6295 3 05 PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 40

SECTION 3.

05
ESP PANEL DESCRIPTIONS
INTRODUCTION
This section provides a description of each ESP panel [F6] AFR Primary Fuel Panel Description
and the fields and buttons found on each panel. ................................................................... Page 3.05-20
Figure 3.05-1 identifies and describes the common fea-
[F8] AFR Setup Panel Description............. Page 3.05-26
tures found on the ESP panels.
[F10] Status Panel Description ...................Page 3.05-30
[F2] Engine Panel Description...................... Page 3.05-2
[F11] Advanced Panel Description .............Page 3.05-36
[F3] Start-Stop Panel Description ................ Page 3.05-4
Fault Log Description................................. Page 3.05-38
[F4] Governor Panel Description.................. Page 3.05-8
[F5] Ignition Panel Description ................... Page 3.05-14

The ESP Title Bar lists the ESP version number, ECU The Communication Icon indicates whether or not there is
serial number, engine serial number, and calibration communication between the ECU and ESP. The icon shown
part number. here is indicating communication. When there is no communi-
cation, the icon has a red circle with a bar over it.

ESP displays engine information on panels. Each


panel is viewed by clicking the tab or by pressing
the function key [F#] on the keyboard.
The “Engine Alarm” field provides a
general overview of alarm status.
When no alarms are active, the
field is gray. If an alarm occurs, the
field turns yellow and signals that
“YES” at least one alarm is active.

Each of the panels displays engine status


and operation information. ESP panels can
Some ESP panels provide for programming system be set to display in either U.S. units or in
parameters like pre/post lube, the WKI value, and load metric measurement units. Change units on
inertia. Fields that are programmable are dark blue. the [F10] Status Panel.

On ESP panels that have programmable fields,


To access the electronic help file, additional buttons are included to enable editing,
E-Help, while using ESP, press [F1]. allow saving, and undo changes.

Figure 3.05-1 Description of Common Features Found on ESP Panels

FORM 6295 Fourth Edition 3.05-1


ESP PANEL DESCRIPTIONS

[F2] ENGINE PANEL DESCRIPTION


The Engine Panel displays current system readings of engine speed, left and right bank intake manifold pressures,
oil pressure, intake manifold temperature, coolant temperature, and oil temperature. Displayed under the engine
speed is the engine setpoint RPM, percent of rated load, and estimated power. If a sensor or wiring failure is
detected, the status bar, under the affected sensor, will change from teal (blue-green) to yellow, and a message will
appear in the status bar telling the user to check sensor and wiring for proper operation. Also, the “Engine Alarm”
field in the upper right corner will change from gray (deactivated/no engine alarm) to yellow (alarm). In case of a
shutdown, the deactivated (gray) status bar under the “Engine Setpoint RPM” field turns red and a message sig-
nals the user of the emergency shutdown.

1 9

2 10

3 5 6 7 11

Figure 3.05-2 Engine Panel in ESP – Fields 1 through 11

3.05-2 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F2] ENGINE PANEL DESCRIPTION – REFER TO FIGURE 3.05-2


1 “Intake Mnfld LB” This field displays the 8 “ESD/No ESD” This field signals the user that
engine’s left bank intake manifold pressure. an emergency shutdown is in process. When
Units are in-Hg absolute (kPa absolute). If an intake the engine is operating or off, the field remains deacti-
manifold pressure sensor or wiring fault occurs, the vated (gray). If the engine shuts down due to an emer-
status bar beneath this field signals an alarm (turns gency, the field signals the emergency shutdown
yellow) and provides the user a message to fix the (turns red) and provides the user a message indicating
sensor or wiring. NOTE: When a sensor or wiring fault an emergency shutdown is in process. When the shut-
is detected, the field displays a default value, not the down is complete, the field deactivates (turns gray)
actual value. and the shutdown is recorded in the fault log history.
However, the field remains active (in shutdown mode)
2 “Intake Mnfld RB” This field displays the if the lockout or E-Stop (emergency stop) button(s) on
engine’s right bank intake manifold pressure. the engine is depressed.
Units are in-Hg absolute (kPa absolute). If an intake
manifold pressure sensor or wiring fault occurs, the 9 “Intake Mnfld Temp” This field displays the
status bar beneath this field signals an alarm (turns engine’s left bank intake manifold temperature.
yellow) and provides a message to fix the sensor or Units are ° F (° C). If an intake manifold temperature
wiring. NOTE: When a sensor or wiring fault is sensor or wiring fault occurs, the status bar beneath
detected, the field displays a default value, not the this field signals an alarm (turns yellow) and provides
actual value. the user a message to fix the sensor or wiring.
NOTE: When a sensor or wiring fault is detected, the
3 “Oil Pressure” This field displays the engine’s field displays a default value, not the actual value.
gauge oil pressure in the main oil header. Units
are psi (kPa gauge). If an oil pressure sensor or wiring 10 “Coolant Temp” This field displays the
fault occurs, the status bar beneath this field signals engine’s coolant temperature at the outlet of the
an alarm (turns yellow) and provides a message to fix engine. Units are ° F (° C). If a coolant temperature sen-
the sensor or wiring. NOTE: When a sensor or wiring sor or wiring fault occurs, the status bar beneath this
fault is detected, the field displays a default value, not field signals an alarm (turns yellow) and provides the
the actual value. user a message to fix the sensor or wiring.
NOTE: When a sensor or wiring fault is detected, the
4 “Engine Speed” This field displays current field displays a default value, not the actual value.
engine speed (rpm).
11 “Oil Temp” This field displays the engine’s oil
5 “Engine Setpoint” This field displays the temperature in the main oil header. Units are ° F
engine speed (rpm) setpoint. The engine speed (° C). If an oil temperature sensor or wiring fault occurs,
setpoint is determined by a user input, not internal cal- the status bar beneath this field signals an alarm
ibrations. (turns yellow) and provides the user a message to fix
the sensor or wiring. NOTE: When a sensor or wiring
6 “Percent Rated Load” This field displays an fault is detected, the field displays a default value, not
approximation of percent rated torque (load). the actual value.
The approximation is based on ECU inputs and engine
operating factors. Not applicable for 7042GSI/GL
engines.

7 “Estimated Power” This field displays an


approximation (±5%) of actual engine power in
BHP (kW). The approximation is based on ECU inputs
and assumes correct engine operation. Not applicable
for 7042GSI/GL engines.

FORM 6295 Fourth Edition 3.05-3


ESP PANEL DESCRIPTIONS
[F3] START-STOP PANEL DESCRIPTION

1 2 3 4 5

6 7 8

9 10 11

12

13

Figure 3.05-3 Start-Stop Panel in ESP – Fields 1 through 13

1 2 3 4 5

6 7 8

9 10 11

12

13

Figure 3.05-4 Start-Stop Panel in ESP – Fields 1 through 13 (7042GL Engine)

3.05-4 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F3] START-STOP PANEL DESCRIPTION – REFER TO FIGURE 3.05-3 AND FIGURE 3.05-4
The engine Start-Stop Panel displays engine speed, fuel valve is disengaged, the field is gray and signals
throttle position, average intake manifold pressure the user it is OFF.
(IMAP), and oil pressure (see Figure 3.05-3). The dis-
play also has signals for pre/post lube state, starting, 8 “User ESD” This field signals that an emer-
ignition enabled, starter engagement, main fuel, and if gency shutdown is in process based on a cus-
there is an emergency or normal shutdown. This panel tomer input. During an emergency shutdown, the field
also allows the user to make Start-Stop adjustments is red and signals the user that an E-STOP (emer-
by calibrating pre/post lube time, purge time, cool gency stop) is active. When E-STOP is displayed, the
down, fuel on RPM, starter off RPM, and driven equip- engine cannot be restarted. When the engine is not in
ment ESD speed. an emergency shutdown mode, the field is gray and
signals the user that the engine is ready to RUN.
The Start-Stop Panel on 7042GL/GSI engines also
displays prechamber fuel valve engagement informa-
9 “Avg IMAP” This field displays the average
tion and fields for calibration (see Figure 3.05-4).
intake manifold pressure. Units are in-Hg abso-
1 “Engine Speed” This field displays current lute (kPa absolute). On a vee engine, the left and right
engine speed (rpm). intake manifold pressure readings are averaged
together and displayed in this field. If one of the intake
2
“Throttle Position” This field displays throttle manifold pressure sensors fails, the field displays only
position in terms of the percentage the throttle the reading from the working sensor. If both sensors
valve is open. fail, the field is unable to display the actual value and a
default value is displayed instead.
3
“Starting Signal” This field signals when the
digital start signal, a digital input to the ECU, is 10 “Oil Pressure” This field displays the engine’s
high (8.6 – 36 volts) or low (< 3.3 volts). During the gauge oil pressure in the main oil header. Units
time the digital start signal is high, the field is green are psi (kPa gauge). If an oil pressure sensor or wiring
and signals the user it is ON. During the time the digi- fault occurs, the status bar beneath this field signals
tal start signal is low, the field is gray and signals the an alarm (turns yellow) and provides the user a mes-
user it is OFF. sage to fix the sensor or wiring. When a sensor or wir-
ing fault is detected, the field displays a default value,
4
“Pre/Post Lube” This field signals when the oil not the actual value.
pump is engaged and is either in pre- or
postlube. During the time the prelube oil pump is 11 “User RUN/STOP” This field signals that a nor-
engaged, the field is green and signals the user it is mal shutdown is in process based on a cus-
ON. During the time the prelube oil pump is disen- tomer input. During a normal shutdown, the field is red
gaged, the field is gray and signals the user it is OFF. and signals the user that the engine will STOP. When
STOP is displayed, the engine cannot be restarted.
5
“Ignition” This field signals when the IPM-D is When the engine is not in a shutdown mode, the field
enabled and is ready to receive a signal from is gray and signals the user that the engine is ready to
the ECU to fire each spark plug. During the time the RUN.
IPM-D is enabled, the field is green and signals the
user it is ON. During the time the ignition is disabled, 12 “Pre Lube Time” This field allows the user to
the field is gray and signals the user it is OFF. program engine prelube timing. Units are in sec-
onds. Prelube timing can be programmed from
6 “Starter” This field signals when the starter 0 – 10,800 seconds (0 – 180 minutes).
motor is engaged. The starter motor is engaged
based on “Starter Off RPM” and “Purge Time” set- 13 “Pre Lube Timer” This field allows the user to
tings. During the time the starter motor is engaged, the see the remaining time left for prelube. For
field is green and signals the user it is ON. During the example, if 300 seconds has been entered in the
time the starter motor is disengaged, the field is gray “Pre Lube Time” field, the “Pre Lube Timer” field will
and signals the user it is OFF. display zero until a start is requested. After the start
request, the pre lube timer will start counting down
7 “Main Fuel” This field signals when the main (from 300 seconds).
fuel valve is engaged by the ECU. During the
time the main fuel valve is engaged, the field is green
and signals the user it is ON. During the time the main
Field descriptions continued on next page...

FORM 6295 Fourth Edition 3.05-5


ESP PANEL DESCRIPTIONS
[F3] START-STOP PANEL DESCRIPTION

14 16 18 19 20

15 17 21 22 24

23 25

Figure 3.05-5 Start-Stop Panel in ESP – Fields 14 through 25 (VHP Series Four Engine)

26

19 21

16 14 27 18 20

17 15 28 22 24

23 25

Figure 3.05-6 Start-Stop Panel in ESP – Fields 14 through 28 (7042GL Engine)


3.05-6 FORM 6295 Fourth Edition
ESP PANEL DESCRIPTIONS
[F3] START-STOP PANEL DESCRIPTION – REFER TO FIGURE 3.05-5 AND FIGURE 3.05-6
14 15 “Fuel On RPM Adj” and “Fuel On RPM” 22 “Save to ECU” This button is used to save pro-
These fields allow the user to view and pro- grammed values to NVRAM (permanent mem-
gram the rpm at which the fuel valve is turned on. The ory) in the ECU. Changes saved to permanent
teal (blue-green) “Fuel On RPM” field displays the memory will not be lost if power to the ECU is
actual programmed rpm setting. The dark blue “Fuel removed. See Section 3.10 ESP Programming “Sav-
On RPM Adj” field allows the user to adjust the actual ing to Permanent Memory” for more information.
setting by entering a value from -50 to +100 rpm. NOTE: Programmed values not saved to permanent
When an adjustment is entered, the actual “Fuel On memory are stored in RAM (temporary memory).
RPM” is updated to reflect the adjustment. When values are in RAM, ESP can be closed and the
PC disconnected from the ECU while keeping all
16 17 “Starter Off RPM Adj” and “Starter Off changes; however, changes will be lost if power to the
RPM” These fields allow the user to view ECU is removed or when the engine is shut down.
and program the rpm at which the starter motor is
turned off. The teal (blue-green) “Starter Off RPM” 23 “Start Editing” This button must be clicked
field displays the actual programmed rpm setting. The prior to editing programmable (dark blue) fields
dark blue “Starter Off RPM Adj” field allows the user to in ESP. Clicking this button puts ESP in “editing mode.”
adjust the actual setting by entering a value from The user will not be able to enter new values if ESP is
0 to +100 rpm. When an adjustment is entered, the not in editing mode. While in editing mode, the button
actual “Starter Off RPM” is updated to reflect the will read, “Stop Editing – Currently Editing.” When the
adjustment. editing mode is off, the button will read “Start Editing.”
See Section 3.10 ESP Programming “Basic Program-
18 “Post Lube Time” This field allows the user to ming in ESP” for more information.
program engine postlube timing. Units are in
seconds. Postlube timing can be programmed from 24 “Undo Last Change” This button allows the
0 to 10,800 seconds (0 to 180 minutes). user to reset the last change made while in edit-
ing mode back to the programmed value that was last
“Cool Down” This field allows the user to pro- saved to permanent memory (NVRAM) in the ECU.
19
gram engine cooldown. Units are in seconds.
Cooldown is the amount of time that the engine will 25 “Undo All Changes” This button allows the
continue to run after a normal shutdown is activated. user to reset all the programmable fields back to
Cooldown can be programmed from the programmed parameters that were last saved to
0 to 10,800 seconds (0 to 180 minutes). permanent memory (NVRAM) in the ECU.

“Purge Time” This field allows the user to pro- 26 “Pre Ch Fuel” This field signals when the pre-
20
gram a purge time. Units are in seconds. Purge chamber fuel valve is turned on. During the time
time is the amount of time after first engine rotation the prechamber fuel valve is engaged, the field is
that must expire before the fuel valve and ignition are green and signals the user it is ON. During the time
turned on. NOTE: Although purge time can be pro- the prechamber fuel valve is disengaged, the field is
grammed from 0 to 1800 seconds (30 minutes), a gray and signals the user it is OFF.
purge time greater than 30 seconds will prevent the “Pre Ch On RPM Adj” and “Pre Ch On
27 28
engine from starting. RPM” These fields allow the user to view
and program the rpm at which the prechamber fuel
21 “Driven Equipment ESD” This field allows the valve is turned on. The teal (blue-green) “Pre Ch On
user to program an overspeed shutdown to pro- RPM” field displays the actual programmed rpm set-
tect driven equipment. Driven equipment overspeed ting. The dark blue “Pre Ch On RPM Adj” field allows
can be programmed from 0 to 2200 rpm. If pro- the user to adjust the actual setting by entering a value
grammed driven equipment overspeed exceeds from -50 to +300 rpm. When an adjustment is entered,
engine overspeed, the engine overspeed value takes the actual “Pre Ch On RPM” is updated to reflect the
precedence. For example, a VHP has a factory-pro- adjustment.
grammed engine overspeed trip point of 1320 rpm. If
the driven equipment overspeed is set to 1500 rpm,
and the engine speed exceeds 1320 rpm, the engine
will be shut down. If the driven equipment overspeed is
set to 1100 rpm and the engine speed exceeds
1100 rpm, but is less than 1320 rpm, the engine will
be shut down.

FORM 6295 Fourth Edition 3.05-7


ESP PANEL DESCRIPTIONS
[F4] GOVERNOR PANEL DESCRIPTION
The Governor Panel displays engine speed, throttle feedback, throttle position percentage, engine and remote
RPM setpoints, and average intake manifold pressure. In addition, this display shows the current state of the alter-
nate governing dynamics, load coming input, throttle alarm, remote RPM, and idle rpm activity. This panel also
allows the user to make governor adjustments by calibrating gain, droop, load inertia, idle, and other ESM system
governing control features such as synchronization speed, feedforward adjustments, and auto actuator calibration.

1 5 6 7
4

2 8 9

3 10 11

12

Figure 3.05-7 Governor Panel in ESP – Fields 1 through 12

3.05-8 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F4] GOVERNOR PANEL DESCRIPTION – REFER TO FIGURE 3.05-7


1 “Engine Speed” This field displays current 8 “Avg Intake Mnfld” This field displays the aver-
engine speed (rpm). age intake manifold pressure. Units are in-Hg
absolute (kPa absolute). On a vee engine, the left and
2 “Engine Setpoint RPM” This field displays the right intake manifold pressure readings are averaged
engine speed (rpm) setpoint. The engine speed together and displayed in this field. If one of the intake
setpoint is determined by a user input, not internal cal- manifold pressure sensors fails, the field displays only
ibrations. the reading from the working sensor. If both sensors
fail, the field is unable to display the actual value and a
3 “Remote RPM Setpoint” This field displays the default value is displayed instead.
remote rpm setpoint if the remote rpm input
4 – 20 mA (0.875 – 4.0 V) is active. The setpoint is 9 “Remote RPM” This field signals when the
only displayed in mA. remote rpm is ON or OFF. Remote rpm is deter-
mined by a customer digital input. When the input is
4 “Throttle Position” This field displays throttle high (8.6 – 36 volts), remote rpm is active. During the
position in terms of the percentage the throttle time the remote rpm input is high, the field is green
valve is open. and signals the user it is ON. During the time the
remote rpm input is low (< 3.3 volts), the field is gray
5 “Alt Dynamics” This field signals when the and signals the user it is OFF. When remote rpm is
Alternate Governor Dynamics digital input is OFF, engine speed is based on “Idle” (Field 11) and
high (8.6 – 36 volts) or low (< 3.3 volts). Alternate “High Idle RPM” (Field 13) or “Low Idle RPM”
dynamics or synchronizer mode is used to rapidly syn- (Field 17).
chronize an engine to the electric power grid by using
cylinder timing to maintain constant engine speed. 10 “Throttle Feedback” This field displays the
During the time the alternate dynamics input is high, throttle actuator’s position in mA. 4 mA = 0%;
the field is green and signals the user it is ON. During 20 mA = 100%.
the time the alternate dynamics input is low, the field is
gray and signals the user it is OFF. The lower gain val- 11 “Idle” This field indicates whether low idle rpm
ues can be used to minimize actuator movement when or high idle rpm is active. Low or high idle rpm is
the engine is synchronized to the grid and fully loaded determined by a customer digital input. When the input
to maximize actuator life. is low (< 3.3 volts), LOW is displayed in the pink field.
When the input is high (8.6 – 36 volts), HIGH is dis-
6 “Load Coming” This field signals when the played in the pink field. See “High Idle RPM” (Field 13)
load coming digital input is high (8.6 – 36 volts) and “Low Idle RPM” (Field 17) for values of high and
or low (< 3.3 volts). Load coming or feedforward con- low idle.
trol is used to allow the engine to accept large load
additions. During the time the load coming input is 12 “Load Inertia” This field must be programmed
high, the field is green and signals the user that YES, by the user for proper engine operation. By pro-
the load coming feature is being used. During the time gramming the load inertia or rotating mass moment of
the load coming input is low, the field is gray and sig- inertia of the driven equipment, the governor gain is
nals the user that NO, the load coming feature is not preset correctly, aiding rapid startup of the engine. If
being used. this field is programmed correctly, there should be no
need to program gain adjustments [“Proportional Gain
7 “Throttle Error” This field signals when the Adj” (Field 15), “Integral Gain Adj” (Field 18), and “Dif-
throttle actuator sends a digital input to the ECU ferential Gain Adj” (Field 20)]. The rotating mass
indicating the actuator is in an alarm state. During the moment of inertia must be known for each piece of
time when the throttle actuator is in an alarm state, the driven equipment and then added together. See
field is yellow and signals the user that YES, a throttle Section 3.10 ESP Programming “Programming Load
actuator fault exists (ALM441). During the time when Inertia” for more information. NOTE: Rotating moment
the throttle actuator is not in an alarm state, the field is of inertia is not the weight or mass of the driven equip-
gray and signals the user that NO throttle actuator fault ment. It is an inherent property of the driven equip-
exists. ment and does not change with engine speed or load.
Contact the coupling or driven equipment manufac-
turer for the moment of inertia value.

Field descriptions continued on next page...

FORM 6295 Fourth Edition 3.05-9


ESP PANEL DESCRIPTIONS

[F4] GOVERNOR PANEL DESCRIPTION

15 18 20

13 16 19

14 17

Figure 3.05-8 Governor Panel in ESP – Fields 13 through 20

3.05-10 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F4] GOVERNOR PANEL DESCRIPTION – REFER TO FIGURE 3.05-8


13 “High Idle RPM” This field allows the user to actual programmed low idle rpm setting. The dark blue
program the high idle rpm. The high idle setting “Low Idle Adj” field allows the user to adjust the actual
is used when the rated speed/idle speed digital input setting by entering a value from -50 to +100 rpm.
is high (8.6 – 36 volts) and “Remote RPM” (Field 9) is When an adjustment is entered, the actual “Low Idle
OFF. The high idle rpm can be programmed from RPM” is updated to reflect the adjustment. NOTE: The
800 to 2200 rpm (not to exceed a preprogrammed low idle rpm cannot be set above the high idle rpm.
maximum speed). Internal calibrations prevent the
engine from running faster than rated speed +10%. 18 “Integral Gain Adj” This field allows the user to
adjust integral gain by a multiplier of
14 “Auto Actuator Calibration” This field allows 0.502 – 1.102 and 0.000. Integral gain is a correction
the user to program the ESM system to auto- function to speed error that is based on the amount of
matically calibrate the throttle actuator during every time the error is present. When an error exists
normal shutdown. The benefits to calibrating the actu- between actual engine speed and engine speed set-
ator automatically are (1) performing the calibration point, an integral gain calibrated by Waukesha Engine
when the actuator is hot (normal operating condition), is multiplied to the integral of the speed error. This is
and (2) if any actuator problems are detected, they are done to increase or decrease throttle response to cor-
found on engine shutdown and not startup. See rect or reduce speed error. Although the user can pro-
Section 3.10 ESP Programming “Actuator Calibration” gram the integral gain multiplier with this field to
for more information. “fine-tune” throttle response, it is typically not adjusted.
“Proportional Gain Adj” (Field 15) and “Differential
15 “Proportion Gain Adj” This field allows the Gain Adj” (Field 20) are also used to correct speed
user to adjust proportional gain by a multiplier of error. See speed error correction equation under the
0.500 – 1.050. Proportional gain is a correction func- description for Field 15.
tion to speed error that is proportional to the amount of
error. When an error exists between actual engine 19 “Sync RPM” This field allows the user to pro-
speed and engine speed setpoint, a proportional gain gram a synchronous rpm to allow easier syn-
calibrated by Waukesha Engine is multiplied to the chronization to the electric grid. The additional rpm
speed error. This is done to increase or decrease programmed in this field is added to the engine set-
throttle response to correct speed error. Although the point rpm if the “Alt Dynamics” field is ON. The syn-
user can program the proportional gain multiplier with chronous rpm can be programmed from 0 to 64 rpm.
this field to “fine-tune” throttle response, it is typically
not adjusted. “Integral Gain Adj” (Field 18) and “Differ- 20 “Differential Gain Adj” This field allows the
ential Gain Adj” (Field 20) are also used to correct user to adjust differential gain by a multiplier of
speed error: 0.502 – 1.102 and 0.000. Differential gain is a correc-
tion function to speed error that is based on direction
Correction = and rate of change. When an error exists between
actual engine speed and engine speed setpoint, a dif-
( speed error × proportional gain × proportional gain adjust ) + ferential gain calibrated by Waukesha Engine is multi-
plied to the derivative of the speed error. This is done
to increase or decrease throttle response to correct or
x reduce speed error. Although the user can program
⎛ ⎞
⎜ ⎟


∫ speed error dt × integral gain × integral gain adjust⎟ +

the differential gain multiplier with this field to
“fine-tune” throttle response, it is typically not adjusted.
⎝ o ⎠ “Proportional Gain Adj” (Field 15) and “Integral Gain
Adj” (Field 18) are also used to correct speed error.
See speed error correction equation under the
⎛ d----------------------------------
speed error
- × differential gain × differential gain adjust⎞ description for Field 15.
⎝ dt ⎠

16 17 “Low Idle Adj” and “Low Idle RPM” These Field descriptions continued on next page...
fields allow the user to view and program the
low idle rpm setting. The low idle setting is used when
the rated speed/idle speed digital input is low
(< 3.3 volts) and “Remote RPM” (Field 9) is OFF. The
teal (blue-green) “Low Idle RPM” field displays the

FORM 6295 Fourth Edition 3.05-11


ESP PANEL DESCRIPTIONS

[F4] GOVERNOR PANEL DESCRIPTION

22

21 23 24

25 26 27 29

28

Figure 3.05-9 Governor Panel in ESP – Fields 21 through 29

3.05-12 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F4] GOVERNOR PANEL DESCRIPTION – REFER TO FIGURE 3.05-9


21 “Proportional Sync” This field allows the user 26 “Save to ECU” This button is used to save pro-
to adjust proportional synchronous gain by a grammed values to NVRAM (permanent mem-
multiplier of 0.500 – 1.050. Proportional synchronous ory) in the ECU. Changes saved to permanent
gain is a correction function to speed error that is pro- memory will not be lost if power to the ECU is
portional to the amount of error when operating in removed. See Section 3.10 ESP Programming “Sav-
Alternate Dynamics mode only. Proportional synchro- ing to Permanent Memory” for more information.
nous gain is a lower multiplier than proportional gain NOTE: Programmed values not saved to permanent
because of the need to synchronize to the electric grid. memory are stored in RAM (temporary memory).
When an error exists between actual engine speed When values are in RAM, ESP can be closed and the
and engine speed setpoint, a Waukesha-calibrated PC disconnected from the ECU while keeping all
proportional synchronous gain is multiplied to the changes; however, changes will be lost if power to the
speed error. This is done to increase or decrease ECU is removed or when the engine is shut down.
throttle response to correct speed error. Although the
user can program the proportional synchronous gain 27 “Undo Last Change” This button allows the
multiplier with this field to “fine-tune” throttle response, user to reset the last change made while in edit-
it is typically not adjusted. “Integral Gain Adj” (Field 18) ing mode back to the programmed parameter that was
and “Differential Gain Adj” (Field 20) are also used to last saved to permanent memory (NVRAM) in the
correct speed error. See speed error correction equa- ECU.
tion on page 3.05-11 under the description for
Field 15. 28 “Undo All Changes” This button allows the
user to reset all the programmable fields back to
22 “Forward Torque” This field allows the user to the programmed parameters that were last saved to
program the forward torque amount of load permanent memory (NVRAM) in the ECU.
coming. When the load coming signal goes high, and
after the forward delay timer has expired, the throttle 29 “Manual Actuator Calibration” This button
opens by the programmed torque percent. The forward allows the user to manually calibrate the throttle
torque can be programmed from 0 to 125%. actuator. To work correctly, the ESM system must
know the fully closed and fully open end points of
23 “Forward Delay” This field allows the user to throttle actuator movement. To establish the fully
program the forward delay timer of load coming. closed and fully open end points, the throttle actuator
When the load coming signal goes high, the forward must be calibrated. A manual calibration can be per-
delay must expire before the throttle opens to the pro- formed when the engine is not rotating and after
grammed torque percent. Units are in seconds. The postlube and the ESM system’s post-processing is
forward delay can be programmed from complete. If an emergency shutdown is active, a man-
0 to 60 seconds. ual calibration cannot be completed. See Section 3.10
ESP Programming “Actuator Calibration” for more
24 “Droop” This field allows the user to adjust the information.
percent of droop. Droop allows steady-state
speed to drop as load is applied. Droop is expressed
as a percentage of normal average speed. Droop can
be programmed from 0 to 5%.

25 “Start Editing” This button must be clicked


prior to editing programmable (dark blue) fields
in ESP. Clicking this button puts ESP in “editing mode.”
The user will not be able to enter new values if ESP is
not in editing mode. While in editing mode, the button
will read “Stop Editing – Currently Editing.” When the
editing mode is off, the button will read “Start Editing.”
See Section 3.10 ESP Programming “Basic Program-
ming in ESP” for more information.

FORM 6295 Fourth Edition 3.05-13


ESP PANEL DESCRIPTIONS

[F5] IGNITION PANEL DESCRIPTION


The Ignition Panel displays engine speed, intake manifold pressure, ignition timing for each cylinder, ignition
enabled, ignition level, maximum retard, WKI value used, and knock detection. This panel also allows the user to
make IPM-D adjustments by calibrating high voltage, low voltage, and no spark limits. In addition, the WKI value
and NOx emission levels (for use on LT engines only) are calibrated on the Ignition Panel.

1 2 3 4 5 6 7

8 9 10

11 12

Figure 3.05-10 Ignition Panel in ESP – Fields 1 through 12

3.05-14 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F5] IGNITION PANEL DESCRIPTION – REFER TO FIGURE 3.05-10


1 “Left Bank Ignition Timing” This field displays 7 “Max Retard” This field alerts the user when
individual cylinder timing in degrees before top any cylinder’s timing has reached the maximum
dead center (° BTDC). retard in timing allowed. If any cylinder’s timing is at
maximum retard, the field is yellow and signals the
2 3 “Left Bank Spark Ref #” and “Right Bank user that YES, a cylinder is at maximum retard. The
Spark Ref #” These fields display the spark user can determine which cylinder(s) are at maximum
reference number for each cylinder. The spark refer- retard by looking for the lowest individual cylinder tim-
ence numbers can be used to represent spark plug ing displayed on the left of the screen. When none of
electrode wear (gap) and can be monitored (for exam- the cylinders are at maximum retard, the field is gray
ple, with MODBUS®) and trended to predict the time of and signals the user that NO cylinders are at maxi-
spark plug failure. The spark reference number is an mum retard.
arbitrary number based on relative voltage demand
and is a feature of the IPM-D’s predictive diagnostics 8 “Engine Speed” This field displays current
capability. A gradual increase in the spark reference engine speed (rpm).
number is expected over time as the spark plug wears.
The closer to end of spark plug life, the faster the num- 9 “Ignition” This field signals when the IPM-D is
ber will increase. If sufficient spark plug wear is moni- enabled and is ready to receive a signal from
tored, IPM-D raises the power level of the ignition coil the ECU to fire each spark plug. During the time the
to Level 2 (see description for “Ignition Energy” field IPM-D is enabled, the field is green and signals the
below). Once Level 2 energy is applied, the spark ref- user it is ON. During the time the ignition is disabled,
erence number will decrease initially but the Fault Log the field is gray and signals the user it is OFF.
will indicate the cylinder number of the spark plug that
is wearing out. NOTE: When using MODBUS® the cyl- 10 “Knocking” This field alerts the user that knock
inder number is in firing order. For example, if #5 cylin- is present when the cylinder timing is at maxi-
der triggers an alarm for having a worn-out spark plug, mum retard. When knock is sensed with at least one
the user should check the spark plug of the 5th cylin- cylinder, the field is yellow and signals the user that
der in the firing order. YES, knock is present. The user can determine which
cylinder(s) is knocking by looking at the individual cyl-
4 “Right Bank Ignition Timing” This field dis- inder timings displayed on the left of the screen.
plays individual cylinder timing in degrees
before top dead center (° BTDC). 11 “User WKI in Use” This field indicates whether
the WKI (Waukesha Knock Index) value used by
5 “Avg Intake Mnfld” This field displays the aver- the ESM system is based on the user-defined value
age intake manifold pressure. Units are in-Hg programmed in “User WKI” (Field 19) or is remotely
absolute (kPa absolute). On a vee engine, the left and inputted to the ECU using a 4 – 20 mA optional user
right intake manifold pressure readings are averaged input. When the WKI value is programmed in ESP, the
together and displayed in this field. If one of the intake field indicates “User WKI in Use.” When the WKI value
manifold pressure sensors fails, the field displays only is being inputted in real time through the optional ana-
the reading from the working sensor. If both sensors log user input, the field indicates “Remote WKI in Use.”
fail, the field is unable to display the actual value and a
default value is displayed instead. 12 “User ESD” This field signals that an emer-
gency shutdown is in process based on a cus-
6 “Ignition Energy” This field indicates at what tomer input. During an emergency shutdown, the field
level of energy the IPM-D is firing the spark is red and signals the user that an E-STOP (emer-
plugs: Level 1 (low/normal) or Level 2 (high). During gency stop) is active. When E-STOP is displayed, the
normal engine operation, the IPM-D fires at a Level 1 engine cannot be restarted. When the engine is not in
ignition energy. The IPM-D fires at a Level 2 ignition an emergency shutdown mode, the field is gray and
energy on engine startup or as a result of spark plug signals the user that the engine is ready to RUN.
wear. If the ignition energy is raised to Level 2 (except
on startup), an alarm is triggered to alert the operator.
The pink field will signal the user whether the ignition Field descriptions continued on next page...
level is LEVEL 1 or LEVEL 2.

FORM 6295 Fourth Edition 3.05-15


ESP PANEL DESCRIPTIONS

[F5] IGNITION PANEL DESCRIPTION

13 15 17

14 16 18

Figure 3.05-11 Ignition Panel in ESP – Fields 13 through 18

3.05-16 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F5] IGNITION PANEL DESCRIPTION – REFER TO FIGURE 3.05-11


13 14 “High Voltage Adj.” and “High Voltage the actual programmed low voltage limit setting. The
Limit” These fields allow the user to view dark blue “Low Voltage Adj.” field allows the user to
and adjust the high voltage alarm limit setting. The high adjust the actual setting by entering a value from -30 to
voltage limit is based on the spark reference number. +30. When an adjustment is entered, the actual “Low
When a cylinder’s spark reference number exceeds the Voltage Limit” is updated to reflect the adjustment. See
high voltage limit, the ignition energy is raised to a Section 3.10 ESP Programming “IPM-D Programming”
Level 2 (high) ignition energy and an alarm is triggered. for more information. NOTE: The “Low Voltage Limit”
Based on a thorough trend analysis of the spark refer- field has a defined range (min./max.) that can be pro-
ence numbers, the user may want to adjust the high grammed. If the user programs a positive or negative
voltage limit to fit the specific needs of the engine. adjustment that exceeds this defined range, the “Low
Improper use of this adjustment may limit the effective- Voltage Limit” field will display the actual low voltage
ness of IPM-D diagnostics. Programming the “High setting, even though the adjustment entered may calcu-
Voltage Adj.” to a positive number will delay triggering late to be different. For example, if the default low volt-
the high voltage limit alarm until the spark plugs are age limit is 100 but cannot exceed 120 for the engine (a
more worn. Likewise, reducing the “High Voltage Adj.” factory setting), the “Low Voltage Limit” field will display
will advance triggering the high voltage limit alarm, the actual low voltage setting. So if the user programs
allowing more time between when an alarm is triggered an adjustment of +30 (which exceeds 120), “30” will
and spark plug failure. The teal (blue-green) “High Volt- appear in the “Low Voltage Adj.” field and “120” will
age Limit” field displays the actual programmed high appear in the “Low Voltage Limit” field. The same holds
voltage limit setting. The dark blue “High Voltage Adj.” true for negative adjustments.
field allows the user to adjust the actual setting by
entering a value from -30 to +30. When an adjustment 17 18 “No Spark Adj.” and “No Spark Limit” The
“No Spark Adj.” and “No Spark Limit” fields
is entered, the actual “High Voltage Limit” is updated to
allow the user to view and adjust the no spark alarm
reflect the adjustment. See Section 3.10 ESP Program-
limit setting. The no spark limit is based on the spark
ming “IPM-D Programming” for more information.
reference number. When a cylinder’s spark reference
NOTE: The “High Voltage Limit” field has a defined
number exceeds the no spark limit, an alarm is trig-
range (min./max.) that can be programmed. If the user
gered, indicating that a spark plug is worn and must be
programs a positive or negative adjustment that
replaced. Based on a thorough trend analysis of the
exceeds this defined range, the “High Voltage Limit”
spark reference numbers, the user may want to adjust
field will display the actual high voltage setting, even
the no spark limit to fit the specific needs of the
though the adjustment entered may calculate to be dif-
engine. Improper use of this adjustment may limit the
ferent. For example, if the default high voltage limit is
effectiveness of IPM-D diagnostics. Typically this limit
170 but cannot exceed 190 for the engine (a factory
is not adjusted. The teal (blue-green) “No Spark Limit”
setting), the “High Voltage Limit” field will display the
field displays the actual programmed no spark limit
actual high voltage setting. So if the user programs an
setting. The dark blue “No Spark Adj.” field allows the
adjustment of +30 (which exceeds 190), “30” will
user to adjust the actual setting by entering a value
appear in the “High Voltage Adj.” field and “190” will
from -25 to +25. When an adjustment is entered, the
appear in the “High Voltage Limit” field. The same
actual “No Spark Limit” is updated to reflect the adjust-
holds true for negative adjustments.
ment. See Section 3.10 ESP Programming “IPM-D
Programming” for more information. NOTE: The “No
15 16 “Low Voltage Adj.” and “Low Voltage Spark Limit” field has a defined range (min./max.) that
Limit” These fields allow the user to view and
can be programmed. If the user programs a positive or
adjust the low voltage alarm limit setting. The low volt-
negative adjustment that exceeds this defined range,
age limit is based on the spark reference number. When
the “No Spark Limit” field will display the actual no
a cylinder’s spark reference number goes below the low
spark setting even though the adjustment entered may
voltage limit, an alarm is triggered, identifying a low volt-
calculate to be different. For example, if the default no
age demand condition that may have resulted from a
spark limit is 200 but cannot exceed 215 for the engine
shorted coil or secondary lead, deposit buildup or a
(a factory setting), the “No Spark Limit” field will dis-
failed spark plug (failure related to “balling” or shorting).
play the actual no spark setting. So if the user pro-
Based on a thorough trend analysis of the spark refer-
grams an adjustment of +25 (which exceeds 215), “25”
ence numbers, the user may want to adjust the low volt-
will appear in the “No Spark Adj.” field and “215” will
age limit to fit the specific needs of the engine. Improper
appear in the “No Spark Limit” field. The same holds
use of this adjustment may limit the effectiveness of
true for negative adjustments.
IPM-D diagnostics. Typically this limit is not adjusted.
The teal (blue-green) “Low Voltage Limit” field displays Field descriptions continued on next page...

FORM 6295 Fourth Edition 3.05-17


ESP PANEL DESCRIPTIONS

[F5] IGNITION PANEL DESCRIPTION

19 20

21 22 23

24

Figure 3.05-12 Ignition Panel in ESP – Fields 19 through 24

3.05-18 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F5] IGNITION PANEL DESCRIPTION – REFER TO FIGURE 3.05-12


19 “User WKI” This field MUST be programmed 22 “Save to ECU” This button is used to save pro-
by the user for proper engine operation. The grammed values to NVRAM (permanent mem-
user must enter the WKI (Waukesha Knock Index) ory) in the ECU. Changes saved to permanent
value of the fuel. The WKI value can be determined memory will not be lost if power to the ECU is
using an application program for the Microsoft® Win- removed. See Section 3.10 ESP Programming “Sav-
dows® XP operating system. The computer program ing to Permanent Memory” for more information.
will calculate the WKI value from a customer’s gas NOTE: Programmed values not saved to permanent
analysis breakdown. The WKI value application pro- memory are stored in RAM (temporary memory).
gram designed by Waukesha Engine uses an index for When values are in RAM, ESP can be closed and the
calculating knock resistance of gaseous fuels. The PC disconnected from the ECU while keeping all
WKI value must be based on the composition of a fuel changes; however, changes will be lost if power to the
sample taken from the engine site and analyzed using ECU is removed or when the engine is shut down.
the application program or as dictated on a Special
Application Approval (SAA). Contact your local Distrib- 23 “Undo Last Change” This button allows the
utor for more information. user to reset the last change made while in edit-
ing mode back to the programmed parameter that was
20 “NOx” (For use on LT engines only.) This field last saved to permanent memory (NVRAM) in the
allows the user to set the desired NOx emis- ECU.
sions level (engine out at the exhaust stack) at which
the engine will run. The field displays the programmed 24 “Undo All Changes” This button allows the
NOx level, not the actual level. Based on the pro- user to reset all the programmable fields back to
grammed NOx level, the ESM system will adjust igni- the programmed parameters that were last saved to
tion timing in an attempt to meet the programmed NOx permanent memory (NVRAM) in the ECU.
level. However, the actual NOx output of the engine
will not always match the programmed NOx level for
several reasons. First, the ESM system calculates
NOx based on a combination of sensor readings
logged by the ECU and Waukesha-calibrated values.
Two examples of Waukesha-calibrated values are
humidity and exhaust oxygen since the ESM system
does not measure these variables. Also, the ESM sys-
tem includes a preprogrammed correction factor to
allow for statistical variations with the engine. As a
result, the engine in most cases will emit less NOx
than the actual programmed NOx level. Units are in
g/BHP-hr or mg/m3 (n) @ 0° C, 101.25 kPa, 5% O2.
The range that NOx can be programmed varies with
the engine (L5794LT range is 1.5 – 5.0 g/BHP-hr).
NOTE: To correct for differences in the actual
engine-out NOx emissions and that of the pro-
grammed NOx level, the user input should be adjusted
in the appropriate direction until the actual engine-out
emissions meet the user’s desired level (e.g., the NOx
field may require a value of 2.5 g/BHP-hr to achieve
2.0 g/BHP-hr NOx emissions at the exhaust stack).

21 “Start Editing” This button must be clicked


prior to editing programmable (dark blue) fields
in ESP. Clicking this button puts ESP in “editing mode.”
The user will not be able to enter new values if ESP is
not in editing mode. While in editing mode, the button
will read “Stop Editing – Currently Editing.” When the
editing mode is off, the button will read “Start Editing.”
See Section 3.10 ESP Programming “Basic Program-
ming in ESP” for more information.

FORM 6295 Fourth Edition 3.05-19


ESP PANEL DESCRIPTIONS

[F6] AFR PRIMARY FUEL PANEL DESCRIPTION


The AFR Primary Fuel Panel is used to monitor AFR system performance. This panel displays engine speed and
target Lambda. Also, displayed for both left and right banks are the actual Lambda, primary stepper position, mini-
mum and maximum stepper setpoints, stepper operating mode, intake manifold pressure, oxygen and exhaust sen-
sor status, and AFR operating mode (automatic or manual). This panel also allows the user to change either bank
from automatic to manual mode and adjust stepper position using the arrow buttons.

1 2 3
13
4 5

6 14
9
7 8

12
10

11

Figure 3.05-13 AFR Primary Fuel Panel in ESP – Fields 1 through 14

3.05-20 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F6] AFR PRIMARY FUEL PANEL DESCRIPTION – REFER TO FIGURE 3.05-13


1 “Start” This field signals when the engine is in 8 “Max Position” This field displays the maxi-
its starting mode and the left bank stepper mum left bank stepper position that is pro-
motor is held at a user-defined start position pro- grammed on the [F8] AFR Setup Panel. The value
grammed on the [F8] AFR Setup Panel. When the displayed is the maximum stepper motor position at
engine is not in start mode, the field is gray. the engine’s current intake manifold pressure level.

2 “Automatic” This field signals that the ESM 9 “Check Box for Left Bank Manual Mode” This
AFR system is automatically controlling stepper field allows the user to change the AFR system
movement. When the AFR system is not in automatic mode of operation on the engine’s left bank from auto-
control, the field is gray. matic to manual mode. Normally the AFR system
operates in automatic mode; however, the user can
3 “Manual” This field signals that the user has click the check box changing the system to manual
selected to be in manual mode. Manual mode mode. Manual mode allows the user to adjust stepper
allows the user to adjust stepper position using the position using the arrow buttons on the panel. When
arrow buttons (<< < > >>). When in manual mode, the changed into manual mode, the AFR system does not
AFR system does not perform any automatic stepper perform any automatic stepper adjustments; it will only
adjustments; it will only move stepper position with move stepper position with user adjustment. Check
user adjustment. When the AFR system is not in man- mark is ON; no check mark is OFF.
ual mode, the field is gray.
10 “Primary Left Stepper Position” This field dis-
4 “Intake Mnfld” This field displays the engine’s plays the current position of the left bank step-
left bank intake manifold pressure. Units are per motor.
in-Hg absolute (kPa absolute). If an intake manifold
pressure sensor or wiring fault occurs, the status bar 11 “Arrow Buttons” and “Home” The AFR sys-
beneath this field signals an alarm (turns yellow) and tem must be in manual mode for the user to use
provides a message to fix the sensor or wiring. NOTE: the left bank arrow buttons. The double arrow buttons
When a sensor or wiring fault is detected, the field dis- (<< >>) move the stepper motor up or down in 400-
plays a default value, not the actual value. step increments. The single arrow buttons (< >) move
the stepper motor up or down in 25-step increments.
5 “Exhaust Temp” This field displays the The home button moves the stepper motor to the
post-turbine, left bank, exhaust temperature. home position and then back to the start position only
Units are ° F (° C). If an exhaust sensor or wiring fault when the engine is not running. If the user clicks on
occurs, the status bar beneath this field signals an the home button while the engine is running, an error
alarm (turns yellow) and provides a message to fix the message appears.
sensor or wiring. NOTE: When a sensor or wiring fault
12 “Oxygen Sensor” This field displays the volt-
is detected, the field displays a default value, not the
age of the left bank oxygen sensor. If an oxygen
actual value.
sensor or wiring fault occurs, the status bar beneath
this field signals an alarm (turns yellow) and provides
6 “Actual Lambda” This field displays actual
a message to fix the sensor or wiring. NOTE: When a
Lambda. Lambda is equal to the amount of air
sensor or wiring fault is detected, the field displays a
present relative to that of a stoichiometric mixture. For
default value, not the actual value.
example, a Lambda of 1.0000 is equal to an air/fuel
ratio of approximately 16:1. Slightly rich of stoichiome- 13 “Engine Speed” This field displays current
try, or a Lambda of 0.995, is the typical setpoint of cat- engine speed (rpm).
alyst engines.
14 “Target Lambda” This field displays the target
7 “Min Position” This field displays the minimum Lambda setpoint the AFR system is adjusting
left bank stepper position that is programmed on the stepper position to maintain. The target Lambda is
the [F8] AFR Setup Panel. The value displayed is the based on a Waukesha-calibrated value and a user off-
minimum stepper motor position at the engine’s cur- set programmed on the [F8] AFR Setup Panel.
rent intake manifold pressure level.

Field descriptions continued on next page...

FORM 6295 Fourth Edition 3.05-21


ESP PANEL DESCRIPTIONS

[F6] AFR PRIMARY FUEL PANEL DESCRIPTION

15 16 17

18 19

20

21
22 23

25
24

26

Figure 3.05-14 AFR Primary Fuel Panel in ESP – Fields 15 through 26

3.05-22 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F6] AFR PRIMARY FUEL PANEL DESCRIPTION – REFER TO FIGURE 3.05-14


15 “Start” This field signals when the engine is in 21 “Check Box For Right Bank Manual Mode”
its starting mode and the right bank stepper This field allows the user to change the AFR sys-
motor is held at a user-defined start position pro- tem mode of operation on the engine’s right bank from
grammed on the [F8] AFR Setup Panel. When the automatic to manual mode. Normally the AFR system
engine is not in start mode, the field is gray. operates in automatic mode; however, the user can
click the check box changing the system to manual
16 “Automatic” This field signals that the ESM mode. Manual mode allows the user to adjust stepper
AFR system is automatically controlling stepper position using the arrow buttons on the panel. When
movement. When the AFR system is not in automatic changed into manual mode, the AFR system does not
control, the field is gray. perform any automatic stepper adjustments; it will only
move stepper position with user adjustment. Check
17 “Manual” This field signals that the user has mark is ON; no check mark is OFF.
selected to be in manual mode. Manual mode
22 “Min Position” This field displays the minimum
allows the user to adjust stepper position using the
right bank stepper position that is programmed
arrow buttons (<< < > >>). When in manual mode, the
on the [F8] AFR Setup Panel. The value displayed is
AFR system does not perform any automatic stepper
the minimum stepper motor position at the engine’s
adjustments; it will only move stepper position with
current intake manifold pressure level.
user adjustment. When the AFR system is not in man-
ual mode, the field is gray.
23 “Max Position” This field displays the maximum
right bank stepper position that is programmed
18 “Exhaust Temp” This field displays the post-tur-
on the [F8] AFR Setup Panel. The value displayed is
bine, right bank, exhaust temperature. Units are
the maximum stepper motor position at the engine’s
°F (°C). If an exhaust sensor or wiring fault occurs, the
current intake manifold pressure level.
status bar beneath this field signals an alarm (turns
yellow) and provides the user a message to fix the sen-
24 “Oxygen Sensor” This field displays the volt-
sor or wiring. NOTE: When a sensor or wiring fault is
age of the right bank oxygen sensor. If an oxy-
detected, the field displays a default value, not the
gen sensor or wiring fault occurs, the status bar
actual value.
beneath this field signals an alarm (turns yellow) and
19 “Intake Mnfld” This field displays the engine’s provides the user a message to fix the sensor or wiring.
right bank intake manifold pressure. Units are NOTE: When a sensor or wiring fault is detected, the
in-Hg absolute (kPa absolute). If an intake manifold field displays a default value, not the actual value.
pressure sensor or wiring fault occurs, the status bar
25 “Primary Right Stepper Position” This field
beneath this field signals an alarm (turns yellow) and
displays the current position of the right bank
provides the user a message to fix the sensor or wiring.
stepper motor.
NOTE: When a sensor or wiring fault is detected, the
field displays a default value, not the actual value.
26 “Arrow Buttons” and “Home” The AFR sys-
tem must be in manual mode for the user to use
20 “Actual Lambda” This field displays actual
the right bank arrow buttons. The double arrow buttons
Lambda. Lambda is equal to the amount of air
(<< >>) move the stepper motor up or down in 400-step
present relative to that of a stoichiometric mixture. For
increments. The single arrow buttons (< >) move the
example, a Lambda of 1.0000 is equal to an air/fuel
stepper motor up or down in 25-step increments. The
ratio of approximately 16:1. Slightly rich of stoichiome-
home button moves the stepper motor to the home
try, or a Lambda of 0.995, is the typical setpoint of cat-
position and then back to the start position only when
alyst engines.
the engine is not running. If the user clicks on the home
button while the engine is running, an error message
appears.

Field descriptions continued on next page...

FORM 6295 Fourth Edition 3.05-23


ESP PANEL DESCRIPTIONS

[F6] AFR PRIMARY FUEL PANEL DESCRIPTION

29
27 28
30

Figure 3.05-15 AFR Primary Fuel Panel in ESP – Fields 27 through 30

3.05-24 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F6] AFR PRIMARY FUEL PANEL DESCRIPTION – REFER TO FIGURE 3.05-15


27 “Stop Editing – Currently Editing” This but-
ton must be clicked prior to editing programma-
ble (dark blue) fields in ESP. Clicking this button puts
ESP in “editing mode.” The user will not be able to
enter new values if ESP is not in editing mode. While in
editing mode, the button will read “Stop Editing – Cur-
rently Editing.” When the editing mode is off, the button
will read “Start Editing.” See Section 3.10 ESP Pro-
gramming “Basic Programming in ESP” for more infor-
mation.

28 “Save to ECU” This button is used to save pro-


grammed values to NVRAM (permanent mem-
ory) in the ECU. Changes saved to permanent memory
will not be lost if power to the ECU is removed. See
Section 3.10 ESP Programming “Saving to Permanent
Memory” for more information. NOTE: Programmed
values not saved to permanent memory are stored in
RAM (temporary memory). When values are in RAM,
ESP can be closed and the PC disconnected from the
ECU while keeping all changes; however, changes will
be lost if power to the ECU is removed or when the
engine is shut down.

29 “Undo Last Change” This button allows the


user to reset the last change made while in edit-
ing mode back to the programmed parameter that was
last saved to permanent memory (NVRAM) in the
ECU.

30 “Undo All Changes” This button allows the


user to reset all the programmable fields back to
the programmed parameters that were last saved to
permanent memory (NVRAM) in the ECU.

FORM 6295 Fourth Edition 3.05-25


ESP PANEL DESCRIPTIONS

[F8] AFR SETUP PANEL DESCRIPTION


The AFR Setup Panel is used to program and fine-tune the AFR system. This panel will only be displayed on an
engine equipped with Waukesha factory installed air/fuel ratio control. This panel displays engine speed, target
Lambda and displayed for both left and right banks are the intake manifold pressure, actual Lambda, and primary
stepper position. This panel also allows the user to calibrate the dither steps, gain, oxygen target Lambda offset,
and the minimum/maximum stepper positions. The user can set either left or right banks start (or home) position,
stepper position using the arrow buttons, length of stepper motor shaft used, and change from automatic to manual
mode.

2
1 3

4 5 11

6 7 12

8 10 13

Figure 3.05-16 AFR Setup Panel in ESP – Fields 1 through 13

3.05-26 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F8] AFR SETUP PANEL DESCRIPTION REFER TO FIGURE 3.05-16


1 “Engine Speed” This field displays current 8 “Primary Left Stepper Position” This field dis-
engine speed (rpm). plays the current position of the left bank step-
per motor.
2 “Dither Steps” This field allows the user to pro-
gram dither steps that allow the AFR system to 9 “Arrow Buttons” and “Home” The AFR sys-
oscillate around the stepper’s normal movements plus tem must be in manual mode for the user to use
or minus a user-programmed number of steps (0 = the left bank arrow buttons. The double arrow buttons
OFF; 8 = ±8 steps; 12 = ±12 steps; 16 = ±16 steps; (<< >>) move the stepper motor up or down in
20 = ±20 steps). 400-step increments. The single arrow buttons (< >)
move the stepper motor up or down in 25-step incre-
3 “Target Lambda” This field displays the target
ments. The home button moves the stepper motor to
Lambda setpoint the AFR system is adjusting
the home position and then back to the start position
stepper position to maintain. The target Lambda is
only when the engine is not running. If the user clicks
based on a Waukesha-calibrated value and a user off-
on the home button while the engine is running, an
set programmed in Field 12.
error message appears.
4 “Intake Mnfld LB” This field displays the
engine’s intake manifold pressure. Units are 10 “Start Position Left” This field displays the
in-Hg absolute (kPa absolute). If an intake manifold start position of the left bank stepper motor.
pressure sensor or wiring fault occurs, the status bar
beneath this field signals an alarm (turns yellow) and 11 “Gain Adjust” This field allows the user to pro-
provides a message to fix the sensor or wiring. NOTE: gram the speed that the stepper motor reaches
When a sensor or wiring fault is detected, the field dis- its setpoint. The range of adjustment is listed at the
plays a default value, not the actual value. bottom of the programming table. The user can pro-
gram the gain with this field to fine-tune both steady-
5 “Check Box for Left Bank Manual Mode” This state and transient AFR performance.
field allows the user to change the AFR system
12 “Oxygen Target Lambda Offset” This field
mode of operation of the engine’s left bank from auto-
allows the user to program an offset to the
matic to manual mode. Normally the AFR system
Waukesha-calibrated target Lambda. By clicking on
operates in automatic mode; however, the user can
the “Edit…” button, a programming table is opened.
click the check box, changing the system to manual
The user programs an offset based on intake manifold
mode. Manual mode allows the user to adjust stepper
pressure by subtracting or adding a slight Lambda
position using the arrow buttons (<< < > >>). When
amount. The range of adjustment is listed at the bot-
changed into manual mode, the AFR system will not
tom of the programming table. The user can program
make automatic stepper adjustments; it will only move
an offset with this field to fine-tune AFR performance.
stepper position with user adjustment. Check mark is
ON; no check mark is OFF.
13 “Stepper Position Edit Min/Max” This field
allows the user to program minimum and maxi-
6 “Actual Lambda” This field displays actual
mum stepper positions at various levels of intake man-
Lambda. Lambda is equal to the amount of air
ifold pressure. By clicking on the “Max…” or “Min…”
present relative to that of a stoichiometric mixture. For
button, a programming table is opened. The AFR sys-
example, a Lambda of 1.0000 is equal to an air/fuel
tem adjusts the stepper motor between two program-
ratio of approximately 16:1. Slightly rich of stoichiome-
mable limits to maintain the oxygen sensor voltage.
try, or a Lambda of 0.995, is the typical setpoint of cat-
The minimum and maximum positions, which define
alyst engines.
the stepper motor adjustment range, are determined
7 “Left Bank Stepper Motor Setup” This field by establishing an air/fuel ratio curve. By defining the
allows the user to program the correct left bank stepper motor adjustment range, the user can main-
stepper motor for their engine. The length of the step- tain stable engine operation and set limits for trouble-
per motor shaft must be programmed so the AFR sys- shooting or indication of sensor wear.
tem knows the stepper motor range. The number of
steps is dependent on engine configuration and fuel Field descriptions continued on next page...
regulator model. The short shaft stepper has
5,800 steps (GSI engines); the long shaft stepper has
20,000 steps (GSID engines). This field will be set at
the factory but can be reprogrammed by the user.

FORM 6295 Fourth Edition 3.05-27


ESP PANEL DESCRIPTIONS

[F8] AFR SETUP PANEL DESCRIPTION

14 15

16 17

18 19

20

21 22 23

24

Figure 3.05-17 AFR Setup Panel in ESP – Fields 14 through 24

3.05-28 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F8] AFR SETUP PANEL DESCRIPTION – REFER TO FIGURE 3.05-17


14 “Check Box for Right Bank Manual Mode” 20 “Arrow Buttons” and “Home” The AFR sys-
This field allows the user to change the AFR tem must be in manual mode for the user to use
system mode of operation of the engine’s right bank the right bank arrow buttons. The double arrow buttons
from automatic to manual mode. Normally the AFR (<< >>) move the stepper motor up or down in
system operates in automatic mode; however, the user 400-step increments. The single arrow buttons (< >)
can click the check box, changing the system to man- move the stepper motor up or down in 25-step incre-
ual mode. Manual mode allows the user to adjust step- ments. The home button moves the stepper motor to
per position using the arrow buttons (<< < > >>). When the home position and then back to the start position
changed into manual mode, the AFR system will not only when the engine is not running. If the user clicks
make automatic stepper adjustments; it will only move on the home button while the engine is running, an
stepper position with user adjustment. Check mark is error message appears.
ON; no check mark is OFF.
21 “Stop Editing – Currently Editing” This button
15 “Intake Mnfld RB” This field displays the must be clicked prior to editing programmable
engine’s intake manifold pressure. Units are (dark blue) fields in ESP. Clicking this button puts ESP
in-Hg absolute (kPa absolute). If an intake manifold in “editing mode.” The user will not be able to enter
pressure sensor or wiring fault occurs, the status bar new values if ESP is not in editing mode. While in edit-
beneath this field signals an alarm (turns yellow) and ing mode, the button will read “Stop Editing – Currently
provides a message to fix the sensor or wiring. NOTE: Editing.” When the editing mode is off, the button will
When a sensor or wiring fault is detected, the field dis- read “Start Editing.” See Section 3.10 ESP Program-
plays a default value, not the actual value. ming “Basic Programming in ESP” for more informa-
tion.
16 “Right Bank Stepper Motor Setup” This field
allows the user to program the correct right
22 “Save to ECU” This button is used to save pro-
bank stepper motor for the engine. The length of the
grammed values to NVRAM (permanent mem-
stepper motor shaft must be programmed so the AFR
ory) in the ECU. Changes saved to permanent
system knows the stepper motor range. The number of
memory will not be lost if power to the ECU is
steps is dependent on engine configuration and fuel
removed. See Section 3.10 ESP Programming “Sav-
regulator model. The short shaft stepper has
ing to Permanent Memory” for more information.
5,800 steps (GSI engines); the long shaft stepper has
NOTE: Programmed values not saved to permanent
20,000 steps (GSID engines). This field will be set at
memory are stored in RAM (temporary memory).
the factory but can be reprogrammed by the user.
When values are in RAM, ESP can be closed and the
17 “Actual Lambda” This field displays actual PC disconnected from the ECU while keeping all
Lambda. Lambda is equal to the amount of air changes; however, changes will be lost if power to the
present relative to that of a stoichiometric mixture. For ECU is removed or when the engine is shut down.
example, a Lambda of 1.0000 is equal to an air/fuel
ratio of approximately 16:1. Slightly rich of stoichiome- 23 “Undo Last Change” This button allows the
try, or a Lambda of 0.995, is the typical setpoint of cat- user to reset the last change made while in edit-
alyst engines. ing mode back to the programmed parameter that was
last saved to permanent memory (NVRAM) in the
18 “Start Position Right” This field displays the ECU.
start position of the right bank stepper motor.
24 “Undo All Changes” This button allows the
19 “Primary Right Stepper Position” This field
user to reset all the programmable fields back to
displays the current position of the right bank
the programmed parameters that were last saved to
stepper motor.
permanent memory (NVRAM) in the ECU.

FORM 6295 Fourth Edition 3.05-29


ESP PANEL DESCRIPTIONS

[F10] STATUS PANEL DESCRIPTION


The Status Panel displays the number of faults occurring in the system, if any type of shutdown is in process, if
there is an engine alarm, and the engine start readiness. The ignition system status displays if the I-PMD is
enabled, ignition energy level, maximum retard, and if there is engine knocking. The ECU status displays ECU tem-
perature, battery voltage, ECU hours, and if calibrations, faults, and statistics are loaded. The engine status dis-
plays engine speed, engine setpoint, if remote RPM is enabled, low or high idle, state of the alternate governor
dynamics, and if the main fuel valve is engaged.
NOTE: In addition, the Status Panel on 7042GL/GSI engines displays prechamber fuel valve engagement in the
lower right corner (see Figure 3.05-21).
The Status Panel also makes it possible for the user to view a log of all the current and historical faults (see “Fault
Log Description” in this section for more information), reset status LEDs, manually calibrate the throttle actuator,
change all ESP panels from U.S. to metric units, and to view version details.

1 2 3 4 5

6 7 8 9 10

Figure 3.05-18 Status Panel in ESP – Fields 1 through 10

3.05-30 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F10] STATUS PANEL DESCRIPTION – REFER TO FIGURE 3.05-18


1 “View Faults” This button allows the user to 6 “User ESD” This field signals that an emer-
view the Fault Log. See “Fault Log Description” gency shutdown is in process based on a cus-
on page 3.05-38 for more information. tomer input. During an emergency shutdown, the field
is red and signals the user that an E-STOP (emer-
2 “Reset Status LEDs” This button allows the gency stop) is active. When E-STOP is displayed, the
user to reset the status LEDs on the ECU. engine cannot be restarted. When the engine is not in
When an ESM system fault is corrected, the fault dis- an emergency shutdown mode, the field is gray and
appears from the ESM ESP active fault log and the signals the user that the engine is ready to RUN.
ESP screens will no longer indicate an alarm; how-
ever, the yellow and/or red Status LED(s) on the ECU 7 “User RUN/STOP” This field signals that a nor-
will remain flashing the fault code(s) even after the mal shutdown is in process based on customer
fault(s) is cleared. The code will continue to flash on input. During a normal shutdown, the field is red and
the ECU until one of two things happens: (1) the signals the user that the engine will STOP. When
LED(s) is reset using ESP or (2) the engine is STOP is displayed, the engine cannot be restarted.
restarted. See Section 3.10 ESP Programming “Reset When the engine is not in a shutdown mode, the field
Status LEDs on ECU” for more information. is gray and signals the user that the engine is ready to
RUN.
3 “Manual Actuator Calibration” This button
allows the user to manually calibrate the throttle 8 “System” This field alerts the user when the
actuator. To work correctly, the ESM system must ESM system activates a shutdown. During an
know the fully closed and fully open end points of ESM system shutdown, the field is red and signals the
throttle actuator movement. To establish the fully user that an E-SHUTDOWN is active. When this field
closed and fully open end points, the throttle actuator indicates E-SHUTDOWN, a 24 VDC signal to the cus-
must be calibrated. A manual calibration can be per- tomer (through the Customer Interface Harness) is
formed when the engine is not rotating and after provided. When the engine is not in an emergency
postlube and the ESM system’s post-processing is shutdown mode, the field is gray and signals the user
complete. If an emergency shutdown is active, no pro- that the engine is OK.
gramming can be completed. See Section 3.10 ESP
Programming “Actuator Calibration” for more informa- 9 “Engine Alarm” This field signals that an ESM
tion. system engine alarm is active. During an active
alarm, the field is yellow and signals the user that an
4 “Change Units” This button allows the user to ALARM is active. When this field indicates an alarm, a
change all the ESP panel fields to display in 24 VDC signal to the customer (through the Customer
either U.S. units or in metric measurement units. See Interface Harness) is provided. During the time when
Section 3.10 ESP Programming “Changing Units – no alarms are present, the field is gray and signals the
U.S. or Metric” for more information. user that the system is OK.

5 “Version Details” This button allows the user 10 “Engine Start” This field indicates system
to view the serial number(s) and calibration readiness to start. If there is no ESM sys-
number of the ECU and engine. This information is tem-related reason not to start the engine, the field is
provided to verify that the ECU is calibrated correctly gray and signals the user that the engine is OK to
for the engine on which it is installed. start. If there is anything preventing the engine from
starting, the field is red and signals the user
NO START is possible.

Field descriptions continued on next page...

FORM 6295 Fourth Edition 3.05-31


ESP PANEL DESCRIPTIONS

[F10] STATUS PANEL DESCRIPTION

11

12 13 14 15 16

17 18 19 20 21

Figure 3.05-19 Status Panel in ESP – Fields 11 through 21

3.05-32 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F10] STATUS PANEL DESCRIPTION – REFER TO FIGURE 3.05-23


11 “Active Faults” This field indicates the total 16 “Engine Knocking” This field alerts the user
number of active faults as determined by the when knock is present in a cylinder. When
ESM system. View the fault log for detailed listing of knock is sensed with at least one cylinder, the field is
active faults. See “Fault Log Description” on yellow and signals the user that YES, knock is present.
page 3.05-38 for more information. The user can determine which cylinder(s) is knocking
by looking at the individual cylinder timings displayed
12 “Ignition” This field signals when the IPM-D is on the [F5] Ignition Panel. If no knock is present, the
enabled and is ready to receive a signal from field is gray and signals the user that NO knock is
the ECU to fire each spark plug. During the time the present.
IPM-D is enabled, the field is green and signals the
user that the IPM-D is ON. During the time the ignition 17 “ECU Temp” This field displays the internal
is disabled, the field is gray and signals the user that temperature of the ECU. Units are ° F (° C). If the
the IPM-D is OFF. ECU temperature is too high, the status bar beneath
the field is yellow and signals the user that the ECU
13 “Ignition Energy” This field indicates at what temperature is HIGH. ALM455 becomes active if the
level of energy the IPM-D is firing the spark ECU temperature increases beyond the maximum rec-
plugs: Level 1 (low/normal) or Level 2 (high). During ommended operating temperature.
normal engine operation, the IPM-D fires at a Level 1
ignition energy. The IPM-D fires at a Level 2 ignition 18 “Battery Voltage” This field displays the cur-
energy on engine startup or as a result of spark plug rent battery voltage. If the battery voltage goes
wear. If the ignition energy is raised to Level 2 (except below 21 VDC, the status bar beneath the field is yel-
on startup), an alarm is triggered to alert the operator. low and signals the user that the voltage is TOO LOW.
The pink field will signal the user whether the ignition Some action must be taken to prevent possible further
level is LEVEL 1 or LEVEL 2. power loss below 18 VDC or the engine will shut
down. ALM454 becomes active if the battery voltage
14 “Ignition” This field alerts the user when the remains below 21 VDC for longer than 30 seconds.
IPM-D is sending a signal to the ECU that indi- ESP does not display the actual voltage if it falls out-
cates that one or both of the E-Stop (emergency stop) side the acceptable range (acceptable range:
buttons on the side of the engine are depressed, or it 21 – 32 volts). For example, if actual voltage is
indicates the IPM-D is not receiving 24 volts, or it indi- 19.4 volts, ESP displays 21 volts on the Status Panel.
cates the IPM-D is not working correctly. When one of
these conditions exists, the field is yellow and signals 19 “ECU Hours” This field displays the number of
the user that an ignition ALARM exists. If the IPM-D hours the engine has been running with the cur-
signal to the ECU is good, the field is gray and signals rent ECU installed.
the user that it is OK.
20 “Cal Loaded” This field should always be
15 “Max Retard” This field alerts the user when green and signal OK. If the field is red and sig-
any cylinder’s timing has reached the maximum nals NO calibration loaded, contact your local Wauke-
retard in timing allowed. If any cylinder is at maximum sha Distributor for technical support.
retard, the field is yellow and signals the user that
YES, at least one cylinder has reached the maximum 21 “Faults Loaded” This field should always be
retard in timing allowed. The user can determine which green and signal the user it is OK. If the field is
cylinder(s) is at maximum retard by looking for the low- red and signals the user that NO faults are loaded,
est individual cylinder timing displayed on the [F5] Igni- contact your local Waukesha Distributor for technical
tion Panel. When none of the cylinders are at support.
maximum retard, the field is gray and signals the user
that NO cylinders are at maximum retard.

Field descriptions continued on next page...

FORM 6295 Fourth Edition 3.05-33


ESP PANEL DESCRIPTIONS

[F10] STATUS PANEL DESCRIPTION

22

23 24 25 26 27 28

Figure 3.05-20 Status Panel in ESP – Fields 22 through 28

29

Figure 3.05-21 Status Panel in ESP – Field 29 (7042GL Prechamber Fuel)

3.05-34 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F10] STATUS PANEL DESCRIPTION – REFER TO FIGURE 3.05-20 and FIGURE 3.05-21
22 “Stats Loaded” This field should always be 26 “Idle” This field indicates whether low idle rpm
green and signal the user it is OK. If the field is or high idle rpm is active. Low or high idle rpm is
red and signals the user that NO statistics are loaded, determined by a customer digital input. When the input
contact your local Waukesha Distributor for technical is low (< 3.3 volts), LOW IDLE is displayed in the pink
support. field. When the input is high (8.6 – 36 volts),
HIGH IDLE is displayed.
23 “Engine Speed” This field displays current
engine speed (rpm). 27 “Alternate Dynamics” This field signals when
the Alternate Governor Dynamics digital input is
24 “Eng Setpoint” This field displays the engine high (8.6 – 36 volts) or low (< 3.3 volts). Alternate
speed (rpm) setpoint. The engine speed set- dynamics or synchronizer mode is used to rapidly syn-
point is determined by a customer input, not internal chronize an engine to the electric power grid by using
calibrations. cylinder timing to maintain constant engine speed.
During the time the alternate dynamics input is high,
25 “Remote RPM” This field signals when the the field is green and signals the user it is ON. During
remote rpm is ON or OFF. Remote rpm is deter- the time the alternate dynamics input is low, the field is
mined by a customer digital input. When the input is gray and signals the user it is OFF.
high (8.6 – 36 volts), remote rpm is active. During the
time the remote rpm input is high, the field is green 28 “Main Fuel” This field signals when the main
and signals the user it is ON. During the time the fuel valve is engaged by the ECU. During the
remote rpm input is low (< 3.3 volts), the field is gray time the main fuel valve is engaged, the field is green
and signals the user it is OFF. and signals the user it is ON. During the time the main
fuel valve is disengaged, the field is gray and signals
the user it is OFF.

29 “Pre Ch Fuel” This field signals when the pre-


chamber fuel valve is engaged by the ECU. Dur-
ing the time the prechamber fuel valve is engaged, the
field is green and signals the user it is ON. During the
time the prechamber fuel valve is disengaged, the field
is gray and signals the user it is OFF.

FORM 6295 Fourth Edition 3.05-35


ESP PANEL DESCRIPTIONS

[F11] ADVANCED PANEL DESCRIPTION


The Advanced Panel is used to program MODBUS® settings, and to set alarm and shutdown setpoints for oil pres-
sure, jacket water, intake manifold, and oil temperature. Users can also send updated calibration information to the
ECU, and to signify if a Waukesha alternator is installed. In addition, all active system parameters can be logged
into readable text. This allows the user to review, chart, and/or trend the data logged as desired.

1 2 3 4 6

7 8 9 10

11 12 13

14

Figure 3.05-22 Advanced Panel in ESP – Fields 1 through 14

3.05-36 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

[F11] ADVANCED PANEL DESCRIPTION – REFER TO FIGURE 3.05-22


1 “Baud Rate” This field allows the user to pro- 11 “Start Editing” This button must be clicked
gram MODBUS® baud rate to 1200, 2400, prior to editing programmable (dark blue) fields
9600, or 19,200 bps (bits per second). See in ESP. Clicking this button puts ESP in “editing mode.”
Section 3.10 ESP Programming “Programming Baud The user will not be able to enter new values if ESP is
Rate (MODBUS® Applications)” for more information. not in editing mode. While in editing mode, the button
will read “Stop Editing – Currently Editing.” When the
2 “Slave ID” This field allows the user to program editing mode is off, the button will read “Start Editing.”
a unique identification number for each ECU (up See Section 3.10 ESP Programming “Basic Program-
to 32) on a multi-ECU networked site. The identifica- ming in ESP” for more information.
tion number that can be programmed can range from
12 “Save to ECU” This button is used to save pro-
1 to 247. By programming an identification number,
grammed values to NVRAM (permanent mem-
the user can communicate to a specific ECU through
ory) in the ECU. Changes saved to permanent
MODBUS® using a single MODBUS® master when
memory will not be lost if power to the ECU is
multiple ECUs are networked together. See
removed. See Section 3.10 ESP Programming “Sav-
Section 3.10 ESP Programming “Programming ECU
ing to Permanent Memory” for more information.
MODBUS® Slave ID” for more information.
NOTE: Programmed values not saved to permanent
memory are stored in RAM (temporary memory).
3 “Check Box if Waukesha Alternator is
When values are in RAM, ESP can be closed and the
Installed” This check box must be checked if a
PC disconnected from the ECU while keeping all
Waukesha Engine alternator with the Alternator Moni-
changes; however, changes will be lost if power to the
tor Harness is installed on the engine to properly diag-
ECU is removed or when the engine is shut down.
nose and signal an alarm if an alternator problem
occurs. If the check box is not checked and a Wauke- 13 “Undo Last Change” This button allows the
sha alternator is installed, no alarm will be triggered user to reset the last change made while in edit-
when an alternator problem occurs. If the box is ing mode back to the programmed parameter that was
checked and the engine does not have a Waukesha last saved to permanent memory (NVRAM) in the
alternator, an alarm will be generated all the time. ECU.

4 5 “Start Logging All” and “Stop Logging 14 “Undo All Changes” This button allows the
All” These buttons are used to log all active user to reset all the programmable fields back to
system parameters during a user-determined period of the programmed parameters that were last saved to
time. The file that is saved is a binary file permanent memory (NVRAM) in the ECU.
(extension .ACLOG) that must be extracted into a
usable file format. Using the Log File Processor pro-
gram installed with ESP, the binary file is converted
into a Microsoft® Excel-readable file (.TSV) or a text
file (.TXT). Once the data is readable as a .TSV
or .TXT file, the user can review, chart, and/or trend
the data logged as desired. See Section 3.10 ESP
Programming “Logging System Parameters” for more
information.

6 “Send Calibration to ECU” This button is used


to send a calibration file to the ECU.

7 8 9 10 “Offset” These fields allow the


user to adjust the alarm and shut-
down fields. This enables the user to fine tune alarm
and shutdown settings or test safeties. Setpoints are
only adjustable in the safe direction from the factory
settings. The alarm and shutdown fields display the
setting for the alarm and shutdown.

FORM 6295 Fourth Edition 3.05-37


ESP PANEL DESCRIPTIONS

FAULT LOG DESCRIPTION


One method of obtaining diagnostic information is by information is resettable except for the total number of
viewing the Fault Log in ESP. ESP displays the data times the fault occurred during the lifetime of the ECU.
provided by the ECU. The Fault Log can be displayed
The faults listed in the Fault Log can be sorted by click-
either to list only the active faults or to list the history of
ing on a column name. For example, clicking on “Fault”
all the faults that occurred in the lifetime of the ECU.
will sort alarms/shutdowns in numerical order based
The Fault Log displays the name of the fault, the first on the fault code. Clicking on “First Occurrence” will
time the fault occurred since the fault was reset (in sort alarms/shutdowns in order of occurrence.
ECU hours:minutes:seconds), the last time the fault
As an additional aid in troubleshooting, double-clicking
occurred since reset, the number of times the fault
a fault listed in the Fault Log will open E-Help directly
occurred since reset, and the total number of times the
to the troubleshooting information for that fault.
fault occurred in the lifetime of the ECU. All the fault

View Faults Reset Status LEDs Manual Actuator Change Units Version Details
Calibration

1 2 3 4 5

This is the only “active” fault listed in the Fault Log. The alarm condition is
indicated on the [F10] Status Panel and with flashing LEDs on the ECU. To
troubleshoot this alarm, the user would double-click the fault description.

6 7 8 9 10 11 12

Figure 3.05-23 Fault Log in ESP – Fields 1 through 12

3.05-38 FORM 6295 Fourth Edition


ESP PANEL DESCRIPTIONS

FAULT LOG DESCRIPTION – REFER TO FIGURE 3.05-23


1 “Fault” This field displays the fault code and 9 “Fault Help” This button allows the user to
description for the alarm or shutdown condition open E-Help.
that exists. Alarm codes in ESP are identified with the
letters “ALM” preceding the alarm code. Emergency 10 “Refresh” This button allows the user to update
shutdown codes are identified with the letters “ESD” or refresh the Fault Log. When the Fault Log is
preceding the shutdown code. Double-clicking a fault open, the information is not automatically refreshed.
listed in the Fault Log will open E-Help directly to the For example, if the Fault Log is displayed on screen,
troubleshooting information for that fault. and a fault is corrected, the Fault Log will not refresh
itself to reflect the change in active faults. The user
2 “First Occurrence” This field displays the first must refresh the Fault Log to view the updated infor-
time the fault listed occurred since the fault was mation.
reset (in ECU hours:minutes:seconds). This field is
resettable. 11 “Copy To Clipboard” This button allows the
user to copy to the PC’s clipboard the Fault Log
3 “Last Occurrence” This field displays the last information. The information can then be pasted as
time the fault listed occurred since the fault was text in Microsoft® Word or another word processing
reset (in ECU hours:minutes:seconds). This field is program. See Section 3.10 ESP Programming “Copy-
resettable. ing Fault Log Information to the Clipboard” for more
information.
4 “Total Since Reset” This field displays the
number of times the fault occurred since the 12 “Close” This button closes the Fault Log.
fault was reset. This field is resettable.

5 “Lifetime Total” This field displays the total


number of times the fault occurred in the lifetime
of the ECU. This field is not resettable.

6 7 “List Active Faults” and “Total Fault His-


tory” These buttons allow the user to view
either the active fault listing or the total fault history.
The Active Fault Log only lists active faults indicated
by flashing Status LEDs and alarm fields on the ESP
panels. The Total Fault History lists all the faults that
occurred in the lifetime of the ECU.

8 “Reset Selected Fault” This button allows the


user to reset Fields 2, 3, and 4 back to zero of
the selected (or highlighted) fault listed in the log.

FORM 6295 Fourth Edition 3.05-39


ESP PANEL DESCRIPTIONS

3.05-40 FORM 6295 Fourth Edition

You might also like