NBC 2016
NBC 2016
1 SCOPE
2.39 Horizontal Exit-A horizontal exit shall be 3.1 Classification of Buildings Based upon
througha fire door of 120 min rating in a fire Occupancy
All buildings, whether existing or hereafter erected storage, under pressure of more than
shallbe classified according to use or the character 0.1 N/mm' and in quantities
exceeding 70 111" of acetylene,
ofoccupancy in one of the following groups: hydrogen, illuminating and natural
gases, ammonia, chlorine,
Group A Residential phosgene, Sulphur dioxide, carbon
Group B Educational dioxide, methyl oxide and all gases
Group C Institutional Group Hazardous subject to explosion, fume or toxic
Group D Assembly J Buildings hazard, cryogenic gases, etc.;
Group E Business storage and handling of hazardous
and highlyflammable liquids,
Group F Mercantile
liquefiable gases like LPG, rocket
Group G Industrial propellants, etc.; explosive materials
Group H Storage (other than liquids); manufacture of
Group J Hazardous artificial flowers, synthetic leather,
ammunition, explosives and fireworks.
Group Type Locations
Lodging and rooming houses, One or 3.4.5 Openings in Fire Resistant Walls and Floors
Group Residential two family private
A Buildings dwellings, Dormitories, Apartment 3.4.5.2For Types I to 3 constructions, a doorway or. Opening
houses Hotels, Starred hotels in a fire resistant wall on any floor shall be limited to 5.6 m2 in
Group Educational Schools up to senior secondary level, area with a maximum height/width. 01'2.75 m. Every wall
B Buildings All others/training institutions opening shall be protected with fire-resisting doors, having
Hospitals and sanatoria, Custodial the fire rating of not less than 120 min.
Group Institutional
institutions, Penal and mental
C Buildings 3.4.5.4 Service ducts and shafts
institution
theatrical or motion picture or any
other stage and fixed seats for over The inspection door for electrical shafts/duetsshall be
I000 persons & Upto 1000 persons, not less than 120 min.
Buildings without a permanent stage
having accommodation for less than For plumbing shafts in the core of the building,
300 or more than 300 persons, withshaft door opening inside the building, the shafts
temporary structures designed for shallhave inspection doors having fire resistance rating
Group Assembly
assembly of people, Buildings having notless than 30 min.
D Buildings
mixed occupancies of assembly and
mercantile (for example, shopping 3.4.6.3 Substation/Transformers
malls providing facilities such as
shopping, cinema theatres, The MV panel room shall be provided withfire resistant
multiplexes and restaurants/food
walls and doors of fire resistance of notless than 120
courts), Underground and elevated
mass rapid transit system
min.
Offices, banks, professional
establishments, like offices of 3.4.12 Fire Command Centre (FCC)
architects, engineers, doctors,
lawyers, post offices and police Fire command center shall be constructed with120 min
stations, Laboratories, outpatient rating walls with a fire door.
clinics, research establishments,
Group Business
libraries and test houses, Electronic 4.2 General Exit Requirements
E Buildings
data processing centers) computer
installations, information technology 4.2.7 For non-naturally ventilated areas, fire doors
parks and call centers, Telephone with120 min fire resistance rating shall be provided
exchanges, Broadcasting stations, andparticularly at the entrance to lift lobby and stair
T.V. stations and air traffic control wellwhere a 'funnel or flue effect' may be created,
towers inducingan upward spread of fire, to prevent spread
Shops, stores, departmental stores,
of fire andsmoke.
markets (any with covered area up
to 500 m-), Shops, stores,
Group Mercantile
departmental stores, markets (any
4.4.2.4.3 Staircases
F Buildings
with
covered area more than 500 m-), 4.4.2.4.3.2 Internal staircases
Underground shopping centers
Buildings used for low hazard h) The design of staircase shall also take intoaccount
Group Industrial the following:
industries, moderate hazard
G Buildings
industries, high hazard industries·
warehouses, coldstorages, freight 2) Access to exit staircase shall be througha fire door
depots, transit sheds, storehouses, of 11 minimum 120 min fireresistance rating.
Group Storage
truck and marine terminals, garages,
H Buildings
hangars, grain elevators, barns and
stables.
9) The floor indication board, indicating
thelocation/designated number of
staircase,respective floor number and direction toexit
discharge shall be placed inside the.staircase, on the
wall neatest to the~ firedoor. It shallhave size not less
than300 mm x 200 mm (see Fig. 9).
4.4:2.4.1 Doorways
4.6.1 Smoke Exhaust andPressurization f) All fire rated doors and assembly shall be
ofAreasaboveGround provided with certificate and labels
prominently indicating the manufacturer's
Exit access corridors ofguest rooms and indoor identification, door details covering door type,
patientdepartment/areas having patients lacking self- serial/batch number, month and year of
preservation and for sleeping accommodations such manufacture, fire resistance rating, etc. The
asapartments, custodial, penal and mental doors and assembly shall be certified with all
institutions,etc.,shall be provided with 60 min tire prescribed hardware such as hinges, locks,
resistant wall and20 min self-closing fire doors. panic bars, door closer, and door viewers.
All compartments shall be divided with self- 6.7 Industrial Buildings (Group G)
closing(door closers) fire doors withelectromagnetic
hold open. A coordinatorshall be provided to 6.7.1 Fire Prevention
sequence the closing ofdouble leaf in case of
emergency. 6.7.1.1 Fire separating walls, fire separatingfloors
andfire partitions
d) Doors in fire resistant walls shall be soinstalled that
these may normally be kept inopen position, but will g) Doors and window openings in external walls
close automatically.Corridor door openings shall be within 3 m of the fire separating walls shall be
not less than2.0 m in width of double swing double protected by fire doors having a rating of at
leaftype door.A coordinator shall be provided least 60 min and window openings may be
asabove, for closing of double leaf in case protected by fire resistant glass assembly
ofemergency. having same fire rating.