6295 2 20 PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

SECTION 2.

20
GOVERNING

GOVERNOR/SPEED CONTROL
This section discusses the ESM system’s governing The digital signal input to the ECU must be connected
and speed control. to +24 VDC nominal (8.6 – 36 volts) for rated speed,
open circuit for idle speed, and remote speed setting
The ESM speed governing system provides speed
enable (GOVREMSEL) must be an open circuit. When
and load control using information based on digital and
using the Remote Speed/Load Setting, GOVHL IDL
analog inputs from the customer. The ESM system’s
should be set to a safe mode. “Safe mode” means that
governor has two different operating modes: speed
if the wire that enables remote rpm operation
control and load control. In speed control mode, the
(GOVREMSEL) fails, the speed setpoint will default to
governor will control the engine speed by increasing or
the GOVHL IDL idle value. Consider all process/driven
decreasing the engine power output. In load control
equipment requirements when programming idle
mode, the speed is controlled by an exterior force such
requirements.
as the electrical grid and the load is varied by a gener-
ator control product. Variable Speed
SPEED CONTROL MODE Connecting the GOVREMSEL digital input to the ECU
at +24 VDC nominal enables variable speed mode.
The engine speed setpoint can be controlled to a fixed
The speed setpoint can then be varied with either a
value or can be varied in response to a process vari-
4 – 20 mA or a 0.875 – 4.0 volt input (see
able such as desired flow rate of gas if the engine is
Figure 2.20-2).
powering a gas compressor.
The ESM system checks for an out-of-range input that
Fixed Speed
is less than 2 mA, greater than 22 mA, less than
0.45 volts, or greater than 4.3 volts. If an out-of-range
WARNING speed setpoint is detected, the engine will then run at
the speed indicated by the status of the high idle/low
Never set the high idle speed above the safe
idle digital input. The engine speed setpoint range is
working limit of the driven equipment. If the
already preadjusted to go from minimum to maximum
GOVREMSP signal goes out of range or the
engine speed using the 4 – 20 mA input (see
GOVREMSEL signal is lost, then the engine will
Table 2.20-1). See Figure 2.20-3 for a logic diagram
run at the speed determined by the status of
showing variable speed.
GOVHL IDL and calibrated low or high idle speeds.
Disregarding this information could result in
Table 2.20-1 Setpoint Speed Range
severe personal injury or death.
SPEED RANGE
There are two fixed speeds available: low idle and high ENGINE MODEL
(4 – 20 mA RANGE)
idle. Low idle speed is the default, and high idle is F3514GSI/F3524GSI 750 – 1206 rpm
obtained by connecting a digital input to the ECU of L7042GSI/L7044GSI 750 – 1206 rpm
+24 VDC nominal. Low idle speed is preset for each L5774LT 750 – 1206 rpm
engine family, but by using ESP the low idle speed can
L5794GSI 750 – 1206 rpm
be offset lower or higher than the preset value. High
L5794LT 750 – 1206 rpm
idle speed is also adjustable directly using ESP but is
L7042GL
constrained to be higher than low idle speed and no (Minimum idle speed of 800
higher than the maximum rated speed of the engine. rpm, if variable speed mode is 800 – 1206 rpm
selected, the minimum setpoint
See Figure 2.20-1 for a logic diagram showing fixed rpm is 800 rpm)
speed.

FORM 6295 Fourth Edition 2.20-1


GOVERNING

TYPICAL APPLICATIONS = ELECTRIC POWER GENERATION ISLAND OR GRID

RPM DROOP
WOODWARD™ LOAD GOVAUXSIG
SHARING MODULE GOVAUXGND
P/N 9907-173

INITIAL + MODIFIED +
+ RPM RPM
+ +
+

TARGET RPM

RAMP LIMIT THE


LOW/HIGH GOVHL IDL FUNCTION RPM VALUE
IDLE DIGITAL +
INPUT

CALIBRATED
LOW IDLE RPM
LIMIT (RAMP)
RPM CHANGE
CALIBRATED AD
LO
HIGH IDLE RPM
CALIBRATED
G
LR

RAMP TIME

FINAL RPM VALUE TO BE


USED IN GOVERNOR
ALTERNATE DYNAMICS CALCULATION
DIGITAL INPUT

SYNC RPM

Figure 2.20-1 Logic Diagram Showing Fixed Speed

4 – 20 mA SIGNAL + 39 GOV REMSP +

4 – 20 mA SIGNAL - 27 GOV REMSP -


CUSTOMER INTERFACE HARNESS
40 GOV 40
JUMPERED
41 GOV 41

X 39 GOV REMSP +
NO CONNECTION
X 27 GOV REMSP -
CUSTOMER INTERFACE HARNESS
0.875 – 4.0 V SIGNAL + 40 GOV 40

0.875 – 4.0 V SIGNAL - 41 GOV 41

Figure 2.20-2 Connection Options for Variable Speed Setting Input

2.20-2 FORM 6295 Fourth Edition


GOVERNING

RPM DROOP
REMOTE SPEED SELECTION GOVREMSEL
DIGITAL INPUT

GOV REMSP+ INITIAL MODIFIED +


GOV REMSP- RPM RPM
REMOTE SPEED OR + + +
ANALOG INPUT GOV 40
GOV 41

SEE NOTE

LIMIT THE
RPM VALUE

TYPICAL APPLICATIONS = GAS COMPRESSION


AND MECHANICAL DRIVES

LIMIT (RAMP)
RPM CHANGE

CALIBRATED
RAMP TIME

FINAL RPM VALUE TO BE


USED IN GOVERNOR
NOTE: If Remote Speed Selection Digital Input goes open circuit, CALCULATION
then engine will run at Calibrated Low or High Idle rpm
depending on status of Low/High Idle Digital Input.

Figure 2.20-3 Logic Diagram Showing Variable Speed

LOAD CONTROL MODE


Load control mode is only applicable when the engine When an external synchronizer determines that the
speed is already controlled by an external force such voltage and phase of the generator match the grid, the
as an electric grid. To run in load control mode, the breaker is closed. The load of the engine can now be
engine must be first synchronized to the electric grid. controlled by an external load control such as the
The ESM system has a unique feature for easier syn- Woodward™ Load Sharing Module (Woodward™
chronization to the grid by better controlling idle speed P/N 9907-173) through the GOVAUXSIG and
by using the spark timing in addition to the throttle. GOVAUXGND -2.5 to +2.5 volt input of the ESM sys-
Synchronizer or alternate dynamics mode can be tem (see Figure 2.20-4).
enabled by bringing a digital input on the ECU to
The speed bias output of most load sharing devices
+24 VDC nominal. In addition to providing an excellent
can be configured to match the -2.5 to +2.5 volt input
stable idle, synchronizer mode can also be used to off-
range of the ESM GOVAUXSIG and GOVAUXGND
set the idle speed higher.
inputs. Refer to the load sharing device manual for
The SYNC RPM is adjusted so that the actual engine information on how to configure the range and offset of
speed setpoint is approximately 0.2% higher than syn- the speed bias output of your load sharing device.
chronous speed. For example, if the grid frequency is Next start the engine and adjust the Proportional and
60 Hz (1200 rpm), the high idle is adjusted so that the Integral gains of the load sharing device to obtain sta-
engine speed setpoint is 1.002 times 1200 rpm, which ble operation of the engine power output. Refer to the
is 1202 rpm. This ensures that the electric phasing of load sharing device manual for more information on
the grid and the engine are different so that the phases how to set the gains of the device.
will slide past each other.

FORM 6295 Fourth Edition 2.20-3


GOVERNING

Setting the rotating moment of inertia (or load inertia)


CUSTOMER INTERFACE HARNESS with ESP is the first task when setting up an engine
and must be done with the engine not rotating. The
rotating moment of inertia value is programmed on the

GOVAUXGND

GOVAUXSHD
GOVAUXSIG
[F4] Governor Panel in ESP.
Refer to Section 3.10 ESP Programming “Program-
ming Load Inertia” for programming steps.
FEEDFORWARD CONTROL (LOAD COMING)
29 28 46
The ESM system has a feature, Feedforward Control,
that can be used to greatly improve engine response
to large loads. One example of how this feature can be
USE SHIELDED used would be in stand-alone electric power genera-
TWISTED PAIR tion applications where the engine is supplying vari-
CABLE
able loads such as lights, miscellaneous small loads,
and one large electric motor.
For example, the starter for a large electric motor
could be routed to a PLC so that a request to start the
OUTPUT electric motor would go through the PLC. When the
19 20 PLC received the request to start the electric motor, it
first would set the large load coming digital input on
the ECU high for 0.5 seconds and then 1 second later
WOODWARD™ LOAD SHARING MODULE
actually start the electric motor. This would give the
ESM system a 1 second head start to open the throttle
Figure 2.20-4 External Load Control – Woodward™ Load even before the load was applied and the engine
Sharing Module speed drops.

ROTATING MOMENT OF INERTIA / ADJUSTING The behavior of the large load coming digital input can
GAIN be customized through “trial and error” with ESP. The
percent of rated load of the electric motor is set in the
The ESM system has the unique feature that the cor- “Forward Torque” field on the [F4] Governor Panel.
rect gains for an engine model are preloaded to the The Forward Delay is the lag time of the ESM system
ECU. Having the gains preloaded can greatly reduce from receipt of the Load Coming signal until action
startup time when compared to using aftermarket gov- is taken. As the LRG LOAD digital input goes high
ernors. (8.6 – 36 volts), the engine speed should go above
To make this work, the ECU needs only one piece of setpoint rpm for approximately 1 second before the
information from the customer: the rotating moment of load is applied. Typically the “Forward Torque” field is
inertia or load inertia of the driven equipment. Once set to 125% and “Forward Delay” is programmed to
this information is available, the ECU calculates the optimize the system’s behavior.
actual load changes on the engine based on speed ACTUATOR AUTOMATIC CALIBRATION
changes. Rotating moment of inertia is not the
weight or mass of the driven equipment. Rotating To work correctly, the ESM system must know the fully
moment of inertia is needed for all driven equipment. closed and fully open end points of throttle actuator
movement. Using ESP, the ESM system can be set up
Ensure that the cor- to automatically go through calibration each time the
CAUTION rect rotating moment engine stops (except on Emergency Shutdown). Allow
of inertia (load inertia) is programmed in ESP for 30 seconds after the engine stops for the actuator cali-
the engine’s driven equipment. Failure to program bration to finish. If the engine has been shut down by
the moment of inertia for the driven equipment on an Emergency Shutdown, then no actuator automatic
the engine in ESP will lead to poor steady state calibration will occur. If a start signal is received while
and transient speed stability. Disregarding this the actuator is calibrating, the calibration procedure
information could result in product damage and/or will be aborted and the engine will initiate its start
sequence.
personal injury.
Refer to Section 3.10 ESP Programming “Actuator
Calibration” for more information.

2.20-4 FORM 6295 Fourth Edition

You might also like