Pump selection

Customer: KCP Solar Industry


Mr. Ashok Kumar HERMETIC-Pumpen GmbH
Gewerbestrasse 51
Address: 37, Trichy Main Road, Gugai D-79194 Gundelfingen
Salem-636006 phone +49 761 5830-0
Tamilnadu, fax +49 761 5830-280
India hermetic@hermetic-pumpen.com
www.hermetic-pumpen.com

(For Refrigerant R134a+ Dimethylformamide (DMF) Sharan Hiremath


solution phone
IEC CODE: 3207006728 Hiremath.Sharan@hermetic-pumpen.com
Subject:
Date: 18/02/2023
Design data:
Refrigerating plant: Refrigerant: R134a
Refrigerating capacity Q0: 35.71 [kW] Evaporation temperature Top: 0.0 [°C]
Circulation factor k: 4.0 Density ρ(Top): 1.295 [kg/l]
Pressure drop Δpr: 11.05 [bar] Specific heat capacity cp(Top): 0.320 [kcal/kgK]
NPSH available NPSHA: 1.00 [m] Vapour pressure pv(Top): 2.93 [bar]

Operating point: Equipment: ■ None


3
Volume flow Qr: 2.00 [m /h]
Delivery head Hr: 87.00 [m]
Net frequency fN: 50 [Hz]
000000

Nominal data:
Pump: CAM 2/6 Drive: AGX4.5
Stages: 6 Rated input P1: 6.40 [kW]
Impeller diameter D2: Ø114.0/130.0 [mm] Rated output P2: 4.50 [kW]
Construction: Without inducer Frequency fN: 50 [Hz]
Volume flow Qopt: 10.31 [m3/h] Rated speed n: 2780 [min-1]
Delivery head Hopt: 55.30 [m] Rated voltage UN: 400±10% [V]
Rated current IN: 11.0 [A]
Starting current ratio IA/IN: 4.1
Power factor cos φ: 0.84
Insulation class: H

Operating range:
Qmin,ad Qr Qmax,ad Remarks:
3
Volume flow Q: 1.00 2.00 6.60 [m /h] ■ Pay attention to the admissible
Delivery head H: 89.12 87.18 72.69 [m] operating range as shown in the
Input power P1: 4.48 4.77 5.71 [kW] performance curve on page 2.
NPSH required NPSHR: 0.55 0.29 0.30 [m] ■ The pump selection will be checked
Speed n: 2880 2870 2835 [min-1] and confirmed in case of order!
■ Delivery time: 6 weeks

page 1/2
■ HERMETIC-Pumpen GmbH · Gewerbestraße 51 · D-79194 Gundelfingen · phone +49 761 5830-0 · fax +49 761 5830-280 · www.hermetic-pumpen.com
Registergericht Freiburg HRB 365 · Geschäftsführer: Nicolaus Krämer (CEO, COO), Christiane Krämer (CFO), Sebastian Dahlke (CCO)
Performance curve:
000000

page 2/2
■ HERMETIC-Pumpen GmbH · Gewerbestraße 51 · D-79194 Gundelfingen · phone +49 761 5830-0 · fax +49 761 5830-280 · www.hermetic-pumpen.com
Registergericht Freiburg HRB 365 · Geschäftsführer: Nicolaus Krämer (CEO, COO), Christiane Krämer (CFO), Sebastian Dahlke (CCO)

Powered by TCPDF (www.tcpdf.org)

You might also like