SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Pre-Engineered Buildings - Interior and Exterior Final


SAIC-M-1034 15-Nov-17 CIVIL-
Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Vendor shall submit detailed specifications covering the finish of exterior


and interior surfaces of sheet metal paneling, trim and related
components, for Saudi Aramco written approval. The procedures shall 12-SAMSS-014
A1
cover surface cleaning, pretreatment, quality of coating materials, Sec. 7.1
application of primer finish, curing or baking, thickness of coating color.
The Vendor shall maintain the quality of work and records.

12-SAMSS-014
A2 Roof panels shall be ribbed to provide adequate rigidity.
Sec. 6.5.1.b

Panels shall provide a net coverage width of 900 mm (3 ft nominal) 12-SAMSS-014


A3
minimum. Sec. 6.5.1.c

Panel joints shall interlock in such a way as to provide complete water-


12-SAMSS-014
A4 tightness and an allowance for thermal expansion for a thermal differential
Sec. 6.5.1.d
of 67°C.

Fasteners shall be provided to secure the roof panels against wind uplift,
mechanical movement, and to maintain water-tight panel joints. Particular 12-SAMSS-014
A5
care should be taken to ensure compliance with UBC Section 1622 and Sec. 6.5.1.i
Table 16-H with regard to local wind pressure effects.

All panels shall be attached to secondary framing members by means of


self-drilling or self-tapping screws. The screws shall be hex head carbon
steel screws assembled with an EPDM washer and mechanically zinc
12-SAMSS-014
A6 coating in accordance ASTM B695, Class 50. However, in coastal areas,
Sec. 6.6
as defined in paragraph 4.3.3(b), anaustenitic (300 series) stainless steel
fasteners shall be used. Fastener heads shall be coated the same color
as the panels.

A sealing compound shall be provided to seal ends and side laps of


panels. The material shall consist of a blend of non-toxic, synthetic resin 12-SAMSS-014
A7
base ingredients and inert extenders. Asphalt or asphalt derivatives are Sec. 6.7.1.a
not permitted.

The application of sealant shall be of a cross-sectional area to provide a 12-SAMSS-014


A8
positive seal between adjacent surfaces. Sec. 6.7.1.b

The sealant material shall have sufficient adhesion to metal and plastic so
12-SAMSS-014
A9 as to remain in place during normal handling operations. Adhesive tensile
Sec. 6.7.1.c
strength shall be a minimum of 28 kPa (4Psi).

Flashing and/or trim shall be furnished at the rake, corners, eaves, at


framed openings, and wherever necessary to provide weather tightness
12-SAMSS-014
A10 and a finished appearance. Color will be as specified in the purchase
Sec. 6.7.2.a & c
order. A formed panel matching the slope and profile of adjoining panels
shall be provided along the building ridge.

Saudi Aramco: Company General Use


SAUDI ARAMCO ID/PIEU - 15-Nov-2017 - REV. 2016.06.00 (Standards Cutoff -June 30, 2016) Rev. 2016.06.00 30-Jun-16

SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED QR NUMBER

Pre-Engineered Buildings - Interior and Exterior Final


SAIC-M-1034 15-Nov-17 CIVIL-
Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Preformed closures matching the profile of the panel shall be installed


along the eave and other locations as specified on drawings or as 12-SAMSS-014
A11
required for weather tightness, and may be made of solid or closed cell Sec. 6.7.1.d
plastic materials subject to approval

Dissimilar Materials which are not compatible with the adjoining materials
when exposed to moisture must be separated by means of approved
coatings, gaskets, or other effective means. Aluminum alloy shall be 12-SAMSS-014
A12
considered compatible with zinc and calcium coated surfaces and the 300 Sec. 7.2
and 400 AISI Series Stainless Steel Alloys and do not require application
of barrier material.

REMARKS:

REFERENCE DOCUMENTS:
1- 12-SAMSS-014 -- Pre-Engineered Metal Buildings, 16January 2014

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others