Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 7

SAUDI ARAMCO ID/PIEU - 15-Nov-2017 - REV. 2016.06.00 (Standards Cutoff -June 30, 2016) Rev. 2016.06.

00 30-Jun-16

SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Pre-Engineered Building - Components and Accessories


SAIC-M-1033 15-Nov-17 CIVIL-
Installation Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

A Pre-Engineered Building Components Installation

Roof panels shall be laid full length from ridge to eaves where possible to
minimize the possibility of water leaks at the end laps. When required, end 12-SAMSS-014
A1
lap shall be a minimum of 100 mm (4 inches nominal). Panel joints shall Sec. 6.5.1.c & d
interlock in such a way as to provide complete water tightness.

Fasteners shall be provided to secure the roof panels against wind uplift, 12-SAMSS-014
A2
mechanical movement, and to maintain water-tight panel joints Sec. 6.5.1.i

Wall panels shall be in one length from base to building eaves. Wall panel
length for above and below windows shall be as indicated on the
drawings. Wall panels shall be supported at their base by a raised curb or
grade beam that is a minimum of 150 mm above the building floor level.
12-SAMSS-014
A3 Wall panels shall extend not less than 38 mm below the concrete support,
Sec. 6.5.3.d & e
and sit in a recess in the concrete grade beam or curb to close off the
lower end of the panels. The panels shall be self-draining to the exterior.
Galvanized sill angles shall be provided to secure wall panels to the grade
beam or curb.

All roof and wall panels shall be attached to secondary framing members
by means of self-drilling or self-tapping screws. The screws shall be hex
head carbon steel screws assembled with an EPDM washer and
12-SAMSS-014
A4 mechanically zinc coating in accordance ASTM B695, Class 50. In coastal
Sec. 6.6
areas, as defined in paragraph 4.3.3(b), anaustenitic (300 series)
stainless steel fasteners shall be used. Fastener heads shall be coated
the same color as the panels.

A sealing compound shall be provided to seal ends and side laps of


panels. The material shall consist of a blend of non-toxic, synthetic resin
12-SAMSS-014
A5 base ingredients and inert extenders. Asphalt or asphalt derivatives are
Sec. 6.7.1.a & b
not permitted. The application of sealant shall be of a cross-sectional area
to provide a positive seal between adjacent surfaces.

The sealant material shall have sufficient adhesion to metal and plastic so
12-SAMSS-014
A6 as to remain in place during normal handling operations. Adhesive tensile
Sec. 6.7.1.c
strength shall be a minimum of 28 kPa (4Psi).

Flashing and/or trim shall be furnished at the rake, corners, eaves, at


framed openings, and wherever necessary to provide weather tightness
12-SAMSS-014
A7 and a finished appearance. Color will be as specified in the purchase
Sec. 6.7.2.a & c
order. A formed panel matching the slope and profile of adjoining panels
shall be provided along the building ridge.

Saudi Aramco: Company General Use


Preformed closures matching the profile of the panel shall be installed
along the eave and other locations as specified on drawings or as 12-SAMSS-014
A8
required for weather tightness, and may be made of solid or closed cell Sec. 6.7.2.d
plastic materials subject to approval

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU - 15-Nov-2017 - REV. 2016.06.00 (Standards Cutoff -June 30, 2016) Rev. 2016.06.00 30-Jun-16

SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Pre-Engineered Building - Components and Accessories


SAIC-M-1033 15-Nov-17 CIVIL-
Installation Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

B Pre-Engineered Building Accessories Installation

Windows shall be designed and constructed for integral installation with


the building system.Unless required otherwise in the contract documents,
provide building manufacturer's standard insulated double-pane window 12-SAMSS-014
B.1
(AAMA HS-C20 horizontal sliding, commercial grade) with medium natural Sec. 8.2
anodized finish (NAAMM AA-C22A31). (Alternative if selected by buyer:
fixed sash AAMA, Grade C20.)

Fasteners: Provide aluminum, stainless steel, or other material warranted


by the manufacturer to be non-corrosive and compatible with aluminum 12-SAMSS-014
B.2
window members, trim, hardware, anchors and other components of Sec. 8.2.2
window units.

Compression Glazing Strips and Weather Striping: Provide molded


EPDM, neoprene gasket complying with ASTM D2000 designation
12-SAMSS-014
B.3 2BC415 to 3BC620, molded PVC gasket complying with ASTM D2287,
Sec. 8.2.4
Grade 4, or molded expanded neoprene gasket complying with ASTM
C509.

Sealants: Provide manufacturer's standard for the joint size or aniticipated


12-SAMSS-014
B.4 movement. The sealant shall remain permanently elastic and non-
Sec. 8.2.6
shrinking and non-migrating.

Door shall comply with PIP Specification ARS08111. Door leaves shall be
of 45mm thick, full flush fabricated from Class G90 (Z275) zinc coated 12-SAMSS-014
B.5
sheets or better. Jamb extensions shall be furnished where required to Sec. 8.3.1
provide secure attachment to the wall framing.

For door assemblies required to be fire rated and exceeding limitations of


labeled assemblies, certification that each door and frame assembly is in
12-SAMSS-014
B.6 accordance with the design, materials, and construction for labeled
Sec. 8.3.1
construction in NFPA 80, NFPA 252, and UL 10B. (PIP ARS0811 Sec.
4.2.7)

Each door leaf shall be provided with a three 114mm x 114mm galvanized 12-SAMSS-014
B.7
steel, interlocking template butt hinges. Sec. 8.3.3

Door leaves shall be shop-painted with one coat of primer or finished to 12-SAMSS-014
B.8
match the walls. Sec. 8.3.4

The threshold shall be extruded aluminum shape to provide a positive 12-SAMSS-014


B.9
weather seal. Sec. 8.3.5

12-SAMSS-014
B.10 All exit doors shall be a minimum of 915 mm wide by 2035 mm high.
Sec. 8.3.6

Equipment door leaves shall be constructed of steel framing and panels


as specified for the walls. The door leaves shall be adequately flashed 12-SAMSS-014
B.11
and counter-flashed for weather tightness. Large doors may be field Sec. 8.4.1
assembled with bolted connections.

The leaves of sliding doors shall be suspended from a "C" section or other
appropriate structural member as a track header with the galvanized track
field bolted. Trolley shall be galvanized steel with dual, nylon wheels. The 12-SAMSS-014
B.12
track and trolleys shall be protected by a counter-flashed hood. When the Sec. 8.4.2
door is in the closed position the vertical gaps between the door edges
and the wall shall be automatically sealed with a closure device.

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU - 15-Nov-2017 - REV. 2016.06.00 (Standards Cutoff -June 30, 2016) Rev. 2016.06.00 30-Jun-16

SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Pre-Engineered Building - Components and Accessories


SAIC-M-1033 15-Nov-17 CIVIL-
Installation Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

12-SAMSS-014
B.13 The doors shall have inside and outside locking devices.
Sec. 8.4.3

Provide complete overhead roll-up door assemblies including door curtain,


12-SAMSS-014
B.14 guides, counterbalance, operators and installation accessories as
Sec. 8.5.1
specified herein, unless otherwise required in the contract documents.

Weather seals: At exterior doors, provide 3 mm (1/8") thick continuous


rubber or neoprene sheet weather seals on metal pressure bars secured 12-SAMSS-014
B.15
to inside of curtain coil hood. At door jambs, use 3 mm (1/8") thick Sec. 8.5.6
continuous strip secured to exterior side of jamb guide.

Eave gutters shall be box shaped 0.5 mm (26 gage) galvanized or


aluminum-zinc alloy-coated steel. The outside face of the gutter shall be 12-SAMSS-014
B.16
supported with 2.0 mm galvanized steel straps to the eave member at a Sec. 8.7.1
maximum spacing of 1000 mm.

Downspouts shall be round or rectangular 0.5mm (26 gage) galvanized or


aluminum-zinc alloy coated steel. Down spouts shall have a 45 degree 12-SAMSS-014
B.17
elbow at the bottom and shall be supported by attachment to the wall Sec. 8.7.2
covering at 3 meters maximum spacing.

Ventilators and roof openings shall be weather tight and shall be framed
12-SAMSS-014
B.18 and braced adequately to sustain the design wind and roof loads around
Sec. 8.8
the openings. Ventilators shall be furnished with bird screens.

Louver frames shall be fabricated from 1.22 mm (18 gage) galvanized


steel, and blades from 0.91mm (20 gage) galvanized steel. Louvers shall
have blades of the overlapping type providing maximum weather tightness 12-SAMSS-014
B.19
while allowing free air flow. Louver frames and blade fabricated from Sec. 8.9
extruded aluminum sheet of 1.22 mm(18 gage) thickness are also
acceptable.

Louvers are fixed sand trap type or adjustable by means of a crank, as 12-SAMSS-014
B.20
specified in the Purchase Documents. Sec. 8.9

REMARKS:

REFERENCE DOCUMENTS:
1- 12-SAMSS-014 -- Pre-Engineered Metal Buildings, 16 January 2014

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU - 15-Nov-2017 - REV. 2016.06.00 (Standards Cutoff -June 30, 2016) Rev. 2016.06.00 30-Jun-16

SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Pre-Engineered Building - Components and Accessories


SAIC-M-1033 15-Nov-17 CIVIL-
Installation Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU - 15-Nov-2017 - REV. 2016.06.00 (Standards Cutoff -June 30, 2016) Rev. 2016.06.00 30-Jun-16
SATR NUMBER DATE APPROVED DISCIPLINE

Re-Instatement Punch List Form


SATR-A-2011 30-Apr-13 CIVIL-
PROJECT TITLE WBS/BI/JO NUMBER CONTRACTOR/SUBCONTRACTOR

Note : SATR-A-2011 forms part of SAIC-M-1033 (Pre-Engineered Buildings - Accessories & Installation Inspection)
MCC No.: Test Packs No.
System Description
Description:
ITEM Covered Originator / Completion Verified/
Description Remarks
No. Y N Agency Date Accepted

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU - 15-Nov-2017 - REV. 2016.06.00 (Standards Cutoff -June 30, 2016) Rev. 2016.06.00 30-Jun-16

SAUDI ARAMCO INSPECTION CHECKLIST SATR NUMBER DATE APPROVED QR NUMBER

SATR-W-2008 15-Nov-17
Attachment 3
WELD SUMMARY SHEET
Note : SATR-W-2008 forms part of SAIC-M-1033 (Pre-Engineered Buildings - Accessories & Installation Inspection)
Drawing Line Spool Matl. Joint Shop Sch. Diam- Welder's NDE PMI/MPI Hardness
Item # PWHT Remarks
Number No. Number Type No. Field Thick. eter Code ACC. REJ. ACC. REJ. Test

Saudi Aramco: Company General Use

You might also like