MiCOM

P921/P922 & P923


Voltage and Frequency Relays

P92x/EN T/I52

Software Version: V12.A

Technical Guide
Introduction P92x/EN IT/I52

MiCOM P921/P922/P923

INTRODUCTION
P92x/EN GS/I52 Technical Guide
Getting Started
Page 8/18 MiCOM P921-P922-P923

6. INTRODUCTION TO THE MiCOM P921-P922-P923 RELAYS


The range of MiCOM protection relays follows on from the success of the MIDOS, K
and MODN ranges by incorporating the last changes in digital technology. The relays
MiCOM P921-P922 and P923 are fully compatible and use the same modular box
concept. The MiCOM P921-P922 and P923 of relays provides more protection for
the most demanding applications.
Each relay has a large number of functions for controlling and collecting data. This
can form part of a fully integrated system covering protection, control,
instrumentation, data acquisition and the recording of faults, events and
disturbances. The relays are equipped on the front panel with a liquid crystal display
(LCD) with 2 x 16 back-lit alphanumerical characters, a tactile 7 button keypad (to
gain access to all the parameters, alarms and measurements) and 8 LEDs simply
displaying the state of the MiCOM P921-P922 and P923 relays. In addition, the use
of the RS485 communication port makes it possible to read, reinitialise and change
the settings of the relays, if required, from a local or remote PC computer equipped
with appropriate software.
Its flexibility of use, reduced maintenance requirements and ease of integration allow
the MiCOM P921-P922 and P923 to provide an evolving solution for the problems of
the protection of electric networks.
The MiCOM P921-P922 and P923 relays provide comprehensive voltage and
frequency protection for phase and ground faults together with measurements,
control and recording facilities.
Functions MiCOM P921 MiCOM P922 MiCOM P923
Protection functions
Under voltage (27) X X X
Over voltage (59) X X X
Residual over voltage (59N) X X X
Negative sequence overvoltage (47) X X
Positive sequence undervoltage (27D) X X
Under frequency (81U) X X
Over frequency (81O) X X
Rate of change of frequency (81R) X
Undervoltage blocking (settable for P923) X X
Balance Voltage X
Ancillary functions
Settings groups 1 2 2
Measurements X X X
Circuit Breaker Control X X X
Circuit Breaker Supervision X X
Output relay latching X X X
Blocking logic X X X
Programmable logic equations X X X
Peak demand X X
Rolling demand X X
Fault record X X
Events records X X
Disturbance recording X X
Rear communication port X X X
Front communication port X X X
Frequency disturbance recording X
Technical Guide P92x/EN GS/I52
Getting Started
MiCOM P921-P922-P923 Page 9/18

7. RELAY FRONT DESCRIPTION


7.1 Front view
The front panel of the relay is shown in figure 1, with the hinged covers at the top
and bottom of the relay shown closed. Extra physical protection for the front panel
can be provided by an optional transparent front cover. This allows read access only
to the relay’s settings and data but does not affect the relay’s IP rating. When full
access to the relay keypad is required, for editing the settings, the transparent cover
can be unclipped and removed when the top and bottom covers are open.
Note that the MiCOM P921-P922 and P923 have the same size and the same front
panel.

FIGURE 1: RELAY FRONT VIEW


The front panel of the relay includes the following, as indicated in Figure 1:
• a 16-character by 2-line alphanumeric liquid crystal display (LCD).
• a 7-key keypad comprising 4 arrow keys (, , , , an enter key , a clear
key , and a read key c).

• 8 LEDs; 4 fixed function LEDs and 4 programmable function LEDs on the left
hand side of the front panel.
• Under the top hinged cover:
− the relay serial number, and the relay’s voltage rating information (see
figure 3 in this chapter).
Technical Guide P92x/EN CM/I52
Commissioning Guide
MiCOM P921/P922 & P923 Page 15/26

5.3 Testing the "Phase overvoltage protection" and "Phase undervoltage


protection" functions
5.3.1 Wiring diagram

Auxiliary
power supply + 33 37
35 Watchdog
34 WD
_ 36

6
4 Stop
RL1 RL1
2 chrono

12

Auxiliary +
MiCOM P92* RL2
10
8
RL2

power supply _
41 16
A RL3
RL3 14
42 20
Voltage 43
B RL4 18 RL4
source
44 3
45 RL5 1 RL5
C

N 7
See note 3 46 RL6 5 RL6
49
See note 1
9
RL7 11 RL7
50
13
RL8 15 RL8

22 LEDs
EL1 4 programmable
24
LEDs
26
EL2
28
17 Case earth
EL3 29
19 -
21 ** 30
RS 485
EL4 See note 2
23 31 communication port
+ (Modbus, Courier,
25
CEI60870-5-103)
EL5
27
32 _

(* For the last relay


of the RS 485 link,
connect terminal 30 to terminal 32)
Notes :
(1) Supplementary hardware for MiCOM P922-P923 relay
(2) Supplementary hardware for MiCOM P922-P923 relay
(3) 3VT assembly, Phase-Neutral
P0408ENa

FIGURE 2: (V>) AND (V>>) STAGE TEST