Professional Documents
Culture Documents
Rele Ahe
Rele Ahe
HE-S RELAYS
Compact size 2a and 2a1b 40A power relays for energy management and industrial equipment
TYPICAL APPLICATIONS
Photovoltaic power generation system
UPS (Uninterruptible power supply)
Inverter
Industrial air conditioner
(Unit:mm) Industrial equipment
DETAILS FEATURES
When Form A
Reduced coil holding voltage* contributes to saving Condi- Normal operation
contact welded
tions
energy of equipment Non-excitation Excitation Non-excitation
The coil holding voltage can be reduced up to 30%V of
Form A Form B Form A Form B Form A Form B
the rated coil voltage. This equals to operating power of contact contact contact contact contact contact
Mirror
approximately 170 mW, which contributes equipment energy contact
savings. mecha- Welding Min.
nisms 0.5mm
* Coil holding voltage is the coil voltage after 100 ms from the applied rated coil
voltage.
AHES 9
Contact arrangement/Operating function Contact specifications Terminals shape Rated coil voltage(DC) Approved standards
3:2 Form A Single side stable 1:Standard type 9:PC board terminal 0:6V Q :UL/C-UL, VDE, CQC
4:2 Form A 1 Form B Single side stable 2:Long life type 1:12V Nil:UL/C-UL, VDE
2:24V
3:48V
5:9V
TYPES
PC board terminal
Carton
Part No. Standard packing
Contact arrangement Rated coil voltage
Standard type Long life type Inner carton Outer carton
6 V DC AHES3190(Q) AHES3290(Q)
9 V DC AHES3195(Q) AHES3295(Q)
2 Form A 12 V DC AHES3191(Q) AHES3291(Q)
24 V DC AHES3192(Q) AHES3292(Q)
48 V DC AHES3193(Q) AHES3293(Q)
25 pcs. 100 pcs.
6 V DC AHES4190(Q) AHES4290(Q)
9 V DC AHES4195(Q) AHES4295(Q)
2 Form A 1 Form B
12 V DC AHES4191(Q) AHES4291(Q)
(2a1b)
24 V DC AHES4192(Q) AHES4292(Q)
48 V DC AHES4193(Q) AHES4293(Q)
Note) CQC compliant type are available. Ex) AHES3190Q
RATING
Coil data
perating characteristics such as ‘Operate voltage’ and ‘Release voltage’ are influenced by mounting conditions, ambient
O
temperature, etc.
Therefore, please use the relay within ± 5% of rated coil voltage.
‘Initial’ means the condition of products at the time of delivery.
Operate voltage*1 Release voltage*1 Rated operating current Coil resistance Max. allowable voltage
Rated coil voltage Rated operating power
(at 20°C) (at 20°C) (±10%, at 20°C) (±10%, at 20°C) (at 55°C)
6 V DC 313 mA 19.1 Ω
9 V DC 209 mA 43.1 Ω 110% V of rated
Max. 75% V of Min. 5% V of coil voltage
1,880 mW
12 V DC rated coil voltage rated coil voltage 157 mA 76.6 Ω
Holding*2: 170 mW*3 150% V of rated
24 V DC (Initial) (Initial) 78 mA 306.4 Ω coil voltage*4
48 V DC 39 mA 1,225.5 Ω
*1. Square, pulse drive
*2. When using with the holding voltage, switch to the holding voltage after 100ms from the application of the coil rated voltage.
*3. With 30% V coil holding voltage
*4. Total application time: Max. 24 hours
Specifications
Item Specifications
Contact arrangement 2 Form A, 2 Form A 1 Form B (2a1b)
Contact data Form A contact Max. switching voltage 480 V AC, 110 V DC
Max. switching current 40 A
Min. switching load
100 mA 5 V DC
(reference value)*1
Contact rating (resistive) 1 A 277 V AC, 1 A 30 V DC
Max. switching power
277 VA, 30 W
(resistive)
Form B contact*6 Max. switching voltage 277 V AC, 30 V DC
Max. switching current 1A
Min. switching load
10 mA 5 V DC
(reference value)*1
Insulation resistance (initial) Min. 1,000 MΩ (at 500 V DC, Measured portion is the same as the case of dielectric strength)
Short current (Form A contact, initial) Max. 1,000 A 1 ms, 3 times (reference value)
Between open Form A contacts 2,000 Vrms for 1 min (detection current: 10 mA)
Between Form A contact and coil 5,000 Vrms for 1 min (detection current: 10 mA)
Dielectric Between Form A contact sets 5,000 Vrms for 1 min (detection current: 10 mA)
strength (initial) Between open Form B contacts*6 1,000 Vrms for 1 min (detection current: 10 mA)
Between Form B contact and coil* 6
2,000 Vrms for 1 min (detection current: 10 mA)
Between Form A contact and Form B contact*6 5,000 Vrms for 1 min (detection current: 10 mA)
Time characteristics Operate time Max. 30 ms (at rated coil voltage, at 20°C, without bounce)
(initial) Release time*4 Max. 10 ms (at rated coil voltage, at 20°C, without bounce, without diode)
Functional 98 m/s2 (half-sine shock pulse: 11 ms, detection time: 10 μs)
Shock resistance
Destructive 980 m/s2 (half-sine shock pulse: 6 ms)
Vibration Functional 10 to 55Hz (at double amplitude of 1 mm, detection time: 10 μs)
resistance Destructive 10 to 55Hz (at double amplitude of 1.5 mm)
Expected life Mechanical life Min. 5×106 ope. (at 180 times/min)
*1.This value can change due to the switching frequency, environmental conditions, and desired reliability level, therefore it is recommended to check this with the actual load.
*2.Wave is standard shock voltage of ± 1.2 × 50 μs according to JEC-212-1981
*3.Coil holding voltage is the coil voltage after 100 ms from the applied rated coil voltage.
*4.Release time will lengthen if a diode, etc., is connected in parallel to the coil. Be sure to verify operation under actual conditions.
*5.When using at 55°C or higher, the coil holding voltage should be 30 to 60% V. And for ambient temperature, please read "GUIDELINES FOR RELAY USAGE".
*6.Regarding Form B contact, only the 2 Form A 1 Form B (2a1b) type applies.
REFERENCE DATA
1. Max. switching capacity 2. Switching life curve
100 1,000
50 500
No. of operations(×10 4)
30
Contact current(A)
20
250V AC
10 100 resistive load
DC AC
5 resistive load resistive load 50
0.1 1
10 30 100 500 1,000 0 5 10 15 20 25 30 35 40
Contact voltage(V) Contact current(A)
70 25℃ 35A
20
Temperature rise(℃)
60
85℃ 35A 10
50 25℃ 0A
ー60 ー40 ー20 0
40
20 40 60 80 100
85℃ 0A Ambient
30 Operate (℃)
temperature
voltage ー10
20
Release ー20
10 voltage
0 ー30
50 60 70 80 90 100 110
Coil applied voltage(%V)
DIMENSIONS CAD The CAD data of the products with a “CAD” mark can be downloaded from our Website. Unit: mm
■ 2 Form A
CAD External dimensions Recommended PC board pattern
30.0 36.0 (BOTTOM VIEW)
7.6
2‒1.6dia.
(38.0)
40.0
21.3
11
2.4
1.6
2.0
4 R0.8
4.0
24.4
19
29.4
27.0
Tolerance ±0.1
2-φ0.8 7.6
Schematic
(BOTTOM VIEW)
21.3
4 5
4-0.8
11.0
2 7
1.0
4-3.3
19.0
General tolerance ±0.3 1 8
22.9
7.6 2‒1.6dia.
2‒2.2dia.
(38.0)
40.0
21.3
11
2.4
2.0
4.0
24.4
1.6
4 R0.8
29.4 19
27.0 Tolerance ±0.1
22.9
7.6 2-1.2
2-1.2
2-φ0.8 Schematic
(BOTTOM VIEW)
3 4 5 6
21.3
4-0.8
11.0
2 7
4-3.3 1 8
1.0
19.0
General tolerance ±0.3
Note: Terminal dimensions are values without pre-soldering thickness.
SAFETY STANDARDS Each standard may be updated at any time, so please check our Website for the latest information.
UL/C-UL (Approved)
Standard type Long life type
2 Form A, 2 Form A 1 Form B (2a1b) (Form A contact) 2 Form A, 2 Form A 1 Form B (2a1b) (Form A contact)
Ambient Ambient
File No. Contact rating Operations File No. Contact rating Operations
temperature temperature
35 A 277 V AC resistive 30 × 103 85°C 35 A 277 V AC resistive 50 × 103 85°C
E43149 20 A 277 V AC resistive 100 × 103 85°C E43149 20 A 277 V AC resistive 200 × 103 85°C
15 A 480 V AC resistive 100 × 103 85°C 15 A 480 V AC resistive 100 × 103 85°C
2 Form A 1 Form B (2a1b) (Form A contact) 2 Form A 1 Form B (2a1b) (Form A contact)
Ambient Ambient
File No. Contact rating Operations File No. Contact rating Operations
temperature temperature
Make/Break 35 A , Rated 45 A Make/Break 35 A , Rated 45 A
E43149 6×103 85°C E43149 6×103 85°C
277 V AC Resistive 277 V AC Resistive
2 Form A 1 Form B (2a1b) (Form B contact) 2 Form A 1 Form B (2a1b) (Form B contact)
Ambient Ambient
File No. Contact rating Operations File No. Contact rating Operations
temperature temperature
1 A 277 V AC resistive 100 × 103 85°C 1 A 277 V AC resistive 100 × 103 85°C
E43149 E43149
1 A 30 V DC resistive 100 × 10 3
85°C 1 A 30 V DC resistive 100 × 103 85°C
CSA (Approved)
CSA standard certified by C-UL
VDE (Approved)
Standard type and Long life type(Common)
2 Form A, 2 Form A 1 Form B (2a1b) (Form A contact)
Ambient
File No. Contact rating Operations
temperature
AC-3 480 V AC 8 A cosφ = 0.65 30 × 103
AC-3 230 V AC 12 A cosφ = 0.65 30 × 103
40042442 250 V AC 20 A cosφ = 1 80 × 103 85°C
TV rating
Standard type Long life type
2 Form A, 2 Form A 1 Form B (2a1b) (Form A contact) 2 Form A, 2 Form A 1 Form B (2a1b) (Form A contact)
File No. Rating File No. Rating
E43149 TV-8 E43149 TV-10
Form A 1 Form B (2a1b) (Form B contact) Form A 1 Form B (2a1b) (Form B contact)
Ambient Ambient
File No. Contact rating Operations File No. Contact rating Operations
temperature temperature
CQC20002260136 1 A 277 V AC 10 × 103 -40 to +20°C CQC20002260136 1 A 277 V AC 15 × 103 -40 to +70°C
CQC20002260136 1 A 30 V DC 10 × 10 3
-40 to +20°C CQC20002260136 1 A 30 V DC 15 × 103 -40 to +70°C
Item Characteristics
Clearance/Creepage distance (IEC61810-1) Min. 5.5/8.0 mm (Form A contact)
Category of protection (IEC61810-1) RT II
Tracking resistance (IEC60112) PTI 175
Insulation material group III a
Over voltage category III
Rated voltage 250 V
Pollution degree 3
Type of insulation (Between contact and coil) Reinforced insulation
Type of insulation (Between open contact) Full disconnection
Note(s): Actual value.
40 A 35 A
Max. carrying current
For cautions for use, please read “GUIDELINES FOR RELAY USAGE”.
https://industrial.panasonic.com/ac/e/control/relay/cautions_use/index.jsp
Long term current carrying Maximum allowable voltage and temperature rise
A circuit that will be carrying a current continuously for long periods Proper usage requires that the rated coil voltage be impressed on
without relay switching operation. (circuits for emergency lamps, the coil. Note, however, that if a voltage greater than or equal to the
alarm devices and error inspection that, for example, revert only maximum continuous voltage is impressed on the coil, the coil may
during malfunction and output warnings with form B contacts) burn or its layers short due to the temperature rise. Furthermore, do
Continuous, long-term current to the coil will facilitate deterioration not exceed the usable ambient temperature range listed in the
of coil insulation and characteristics due to heating of the coil itself. catalog.
For circuits such as these, please use a magnetic-hold type latching Operate voltage change due to coil temperature rise
relay. If you need to use a single stable relay, use a sealed type In DC relays, after continuous passage of current in the coil, if the
relay that is not easily affected by ambient conditions and make a current is turned OFF, then immediately turned ON again, due to the
failsafe circuit design that considers the possibility of contact failure temperature rise in the coil, the operate voltage will become
or disconnection. somewhat higher. Also, it will be the same as using it in a higher
DC Coil operating power temperature atmosphere. The resistance/temperature relationship
Steady state DC current should be applied to the coil. The wave for copper wire is about 0.4% for 1°C, and with this ratio the coil
form should be rectangular. If it includes ripple, the ripple factor resistance increases. That is, in order to operate of the relay, it is
should be less than 5%. necessary that the voltage be higher than the operate voltage and
However, please check with the actual circuit since the electrical the operate voltage rises in accordance with the increase in the
characteristics may vary. The rated coil voltage should be applied to resistance value. However, for some polarized relays, this rate of
the coil and the set/reset pulse time of latching type relay differs for change is considerably smaller.
each relays, please refer to the relay's individual specifications.
Coil connection
When connecting coils of polarized relays, please check coil polarity
(+,-) at the internal connection diagram (Schematic). If any wrong
connection is made, it may cause unexpected malfunction, like
abnormal heat, fire and so on, and circuit do not work. Avoid
impressing voltages to the set coil and reset coil at the same time.
Ambient Environment
Others
Cleaning
• Although the environmentally sealed type relay (plastic sealed type, • Cleaning with the boiling method is recommended(The temperature
etc.) can be cleaned, avoid immersing the relay into cold liquid (such of cleaning liquid should be 40°C or lower ).
as cleaning solvent) immediately after soldering. Doing so may Avoid ultrasonic cleaning on relays. Use of ultrasonic cleaning may
deteriorate the sealing performance. cause breaks in the coil or slight sticking of the contacts due to
ultrasonic energy.