Professional Documents
Culture Documents
Lecture#2-Introduction of Air Conditioning System - Part II
Lecture#2-Introduction of Air Conditioning System - Part II
Lecture#2-Introduction of Air Conditioning System - Part II
LECTURE
2
Introduction of Air
Conditioning System
HVAC System
Major Component of HVAC System:
1. Air Conditioning & Refrigeration
Equipment.
2. Duct Works.
3. Air Terminals.
4. Chilled Water Piping.
5. Refrigerant Piping.
6. Control System.
7. Filtration System.
8. Exhaust System.
9. Humidification.
HVAC System
Major Component of HVAC System:
HVAC water chillers and heaters
Hot water generator (if chiller does produce chilled water only) or furnace
Chilled water pumps
Cooling water pumps
Electrical power supply control or Motor control center (MCC)
Cooling towers
Piping for chilled water and cooling water or condenser side water
Valves for chilled water and cooling water sides
Air handling units (AHUs), heating coils and cooling Coils
Ducts in ventilation system (supply ducts and return ducts)
Fan Coil Units (FCUs) and thermostats
HVAC Diffusers and grills
HVAC controls (instrumentation & Control components) installed at various
locations
HVAC software for building HVAC control or building management system
(BMS)
An Assembly of all above components forms an HVAC system.
Classification of Air Conditioning Equipment :
The Five System Loops
HVAC system can be demonstrated
into basic subsystems. These
subsystems will be referred to as
“loops.” There are five primary loops
that can describe virtually any type of
HVAC system.
► Airside Loop.
► Chilled-water Loop.
► Refrigeration Loop.
► Heat-rejection Loop.
► Controls Loop.
Second, the temperatures
Important observations: First, while
used in this lecture are
these five loops can be used to
representative of conditions in
describe virtually any HVAC system,
a typical HVAC system, but will
not every system uses all five loops.
differ from application to
application.
Airside Loop
Airside Loop-Conditioned Space
First component of this loop is the conditioned
space.
The first two comfort requirements mentioned were
dry bulb temperature and humidity.
In order to maintain the dry-bulb temperature in the
conditioned space, heat (referred to as sensible
heat) must be added or removed at the same rate
as it leaves or enters the space.
In order to maintain the humidity level in the space,
moisture (sometimes referred to as latent heat)
must be added or removed at the same rate as it
leaves or enters the space.
Most HVAC systems used today deliver conditioned (heated, cooled,
humidified, or dehumidified) air to conditioned space to add or remove
sensible heat and moisture. This conditioned air is called supply air.
The air that carries the heat and moisture out of the space is called
return air.
If the supply air is colder, it can remove more sensible heat from the
space. If the supply air is drier, it can remove more moisture from the
space.
Airside Loop-Supply Fan and Filter
The next component of the airside loop is a
supply fan that delivers the supply air (SA)
to the space.
This same supply fan is often used to also
draw the return air out of the space.
Alternatively, some systems use a second
fan, called a return fan, to draw air from the
space and move it back to the equipment that
contains the supply fan.
Provide an adequate amount of fresh,
outdoor air to the space, the required
amount of outdoor air (OA) for ventilation is
brought into the building and mixed with the
recirculated portion of the return air (RA). The
remaining return air, that which has been
replaced by outdoor air, is exhausted as
exhaust air (EA) from the building, often by an
exhaust (or relief) fan.
Airside Loop-Cooling Coil
Ensure the air in the conditioned space is
clean. Bringing in an adequate amount of
fresh outdoor air, and exhausting some of
the air from the space, can help meet this
requirement. However, the air must also be
filtered. In a typical HVAC system, the mixed
air passes through a filter to remove many
of the airborne contaminants.
A heat exchanger, commonly known as a
cooling coil, is often used to cool and
dehumidify the supply air before it is delivered
to the space. The supply air must be cold
enough to absorb excess sensible heat
from the space and dry enough to absorb
excess moisture (latent heat).
A typical cooling coil includes rows of tubes
passing through sheets of formed fins. A
cold fluid, either water or liquid refrigerant,
enters one header at the end of the coil and
then flows through the tubes, cooling both the
tubes and the fins.
Chilled-Water Loop
In the airside loop, a cooling coil is used to cool and dehumidify the
supply air. The cold fluid flowing through the tubes of the coil may be
either water or liquid refrigerant. Systems that use water flowing
through the cooling coil also contain a chilled-water loop.
Heat energy flows from a higher-temperature substance to a lower-
temperature substance. Therefore, in order for heat to be transferred
from the air, the fluid
Chilled-Water Loop
The third component of the chilled-water loop is a pump that moves water
around the loop. This pump needs to have enough power to move the water
through the piping, the evaporator, the tubes of the coil, and any other
accessories installed in the chilled-water loop.
Similar to the airside loop, the chilled-water loop responds to changing cooling
loads by varying either the temperature or the quantity of water delivered to
the cooling coil. The most common method, however, is to vary the quantity of
water flowing through the cooling coil by using a control valve. As the cooling
load decreases, the modulating control valve reduces the rate of chilled-water
flow through the coil, decreasing its cooling capacity.
Chilled-Water Loop
At part-load conditions, a two-way control valve
reduces the rate of chilled water flow through the coil.
A three-way control valve also reduces the rate of
flow through the coil, but it bypasses the excess
water to mix downstream with the water that flows
through the coil.
With a three-way valve, the quantity of water flowing
through the system (water flowing through the coil
plus water bypassing the coil) is constant at all
loads. With a two-way valve, the water flowing
through the system varies, which allows the pump to
reduce its capacity and save energy at part load.
Notice that the control valve is located at the outlet,
or downstream, of the cooling coil. This location
ensures that the tubes inside the coil are always
full of water.
A valve located at the inlet, or upstream, of the coil
may modulate to the point where the water just
“trickles” through the tubes, not filling the entire
tube diameter. The result is unpredictable heat
transfer and less-stable control.
Refrigeration Loop
The fourth loop is the heat-rejection loop. In the refrigeration loop, the
condenser transfers heat from the hot refrigerant to air, water, or
some other fluid. In a water-cooled condenser, water flows through the
tubes while the hot refrigerant vapor enters the shell space
surrounding the tubes. Heat is transferred from the refrigerant to the
water, warming the water.
The water flowing through the condenser must be colder than the hot
refrigerant vapor. A heat exchanger is required to cool the water that
returns from the condenser. When a water-cooled condenser is used,
this heat exchanger is typically either a cooling tower or a fluid
cooler (also known as a dry cooler).
Heat-Rejection Loop-Cooling Tower
In a cooling tower, the warm water
returning from the condenser is
sprayed over the fill inside the tower
A propeller fan draws outdoor air
upward through the fill.
One common type of fill consists of
several thin, closely spaced layers of
plastic or wood.
The water spreads over the surface of
the fill to increase the contact with the
passing air. The movement of air
through the fill allows heat to transfer
from the water to the air.
This causes some of the water to
evaporate, a process that cools the
remaining water. The remaining
cooled water then falls to the tower
sump and is returned to the condenser.
Heat-Rejection Loop-Cooling Tower
Controls Loop
The fifth, and final, loop of the HVAC system is the controls loop. Each of
the previous four loops contains several components. Each component
must be controlled in a particular way to ensure proper operation. Typically,
each piece of equipment (which may be comprised of one or more
components of a loop) is equipped with a unit-level, automatic controller.
Control Loop- Building Management System(BMS)
HVAC System Requirements
Classification of HVAC systems
The major classification of HVAC systems is central system
and decentralized or local system.
Types of a system depend on addressing the primary
equipment location to be centralized as conditioning entire
building as a whole unit or decentralized as separately
conditioning a specific zone as part of a building.
Therefore, the air and water distribution system should be
designed based on system classification and the location
of primary equipment.
The criteria as mentioned above should also be applied in
selecting between two systems
Classification of HVAC systems
Criteria Central system Decentralized system
Temperature, humidity,
Fulfilling any or all of the design Fulfilling any or all of the design
and space pressure
parameters parameters
requirements
Considering HVAC diversity
Maximum capacity is required
factors to reduce the installed
for each equipment
Capacity requirements equipment capacity
Significant first cost and Equipment sizing diversity is
operating cost limited
Standby equipment is
accommodated for No backup or standby
Redundancy
troubleshooting and equipment
maintenance
An equipment room is located
outside the conditioned area, or Possible of no equipment room
adjacent to or remote from the is needed
building
Special requirements
Installing secondary equipment Equipment may be located on
for the air and water distribution the roof and the ground
which requires additional cost adjacent to the building
Classification of HVAC systems
Criteria Central system Decentralized system
High capital cost
An induction unit induces the air flow in a room through cabinet by using
high-velocity airflow from a central air handling unit, which replaces the
forced convection of the fan in the fan-coil by the induction or buoyancy
effect of the induction unit.