition COPd 3.36 3.30 3.45 3.30
(2°CD- Pdh kW 9.0 10.3 10.8 11.9
B/1°CWB) PERd % 134.4 132.0 138.0 132.0
C Con- Cdh (Degradation heating) 1.0
dition COPd 5.59 5.70 5.77 5.64
(7°CD- Pdh kW 5.9 6.7 7.4 8.1
B/6°CWB) PERd % 223.6 228.0 230.8 225.6
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 7.87 7.73
Pdh kW 5.2
PERd % 314.8 309.2
Tbiv COPd 3.36 3.30 3.45 3.30
(bivalent Pdh kW 9.0 10.3 10.8 11.9
tempera- PERd % 134.4 132.0 138.0 132.0
ture) Tbiv °C 2
Control systems Class of temperature control VI
Contribution to seasonal space heating % 4
efficiency

Electrical specifications EDLA09DW1 EDLA11DW1 EDLA14DW1 EDLA16DW1


Compressor Starting method Inverter
Pump Type PWM
Compressor com- Main Phase 3N~
ponent power Voltage V 400
supply
Voltage Min. % -10
range Max. % 10
Power supply Name W1
Phase 3~
Frequency Hz 50
Voltage V 400
Voltage range Min. % -10
Max. % 10
Current Maxi- Heating A 14.0
mum
running
current
Recommended fuses A 16

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 37
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Electrical specifications EDLA09DW1 EDLA11DW1 EDLA14DW1 EDLA16DW1
Wiring connec- Optional Quantity 3G
tions domestic Type of wires Minimum 2.5 mm²
2 hot water
tank +
Q2L
R5T Quantity 2
Type of wires Wire included in option EKHWS*
For con- Quantity 2
nection Remark Minimum 0.75 mm²
with R6T
A3P Quantity 4
Type of wires Select diameter and type according to national and local regulations
M2S Quantity 2
Type of wires Select diameter and type according to national and local regulations
M3S Quantity 3
Type of wires Select diameter and type according to national and local regulations
Quantity 2
Type of wires Wire included in option EKFLSW1
For Quantity 4G
power Remark See installation manual outdoor unit
supply
For con- Quantity 4
nection Remark O.75 mm² till 1.25 mm² (max length 200 m)
with user Type of wires 0,75 ~1,25 mm² (P1P2)
interface
Prefer- Quantity Power: 2
ential Remark Power 6.3A
kWh rate
power
supply
Domestic Quantity 3
hot water
pump
Wiring connec- Domestic Remark Minimum 0.75 mm²
tions hot water
pump
Cable require- Cooling/ Maximum running current A 0.3
ments Heating
output
(1)Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) |
(2)Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) |
(3)For more details, see operation range drawing |
(4)Depends on operation mode, refer to installation manual. |
Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB |
Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB |
According to EN14825

Technical specifications EDLA09DV3 EDLA11DV3 EDLA14DV3 EDLA16DV3


Heating capacity Nom. kW 9.37 (1) / 9.00 (2) 10.6 (1) / 9.82 (2) 12.0 (1) / 12.5 (2) 16.0 (1) / 16.0 (2)
Power input Heating Nom. kW 1.91 (1) / 2.43 (2) 2.18 (1) / 2.68 (2) 2.46 (1) / 3.42 (2) 3.53 (1) / 4.56 (2)
COP 4.91 (1) / 3.71 (2) 4.83 (1) / 3.66 (2) 4.87 (1) / 3.64 (2) 4.53 (1) / 3.51 (2)
Casing Colour Silver
Material Polyester painted galvanised steel plate
Dimensions Unit Height mm 870
Width mm 1,380
Depth mm 460
Packed Height mm 1,053
unit Width mm 1,520
Depth mm 650
Weight Unit kg 147
Packed unit kg 164
Packing Material PE wrapping foil / Carton / Wood (pallet)
Weight kg 17
Heat exchanger Length mm 1,136 /1,166 /1,195
Rows Quantity 3
Fin pitch mm 1.4
Passes Quantity 14
Face area m² 0.950 /0.970 /1.00
Stages Quantity 38
Tube type 7.0 Hi-XD
Fin Type WF fin
Treatment Anti-corrosion treatment

38 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09DV3 EDLA11DV3 EDLA14DV3 EDLA16DV3
Fan Type Propeller fan
Quantity 1
Discharge direction
Air flow Heating High m³/min 48.0 55.8
Horizontal
70.4 85.0
2
rate
Fan motor Quantity 1
Model Brushless DC motor
Speed Steps 8
Heating Nom. rpm 400 450 550 650
Output W 230
Drive Direct drive
Compressor Quantity 1
Model 2Y350BPAX1P#C
Compressor Type Hermetically sealed swing compressor
PED Category Category II
Most Name Accumulator
critical Ps*V Bar*l 159
part
Operation range Heating Ambient Min. °CDB -25
Max. °CDB 25 (3)
Water Min. °C 9 (3)
side Max. °C 60 (3)
Domestic Ambient Min. °CDB -25
hot water Max. °CDB 35
Water Min. °C 25
side Max. °C 55 (3)
Refrigerant Type R-32
GWP 675.0
Charge kg 3.80
Charge TCO2Eq 2.57
Control Expansion valve
Circuits Quantity 1
Refrigerant oil Type FW68DA
Charged volume l 1.35
Defrost method Reversed cycle
Defrost control Sensor for outdoor heat exchanger temperature
Capacity control Method Inverter controlled
Safety devices Item 01 High pressure switch
02 Low pressure switch
03 Fan driver overload protector
04 Fuse
05 Compressor motor thermal protector
Pump Quantity 1
Nr of speeds PWM
Nominal Heating kPa 106.5 102.9 97.6 76.7
ESP unit
Power input W 180
Water side Heat Type Plate heat exchanger
exchanger Quantity 1
Water volume l 2.16
Water Heating Nom. l/min 26.9 (1) / 25.8 (2) 30.3 (1) / 28.2 (2) 34.4 (1) / 35.7 (2) 45.9 (1) / 45.9 (2)
flow rate
Insulation material EPDM type
Water side Heat Heater W 50.0
exchanger
Expansion vessel Volume l 8
Max. water pressure bar 4
Pre pressure bar 1
Heater W 65
Water filter Diameter perforations mm 0.8
Material Stainless steel
Water circuit Piping connections diameter inch G 1" (male)
Piping inch 1-1/4"
Piping Max. OU - Tank m 10
length
Level dif- Max. m 5
ference
Safety valve bar 3
Drain valve / fill valve Yes
Shut off valve Yes
Air purge valve Yes (Manually)
Minimum water volume in the system l 50 (4)
Heater W 66.0

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 39
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09DV3 EDLA11DV3 EDLA14DV3 EDLA16DV3
General Supplier/ Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Manu- Name or trademark Daikin Europe N.V.
2 facturer
details
Product Air-to-water heat pump Yes
descrip- Brine-to-water heat pump No
tion Heat pump combination heater No
Low-temperature heat pump No
Supplementary heater integrated No
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825) dB(A) 62.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating Air to Rated airflow (outdoor) m³/h 2,880 3,350 4,220 5,100
general water
unit
Other Capacity control Inverter
Pck (Crankcase heater mode) kW 0.000
Poff (Off mode) kW 0.023
Psb (Standby mode) kW 0.023
Pto (Thermostat off) kW 0.023
Space heating Average General Annual energy kWh 5,488 6,218 6,735 7,444
climate consumption
water ηs (Seasonal % 133 130 132 130
outlet space heating
55°C efficiency)
Prated at -10°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 20 22 24 27
gy consumption
(GCV)

40 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09DV3 EDLA11DV3 EDLA14DV3 EDLA16DV3
Space heating Average General SCOP 3.39 3.32 3.37 3.33
climate Seasonal space heating A++
water
outlet
eff. class
A Condition Cdh (Degradation heating) 1.0
2
55°C (-7°CDB/-8°CWB) COPd 2.09 1.90 2.02 1.95
Pdh kW 8.5 9.3 9.4
PERd % 83.6 76.0 80.8 78.0
B Con- Cdh (Degradation heating) 1.0
dition COPd 3.28 3.25 3.28 3.27
(2°CD- Pdh kW 5.0 5.4 6.2 6.9
B/1°CWB) PERd % 131.2 130.0 131.2 130.8
C Con- Cdh (Degradation heating) 1.0
dition COPd 4.80 4.81 4.88 4.93
(7°CD- Pdh kW 4.4
B/6°CWB) PERd % 192.0 192.4 195.2 197.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 6.45 6.41 6.58 6.60
Pdh kW 5.3
PERd % 258.0 256.4 263.2 264.0
Tol (tem- COPd 1.70 1.6 4 1.70 1.67
perature Pdh kW 6.8 7.6 7.8 8.0
operat- PERd % 68.0 65.6 68.0 66.8
ing limit) TOL °C -10
WTOL °C 55
Rated Psup (at Tdesign kW 2.2 2.4 3.2 4.1
heat -10°C)
output
supple-
mentary
capacity
Tbiv COPd 1.92 1.90 2.09 2.13
(bivalent Pdh kW 8.8 9.3 9.4 10.1
tempera- PERd % 76.8 76.0 83.6 85.2
ture) Tbiv °C -8 -7 -6 -5
Cold General Annual energy kWh 7,427 8,247 8,858 9,650
climate consumption
water ηs (Seasonal % 117 119 120
outlet space heating
55°C efficiency)
Prated at -22°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 27 30 32 35
gy consumption
(GCV)
Warm General Annual energy kWh 2,921 3,184 3,792
climate consumption
water ηs (Seasonal % 162 165 168
outlet space heating
55°C efficiency)
Prated at 2°C kW 9.0 10.0 12.1
Qhe Annual ener- Gj 11 14
gy consumption
(GCV)
B Con- Cdh (Degradation heating) 1.0
dition
(2°CD-
B/1°CWB)

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 41
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09DV3 EDLA11DV3 EDLA14DV3 EDLA16DV3
Space heating Warm B Con- COPd 2.12 2.18 2.17
climate dition Pdh kW 9.0 9.8
2 water
outlet
(2°CD-
B/1°CWB)
PERd % 84.8 87.2 86.8

55°C C Con- Cdh (Degradation heating) 1.0


dition COPd 3.65 3.74 3.83
(7°CD- Pdh kW 6.2 7.6
B/6°CWB) PERd % 146.0 149.6 153.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB)
COPd 5.68 5.69
Pdh kW 5.0
PERd % 227.2 227.6
Tbiv COPd 2.12 2.18 2.40
(bivalent Pdh kW 9.0 9.8 11.0
tempera- PERd % 84.8 87.2 96.0
ture) Tbiv °C 2 3
Average General Annual energy kWh 3,939 4,456 4,923 5,366
climate consumption
water ηs (Seasonal % 186 182
outlet space heating
35°C efficiency)
Prated at -10°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 14 16 18 19
gy consumption
(GCV)
SCOP 4.72 4.64 4.62
Seasonal space heating A+++
eff. class
A Condition COPd 3.07 3.03 2.95 2.87
(-7°CDB/-8°CWB) Pdh kW 8.5 9.2 10.1 11.2
PERd % 122.8 121.2 118.0 114.8
B Con- Cdh (Degradation heating) 1.0
dition COPd 4.52 4.37 4.35 4.33
(2°CD- Pdh kW 4.5 5.5 6.1 6.7
B/1°CWB) PERd % 180.8 174.8 174.0 173.2
C Con- Cdh (Degradation heating) 1.0
dition COPd 6.78 6.74 6.70 6.83
(7°CD- Pdh kW 4.7 4.6 4.7
B/6°CWB) PERd % 271.2 269.6 268.0 273.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 8.75 8.54 8.65 8.82
Pdh kW 5.5 5.4 5.5
PERd % 350.0 341.6 346.0 352.8
Tol (tem- COPd 2.64 2.58 2.51 2.48
perature
operat-
ing limit)

42 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09DV3 EDLA11DV3 EDLA14DV3 EDLA16DV3
Space heating Average Tol (tem- Pdh kW 8.3 10.1 11.2 11.8
climate perature PERd % 105.6 103.2 100.4 99.2
water
outlet
operat-
ing limit)
TOL
WTOL
°C
°C
-10
35
2
35°C Tbiv COPd 2.75 2.58 2.51 2.48
(bivalent Pdh kW 8.7 10.1 11.2 11.8
tempera- PERd % 110.0 103.2 100.4 99.2
ture) Tbiv °C -9 -10
Rated Psup (at Tdesign kW 0.7 0.0
heat -10°C)
output
supple-
mentary
capacity
Cold General Annual energy kWh 5,402 5,783 6,317 7,296
climate consumption
water ηs (Seasonal % 161 168 169 159
outlet space heating
35°C efficiency)
Prated at -22°C kW 10.0 11.0 12.0
Qhe Annual ener- Gj 19 21 23 26
gy consumption
(GCV)
Warm General Annual energy kWh 2,039 2,230 2,435 2,675
climate consumption
water ηs (Seasonal % 233 237 238 237
outlet space heating
35°C efficiency)
Prated at 2°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 7 8 9 10
gy consumption
(GCV)
B Con- Cdh (Degradation heating) 1.0
dition COPd 3.36 3.30 3.45 3.30
(2°CD- Pdh kW 9.0 10.3 10.8 11.9
B/1°CWB) PERd % 134.4 132.0 138.0 132.0
C Con- Cdh (Degradation heating) 1.0
dition COPd 5.59 5.70 5.77 5.64
(7°CD- Pdh kW 5.9 6.7 7.4 8.1
B/6°CWB) PERd % 223.6 228.0 230.8 225.6
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 7.87 7.73
Pdh kW 5.2
PERd % 314.8 309.2
Tbiv COPd 3.36 3.30 3.45 3.30
(bivalent Pdh kW 9.0 10.3 10.8 11.9
tempera- PERd % 134.4 132.0 138.0 132.0
ture) Tbiv °C 2
Control systems Class of temperature control VI
Contribution to seasonal space heating % 4
efficiency

Electrical specifications EDLA09DV3 EDLA11DV3 EDLA14DV3 EDLA16DV3


Compressor Starting method Inverter
Pump Type PWM
Compressor com- Main Phase 1~
ponent power Voltage V 230
supply
Voltage Min. % -10
range Max. % 10
Power supply Name V3
Phase 1~
Frequency Hz 50
Voltage V 230
Voltage range Min. % -10
Max. % 10
Current Maxi- Heating A 30.8
mum
running
current
Recommended fuses A 32

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 43
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Electrical specifications EDLA09DV3 EDLA11DV3 EDLA14DV3 EDLA16DV3
Wiring connec- Optional Quantity 3G
tions domestic Type of wires Minimum 2.5 mm²
2 hot water
tank +
Q2L
R5T Quantity 2
Type of wires Wire included in option EKHWS*
For con- Quantity 2
nection Remark Minimum 0.75 mm²
with R6T
A3P Quantity 4
Type of wires Select diameter and type according to national and local regulations
M2S Quantity 2
Type of wires Select diameter and type according to national and local regulations
M3S Quantity 3
Type of wires Select diameter and type according to national and local regulations
Quantity 2
Type of wires Wire included in option EKFLSW1
For Quantity 2G
power Remark See installation manual outdoor unit
supply
For con- Quantity 4
nection Remark O.75 mm² till 1.25 mm² (max length 200 m)
with user Type of wires 0,75 ~1,25 mm² (P1P2)
interface
Prefer- Quantity Power: 2
ential Remark Power 6.3A
kWh rate
power
supply
Domestic Quantity 3
hot water
pump
Wiring connec- Domestic Remark Minimum 0.75 mm²
tions hot water
pump
Cable require- Cooling/ Maximum running current A 0.3
ments Heating
output
(1)Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) |
(2)Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) |
(3)For more details, see operation range drawing |
(4)Depends on operation mode, refer to installation manual. |
Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB |
Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB |
According to EN14825

Technical specifications EDLA09D3W1 EDLA11D3W1 EDLA14D3W1 EDLA16D3W1


Heating capacity Nom. kW 9.37 (1) / 9.00 (2) 10.6 (1) / 9.82 (2) 12.0 (1) / 12.5 (2) 16.0 (1) / 16.0 (2)
Heater capacity Step 1 kW 3
Power input Heating Nom. kW 1.91 (1) / 2.43 (2) 2.18 (1) / 2.68 (2) 2.46 (1) / 3.42 (2) 3.53 (1) / 4.56 (2)
COP 4.91 (1) / 3.71 (2) 4.83 (1) / 3.66 (2) 4.87 (1) / 3.64 (2) 4.53 (1) / 3.51 (2)
Casing Colour Silver
Material Polyester painted galvanised steel plate
Dimensions Unit Height mm 870
Width mm 1,380
Depth mm 460
Packed Height mm 1,053
unit Width mm 1,520
Depth mm 650
Weight Unit kg 149
Packed unit kg 166
Packing Material PE wrapping foil / Carton / Wood (pallet)
Weight kg 17

44 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09D3W1 EDLA11D3W1 EDLA14D3W1 EDLA16D3W1
Heat exchanger Length mm 1,136 /1,166 /1,195
Rows Quantity 3
Fin pitch
Passes Quantity
mm 1.4
13
2
Face area m² 0.950 /0.970 /1.00
Stages Quantity 38
Empty Quantity 2
tubeplate
hole
Tube type 7.0 Hi-XD
Fin Type WF fin
Treatment Anti-corrosion treatment
Fan Type Propeller fan
Quantity 1
Discharge direction Horizontal
Air flow Heating High m³/min 48.0 55.8 70.4 85.0
rate
Fan motor Quantity 1
Model Brushless DC motor
Speed Steps 8
Heating Nom. rpm 400 450 550 650
Output W 234
Drive Direct drive
Compressor Quantity 1
Model 2Y350BPAY1P#C
Type Hermetically sealed swing compressor
PED Category Category II
Most Name Accumulator
critical Ps*V Bar*l 159
part
Operation range Heating Ambient Min. °CDB -25
Max. °CDB 35
Water Min. °C 15 (3)
side Max. °C 60 (3)
Domestic Ambient Min. °CDB -25
hot water Max. °CDB 35
Water Min. °C 25
side Max. °C 55 (3)
Refrigerant Type R-32
GWP 675.0
Charge kg 3.80
Charge TCO2Eq 2.57
Control Expansion valve
Circuits Quantity 1
Refrigerant oil Type FW68DA
Charged volume l 1.35
Defrost method Reversed cycle
Defrost control Sensor for outdoor heat exchanger temperature
Capacity control Method Inverter controlled
Safety devices Item 01 High pressure switch
02 Low pressure switch
03 Fan driver overload protector
04 Fuse
05 Compressor motor thermal protector
Pump Quantity 1
Nr of speeds PWM
Nominal Heating kPa 106.9 102.7 96.5 71.4
ESP unit
Power input W 180
Water side Heat Type Plate heat exchanger
exchanger Quantity 1
Water volume l 2.16
Water side Heat Water Heating Nom. l/min 26.9 (1) / 25.8 (2) 30.3 (1) / 28.2 (2) 34.4 (1) / 35.7 (2) 45.9 (1) / 45.9 (2)
exchanger flow rate
Insulation material EPDM type
Heater W 50.0
Expansion vessel Volume l 8
Max. water pressure bar 4
Pre pressure bar 1
Heater W 65
Water filter Diameter perforations mm 0.8
Material Stainless steel

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 45
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09D3W1 EDLA11D3W1 EDLA14D3W1 EDLA16D3W1
Water circuit Piping connections diameter inch G 1" (male)
Piping inch 1-1/4"
2 Piping
length
Max. OU - Tank m 10

Level dif- Max. m 5


ference
Safety valve bar 3
Drain valve / fill valve Yes
Shut off valve Yes
Air purge valve Yes
Minimum water volume in the system l 20 (4)
Heater W 66.0
General Supplier/ Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Manu- Name or trademark Daikin Europe N.V.
facturer
details
Product Air-to-water heat pump Yes
descrip- Brine-to-water heat pump No
tion Heat pump combination heater No
Low-temperature heat pump No
Supplementary heater integrated Yes
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825) dB(A) 62.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating Air to Rated airflow (outdoor) m³/h 2,880 3,350 4,220 5,100
general water
unit
Other Capacity control Inverter
Pck (Crankcase heater mode) kW 0.000
Poff (Off mode) kW 0.023
Psb (Standby mode) kW 0.023
Pto (Thermostat off) kW 0.023
Inte- Type of energy input Electrical
grated
supple-
mentary
heater
Space heating Average General Annual energy kWh 5,488 6,218 6,735 7,444
climate consumption
water
outlet
55°C

46 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09D3W1 EDLA11D3W1 EDLA14D3W1 EDLA16D3W1
Space heating Average General ηs (Seasonal % 133 130 132 130
climate space heating
water
outlet
efficiency)
Prated at -10°C kW 9.0 10.0 11.0 12.0
2
55°C Qhe Annual ener- Gj 20 22 24 27
gy consumption
(GCV)
SCOP 3.39 3.32 3.37 3.33
Seasonal space heating A++
eff. class
A Condition Cdh (Degradation heating) 1.0
(-7°CDB/-8°CWB) COPd 2.09 1.90 2.02 1.95
Pdh kW 8.5 9.3 9.4
PERd % 83.6 76.0 80.8 78.0
B Con- Cdh (Degradation heating) 1.0
dition COPd 3.28 3.25 3.28 3.27
(2°CD- Pdh kW 5.0 5.4 6.2 6.9
B/1°CWB) PERd % 131.2 130.0 131.2 130.8
C Con- Cdh (Degradation heating) 1.0
dition COPd 4.80 4.81 4.88 4.93
(7°CD- Pdh kW 4.4
B/6°CWB) PERd % 192.0 192.4 195.2 197.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 6.45 6.41 6.58 6.60
Pdh kW 5.3
PERd % 258.0 256.4 263.2 264.0
Tol (tem- COPd 1.70 1.6 4 1.70 1.67
perature Pdh kW 6.8 7.6 7.8 8.0
operat- PERd % 68.0 65.6 68.0 66.8
ing limit) TOL °C -10
WTOL °C 55
Rated Psup (at Tdesign kW 2.2 2.4 3.2 4.1
heat -10°C)
output
supple-
mentary
capacity
Tbiv COPd 1.92 1.90 2.09 2.13
(bivalent Pdh kW 8.8 9.3 9.4 10.1
tempera- PERd % 76.8 76.0 83.6 85.2
ture) Tbiv °C -8 -7 -6 -5
Cold General Annual energy kWh 7,142 7,899 8,858 9,561
climate consumption
water ηs (Seasonal % 121 122 119 121
outlet space heating
55°C efficiency)
Prated at -22°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 26 28 32 34
gy consumption
(GCV)
Warm General Annual energy kWh 2,921 3,184 3,792
climate consumption
water ηs (Seasonal % 162 165 168
outlet space heating
55°C efficiency)

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 47
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09D3W1 EDLA11D3W1 EDLA14D3W1 EDLA16D3W1
Space heating Warm General Prated at 2°C kW 9.0 10.0 12.1
climate Qhe Annual ener- Gj 11 14
2 water
outlet
gy consumption
(GCV)
55°C B Con- Cdh (Degradation heating) 1.0
dition COPd 2.12 2.18 2.17
(2°CD- Pdh kW 9.0 9.8
B/1°CWB) PERd % 84.8 87.2 86.8
C Con- Cdh (Degradation heating) 1.0
dition COPd 3.65 3.74 3.83
(7°CD- Pdh kW 6.2 7.6
B/6°CWB) PERd % 146.0 149.6 153.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 5.68 5.69
Pdh kW 5.0
PERd % 227.2 227.6
Tbiv COPd 2.12 2.18 2.40
(bivalent Pdh kW 9.0 9.8 11.0
tempera- PERd % 84.8 87.2 96.0
ture) Tbiv °C 2 3
Average General Annual energy kWh 3,939 4,456 4,923 5,366
climate consumption
water ηs (Seasonal % 186 182
outlet space heating
35°C efficiency)
Prated at -10°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 14 16 18 19
gy consumption
(GCV)
SCOP 4.72 4.64 4.62
Seasonal space heating A+++
eff. class
A Condition COPd 3.07 3.03 2.95 2.87
(-7°CDB/-8°CWB) Pdh kW 8.5 9.2 10.1 11.2
PERd % 122.8 121.2 118.0 114.8
B Con- Cdh (Degradation heating) 1.0
dition COPd 4.52 4.37 4.35 4.33
(2°CD- Pdh kW 4.5 5.5 6.1 6.7
B/1°CWB) PERd % 180.8 174.8 174.0 173.2
C Con- Cdh (Degradation heating) 1.0
dition COPd 6.78 6.74 6.70 6.83
(7°CD- Pdh kW 4.7 4.6 4.7
B/6°CWB) PERd % 271.2 269.6 268.0 273.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 8.75 8.54 8.65 8.82

48 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09D3W1 EDLA11D3W1 EDLA14D3W1 EDLA16D3W1
Space heating Average D Condition Pdh kW 5.5 5.4 5.5
climate (12°CDB/11°CWB) PERd % 350.0 341.6 346.0 352.8
water
outlet
Tol (tem-
perature
COPd
Pdh kW
2.64
8.3
2.58
10.1
2.51
11.2
2.48
11.8
2
35°C operat- PERd % 105.6 103.2 100.4 99.2
ing limit) TOL °C -10
WTOL °C 35
Tbiv COPd 2.75 2.58 2.51 2.48
(bivalent Pdh kW 8.7 10.1 11.2 11.8
tempera- PERd % 110.0 103.2 100.4 99.2
ture) Tbiv °C -9 -10
Rated Psup (at Tdesign kW 0.7 0.0
heat -10°C)
output
supple-
mentary
capacity
Cold General Annual energy kWh 5,031 5,783 6,317 7,296
climate consumption
water ηs (Seasonal % 173 168 169 159
outlet space heating
35°C efficiency)
Prated at -22°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 18 21 23 26
gy consumption
(GCV)
Warm General Annual energy kWh 2,039 2,230 2,435 2,675
climate consumption
water ηs (Seasonal % 233 237 238 237
outlet space heating
35°C efficiency)
Prated at 2°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 7 8 9 10
gy consumption
(GCV)
B Con- Cdh (Degradation heating) 1.0
dition COPd 3.36 3.30 3.45 3.30
(2°CD- Pdh kW 9.0 10.3 10.8 11.9
B/1°CWB) PERd % 134.4 132.0 138.0 132.0
C Con- Cdh (Degradation heating) 1.0
dition COPd 5.59 5.70 5.77 5.64
(7°CD- Pdh kW 5.9 6.7 7.4 8.1
B/6°CWB) PERd % 223.6 228.0 230.8 225.6
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 7.87 7.73
Pdh kW 5.2
PERd % 314.8 309.2
Tbiv COPd 3.36 3.30 3.45 3.30
(bivalent Pdh kW 9.0 10.3 10.8 11.9
tempera- PERd % 134.4 132.0 138.0 132.0
ture) Tbiv °C 2
Control systems Class of temperature control VI
Control systems Contribution to seasonal space heating % 4
efficiency

Electrical specifications EDLA09D3W1 EDLA11D3W1 EDLA14D3W1 EDLA16D3W1


Compressor Starting method Inverter
Pump Type PWM
Compressor com- Main Phase 3N~
ponent power Voltage V 400
supply
Voltage Min. % -10
range Max. % 10

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 49
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Electrical specifications EDLA09D3W1 EDLA11D3W1 EDLA14D3W1 EDLA16D3W1
Hydraulic compo- Back-up Type 3V3
nent heater Power Phase 1~
2 current supply Frequency
Voltage
Hz
V
50
230
Running Back-up heater A 13.0
current
Voltage Min. % -10
range Max. % 10
Wiring Type of wires Select diameter and type according to national and local regulations
connec-
tions
Power supply Name W1
Phase 3~
Frequency Hz 50
Voltage V 400
Voltage range Min. % -10
Max. % 10
Current Maxi- Heating A 14.0
mum
running
current
Recommended fuses A 16
Wiring connec- Optional Quantity 3G
tions domestic Type of wires Minimum 2.5 mm²
hot water
tank +
Q2L
R5T Quantity 2
Type of wires Wire included in option EKHWS*
For con- Quantity 2
nection Remark Minimum 0.75 mm²
with R6T
A3P Quantity 4
Type of wires Select diameter and type according to national and local regulations
M2S Quantity 2
Type of wires Select diameter and type according to national and local regulations
M3S Quantity 3
Type of wires Select diameter and type according to national and local regulations
Quantity 2
Type of wires Wire included in option EKFLSW1
Wiring connec- For Quantity 4G
tions power Remark See installation manual outdoor unit
supply
For con- Quantity 4
nection Remark O.75 mm² till 1.25 mm² (max length 200 m)
with user Type of wires 0,75 ~1,25 mm² (P1P2)
interface
Prefer- Quantity Power: 2
ential Remark Power 6.3A
kWh rate
power
supply
Domestic Quantity 3
hot water Remark Minimum 0.75 mm²
pump
Cable require- Cooling/ Maximum running current A 0.3
ments Heating
output
(1)Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) |
(2)Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) |
(3)For more details, see operation range drawing |
(4)Depends on operation mode, refer to installation manual. |
Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB |
Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB |
According to EN14825

Technical specifications EDLA09D3V3 EDLA11D3V3 EDLA14D3V3 EDLA16D3V3


Heating capacity Nom. kW 9.37 (1) / 9.00 (2) 10.6 (1) / 9.82 (2) 12.0 (1) / 12.5 (2) 16.0 (1) / 16.0 (2)
Heater capacity Step 1 kW 3
Power input Heating Nom. kW 1.91 (1) / 2.43 (2) 2.18 (1) / 2.68 (2) 2.46 (1) / 3.42 (2) 3.53 (1) / 4.56 (2)
COP 4.91 (1) / 3.71 (2) 4.83 (1) / 3.66 (2) 4.87 (1) / 3.64 (2) 4.53 (1) / 3.51 (2)
Casing Colour Silver
Material Polyester painted galvanised steel plate

50 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09D3V3 EDLA11D3V3 EDLA14D3V3 EDLA16D3V3
Dimensions Unit Height mm 870
Width mm 1,380

Packed
Depth
Height
mm
mm
460
1,053
2
unit Width mm 1,520
Depth mm 650
Weight Unit kg 149
Packed unit kg 166
Packing Material PE wrapping foil / Carton / Wood (pallet)
Weight kg 17
Heat exchanger Length mm 1,136 /1,166 /1,195
Rows Quantity 3
Fin pitch mm 1.4
Passes Quantity 14
Face area m² 0.950 /0.970 /1.00
Stages Quantity 38
Tube type 7.0 Hi-XD
Fin Type WF fin
Treatment Anti-corrosion treatment
Fan Type Propeller fan
Quantity 1
Discharge direction Horizontal
Air flow Heating High m³/min 48.0 55.8 70.4 85.0
rate
Fan motor Quantity 1
Model Brushless DC motor
Speed Steps 8
Heating Nom. rpm 400 450 550 650
Output W 230
Drive Direct drive
Compressor Quantity 1
Compressor Model 2Y350BPAX1P#C
Type Hermetically sealed swing compressor
PED Category Category II
Most Name Accumulator
critical Ps*V Bar*l 159
part
Operation range Heating Ambient Min. °CDB -25
Max. °CDB 35
Water Min. °C 15 (3)
side Max. °C 60 (3)
Domestic Ambient Min. °CDB -25
hot water Max. °CDB 35
Water Min. °C 25
side Max. °C 55 (3)
Refrigerant Type R-32
GWP 675.0
Charge kg 3.80
Charge TCO2Eq 2.57
Control Expansion valve
Circuits Quantity 1
Refrigerant oil Type FW68DA
Charged volume l 1.35
Defrost method Reversed cycle
Defrost control Sensor for outdoor heat exchanger temperature
Capacity control Method Inverter controlled
Safety devices Item 01 High pressure switch
02 Low pressure switch
03 Fan driver overload protector
04 Fuse
05 Compressor motor thermal protector
Pump Quantity 1
Nr of speeds PWM
Nominal Heating kPa 106.9 102.7 96.5 71.4
ESP unit
Power input W 180
Water side Heat Type Plate heat exchanger
exchanger Quantity 1
Water volume l 2.16
Water Heating Nom. l/min 26.9 (1) / 25.8 (2) 30.3 (1) / 28.2 (2) 34.4 (1) / 35.7 (2) 45.9 (1) / 45.9 (2)
flow rate
Water side Heat Insulation material EPDM type
exchanger Heater W 50.0

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 51
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09D3V3 EDLA11D3V3 EDLA14D3V3 EDLA16D3V3
Expansion vessel Volume l 8
Max. water pressure bar 4
2 Pre pressure
Heater
bar
W
1
65
Water filter Diameter perforations mm 0.8
Material Stainless steel
Water circuit Piping connections diameter inch G 1" (male)
Piping inch 1-1/4"
Piping Max. OU - Tank m 10
length
Level dif- Max. m 5
ference
Safety valve bar 3
Drain valve / fill valve Yes
Shut off valve Yes
Air purge valve Yes
Minimum water volume in the system l 20 (4)
Heater W 66.0
General Supplier/ Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Manu- Name or trademark Daikin Europe N.V.
facturer
details
Product Air-to-water heat pump Yes
descrip- Brine-to-water heat pump No
tion Heat pump combination heater No
Low-temperature heat pump No
Supplementary heater integrated Yes
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825) dB(A) 62.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating Air to Rated airflow (outdoor) m³/h 2,880 3,350 4,220 5,100
general water
unit
Other Capacity control Inverter
Pck (Crankcase heater mode) kW 0.000
Poff (Off mode) kW 0.023
Psb (Standby mode) kW 0.023
Pto (Thermostat off) kW 0.023
Inte- Type of energy input Electrical
grated
supple-
mentary
heater
Space heating Average General Annual energy kWh 5,488 6,218 6,735 7,444
climate consumption
water ηs (Seasonal % 133 130 132 130
outlet space heating
55°C efficiency)

52 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09D3V3 EDLA11D3V3 EDLA14D3V3 EDLA16D3V3
Space heating Average General Prated at -10°C kW 9.0 10.0 11.0 12.0
climate Qhe Annual ener- Gj 20 22 24 27
water
outlet
gy consumption
(GCV)
2
55°C SCOP 3.39 3.32 3.37 3.33
Seasonal space heating A++
eff. class
A Condition Cdh (Degradation heating) 1.0
(-7°CDB/-8°CWB) COPd 2.09 1.90 2.02 1.95
Pdh kW 8.5 9.3 9.4
PERd % 83.6 76.0 80.8 78.0
B Con- Cdh (Degradation heating) 1.0
dition COPd 3.28 3.25 3.28 3.27
(2°CD- Pdh kW 5.0 5.4 6.2 6.9
B/1°CWB) PERd % 131.2 130.0 131.2 130.8
C Con- Cdh (Degradation heating) 1.0
dition COPd 4.80 4.81 4.88 4.93
(7°CD- Pdh kW 4.4
B/6°CWB) PERd % 192.0 192.4 195.2 197.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 6.45 6.41 6.58 6.60
Pdh kW 5.3
PERd % 258.0 256.4 263.2 264.0
Tol (tem- COPd 1.70 1.6 4 1.70 1.67
perature Pdh kW 6.8 7.6 7.8 8.0
operat- PERd % 68.0 65.6 68.0 66.8
ing limit) TOL °C -10
WTOL °C 55
Rated Psup (at Tdesign kW 2.2 2.4 3.2 4.1
heat -10°C)
output
supple-
mentary
capacity
Tbiv COPd 1.92 1.90 2.09 2.13
(bivalent Pdh kW 8.8 9.3 9.4 10.1
tempera- PERd % 76.8 76.0 83.6 85.2
ture) Tbiv °C -8 -7 -6 -5
Cold General Annual energy kWh 7,427 8,247 8,858 9,650
climate consumption
water ηs (Seasonal % 117 119 120
outlet space heating
55°C efficiency)
Prated at -22°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 27 30 32 35
gy consumption
(GCV)
Warm General Annual energy kWh 2,921 3,184 3,792
climate consumption
water ηs (Seasonal % 162 165 168
outlet space heating
55°C efficiency)
Prated at 2°C kW 9.0 10.0 12.1

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 53
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09D3V3 EDLA11D3V3 EDLA14D3V3 EDLA16D3V3
Space heating Warm General Qhe Annual ener- Gj 11 14
climate gy consumption
2 water
outlet B Con-
(GCV)
Cdh (Degradation heating) 1.0
55°C dition COPd 2.12 2.18 2.17
(2°CD- Pdh kW 9.0 9.8
B/1°CWB) PERd % 84.8 87.2 86.8
C Con- Cdh (Degradation heating) 1.0
dition COPd 3.65 3.74 3.83
(7°CD- Pdh kW 6.2 7.6
B/6°CWB) PERd % 146.0 149.6 153.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 5.68 5.69
Pdh kW 5.0
PERd % 227.2 227.6
Tbiv COPd 2.12 2.18 2.40
(bivalent Pdh kW 9.0 9.8 11.0
tempera- PERd % 84.8 87.2 96.0
ture) Tbiv °C 2 3
Average General Annual energy kWh 3,939 4,456 4,923 5,366
climate consumption
water ηs (Seasonal % 186 182
outlet space heating
35°C efficiency)
Prated at -10°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 14 16 18 19
gy consumption
(GCV)
SCOP 4.72 4.64 4.62
Seasonal space heating A+++
eff. class
A Condition COPd 3.07 3.03 2.95 2.87
(-7°CDB/-8°CWB) Pdh kW 8.5 9.2 10.1 11.2
PERd % 122.8 121.2 118.0 114.8
B Con- Cdh (Degradation heating) 1.0
dition COPd 4.52 4.37 4.35 4.33
(2°CD- Pdh kW 4.5 5.5 6.1 6.7
B/1°CWB) PERd % 180.8 174.8 174.0 173.2
C Con- Cdh (Degradation heating) 1.0
dition COPd 6.78 6.74 6.70 6.83
(7°CD- Pdh kW 4.7 4.6 4.7
B/6°CWB) PERd % 271.2 269.6 268.0 273.2
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 8.75 8.54 8.65 8.82
Pdh kW 5.5 5.4 5.5

54 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Technical specifications EDLA09D3V3 EDLA11D3V3 EDLA14D3V3 EDLA16D3V3
Space heating Average D Condition PERd % 350.0 341.6 346.0 352.8
climate (12°CDB/11°CWB)
water
outlet
Tol (tem-
perature
COPd
Pdh kW
2.64
8.3
2.58
10.1
2.51
11.2
2.48
11.8
2
35°C operat- PERd % 105.6 103.2 100.4 99.2
ing limit) TOL °C -10
WTOL °C 35
Tbiv COPd 2.75 2.58 2.51 2.48
(bivalent Pdh kW 8.7 10.1 11.2 11.8
tempera- PERd % 110.0 103.2 100.4 99.2
ture) Tbiv °C -9 -10
Rated Psup (at Tdesign kW 0.7 0.0
heat -10°C)
output
supple-
mentary
capacity
Cold General Annual energy kWh 5,402 5,783 6,317 7,296
climate consumption
water ηs (Seasonal % 161 168 169 159
outlet space heating
35°C efficiency)
Prated at -22°C kW 10.0 11.0 12.0
Qhe Annual ener- Gj 19 21 23 26
gy consumption
(GCV)
Warm General Annual energy kWh 2,039 2,230 2,435 2,675
climate consumption
water ηs (Seasonal % 233 237 238 237
outlet space heating
35°C efficiency)
Prated at 2°C kW 9.0 10.0 11.0 12.0
Qhe Annual ener- Gj 7 8 9 10
gy consumption
(GCV)
B Con- Cdh (Degradation heating) 1.0
dition COPd 3.36 3.30 3.45 3.30
(2°CD- Pdh kW 9.0 10.3 10.8 11.9
B/1°CWB) PERd % 134.4 132.0 138.0 132.0
C Con- Cdh (Degradation heating) 1.0
dition COPd 5.59 5.70 5.77 5.64
(7°CD- Pdh kW 5.9 6.7 7.4 8.1
B/6°CWB) PERd % 223.6 228.0 230.8 225.6
D Condition Cdh (Degradation heating) 1.0
(12°CDB/11°CWB) COPd 7.87 7.73
Pdh kW 5.2
PERd % 314.8 309.2
Tbiv COPd 3.36 3.30 3.45 3.30
(bivalent Pdh kW 9.0 10.3 10.8 11.9
tempera- PERd % 134.4 132.0 138.0 132.0
ture) Tbiv °C 2
Control systems Class of temperature control VI
Contribution to seasonal space heating % 4
efficiency

Electrical specifications EDLA09D3V3 EDLA11D3V3 EDLA14D3V3 EDLA16D3V3


Compressor Starting method Inverter
Pump Type PWM
Compressor com- Main Phase 1~
ponent power Voltage V 230
supply
Voltage Min. % -10
range Max. % 10

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 55
Daikin Altherma low temperature monobloc

2 Specifications
1 - 4 EDLA09-16D3W1, EDLA09-16D3V3

Electrical specifications EDLA09D3V3 EDLA11D3V3 EDLA14D3V3 EDLA16D3V3
Hydraulic compo- Back-up Type 3V3
nent heater Power Phase 1~
2 current supply Frequency
Voltage
Hz
V
50
230
Running Back-up heater A 13.0
current
Voltage Min. % -10
range Max. % 10
Wiring Type of wires Select diameter and type according to national and local regulations
connec-
tions
Power supply Name V3
Phase 1~
Frequency Hz 50
Voltage V 230
Voltage range Min. % -10
Max. % 10
Current Maxi- Heating A 30.8
mum
running
current
Recommended fuses A 32
Wiring connec- Optional Quantity 3G
tions domestic Type of wires Minimum 2.5 mm²
hot water
tank +
Q2L
R5T Quantity 2
Type of wires Wire included in option EKHWS*
For con- Quantity 2
nection Remark Minimum 0.75 mm²
with R6T
A3P Quantity 4
Type of wires Select diameter and type according to national and local regulations
M2S Quantity 2
Type of wires Select diameter and type according to national and local regulations
M3S Quantity 3
Type of wires Select diameter and type according to national and local regulations
Quantity 2
Type of wires Wire included in option EKFLSW1
Wiring connec- For Quantity 2G
tions power Remark See installation manual outdoor unit
supply
For con- Quantity 4
nection Remark O.75 mm² till 1.25 mm² (max length 200 m)
with user Type of wires 0,75 ~1,25 mm² (P1P2)
interface
Prefer- Quantity Power: 2
ential Remark Power 6.3A
kWh rate
power
supply
Domestic Quantity 3
hot water Remark Minimum 0.75 mm²
pump
Cable require- Cooling/ Maximum running current A 0.3
ments Heating
output
(1)Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) |
(2)Condition: Ta DB/WB 7°C/6°C - LWC 45°C (Dt=5°C) |
(3)For more details, see operation range drawing |
(4)Depends on operation mode, refer to installation manual. |
Cooling: EW 12°C; LW 7°C; ambient conditions: 35°CDB |
Cooling: EW 23°C; LW 18°C; ambient conditions: 35°CDB |
According to EN14825

56 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

3 Electrical data
3 - 1 Electrical Data

EBLA09-16(3DW1-3DV3) / EDLA09-16(3DW1-3DV3) Electrical specifications
Type 3V
Capacity setting kW 3
Capacity stage · · 1 3
Capacity stage ·1· kW 3
Capacity stage ·2· kW -

Minimum time delay between stages Note ·3·


Backup heater
Power supply Phase 1~
(1) Frequency Hz 50
Voltage V 230 +-10%
Nominal running current A 13
Ω -
Current Zmax (backup heater) (2)
Complex -
Minimum Ssc value kVA -

(1) The above-mentioned power supply of the hydrobox is for the backup heater only.

In accordance with EN/IEC 61000-3-11, it may be necessary to consult the distribution network operator to ensure that
(2)
the equipment is connected only to a supply with Zsys ≤ Zmax.

European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public
EN/IEC 61000-3-11 low-voltage supply systems for equipment with rated current ≤ 75 A.
Notes

European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to
EN/IEC 61000-3-12 public low-voltage systems with input current > 16 A and ≤ 75 A per phase.

Zsys System impedance

Note ·3· Backup heater ·(3V)· Minimum time delay between stages
Capacity [kW]
·1· min. ·10· min.

Stage ·1·
Time
4D128962

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 57
Daikin Altherma low temperature monobloc

4 Combination table
4 - 1 Combination Table

EBLA09-16(DW1-DV3) / EBLA09-16(3DW1-3DV3) / EDLA09-16(DW1-DV3) / EDLA09-16(3DW1-3DV3)

4 Kit availability for ·E(B/D)LA*DA*·


E(B/D)LA(09/11/14/16)DA
No backup heater Backup heater
Reference Description Notes Heating only Reversible Heating only Reversible
EDLA(09/11/14/16) EBLA(09/11/14/16) EDLA(09/11/14/16) EBLA(09/11/14/16)
DA(V3/W1) DA(V3/W1) DA3(V3/W1) DA3(V3/W1)
EKRP1HBAA Digital I/O PCB (1) o o o o
EKRP1AHTA Demand PCB o o o o
BRC1HHDA* Remote user interface o o o o
BRP069A78 WLAN cartridge (2) o o o o
EKRELSG Relay for Smart Grid o o o o
KRCS01-1 Remote indoor sensor (3) o o o o
EKRSCA1 Remote sensor for outdoor (3) o o o o
EKPCCAB4 PC cable kit o o o o
EKCC8-W Universal centralised user interface o o o o
EKHY3PART Third-party tank connection kit for thermistor pocket (4) (6) o o o o
EKHY3PART2 Third-party tank connection kit for thermostat contact (5) (6) o o o o
EKLBUHCB6W Backup heater kit (7) o o - -
EKMBHBP1 Valve kit (7) - o - -
EKFLSW1 Flow switch (8) o o o o
AFVALVE1 Freeze protection valve o o o o
FWXV10-15-20ATV3* Heat pump convector Floor standing unit o o o o
FWXT10-15-20ATV3* Heat pump convector Wall mounted type o o o o
FWXM10-15-20ATV3* Heat pump convector Conceiled ceiling o o o o
EKHWS150D3V3 Domestic hot water tank ·LT 150 | 1~230V· o o o o
EKHWS180D3V3 Domestic hot water tank ·LT 180 | 1~230V· o o o o
EKHWS200D3V3 Domestic hot water tank ·LT 200 | 1~230V· o o o o
EKHWS250D3V3 Domestic hot water tank ·LT 250 | 1~230V· o o o o
EKHWS300D3V3 Domestic hot water tank ·LT 300 | 1~230V· o o o o
EKHWSU150D3V3 Domestic hot water tank ·LT 150 | 1~230V· (only for UK) (9) o o o o
EKHWSU180D3V3 Domestic hot water tank ·LT 180 | 1~230V· (only for UK) (9) o o o o
EKHWSU200D3V3 Domestic hot water tank ·LT 200 | 1~230V· (only for UK) (9) o o o o
EKHWSU250D3V3 Domestic hot water tank ·LT 250 | 1~230V· (only for UK) (9) o o o o
EKHWSU300D3V3 Domestic hot water tank ·LT 300 | 1~230V· (only for UK) (9) o o o o
EKHWP300B Domestic hot water tank ·HT 300· (10) (11) o o o o
EKHWP500B Domestic hot water tank ·HT 500· (10) (11) o o o o
EKHWP300PB Domestic hot water tank ·HT 300· (10) (11) o o o o
EKHWP500PB Domestic hot water tank ·HT 500· (10) (11) o o o o
BZKA7V3 Bizone kit o o o o
EKRTWA Wired room thermostat o o o o
EKRTR1 Wireless room thermostat o o o o
EKRTETS External temperature sensor option kit (12) o o o o
EKWUFHTA1V3 Multi zoning kit o o o o

Notes

(1) Additional relays to allow bivalent control in combination with an external room thermostat are field-supplied.
(2) This option cannot be installed in certain countries. Refer to the country compliance overview of the option.
(3) Only 1 remote sensor can be connected: indoor OR outdoor sensor.
(4) ·EKHY3PART· can be used if you have a tank in which you can insert a thermistor.

(5) ·EKHY3PART2· can be used if you have a tank in which you cannot insert a thermistor.

(6) Conditions for third-party tank


Third-party with identical specifications as ·EKHWS*·
Coil surface >·1.05·m² and <·3.7·m²
Tank thermistor and booster heater above heat pump coil.

(7) Necessity to install a bypass kit ·EKMBHBP1· to avoid sweat on the BUH, when the BUH is installed in combination with a reversible model.
(8) ·EKFLSW1· is obligatory for Monoblock & Mini-chiller in case Glycol is used.
(9) Only possible in combination with ·EKEXPVES·
(10) Domestic hot water tank with solar connection
Dedicated connection kit available.
Other options EKRSP4A* Solar pump station
For the combination with ·EKHWP*·, refer to the combination table of ·EKHWP*·.
(11) The installation of ·EKBH3S*· is mandatory.
As backup or for tank preheating.
For details, see the installer reference guide.
(12) Can only be used in combination with the wireless room thermostat.

Remark
Other combinations than mentioned in this combination table are prohibited.

4D128949B

58 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

5 Capacity graphs
5 - 1 Cooling Capacity Graphs

EBLA09-16(DW1-DV3) / EBLA09-16(3DW1-3DV3)
Maximum cooling capacity
5
CCmax [kW]
CCmax [kW]
EBLA09DA* EBLA14DA*
20 25

20
15

15

10
10

5 5
20 25 30 35 40 45 20 25 30 35 40 45

Tamb [°C] Tamb [°C]

LWE 7°C LWE 13°C LWE 18°C LWE 7°C LWE 13°C LWE 18°C

CCmax [kW] CCmax [kW]


EBLA11DA* EBLA16DA*
20 25

20
15

15

10
10

5 5
20 25 30 35 40 45 20 25 30 35 40 45
Tamb [°C] Tamb [°C]

LWE 7°C LWE 13°C LWE 18°C LWE 7°C LWE 13°C LWE 18°C

Symbols
CCmax Cooling capacity at maximum operating frequency, measured according to EN 14511.

LWE Leaving water evaporator temperature [°C]


Tamb Ambient temperature [°C DB]

Conditions
Cooling capacity
Capacity according to standard EN 14511 and valid for chilled water range ΔT = 3~8°C.

Notes
The capacity and power input is valid for ·V3· models at ·230·V and for for ·W1· models at ·400·V.

The capacity and the power input are at maximum operation.

4D128952

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 59
Daikin Altherma low temperature monobloc

5 Capacity graphs
5 - 2 Heating Capacity Graphs

E(B‐D)LA09‐16DV3_DW1
E(B‐D)LA09‐16D3V3_D3W1
5 Maximum heating capacity - integrated value

HCmax  HCmax 
[kW] E(B/D)LA09DA* [kW] E(B/D)LA16DA*
16 20
14 18
12 16
10 14
8 12
6 10
4 8
‐20 ‐15 ‐10 ‐5 0 5 10 15 6
Tamb [°C]
4
‐20 ‐15 ‐10 ‐5 0 5 10 15
LWC 35°C LWC 45°C LWC 55°C
Tamb [°C]

HCmax  LWC 35°C LWC 45°C LWC 55°C


[kW] E(B/D)LA11DA*
18
16
14
12
10
8
6
4
‐20 ‐15 ‐10 ‐5 0 5 10 15
Tamb [°C]

LWC 35°C LWC 45°C LWC 55°C

HCmax 
[kW] E(B/D)LA14DA*
18
16
14
12
10
8
6
4
‐20 ‐15 ‐10 ‐5 0 5 10 15
Tamb [°C]
LWC 35°C LWC 45°C LWC 55°C

Symbols
HCmax Heating capacity for maximum load, measured according to EN 14511
LWC Leaving water condensor temperature [°C]
Tamb Ambient temperature [°C DB]

Conditions
Heating capacity
Capacity according to standard EN 14511 and valid for heated water range ΔT = 3~8°C.

Notes
The capacity and power input is valid for ∙V3∙ models at ∙230∙V and for for ∙W1∙ models at ∙400∙V.
The capacity and the power input are at maximum operation.
 4D128951B

60 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

6 Capacity tables
6 - 1 Certification Programs

E(B‐D)LA09‐16DV3_DW1
E(B‐D)LA09‐16D3V3_D3W1
6

Rated data for certification programmes ‐ heating mode

  E(B/D)LA09DA(V3/3V3) E(B/D)LA11DA(V3/3V3) E(B/D)LA14DA(V3/3V3) E(B/D)LA16DA(V3/3V3) E(B/D)LA09DA(W1/3W1) E(B/D)LA11DA(W1/3W1) E(B/D)LA14DA(W1/3W1) E(B/D)LA16DA(W1/3W1) Used for:


Tamb EWC LWC HC COP HC COP HC COP HC COP HC COP HC COP HC COP HC COP
[°C] [°C] [°C] [kW] [‐] [kW] [‐] [kW] [‐] [kW] [‐] [kW] [‐] [kW] [‐] [kW] [‐] [kW] [‐]
10/9 30 35 9,20 5,32 9,20 5,32 9,20 5,32 9,20 5,32 9,20 5,32 9,20 5,32 9,20 5,32 9,20 5,32 BAFA
7/6 30 35 9,37 4,91 10,56 4,83 12,00 4,87 16,00 4,53 9,37 4,91 10,56 4,83 12,00 4,87 16,00 4,53 Keymark, EHPA, BAFA, GET
2/1 (30) 35 7,64 3,79 9,00 3,65 10,80 3,50 12,00 3,30 7,64 3,79 9,00 3,65 10,80 3,50 12,00 3,30 EHPA, GET
2/1 (30) 35 6,29 4,01 6,29 4,01 6,29 4,01 6,29 4,01 6,29 4,01 6,29 4,01 6,29 4,01 6,29 4,01 BAFA
‐7/‐8 (30) 35 8,00 2,81 8,75 2,92 9,30 2,86 10,60 2,70 8,00 2,81 8,75 2,92 10,50 3,00 12,30 2,87 EHPA, BAFA, GET
7/6 40 45 9,00 3,71 9,82 3,66 12,45 3,64 16,00 3,51 9,00 3,71 9,82 3,66 12,45 3,64 16,00 3,51 EHPA
‐2/‐3 (40) 45 9,00 2,35 10,86 2,35 11,30 2,30 12,00 2,30 9,00 2,35 10,86 2,35 12,37 2,58 13,93 2,46 MCS
‐7/‐8 (40) 45 7,76 2,22 8,72 2,35 8,98 2,29 10,49 2,10 7,76 2,22 8,72 2,35 8,98 2,29 10,49 2,10 EHPA
7/6 47 55 9,57 2,91 10,64 2,94 11,87 2,89 15,63 2,75 9,57 2,91 10,64 2,94 11,87 2,89 15,63 2,75 Keymark, EHPA, GET
‐7/‐8 47 55 7,13 1,80 7,89 1,82 8,47 1,82 8,87 1,78 7,13 1,80 7,89 1,82 8,47 1,82 8,87 1,78 GET, EHPA

Rated data for certification programmes ‐ cooling mode
Nominal cooling capacity
EBLA09DA(3)(V3/W1) EBLA11DA(3)(V3/W1) EBLA14DA(3)(V3/W1) EBLA16DA(3)(V3/W1) Used for:
Tamb EWE LWE CC EER CC EER CC EER CC EER
[°C] [°C] [°C] [kW] [‐] [kW] [‐] [kW] [‐] [kW] [‐]
35 23 18 9,10 5,34 11,51 5,31 12,68 5,04 15,33 4,74 General DACI
35 12 7 9,35 3,35 11,59 3,26 12,82 3,16 14,01 3,06 Keymark DAPT

Seasonal data ‐ cooling LWE 7°C Low temperature


Application
EBLA09DA(3)(V3/W1) EBLA11DA(3)(V3/W1) EBLA14DA(3)(V3/W1) EBLA16DA(3)(V3/W1)
Pdes [kW] 9,3 11,5 12,8 14,000
SEER [‐] 5,62 5,79 5,71 5,59
ηs,c [‐] 222 229 226 221
QCE [kWh/annum] 993 1190 1340 1500

Rated data for certification programmes ‐ standby power consumption

E(B/D)LA(09/11/14/16)DA(3)(V3/W1) Used for:
Standby power input [W] 23 Taux

Symbols
HC Heating capacity measured according to EN 14511
CC Cooling capacity, measured according to ∙EN 14511∙.
COP/EER Coefficient of Performance/Energy efficiency ratio according to EN 14511.
EWC Entering water condenser temperature [°C]
LWC Leaving water condensor temperature [°C]
EWE Entering water evaporator temperature [°C]
LWE Leaving water evaporator temperature [°C]
Tamb Ambient temperature [°C DB/WB]
Pdes Nominal capacity value at design temperature [kW]
SEER Seasonal energy efficiency ratio according to ∙EN14825∙
ηs,c Seasonal space cooling energy efficiency according to ∙EN14825∙
QCE Annual energy consumption for cooling according to ∙EN14825∙

Rated data for certification programmes ‐ domestic hot water performance

Outdoor unit E(B/D)LA(09/11/14/16)DA(3)V3 E(B/D)LA(09/11/14/16)DA(3)W1


Domestic hot water tank EKHWS(U)250D3V3 EKHWS(U)300D3V3 EKHWS(U)250D3V3 EKHWS(U)300D3V3
Tapping pattern XL XL XL XL
Application Average climate (design temperature: ∙7∙°C )
COPDHW [] 2,51 2,73 2,69 2,87
ηwh [%] 102,9% 112,0% 110,1% 117,5%
AEC [kWh] 1628 1495 1521 1426
Application Colder climate (design temperature: ∙2∙°C )
COPDHW [] 2,04 2,24 2,20 2,35
ηwh [%] 83,3% 91,8% 89,8% 96,1%
AEC [kWh] 2011 1826 1865 1744
Application Warmer climate (design temperature: ∙14∙°C )
COPDHW [] 2,96 3,23 3,12 3,40
ηwh [%] 121,8% 132,9% 128,0% 139,5%
AEC [kWh] 1375 1261 1309 1200

Symbols
COPDHW Domestic hot water COP
According to EN16147.
ηwh Ƞwh (Water heating energy efficiency)
AEC Annual energy consumption [kWh]

 3D130658B

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 61
Daikin Altherma low temperature monobloc

7 Dimensional drawings
7 - 1 Dimensional Drawings

EBLA09-16(DW1-DV3) / EDLA09-16(DW1-DV3)
Water in connection ·1"M·
7
1

30
Water out connection ·1"M·
7 2
3 Wiring intake (low voltage wiring)
4 Wiring intake (high voltage wiring)
485

460
5 Wiring intake (power supply)
6 Backup heater power supply
171 758 300 7 Shut-off valve / filter (included accessory)

1378 30 70 10 13

12

14
11
3
867

2
1 9
26

76 90
65 70
Total volume = ·0.598· m³ 5 6
8
4
15 16 16 16

Drain valve water circuit


111

8
214
349

9 Flow sensor
408
413

10 Expansion vessel
11 Space heating water pressure sensor
15 44
48 12 Safety valve
16 15 16 15 16
108 13 Manual air purge valve
289 14 Pump
452
614 15 Drain outlet
777 16 ·6· holes for anchor bolts

3D129505A

EBLA09-16(3DW1-3DV3) / EDLA09-16(3DW1-3DV3)
1 Water in connection ·1"M·
7
2 Water out connection ·1"M·
30

3 Wiring intake (low voltage wiring)


4 Wiring intake (high voltage wiring)
485

460

5 Wiring intake (power supply)


6 Backup heater power supply
171 758 300 7 Shut-off valve / filter (included accessory)
30

1378 70 10 13 12

14

15 11
3
867

2
1 9
26

76 90

65 70 8
5 6
4
Total volume = ·0.598· m³
8 Drain valve water circuit
16 17 17 17 9 Flow sensor
10 Expansion vessel
111
214

11 Backup heater
349
408
413

12 Automatic air purge valve


16 44 13 Space heating water pressure sensor
48 17 16 17 16 17 14 Safety valve
108
289 15 Pump
452
614
16 Drain outlet
777 17 ·6· holes for anchor bolts

3D128950A

62 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

7 Dimensional drawings
7 - 1 Dimensional Drawings

E(B‐D)LA09‐16DV3_DW1
E(B‐D)LA09‐16D3V3_D3W1

160 32.7 50 30 30

34.8
135.3

60
1

40.4
2

36.5
Required installation space
≥ 30

≥ 100 ≥5

1 USB Connector
2 WLAN cartridge
≥ 30

3D132732

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 63
Daikin Altherma low temperature monobloc

8 Centre of gravity
8 - 1 Centre of Gravity

EBLA09-16(DW1-DV3) / EBLA09-16(3DW1-3DV3) / EDLA09-16(DW1-DV3) / EDLA09-16(3DW1-3DV3)

395
657 234
171 758 300 485

4D128956

64 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
9
Screw connection Brazed connection
9 - 1

Quick coupling Flare connection

1N~ 3N~
* *
Heating
9 Cooling 15
10
16
12 11

21
Piping Diagrams

R4T
1 1N~ 3N~
8 15
** **
** 23
B1PW 19
Leaving water 27
25
EBLA09-16(DW1-DV3) / EDLA09-16(DW1-DV3)

R1T
18
Piping diagrams

20
6 34

5 36 35 34
R1T S1NPH
*

7 33
S1PH 32 17
28 R5T

R2T

R3T
4 24

22
Entering water
13 14
2 31
R4T R3T

S1PL
1 29
30
26
3

1 Screw connection ·1"M· 15 Filter 31 Compressor


2 R4T - Inlet water thermistor 16 Rectifier 32 R2T - Thermistor (discharge)
3 Drain valve water circuit 17 Economiser 33 High pressure switch
4 Plate heat exchanger 18 Heat sink 34 Muffler
5 R1T - Outlet water heat exchanger thermistor 19 Electronic expansion valve (main) 35 Pressure sensor
6 Flow sensor 20 Electronic expansion valve (injection) 36 Gas stop valve with service port
7 Expansion vessel 21 R4T - Thermistor (heat exchanger)
8 Space heating water pressure sensor 22 Distributor
9 Safety valve 23 Heat exchanger
10 Manual air purge valve 24 R5T - Thermistor (heat exchanger middle)
11 Pump 25 R1T - Outdoor air
12 Connection for optional flow switch 26 Service port ·5/16"· flare
13 R3T - Refrigerant liquid side thermistor 27 4-way valve
14 Liquid stop valve with service port 28 R3T - Thermistor (suction)
29 Accumulator
30 Low pressure switch

3D128954A

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

65
9

66
9
Screw connection Brazed connection
9 - 1

Quick coupling Flare connection

1N~ 3N~
* *

11 Heating
12 Cooling 17
9
18

B1PW
14 13 10
R2T
23
Piping Diagrams

R4T
1 1N~ 3N~
17 ** ** **
25
8 21
Leaving water 29
27

R1T
20
Piping diagrams

22
6 36
EBLA09-16(3DW1-3DV3) / EDLA09-16(3DW1-3DV3)

5 38 37 36
R1T S1NPH *

7 35
S1PH 34 19
R5T

R2T
30

R3T
4 26

24
Entering water
15 16
2 33
R4T R3T

S1PL
1 31
32
28
3

1 Screw connection ·1"M· 17 Filter 33 Compressor


2 R4T - Inlet water thermistor 18 Rectifier 34 R2T - Thermistor (discharge)
3 Drain valve water circuit 19 Economiser 35 High pressure switch
4 Plate heat exchanger 20 Heat sink 36 Muffler
5 R1T - Outlet water heat exchanger thermistor 21 Electronic expansion valve (main) 37 Pressure sensor
6 Flow sensor 22 Electronic expansion valve (injection) 38 Gas stop valve with service port
7 Expansion vessel 23 R4T - Thermistor (heat exchanger)
8 Backup heater 24 Distributor
9 Automatic air purge valve 25 Heat exchanger
10 R2T - Outlet water backup heater thermistor 26 R5T - Thermistor (heat exchanger middle)
11 Space heating water pressure sensor 27 R1T - Outdoor air
12 Safety valve 28 Service port ·5/16"· flare
13 Pump 29 4-way valve
14 Connection for optional flow switch 30 R3T - Thermistor (suction)
15 R3T - Refrigerant liquid side thermistor 31 Accumulator
16 Liquid stop valve with service port 32 Low pressure switch

3D128953A

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc
: Option
X14M, X15M : Main terminal

: Earth wiring : Wiring depending


15 on modelAltherma low temperature monobloc
Daikin
: Wire number 15
: switch box
: Field supply
10 Wiring diagrams 1 : Several wiring : PCB
10 - 1 Notes & Legend possibilities
Optional backup heater configuration :
 (only for EKLBUHCB6W1)
1N~, 230V, 3kW or 6kW
3N~, 400V, 6kW or 9kW
EBLA09-16(DW1-DV3) / EBLA09-16(3DW1-3DV3) / EDLA09-16(DW1-DV3) / EDLA09-16(3DW1-3DV3)
X1M
X1M (3) BUH kit switch box (4) Legend
X1M Translation can be found
in the installation manual.
15
15
(2) Notes
15 (3) BUH kit switch box (4) Legend 10
X1M
X1M Part n° Description
X1M
X14M, X15M : Main terminal Part n° Description
X14M E1H BUH element
E1H BUH(1 element
kW) (1kW)
: Earth wiring
15
15 E2H E2H
BUH element BUH(2 element
kW) (2kW)
15 : Wire number 15
**/12.2 : Field supply F1B F1B
OvercurrentOvercurrent
fuse BUH fuse BUH
**/12.2
**/12.2
1 K2M K1M F1T Thermal fuse BUH
11 F1T Thermal fuse BUH
: Several wiring possibilities F1U Fuse
Q1L F1U Fuse
K1M Contactor BUH (Step 1)
**/12.2
**/12.2 K1M K2M
Contactor BUHContactor
(StepBUH1) (Step 2)
**/12.2
1 K5M Safety contactor
1
1 : Option
K5M K2M Contactor BUH (Step 2) BUH
Q3DI # Earth leakage circuit breaker
K5M Safety contactor BUH
Q1L Thermal protector BUH
Q3DI # R2T
Earth leakage circuit
Outlet BUHbreaker
thermistor
: Wiring depending on model Q1L X*M TerminalBUH
Thermal protector strip
F1B # :Outlet
field supply
X15M R2T BUH thermistor

: switch box X*M Terminal strip

EKLBUHCB6W1 # : field supply

: PCB

Optional backup heater □ 1N~, 230V, 3kW or 6kW


configuration: (only for
EKLBUHCB6W1)
□ 3N~, 400V, 6kW or 9kW

Description Unit name Drawing number

Daikin Europe N.V. Notes & Legend - External BUH option MB & MC GQI TBM 4D124072

4D124072B

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 67
Daikin Altherma low temperature monobloc

10 Wiring diagrams
10 - 2 Control Circuit

EBLA09-16(DW1-DV3) / EBLA09-16(3DW1-3DV3) / EDLA09-16(DW1-DV3) / EDLA09-16(3DW1-3DV3)

A11P
10
X1B
X5M.11 4
X22
X5M.12 3 P1P2
+
X5M.16 2
PSU
X5M.15 1
30

CAN X3A

P1M
USB X4

WLAN SD CARD X10


Cartridge SW1 SW2
SW3 SW4 SW5

X9
1
2
3 WLAN UART
4 Interface
5

X5
1
2
3 Debug UART
4 Interface
5

4D124072B

68 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
: Field supply 1P
1 : Several wiring possibilities Part n°
A1P
A2P
: Option Daikin Altherma
: Notlow temperature
mounted in switch box monoblocA3P
C* (A*P)
BS* (A1P)
: Wiring depending on model : PCB DS1 (A1P)

10 Wiring diagrams NOTES:


1. Refer to the wiring diagram sticker (on the back of the front plate) for how to use the BS1~BS4
F1U, F3U~F4U (A2P)
F2U (A2P)
F6U (A1P)

10 - 3 Compressor - Notes & Legend and DS1 switches.


H1~7P (A1P)

2. When operating, do not short-circuit protection device Q1, S1PH and S1PL. HAP (A1P)

 3. Refer to the combination table and the option manual for how to connect the wiring to X6A, X41A and X77A.
4. Colours: BLK:black; RED:red; BLU:blue; WHT:white; GRN:green; BRN:brown; YLW:yellow; ORG:orange K1R (A1P)

X1M K10R (A1P)


EBLA09-16(DW1-DV3)
X1M
X1M / EBLA09-16(3DW1-3DV3) / EDLA09-16(DW1-DV3) / EDLA09-16(3DW1-3DV3)
5. Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of
all switches: OFF
K11M (A1P)
K14~15R (A2P)
L*R (A1P)

15
15
M1C
15 M1F
X1M
NOTES to go through before starting the unit POSITION IN SWITCH BOX
POSITION IN SWITCH BOX PS (A1P)
Q1 10
Q1DI #
X1M
X1M : Main terminal 1PH UNIT 3PH UNIT R1~5 (A*P)
15 R1T
: Earth wiring R2T
**/12.2
15 : Field supply R3T
**/12.2
**/12.2 A3P
1 R4T
11 R5T

: Several wiring possibilities A1P A1P


R11T (A1P)
RC (A2P)
A2P A2P
S1NPH
**/12.2 S1PH
1 S1PL
**/12.2 : Option X1M X1M
TC (A2P)
V*D (A1P)
1
Front Rear Front Rear V1R (A1P)
V2R (A1P)
V*T (A1P)

: Wiring depending on model X1M


X*A, X*Y (A*P)
Y1E, Y3E
Y1S

Position of compressor terminal Z*C

: Not mounted in switch box Z*F (A*P)

: PCB

Description Unit name


NOTES
Daikin Europe N.V. Compressor - Notes + Legend MB & MC GQ
1. Refer to the wiring diagram sticker (on the back of the front plate) for how to use the BS1~BS4 and DS1 switches.
2. When operating, do not short-circuit protection device Q1, S1PH and S1PL.
3. Refer to the combination table and the option manual for how to connect the wiring to X6A, X41A and X77A.
4. Colours: BLK:black; RED:red; BLU:blue; WHT:white; GRN:green; BRN:brown; YLW:yellow; ORG:orange
5. Confirm the method of setting the selector switches (DS1) by service manual. Factory setting of all switches: OFF

LEGEND
1PH UNIT 3PH UNIT
Part n° Description Part n° Description
A1P Printed circuit board (main) A1P Printed circuit board (main)
A2P Printed circuit board (noise filter) A2P Printed circuit board (noise filter)
A3P Printed circuit board (flash) C* (A1P) Capacitor
C* (A*P) Capacitor BS* (A1P) Push-button switch
BS* (A1P) Push-button switch DS1 (A1P) Dipswitch
DS1 (A1P) Dipswitch F1U, F3U (A2P) Fuse T 6,3 A 250 V
F1U, F3U~F4U (A2P) Fuse T 6,3 A 250 V F4U, F5U (A2P) Fuse T 30 A 500 V
F2U (A2P) Fuse T 56 A 250 V F7U (A1P) Fuse T 5 A 250 V
F6U (A1P) Fuse T 5 A 250 V HAP (A1P) Light emitting diode (service monitor is green)
H1~7P (A1P) Indication light emitting diode (service monitor is orange) K1R (A1P) Magnetic relay (Y1S)
HAP (A1P) Light emitting diode (service monitor is green) K5~8R (A1P) Magnetic relay
K1R (A1P) Magnetic relay (Y1S) K*M (A1P) Magnetic relay (main)
K10R (A1P) Magnetic relay L*R (A*P) Reactor
K11M (A1P) Magnetic relay (main) M1C Compressor motor
K14~15R (A2P) Magnetic relay M1F Fan motor
L*R (A1P) Reactor PS (A1P) Switching power supply
M1C Compressor motor Q1 Thermal overcurrent protector
M1F Fan motor Q1DI # Earth leakage circuit breaker (30mA)
PS (A1P) Switching power supply R1~9 (A1P) Resistor
Q1 Thermal overcurrent protector R1T Thermistor (air)
Q1DI # Earth leakage circuit breaker (30mA) R2T Thermistor (discharge)
R1~5 (A*P) Resistor R3T Thermistor (suction)
R1T Thermistor (air) R4T Thermistor (distribution pipe)
R2T Thermistor (discharge) R5T Thermistor (heat exchanger middle)
R3T Thermistor (suction) R11T (A1P) Thermistor (fin)
R4T Thermistor (distribution pipe) RC (A1P) Signal receiver circuit
R5T Thermistor (heat exchanger middle) S1NPH Pressure sensor
R11T (A1P) Thermistor (fin) S1PH High pressure switch
RC (A2P) Signal receiver circuit S1PL Low pressure switch
S1NPH Pressure sensor SEG* (A1P) 7-segment display
S1PH High pressure switch TC (A1P) Signal transmission circuit
S1PL Low pressure switch V*D (A1P) Diode
TC (A2P) Signal transmission circuit V1~2R (A1P) Diode module
V*D (A1P) Diode V3~5R (A1P) Power module
V1R (A1P) Power module X1M Terminal strip
V2R (A1P) Diode module X*A, X*Y (A*P) Connector
V*T (A1P) IGBT Y1E, Y3E Electronic expansion valve
X1M Terminal strip Y1S Solenoid valve (4-way valve)
X*A, X*Y (A*P) Connector Z*C Noise filter (ferrite core)
Y1E, Y3E Electronic expansion valve Z*F (A*P) Noise filter
Y1S Solenoid valve (4-way valve)
* : optional # : field supply
Z*C Noise filter (ferrite core)
Z*F (A*P) Noise filter
4D124072B

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 69
Daikin Altherma low temperature monobloc

10 Wiring diagrams
10 - 4 Compressor - Single phase

EBLA09-16(DW1-DV3) / EBLA09-16(3DW1-3DV3) / EDLA09-16(DW1-DV3) / EDLA09-16(3DW1-3DV3)

10 Z7C C4 Z1C RED


F2U F4U A2P
X1M N=1 + N=2 LA

Z1F

Z3F
F1U
K15R
L
N C2 C3 R3
GRN/YLW + + X803A X7YA X7Y X1M
Z5F Z4F 1 BLK 1 BLK
3 2
1 A1P/X19A.1
BLU WHT WHT
Z6C 2 A1P/X19A.3

TC
NA 5 RED 3 RED
N=3 3 A1P/X19A.5
OUTDOOR
GRN

E2 Z2C Hydro

Z2F
K14R N=2

RC
R4
F3U
A3P 3 1 1 2 3 4 5 6 7 8 9 10
E11 L1 N
LB NB X98A E3 X802A
GRN

GRN
RED

BLU
R11T R1T R2T R3T R4T R5T
Q1DI Z3C Z5C - t° - t° - t° - t° - t° - t°
N=2 N=1
L N PE
A1P
1N~, 50 Hz LC NC X99A X801A X111A X11A X12A
3 1 1 2 1 2 3 1 2 3 4 5 6 7 8
220 - 240 V AC K10R 1 2 3 4 5 6 7 8 9 10

K11M see note 3


X6A
K1R 1
R1 1 2 1 2 1 2 1 2 2
Z6F X806A X31A X32A X25A 3
E1 X804A
Z10C 4
1
N=4 V2R 5
2 P< P> Y1S
GRN

6
K13R X805A S1PL S1PH 7
L1R L2R L3R see note 2 see note 2
1 8
2 9
V4D Q1 10
R5 see note 2 11
12
V3T PS
see note 3
V2T H1P H2P H3P H4P H5P H6P H7P X41A
1
R2 BS1 BS2 BS3 BS4 DS1 2
V1T F6U HAP ON
3
OFF 1 2
V1D V2D V3D 4
V1R 5
C1
+ 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4
U V W X106A X22A X21A X17A
WHT
RED

BLK

Z4C
N=5

U V W
Y3E M Y1E M
MS M1C M1F MS S1NPH
3~ 3~ Injection Main
OUTDOOR
4D124072B

70 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

10 Wiring diagrams
10 - 5 Compressor - Three phase

EBLA09-16(DW1-DV3) / EBLA09-16(3DW1-3DV3) / EDLA09-16(DW1-DV3) / EDLA09-16(3DW1-3DV3)

L1
RED

WHT
F4U F1U A2P BLK

WHT
X7YA X7Y
1
2
BLK

WHT
X1M
1 A1P/X19A.1
10
L2 L1A 2 A1P/X19A.3

Z2F
BLK RED 3 RED
L3 3 A1P/X19A.5
OUTDOOR
N BLU
L2A F5U
Hydro
GRN/YLW
Z1C L3A
X1M N=1 NA

Z3F
Z2C GRN
Z1F
E1
N=5
L1R R1T R2T R3T R4T R5T R11T
F3U
- t° - t° - t° - t° - t° - t°
Z4F

L1B
L2B
L3B
1 2 1 2
X803A X77A
X602 X601 1 3 5 see note 3 1 2 1 2 3 1 2 3 4 5 6 7 8 1 2
WHT X11A X12A X111A
RED

BLK
Z3C X801A
Q1DI N=1 1
2
1 2 1 2 1 2
L1 L2 L3 N PE
A1P K7R X31A X32A X33A
3N~, 50 Hz X802A TC
+
S1PL S1PH Q1
L1C
L2C
L3C

380 - 415 V AC + t° 1 2

C5 P< P> see note 3


RC
K1M K2M see note 2 see note 2 see note 2
X6A
L5R X804A
1 1
K3M L4R 2 2
Z5F

3
R5 K6R
L3R X805A 4
1 5
2 6
V1R
V5R K5R + t° V3D Y1S 7
L2R K8R 8
9
E
GRN

X25A 10
R7 V2R PS
C6 C7 2 1 11
C1 + + 12
+
EB DS1 C4 K1R
GRN

see note 3
ON +
OFF 1 2 X41A
R8 R9 HAP
1
F7U R6 2
EC R4
GRN

3
V1D C2 C3 4
BS1 BS2 BS3
+ + V4R 5
V2D V3R SEG1 SEG2 SEG3
1 2 3 4 1 2 3 1 2 3 4 5 6 1 2 3 4 5 6
R1 R2 R3 U V W X17A X108A X22A X21A
WHT

Z5C Z4C
RED

BLK

N=5 N=1

U V W
MS M1C Y3E M Y1E M
3~ S1NPH M1F MS Injection Main
OUTDOOR
4D124072B

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 71
X5M : Field wiring terminal for DC
A3P *
X9M : Internal backup heater power supply terminal A4P *
X10M : Smartgrid terminal A8P *
: Earth wiring Daikin Altherma low temperature monoblocA11P
A14P *
: Field supply
A15P *
10 Wiring diagrams 1 : Several wiring possibilities
B1L
10 - 6 Hydro Module - Notes & Legend
: Option : Not mounted in switch box B1PW
 CN* (A4P) *
DS1 (A8P) *
EBLA09-16(DW1-DV3) : Wiring depending on model : PCB E3H
EBLA09-16(3DW1-3DV3) Note 1 : Connection point of the power supply for the backup heater & booster heater
E5H *
E6H
EDLA09-16(DW1-DV3) should be foreseen outside the unit.
10 EDLA09-16(3DW1-3DV3)
E7H
Backup heater E8H
3V (1N~, 230V, 3kW)
power
NOTES to go through before starting the unit supply: POSITION
POSITION IN
IN SWITCH SWITCH
BOX BOX E9H
E10H
X1M : Main terminal User installed options: Domestic hot water tank
X2M : Field wiring terminal for AC
Backup heater □ 3V (1N~, 230V, 3kW) E11H, E12H
power supply: External backup heater SWB1 SWB2 SWB2 SWB3
X3M
X1M : External backup heater terminal E*P (A9P)
X1M □

K3M

K1M
Boosterhot heater

X4M

X4M
X1M
X4M : Booster heater power supply User installed Domestic water tank F1B #
terminal options: □ Remote
External user heater
backup interface
X7M
F1T
X5M 15 □

TR1
15
15 : Field wiring terminal for DC Booster heaterthermistor F2B #

X9M

X3M
Ext. indoor
X9M
X1M : Internal backup heater power □ Remote user interface
Ext. outdoor thermistor
F2T
supply terminal
X1M
X10M : Smartgrid terminal
□ Ext. indoor thermistor F1U, F2U *
Digital I/O PCB
15 : Earth wiring
□ Ext. outdoor thermistor (A4P)
**/12.2 □ Demand
Digital PCB
I/O PCB A1P FU1 (A1P)

X2M

X2M
15
**/12.2
**/12.2 : Field supply
1
11 □ Smart grid
Demand PCB K1A, K2A *
: Several wiring possibilities □ WLAN
Smart cartridge
grid K1M

**/12.2
□ WLAN cartridge
Bypass kit
K3M *
1 **/12.2
: Option □ Bypass kit A8P
X5M K*R
MainLWT:
Main LWT: □ On/OFF
ON/OFF thermostat
thermostat (wired)
(wired) 0 0 (A1P-A4P)

X10M
K1A
K2A
1 □ On/OFF
ON/OFF thermostat
thermostat (wireless)
(wireless) For internal For external BUH
M1P
: Wiring depending on model □ Ext.Ext.
thermistor
thermistor BUH model option M2P #
□ Heat pump convector
Heat pump convector
A4P M2S #
Add LWT: □ ON/OFF thermostat (wired) M3S *
: Not mounted in switch box
Add LWT: □ ON/OFF
On/OFF thermostat
thermostat (wired)
(wireless)
□On/OFF thermostat (wireless)
Ext. thermistor M4S *
: PCB
□ Heat pump convector
Ext. thermistor
P1M

Heat pump convector


NOTES
Description Unit name
1. Connection point of the power supply for the backup heater & booster heater should be foreseen outside the unit.
Daikin Europe N.V. Hydro - Notes + Legend MB & MC
LEGEND
Part n° Description Part n° Description
A1P main PCB PHC1 (A4P) * optocoupler input circuit
A2P * ON/OFF thermostat (PC=power circuit) Q1L thermal protector backup heater
A3P * heat pump convector Q2L * thermal protector booster heater
A4P * digital I/O PCB Q4L # safety thermostat
A8P * demand PCB Q*DI # earth leakage circuit breaker
A11P MMI main PCB R1H (A2P) * humidity sensor
A14P * user interface PCB R1T (A1P) outlet water heat exchanger thermistor
A15P * receiver PCB (wireless ON/OFF thermostat) R1T (A2P) * ambient sensor On/OFF thermostat
B1L flow sensor R1T (A14P) * ambient sensor user interface
B1PW water pressure sensor R2T (A1P) internal BUH sensor
CN* (A4P) * connector R2T (A2P) * external sensor (floor or ambient)
DS1 (A8P) * dipswitch R3T refrigerant liquid side thermistor
E3H backup heater element (3 kW) R4T inlet water thermistor
E5H * booster heater element (2,4 kW) R5T * domestic hot water thermistor
E6H PHE heater (50 W) R6T * external indoor or outdoor ambient thermistor
E7H OP10 heater (33 W) S1L * flow switch
E8H OP10 heater (50 W) S1S # preferential kWh rate PS contact
E9H expansion vessel heater (50 W) S*T thermostat
E10H expansion vessel flex heater (15,6 W) S2S # electrical meter pulse input 1
E11H, E12H PHE heater IN/OUT (33 W) S3S # electrical meter pulse input 2
E*P (A9P) indication LED S4S # smartgrid feed-in
F1B # overcurrent fuse backup heater S6S-S9S * digital power limitation inputs
F1T thermal fuse backup heater S10S-S11S # low voltage smartgrid contact
F2B # overcurrent fuse booster heater SS1 (A4P) * selector switch
F2T thermal fuse booster heater SW1~2 (A11P) turn buttons
F1U, F2U (A4P) * fuse 5 A 250 V for digital I/O PCB SW3~5 (A11P) push button
FU1 (A1P) fuse T 5 A 250 V for PCB TR1 power supply transformer
K1A, K2A * high voltage smartgrid relay X4M * booster heater power supply terminal strip
K1M contactor backup heater X6M, X8M # power supply terminal strip client
K3M * contactor booster heater X9M backup heater power supply terminal strip
K*R (A1P-A4P) relay on PCB X10M * smartgrid power supply terminal strip
M1P main supply pump X*, X*A, X*Y connector
M2P # domestic hot water pump X*M terminal strip
M2S # 2 way valve for cooling mode Z*C noise filter (ferrite core)
M3S * 3 way valve for floorheating /domestic hot water
M4S * valve kit * : optional
# : field supply
P1M MMI display
PC (A15P) * power circuit 4D124072C

72 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

10 Wiring diagrams
10 - 7 Hydro Module - Power Supply, Back-up Heater

EBLA09-16(DW1-DV3) / EBLA09-16(3DW1-3DV3) / EDLA09-16(DW1-DV3) / EDLA09-16(3DW1-3DV3)

SWB2 SWB1
10
Internal BUH
domestic hot water tank
F1T E3H
E5H
X12Y SWB2
X12YA 1 2 3
F2T
SWB1
2 3
1 3
K1M Q2L
2 4 1 4
SWB1
SWB2 E5
SWB2 X4M
SWB 2
F
SWB 1
X9M L N PE 1 3
K3M
2 4 Q2L
SWB2 SWB 1

SWB2
X8M X4M
SWB 2

1 3 SWB 1
X6M K3M
F2B SWB 1
1 3 I I
2 4
X8M
F1B
I I Q1DI
2 4

F2B
Q1DI

1N~ or 3~ Q1D
1N~, 50 Hz 50 Hz
L N 230 V AC L/L1 N/L2
230 V AC

4D124072B L

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 73
Daikin Altherma low temperature monobloc

10 Wiring diagrams
10 - 8 Hydro Module - Control Circuit

EBLA09-16(DW1-DV3) / EBLA09-16(3DW1-3DV3)
EDLA09-16(DW1-DV3) / EDLA09-16(3DW1-3DV3)
10 6 7
For normal power supply (standard)
Hydro SWB power supplied from compressor SWB
For preferential kWh rate power supply (outdoor)
Use normal kWh rate power supply for hydro SWB
X2M.35a

X2M.34a
X2M.35

X2M.34

X2M.30

X2M.30

A2P A2P Compressor switch box 1N~, 50 Hz


230 V AC 6,3 A
Compressor switch box
X1M Normal kWh rate L N X1M SWB3 For external For internal
H C H C X2M 6 5 1 2 3
power supply
1 2 3
BUH option BUH model
COM COM
OUTDOOR Q2DI OUTDOOR 9
R1T R1T

X15M.6
X15M.7
1 2 1
-t° -t° X11YB
X11YA TR1 Q1L S1L
2
1
For wired ON/OFF thermostat For wired On/OFF thermostat X2M 6 5 2 SWB2

6 7 X11YA 1 2 X11YB 1 2 X3M 1 2 X7M 5 6


X2M.35a

X2M.34a
X2M.35

X2M.34

X2M.30

X2M.31

X2M.30

X2M.31

SWB2
X11Y 8 X11Y 8
SWB1
A15P A15P Z1C N=2
A1P
X1A X19A X26A X31A X3A X45A X21A
H C COM N L H C COM N L X17A
3 1 1 3 5 1 2 1 3 1 3 1 2 1 3
1
PC PC 3 FU1
X2M 5
35 7
A2P A2P 34 X24A
R1H R1H 35a 1
3
%H20 %H20 34a
R1T R1T 31 5
-t° X1M 1 2 3 -t° X1M 1 2 3
30 7
4 KPR
For wireless ON/OFF For wireless ON/OFF X14A K4R
3 1
thermostat thermostat
3
For ext. sensor For ext. sensor
(floor or (floor or
ambient) R2T ambient) R2T
-t° -t°
KCR KVR K6R K1R K2R K3R

6 7
X2M.35a

1 3 5 1 3 5 1 2 1 3 1 2 1 2 3 4 5 6 5 3 1 3 1 3 1 3 1
X2M.35

X2M.30

X2M.30

1 2
X2M.3

X2M.4

X2M.3

X2M.4

A3P A3P X2A X20A X28A X15A X22A X18A X25A X16A X11A X12A X13A

K1M A1 K3M A1
For heat pump convector For heat pump convector X2M.9
Main LWT zone Add LWT zone X2M.8 A2 A2

PWM
GND
10

FB

PE
N
L
For internal For domestic
MS M1P BUH model hot water
X7M 1 2 3 4 5 6 7 8 X2M 14a 14 13 12 X2M 2 1 X5M 8 7 X5M 12 11 3~ option
SWB1 SWB2

A1P/X11A.1
5
X2M.4

X2M.3

X13Y X14Y M3S M 1 2 SWB1


M2S
1 2 1 2 L
N M2P 1~ SWB2
NO valve X3M 3 4 5
Y DHW pump output R6T A14P
For cooling mode E9H E10H E11H E12H E7H E8H E6H SWB2
Max. load: -t°
A11P/X1B.3
A11P/X1B.4

2-point SPST valve 2 A (inrush) - 230 V AC P1 P2


5
X2M.4

X2M.3

X2M.14a

9 For domestic hot 1 A (continuous)

X15M.9
X15M.8

X15M.10
S1T S2T S3T ext. ambient
M4S For EWA/Y*DA*-H- water option
Y t° t° t° DHW pump sensor option R1T
N -t°
10
(indoor or
L For EB/DLA*DA* For EB/DLA*DA* outdoor) For external
and EWA/Y*DA*-H- and EWA/Y*DA*-H- MMI
Remote user BUH option
For *DAV3/DAW1 interface
4D124072C

EBLA09-16(DW1-DV3)
EBLA09-16(3DW1-3DV3)
EDLA09-16(DW1-DV3)
B1PW
EDLA09-16(3DW1-3DV3)
Digital I/O PCB X7Y
1 2 3
SWB1 A1P
A4P
X33A X5A R1T
X60A
CN1 CN2 1 1 1
1 2 3 4
SS1 1 3 2 2 2 -t°
ON 3 3
OFF 1 For internal BUH model
4 4
F2U F1U X6A 4
5 5 R2T
6 6 1
2 -t°
KCR X40A
1
KFR KHR KHUR PHC1
2
For external BUH option
3 X5M 4
X1 X2 X3 X4 YC Y1 Y2 Y3 Y4
4 1 X15M.1
230V AC
5 2 X15M.2
Control Device
L1 N1 L2 N2 6
7 X7A
SWB1 R3T
Alarm output 8 1
2 -t°
X2M Max. load
0.3 A - 250 V AC X10M 1 2 3 4 X5M 10 9 6 5 X5M 14 13 4 3 X8A
A1P/X28A.1
9
SWB1 R4T
X2M.13 1
8 1 2 3 -t°
2
7
S4S

X9A R5T
L N K1A A1 K2A A1 1
K1A

K2A

Ext. heat source 2 -t°


Max. load 0.3 A - 250 V AC Smartgrid Smartgrid PV
A2 A2 power pulse
Min. load 20 mA - 5 V DC contacts For domestic hot
meter water option
For HV smartgrid For smartgrid
Options: ext. heat source output, alarm output
1
1 X34A
X5M.10
A4P.YC

X5M.9

X5M.6

X5M.5
A4P.Y2

2
X2M 1
A1P/X28A.1
9 3
X2M.13
2 B1L
8 4
3
7 5

Space C/H
S10S

S11S

On/OFF output
Max. load 0.3 A - 250 V AC
For LV smartgrid 1 2 1 2 3 4 5 6
X48A X85A
1 for LV smartgrid
1 2 3
X5M.10

X5M.14

X5M.13
X5M.9

X5M.6

X5M.5

X5M.4

X5M.3

S3S
S2S
S1S

Options: ON/OFF output Q4L A8P


X5M 15 16
For digital I/O PCB option Electric pulse Safety Electric pulse X80A
meter input: thermostat meter input: 1 2 3 4 5 6 7 8 9 10 11 12
Preferential kWh 12 V DC pulse contact: 16 V DC 12 V DC pulse DS1
rate power supply detection detection detection ON
contact: 16 V DC (voltage (voltage (voltage OFF 1 2 3 4 5 X801M
A11P/X1B.1
A11P/X1B.2

detection (voltage supplied by supplied by supplied by 1 2 3 4


supplied by PCB) PCB) PCB) PCB)
For HP tarrif For safety
thermostat
Power limitation digital
S6S
S7S
S8S
S9S

inputs: 12 V DC / 12 mA
detection (voltage
supplied by PCB)

For demand PCB option 4D124072C

74 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

10 Wiring diagrams
10 - 9 External back-up heater - Option Circuit

EBLA09-16(DW1-DV3) / EBLA09-16(3DW1-3DV3) / EDLA09-16(DW1-DV3) / EDLA09-16(3DW1-3DV3)

(1) Connection diagram


10
PE
L1 L2 L3 N L N PE

X5M X15M R2T


- t°
1 1
2 2

F1U Q3DI Q3DI


X3M X15M
1 6
2 7 31 11
3 8 Q1L 2 4 6 8 2 4 6 8
4 9 32 12
5 10 F1B
F1B I I I I I I I I
1 3 5 7 1 3 5 7

OUTDOOR
Hydro A1 2 4 6 14 2 4 6 14
SWB K5M K5M

A2 1 3 5 13 1 3 5 13

A1 2 4 6 2 4 6
K1M K1M

A2 1 3 5 1 3 5
A1 2 4 6 2 4 6
K2M K2M

A2 1 3 5 1 3 5

F1T F1T F1T F1T F1T F1T F1T F1T F1T F1T F1T F1T

E1H E1H E1H E2H E2H E2H E1H E1H E1H E2H E2H E2H

X14M 1 2 3 4 5 6 X14M 1 2 3 4 5 6

12 12
3N~ , 400V , 6kW or 9kW 1N~ , 230V , 3kW or 6kW

BUH Option (EKLBUHCB6W1) 4D124072B

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 75
Daikin Altherma low temperature monobloc

11 External connection diagrams


11 - 1 External Connection Diagrams

EBLA09-16(DW1-DV3)
EBLA09-16(3DW1-3DV3)
11 EDLA09-16(DW1-DV3)
EDLA09-16(3DW1-3DV3)
Electrical connection diagram Daikin Monobloc/Minichiller GQI TBM

STANDARD PART
Power supply COMPRESSOR SIDE
unit power supply: 400 V or 230 V + earth 5 or 3 core X1M: L1-L2-L3-N-earth 5 core
or L-N-earth X1M: 1-2-3
400 or 230 V 230 V

Power supply
1 For preferential kWh rate power supply installation HYDRO SIDE
normal kWh rate power supply for hydro: 230 V 2 core
X2M: 5-6
230 V
Field supply 2 core A1P: X19A
2 Preferential kWh rate 2x0.75
X5M: 9-10
power supply contact Signal A1P: X1A For normal power supply installation 1 Power supply
2 For LV smartgrid Compressor power supply for hydro: 230 V
Smartgrid contact S10S
Field supply
Optional part A4P: Y1-YC 2 core
2 For HV smartgrid X2M: 7-9 Alarm indication
Smartgrid contact K1A Alarm output 230 V

2 core A4P: X1-X2 2 core


2x0.75 Changeover to ext. Ext. heat source (eg boiler)
Smartgrid relais K1A X10M: 1-2 heat source output signal
2 core A4P: Y2-YC
2x0.75 X2M: 7-9 2 core Cooling/heating
Smartgrid relais K2A X10M: 3-4 Cooling/heating
230 V On/OFF output
4 core ON/OFF output
HV smartgrid control supply: 230 V
2 core
X2M: 1-2 Circulation pump for DHW
230 V
3 X5M: 13 2 core
Field supply X5M: 14 X5M: 5-6 Electricity meter pulse input 1 5
3 2 core signal
2x0.75 For HV smartgrid 5
Safety thermostat Q4L X5M: 13-14 Smartgrid contact K2A
4 For LV smartgrid 5
Internal BUH power supply (3 kW): 230 V + earth 3 core Smartgrid contact S11S
X6M X9M: L-N-PE
(F1B)
230 V 2 core 6
X5M: 3-4 Electricity meter pulse input 2
2 core signal
Clixon X7M: 5-6 6
230 V Smartgrid pulse meter
2 core
Thermistor A1P: X6A
signal 2 core 2 way valve 8
2 core NO valve: X2M: 3-4 M2S for cooling mode
Safety contactor A1P: X11A 230 V
230 V
3 core For EKMBHBP1 (bypass kit) 8 Optional part
4 External BUH X2M: 3-4-14a M4S valve
2 core 230 V
Optional part

Thermistor X15M: 1-2 X5M: 1-2


signal
Contactor X15M: 8-9-10 X3M: 3-4-5 Optional part
5 core 2 core
230 V A1P: X45A Flow switch
Clixon X15M: 6-7 X3M: 1-2 signal
2 core For KRCS01-1 or EKRSCA1
5 or 3 core X5M: 7-8 External thermistor (indoor or outdoor)
F1B: 2-4-6-8 + earth signal
400 or 230 V
External BUH power supply (3/6/9 kW): 400 V or 230 V + earth External room thermostat / heat pump convector (main and/or additional zone)
(F1B)
7 3 core for C/H operation For *KRTW
2 core for H only operation (wired room thermostat)
Domestic hot water tank main: X2M: 30-34-35
Optional part

add: X2M: 30-34a-35a A2P: X1M: C-com-H


R5T - thermistor signal signal
A1P: X9A
water temperature 7
3 core 5 core for C/H operation For *KRTR 2 core
3Gx2.5 (wireless room thermostat) For *KRTETS
4 core for H only operation (3m included)
Booster heater Q2L X4M: L-N + earth main: X2M: 30-31-34-35 R2T
230 V A15P: X1M: H-C-com A2P: X1M: 1-3 External sensor
add: X2M: 30-31-34a-35a signal X2M: L-N signal (floor or ambient)

BSH power supply (2,4 kW): 230 V + earth 3 core 7


X8M K3M: 2-4 + earth main: X2M: 30-35
(F2B) add: X2M: 30-35a 4 core For (heat pump convector)
230 V
A3P
3 way valve signal
M3S (when *KHW is installed) 3 core main & add: X2M: 3-4
X2M: 12-13-14a
selection domestic hot water-floor heating 230 V
2 core
2x0.75 For remote user interface
Field supply

For *KRP1AHTA X5M: 11-12 signal A14P: P1-P2 user interface


Power limitation 2 core communication
demand input 1 A8P: X801M: 1-5
signal MMI
Power limitation 2 core
A8P: X801M: 2-5 A11P: X1B: 3-4
demand input 2 signal 4 core
Power limitation 2 core A11P: X10 WLAN cartridge
demand input 3 A8P: X801M: 3-5
signal X5M: 15-16 A11P: X1B: 1-2
Power limitation 2 core
A8P: X801M: 4-5
demand input 4 signal

NOTE
In case of signal cable: keep minimum distance to power cables > 5 cm

For more details please check unit wiring 4D128841B

76 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

12 Installation
12 - 1 Installation Method

EBLA09-16(DW1-DV3) / EBLA09-16(3DW1-3DV3) / EDLA09-16(DW1-DV3) / EDLA09-16(3DW1-3DV3)

Suction-side obstacle Discharge-side obstacle Suction-side obstacle + Discharge-side obstacle 12


0
0
≤ 50
≤ 50

0 0
≤ 50 ≤ 50
≥ 15

≥1000
0
≥1000

≥1000

≥1000
0*
≥30

X<H

X
0*
Top-side obstacle

≥50 ≥30 0*
0 ≥30

X
≥30 00
X<H ≥ 10 00
≥ 10

Wall on suction side Wall on discharge side

≥10
0 0*
≥30
Wall height unrestricted

≥50
0
No top-side obstacle

0*
≥ 30
0
X

≥ 30
X<H 0
≥ 50

*
H
≥ 150

General
3D128957

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 77
Daikin Altherma low temperature monobloc

13 Operation range
13 - 1 Operation Range

EBLA09-16(DW1-DV3) / EBLA09-16(3DW1-3DV3) / EDLA09-16(DW1-DV3) / EDLA09-16(3DW1-3DV3)

13
40 Backup heater No backup heater No backup heater
Backup heater kit With tank preheating
35 See note ·1·.
30 30 30
25 25
20 20 20
Outdoor temperature [°C DB]

Outdoor temperature [°C DB]

Outdoor temperature [°C DB]


15 14
10 10 10

0 0 0

-7 -7 -7
-10 -10 -10

-20 -20 -20


-25 -25 -25

15 20 25 30 35 40 50 60 10 20 25 30 35 40 50 60 5 10 20 25 30 35 40 50 60
18 28 38 9
Leaving water temperature [°C] Leaving water temperature [°C] Leaving water temperature [°C]

Legend

Backup heater only operation


No outdoor unit operation

Heat pump + backup heater operation


Pull-up area

Outdoor unit operation if controller setpoint is regulated to minimal leaving water temperature request.
See dashed lines

Operation of outdoor unit possible, but with possible capacity reduction.

Circulation pump operation only

Notes
1.Tank preheating
For details, see the installer reference guide.
2.If negative ambient temperatures are expected, both in operation or at standstill, take adequate countermeasures against freezing.
For more information, refer to the installation manual.
3.In restricted power supply mode, the outdoor unit and backup heater can only operate separately.

3D130723

EBLA09-16(DW1-DV3) / EBLA09-16(3DW1-3DV3) / EDLA09-16(DW1-DV3) / EDLA09-16(3DW1-3DV3)

40
35
30

20
Outdoor temperature [°C DB]

10

-7
-10
-15
-20
-25

10 20 25 30 35 40 50 55 60 70 75 80
49
Legend Water temperature
Setpoint [°C] [°C]
Domestic hot water
Leaving water temperature [°C]

Pull-up area

Operation of outdoor unit possible, but with possible capacity reduction.

Booster heater only operation (if a booster heater is part of the system)

Notes
1.In restricted power supply mode (·EKHW*· only ), the outdoor unit, booster heater and backup heater can only operate separately.
2.Third-party with identical specifications as ·EKHWS*·
Coil surface >·1.05·m² and <·3.7·m²
Tank thermistor and booster heater above heat pump coil.
3.If negative ambient temperatures are expected, both in operation or at standstill, take adequate countermeasures against freezing.
For more information, refer to the installation manual.

3D120989

78 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

13 Operation range
13 - 1 Operation Range

EBLA09-16(DW1-DV3) / EBLA09-16(3DW1-3DV3)

Outdoor temperature [°C DB]


43 13
40

30

20

10

5 10 20 30 40 50
7 22
Leaving water evaporator temperature [°C]

Legend

In case valve kit ·AFVALVE1· is part of the system, then the minimum
setpoint is ·7·°C.

Pull-down area

Notes
1. For more information, refer to the installation manual.
If negative ambient temperatures are expected, both in operation or at standst
ill, take adequate countermeasures against freezing.
3D130999

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 79
Daikin Altherma low temperature monobloc

14 Hydraulic performance
14 - 1 Static Pressure Drop Unit

EBLA09-16(DW1-DV3) / EDLA09-16(DW1-DV3)

14

ESP = External static pressure [kPa] Space heating/cooling circuit


Flow = Water/glycol flow through the unit Space heating/cooling circuit

A= Minimum water flow rate during normal operation
B= Minimum water flow rate during defrost operation

Notes
1. The operation area is extended to lower flow rates only in case the unit operates with heat 
pump only, and the temperature of the flow medium is sufficiently high.

This does not apply to start‐up operation, defrost operation, and backup heater operation in 
case a backup heater is installed.

See dashed lines

2. The higher operation range limit is only valid if the flow medium is water. If glycol is added to 
the system, the limit is lower.

3. Selecting a flow outside the operating area can damage the unit or cause the unit to 
malfunction.

See also the minimum and maximum allowed water flow range in the technical specifications.

 4D129632

80 EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3
Daikin Altherma low temperature monobloc

14 Hydraulic performance
14 - 1 Static Pressure Drop Unit

EBLA09-16(3DW1-3DV3) / EDLA09-16(3DW1-3DV3)

14

ESP = External static pressure [kPa] Space heating/cooling circuit


Flow = Water/glycol flow through the unit Space heating/cooling circuit

A= Minimum water flow rate during normal operation


B= Minimum water flow rate during defrost operation

Notes
1.
The operation area is extended to lower flow rates only in case the unit operates with
heat pump only, and the temperature of the flow medium is sufficiently high.

This does not apply to start-up operation, defrost operation, and backup heater
operation in case a backup heater is installed.
See dashed lines
2. The higher operation range limit is only valid if the flow medium is water. If glycol is
added to the system, the limit is lower.
3. Selecting a flow outside the operating area can damage the unit or cause the unit to
See also the minimum and maximum allowed water flow range in the technical
specifications.
4D128961

EBLA09-16DW1/EBLA09-16DV3/EBLA09-16D3W1/EBLA09-16D3V3/EDLA09-16DW1/EDLA09-16DV3/EDLA09-16D3W1/EDLA09-16D3V3 81
Daikin Europe N.V.  Naamloze Vennootschap · Zandvoordestraat 300 · 8400 Oostende · Belgium · www.daikin.eu · BE 0412 120 336 · RPR O
ostende (Responsible Editor)

The present leaflet is drawn up by way of information only and does not constitute an
offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of
this leaflet to the best of its knowledge. No express or implied warranty is given for the
completeness, accuracy, reliability or fitness for particular purpose of its content and the
products and services presented therein. Specifications are subject to change without prior
notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in
EEDEN21 06/2021
the broadest sense, arising from or related to the use and/or interpretation of this leaflet.
All content is copyrighted by Daikin Europe N.V.

You might also like