4

1 2 3 5 6 7 8 9 10

BROWN 1.00mm² WIRE TO PAGE


2 OF 4
2

A 380VAC SUPPLY
MCB No.1
L1 L2 L3 E 10A
A

IS
ISOLATOR MCB No.1
63Amp 10A
TYPE
SALZER
TR1
WHITE L5 L7 1

RED L4 L6 N1

B B

TR1 = TRANSFORMER No.1


PRIMARY 400VAC
SECONDARY 24VAC
APPARENT POWER = 100VA

O/L No.1 = OVER LOAD No.1

THERMALS = 2.5 → 4A

C C
C1 = CONTACTOR
MAKING CAPACITY = 160A
BREAKING CAPACITY = 106A
COIL INRUSH = 32VA
COIL SEALED = 6VA
12A @ AC3 DUTY
5.5kW @ 400V

C1

D D

BLACK 1.00mm² WIRE N1 TO PAGE


2 OF 4

U1 V1 W1

E E
M
3

1.1kW ± 2.1A @ 380VAC

1 2 3 4 5 6 7 8 9 10

DATE: 06 -12 -2021 TITLE: CUSTOMER: CHET CHEMICALS GERMISTON

DRAWN: M.M SHEET NO: 1 OF 4


1.1KW JOCKEY CONTROLLER
PANEL TYPE: RELAY LOGIC 380VAC
REV NO: 0