Optimal Operation of Paralleled Power Transformers PDF
Optimal Operation of Paralleled Power Transformers PDF
net/publication/242259195
CITATION READS
1 3,297
2 authors, including:
David Trebolle
Union Fenosa Distribución
14 PUBLICATIONS 132 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by David Trebolle on 10 March 2014.
Abstract: Parallel operation of power transformers is a The present work focuses on reducing circulating
common practice. Interest is placed on minimizing the current while analyzing parallel operation of
reactive current circulation between transformers due to transformers with slightly different impedance, ratio or
mismatching of electrical properties. Several control tap positions.
schemes have been applied over the years to ensure Previous works in the area are focused on
efficient operation of paralleled transformers with paralleling schemes applied as automatic control of the
OLTC. These methods rely either on field on load tap changer at the substation, among the more
measurements of circulating currents or on classic commonly used are the master/follower and circulating
Master/Follower approach and usually assume that the currents method [1],[2].
paralleled transformers have matching impedances and
OLTC positions. On the present work a generalized 2 PARALLELED OPERATION OF
approach is implemented calculating the circulating POWER TRANSFORMER
current and minimizing losses directly at the System
Operation Office and using the distribution system
There are several conditions that must be met to
SCADA to control tap position of the paralleled
operate transformers in parallel, some of these
transformers. This permits the determination of optimal
conditions are convenient and some are mandatory.
tap matching between transformers and calculation of
Among the convenient are: same voltage ratio, same
losses under emergency situations where coupling of
short circuit voltage in p.u., and same short circuit
transformers with slight impedance mismatch might be
power.
considered. In the proposed method a map of circulating
The mandatory conditions are: same connection
current is calculated based on the transformer
index, and same phase sequence.
impedance, X/R ratio and OLTC positions, then the
When the convenient conditions are not met
optimal tap positions (minimizing losses) under parallel
paralleled operation is possible but not optimal, not
operation are determined.
complying with mandatory conditions imply phase to
phase failures so operation in parallel is not feasible.
1 INTRODUCTION
2.1. Ideal working condition.
It is common practice to operate power transformers In ideal working condition the paralleled
in parallel and it is usually due to one of the following transformers will have the same voltage ratio, short-
reasons. circuit voltage and short-circuit power. As seen on
1. Increased Load: If the power of a substation figure 1, this implies that:
must be increased due to load, one of the
economically sound solutions is to add a
second transformer in parallel operation.
I a Z cca = I b Z ccb = ... = I N Z ccN (1)
2. Flexible operation: paralleled transformers
can be operated in several ways ensuring
reliability, safety, critical load selection and
ease of maintenance routine without service
outage.
3. High Power: Due to transport size/weight
restriction, it may be the only solution to high
power requirements.
Figure 4.
4 REFERENCES
[1] E. Tom Jauch, “Factors in Choosing
Transformer Paralleling Methods”, IEEE, PES T&D
2005/2006 Dallas. TX.