GENERAL NOTES NOTES ON CONCRETE MIXES & PLACING

1. IN THE INTERPRETATION OF THE DRAWING, INDICATED DIMENSIONS SHALL GOVERN AND 1. ALL CONCRETE SHALL DEVELOP A MINIMUM COMPRESSIVE STRENGTH AT THE END OF TWENTY
DISTANCES AND SIZES SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. EIGHT (28) DAYS W/ CORRESPONDING MAXIMUM SIZE AGGREGATE & SLUMP AS FOLLOWS.

2. IN REFERENCE TO OTHER DRAWINGS, SEE ARCHITECTURAL DRAWING FOR DEPRESSIONS LOCATION 28DAYS STRENGTH MAX. SIZE OF MAX. SLUMP
IN FLOOR SLABS, OPENING IN THE WALLS AND SLABS, INTERIOR PARTITION, LOCATION AGGREGATE
OF DRAINS ETC.
ALL OTHER, INCLUDING
3. IN CASE OF DISCREPANCIES AS TO THE LAYOUT, DIMENSION AND ELEVATION BETWEEN SUSPENDED SLABS. 4000PSI (27.6MPa) 20mm 100mm
THE STRUCTURAL PLANS AND ARCHITECTURAL DRAWING, THE CONTRACTOR SHALL NOTIFY
BOTH THE STRUCTURAL ENGINEER AND THE ARCHITECT. COLUMNS 4000PSI (27.6MPa) 20mm 100mm

4. ALL CONCRETE WORKS SHALL BE DONE IN ACCORDANCE WITH THE ACI.318 95 BUILDING BEAMS, SLABS 4000PSI (27.6MPa) 20mm 100mm
CODE REQUIREMENTS FOR REINFORCED CONCRETE AND ALL STRUCTURAL STEEL WORK
ACCORDING WITH AISC SPECIFICATION (9th EDITION) IN SO FAR AS THEY DO NOT CONFLICT SLAB ON FILL 3000PSI (20.7MPa) 20mm 100mm
WITH THE LOCAL BUILDING CODE REQUIREMENTS.
2. MAINTAIN MINIMUM CONCRETE COVER FOR REINFORCING STEEL AS FOLLOWS.
5. ACI REFERS TO AMERICAN CONCRETE INSTITUTE, AISC TO AMERICAN INSTITUTE OF STEEL SUSPENDED SLABS--------------------------------------------------------------20mm
CONSTRUCTION AND ASTM TO AMERICAN SOCIETY FOR TESTING MATERIALS. SLAB ON GRADE----------------------------------------------------------------40mm
WALL ABOVE GRADE-------------------------------------------------------------25mm
6. CONSTRUCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE BEAM STIRRUPS AND COLUMN TIES------------------------------------------------25mm
SHOWN OR NOTED. MODIFY TYPICAL DETAILS AS DIRECTED TO MEET SPECIAL CONDITIONS. WHERE CONCRETE IS EXPOSED TO
EARTH BUT POURED AGAINST FORMS-----------------------------------------------50mm
7. SHOP DRAWING WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEELS, WHERE CONCRETE IS DEPOSITED
MISCELLANEOUS IRON, PRE-CAST CONCRETE ETC, SHALL BE SUBMITTED FOR ENGINEERS DIRECTLY AGAINST EARTH-------------------------------------------------------75mm
APPROVAL BEFORE FABRICATION.
3. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT SEGREGATION. RE-HAND
8. CONTRACTOR SHALL NOTE AND PROVIDE ALL MISCELLANEOUS CURBS, SILLS, TOOLS, LING OR PLACING SHALL BE DONE PREFERABLY WITH BUGGIES, BUCKET OR WHEELBARROWS,
EQUIPMENTS AND MECHANICAL DRAWINGS. NO CHUTES WILL BE ALLOWED EXCEPTS TO TRANSFER CONCRETE FROM HOPPERS TO BUGGIES,
WHEELBARROWS OR BUCKET IN WHICH CASE THEY SHALL NOT EXCEED SIX (6) METERS IN
9. ALL RESULTS OF MATERIAL TESTING FOR CONCRETE, REINFORCING BARS & STRUCTURAL AGGREGATES LENGTH.
STEEL MUST BE NOTED & APPROVED BY THE STRUCTURAL DESIGNER.
4. NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS UNLESS
AUTHORIZED IN WRITING BY THE DESIGNERS AND ONLY FOR UNUSUAL CONDITIONS WHERE
VIBRATIONS IN EXTREMELY DIFFICULT TO ACCOMPLISH.
NOTES ON REINFORCEMENT 5. ALL ANCHOR BOLTS, DOWEL AND OTHER INSERT, SHALL BE PROPERLY POSITIONED & SECURE
IN PLACE PRIOR TO PLACING OF CONCRETE.
1. UNLESS OTHERWISE NOTED IN PLANS, THEE YIELD STRENGTH FOR REINFORCING BARS SHALL BE:
A. FOOTING, BEAMS AND GIRDERS------------------------------------fy = 275MPa (4000psi) 6. ALL CONCRETE SHALL BE KEPT MOIST FOR SEVEN CONSECUTIVE DAYS IMMEDIATELY AFTER POURING BY THE USE OF WET
B. COLUMN AND SHEAR WALL-----------------------------------------fy = 275MPa (4000psi) BURLAP, FOG SPRAYING, CURING COMPOUNDS OR OTHER APPROVED METHODS.
C. BEAM AND GIRDER-----------------------------------------------fy = 275MPa (4000psi)
D. NON-LOAD BEARING WALL PARTITIONS, BEDDED SLABS, FLOOR & ROOF SLABS, 7. STRIPPING OF FORMS AND SHORES:
PARAPETS, CATCH BASIN, SIDE WALK------------------------------fy = 227.5MPa (3300psi) FOUNDATION--------------------------------------------------------------------24 HRS
SUSPENDED SLAB EXCEPT WHEN
2. ALL REINFORCING BARS SIZE 10mm OR LARGER SHALL BE DEFORMED IN ACCORDANCE WITH ASTM ADDITIONAL LOADS ARE IMPOSED--------------------------------------------------8 DAYS
A 706 BARS SMALLER THAN 10mm MAY BE PLAIN. WALLS-------------------------------------------------------------------------21 DAYS
BEAMS-------------------------------------------------------------------------14 DAYS
3. SPLICES SHALL BE SECURELY WIRED TOGETHER & SHALL LAP OR EXTEND IN ACCORDANCE W/ TABLE COLUMNS-----------------------------------------------------------------------21 DAYS
A & TABLE B (TABLE OF LAP SPLICES & ANCHORAGE LENGTH) UNLESS OTHERWISE SHOWN ON
DRAWINGS, SPLICES SHALL BE STAGGERED WHENEVER POSSIBLE. 8. THE CONTRACTOR SHALL SUBMIT THE SCHEDULE OF POURING AND THE LOCATION OF THE
CONSTRUCTION JOINTS TO THE STRUCTURAL ENGINEER AT LEAST (4) DAYS PRIOR TO THE
POURING FOR APPROVAL.
NOTES ON WELDS 9. THE CONTRACTOR SHALL FURNISH AND MAINTAIN ADEQUATE FORMS AND SHORING UNTIL THE
CONCRETE MEMBERS HAVE ATTAINED THEIR WORKING CONDITION AND STRENGTH.

NOTES ON EMBEDDED PIPES


A. ALL EMBEDDED PIPES FOR UTILITIES, ETC. THAT PASS THRU BEAM SHALL NOT EXCEED 100mm
IN DIAMETER OR 31 BEAM DEPTH WHICHEVER IS LESS. UNLESS OTHERWISE APPROVED IN
WRITING BY THE STRUCTURAL ENGINEER.

B. NO PIPES SHALL BE ALLOWED TO PASS THRU BEAMS VERTICALLY.

C. NO PIPES SHALL BE EMBEDDED IN COLUMNS.

SIGN AND SEALED APPROVED BY : PROJECT TITLE SHEET CONTENT SHEET NO.
ENGR. ADOLFO D. TANCO III PROPOSED 1 STOREY- 2 BEDROOM
RESIDENTIAL BUILDING AS SHOWN
CIVIL ENGINEER OWNER LOCATION : BRGY. STA. CRUZ, KORONADAL CITY