Calibration Procedure Crowcon Xgard Gas Detectors - 5720273 - 01
Calibration Procedure Crowcon Xgard Gas Detectors - 5720273 - 01
Revision: AA
Date: 27-AUG-2012
INSTRUCTION-PROCEDURE Page: 1 of 16
TITLE: CALIBRATION PROCEDURE, CROWCON XGARD GAS DETECTORS
1.0 Purpose:
This procedure is to detail the work instructions required to calibrate the Crowcon Xgard H2S and
HC gas detectors.
2.0 Scope:
This procedure shall be followed to calibrate the Crowcon Xgard H2S (Type 1) gas detectors and HC
(Type 5) gas detectors.
Manufacturer (Crowcon) recommends the detectors be gas tested at least every 6 months (STEM 2
Maintenance) and re-calibrated as necessary. This procedure therefore details the work
instructions required to perform the calibration.
3.0 Definitions:
Schlumberger Private
3.2 LEL: Lower Explosive Limit
3.3 ppm: Parts per million
4.0 Responsibilities:
4.1 People
4.1.1 Design Engineer:
To provide the procedure to perform the required modification.
Warning: The controlled source document of this document is stored within the Product Data Management (PDM) System Any paper version of
this document is uncontrolled and should be compared with the source document at time of use to ensure it is up-to-date.
PDM # 101179210
Revision: AA
Date: 27-AUG-2012
INSTRUCTION-PROCEDURE Page: 2 of 16
TITLE: CALIBRATION PROCEDURE, CROWCON XGARD GAS DETECTORS
5.0 Procedure:
Schlumberger Private
The above mentioned parts can be ordered via SWPS as M&S by order from PPCS.
Item Manufacturer’s
Description Manufacturer Qty
No. Part Number
Calibration Adaptor for Xgard Gas
1 Crowcon C03005 1
Detector
H2S Gas Can + Regulator:
Calibration Gas: 25ppm Hydrogen
2 Crowcon CRWS0004 1
Sulphide (H2S) Balance Air, 34L
Can, Type 2AL
Regulator 0.5L/min with 2 ft Clear CRWS1002 +
3 Crowcon 1
Tube fits type 2AL CRWS1004
CH4 Gas Can + Regulator:
Calibration Gas: 2.5% vol (50% LEL)
4 Crowcon CRWS0082 1
Methane (CH4) Balance Air, 34L
Can, Type 7HP
Regulator 0.5L/min with 2 ft Clear CRWS1001 +
5 Crowcon 1
Tube fits type 7HP CRWS1003
Warning: The controlled source document of this document is stored within the Product Data Management (PDM) System Any paper version of
this document is uncontrolled and should be compared with the source document at time of use to ensure it is up-to-date.
PDM # 101179210
Revision: AA
Date: 27-AUG-2012
INSTRUCTION-PROCEDURE Page: 3 of 16
TITLE: CALIBRATION PROCEDURE, CROWCON XGARD GAS DETECTORS
Warning
5.4.1 Slacken the grub-screw on the lid of the detector then unscrew the lid by turning in
an anti-clockwise direction.
Schlumberger Private
Note:
Glass reinforced Nylon junction boxes do not include a grub screw.
Warning: The controlled source document of this document is stored within the Product Data Management (PDM) System Any paper version of
this document is uncontrolled and should be compared with the source document at time of use to ensure it is up-to-date.
PDM # 101179210
Revision: AA
Date: 27-AUG-2012
INSTRUCTION-PROCEDURE Page: 4 of 16
TITLE: CALIBRATION PROCEDURE, CROWCON XGARD GAS DETECTORS
5.4.2 Check there is a minimum of 8V DC on the “+” and “–” terminals of the detector.
Schlumberger Private
Warning: The controlled source document of this document is stored within the Product Data Management (PDM) System Any paper version of
this document is uncontrolled and should be compared with the source document at time of use to ensure it is up-to-date.
PDM # 101179210
Revision: AA
Date: 27-AUG-2012
INSTRUCTION-PROCEDURE Page: 5 of 16
TITLE: CALIBRATION PROCEDURE, CROWCON XGARD GAS DETECTORS
5.4.4 Connect a digital volt meter (DVM) to test points TP1 and TP2 on the amplifier PCB,
the DVM should be set to the dc mV range.
Schlumberger Private
Warning: The controlled source document of this document is stored within the Product Data Management (PDM) System Any paper version of
this document is uncontrolled and should be compared with the source document at time of use to ensure it is up-to-date.
PDM # 101179210
Revision: AA
Date: 27-AUG-2012
INSTRUCTION-PROCEDURE Page: 6 of 16
TITLE: CALIBRATION PROCEDURE, CROWCON XGARD GAS DETECTORS
5.4.6 Install the Calibration Adaptor (Crowcon P/N C03005) to the detector.
Schlumberger Private
Warning: The controlled source document of this document is stored within the Product Data Management (PDM) System Any paper version of
this document is uncontrolled and should be compared with the source document at time of use to ensure it is up-to-date.
PDM # 101179210
Revision: AA
Date: 27-AUG-2012
INSTRUCTION-PROCEDURE Page: 7 of 16
TITLE: CALIBRATION PROCEDURE, CROWCON XGARD GAS DETECTORS
5.4.7 Connect the 2ft clear tube (Crowcon P/N CRWS1004) to the 0.5L/min flow regulator
Crowcon P/N CRWS1002). Then connect the regulator to H2S the gas can (Crowcon
P/N CRWS0004).
Schlumberger Private
Figure 6: H2S gas bottle-regulator assembly
Note:
It is recommended that the needle valve of the regulator is left slightly in its ‘Open’
position while making the initial connection to the gas bottle. Once you see the
gas coming out from the other end of the tube fully close the needle valve. This
prevents any chances of air getting inside the cylinder and affecting the gas
concentration.
5.4.8 Connect the loose end of the 2ft clear tube (Crowcon P/N CRWS1004) to either of the
nipples on the calibration adapter.
Warning: The controlled source document of this document is stored within the Product Data Management (PDM) System Any paper version of
this document is uncontrolled and should be compared with the source document at time of use to ensure it is up-to-date.
PDM # 101179210
Revision: AA
Date: 27-AUG-2012
INSTRUCTION-PROCEDURE Page: 8 of 16
TITLE: CALIBRATION PROCEDURE, CROWCON XGARD GAS DETECTORS
Schlumberger Private
Figure 7: Calibrating the H2S detector
5.4.10 Remove the gas and allow the sensor to stabilize then re-check the zero setting.
Close the junction box ensuring it is securely tightened then tighten the grub-screw.
Warning: The controlled source document of this document is stored within the Product Data Management (PDM) System Any paper version of
this document is uncontrolled and should be compared with the source document at time of use to ensure it is up-to-date.
PDM # 101179210
Revision: AA
Date: 27-AUG-2012
INSTRUCTION-PROCEDURE Page: 9 of 16
TITLE: CALIBRATION PROCEDURE, CROWCON XGARD GAS DETECTORS
5.5.1 Slacken the grub-screw on the lid of the detector then unscrew the lid by turning in
an anti-clockwise direction.
Schlumberger Private
Figure 8: Location of the grub-screw on the gas detector
5.5.2 Measure the voltage across the “+” and “–” terminals of the detector and check a
minimum supply of 10V DC is present.
Warning: The controlled source document of this document is stored within the Product Data Management (PDM) System Any paper version of
this document is uncontrolled and should be compared with the source document at time of use to ensure it is up-to-date.
PDM # 101179210
Revision: AA
Date: 27-AUG-2012
INSTRUCTION-PROCEDURE Page: 10 of 16
TITLE: CALIBRATION PROCEDURE, CROWCON XGARD GAS DETECTORS
Schlumberger Private
Warning: The controlled source document of this document is stored within the Product Data Management (PDM) System Any paper version of
this document is uncontrolled and should be compared with the source document at time of use to ensure it is up-to-date.
PDM # 101179210
Revision: AA
Date: 27-AUG-2012
INSTRUCTION-PROCEDURE Page: 11 of 16
TITLE: CALIBRATION PROCEDURE, CROWCON XGARD GAS DETECTORS
Figure 10: Location of Test Points TP3 & TP4 and the potentiometer VR3 Schlumberger Private
Warning: The controlled source document of this document is stored within the Product Data Management (PDM) System Any paper version of
this document is uncontrolled and should be compared with the source document at time of use to ensure it is up-to-date.
PDM # 101179210
Revision: AA
Date: 27-AUG-2012
INSTRUCTION-PROCEDURE Page: 12 of 16
TITLE: CALIBRATION PROCEDURE, CROWCON XGARD GAS DETECTORS
Schlumberger Private
Figure 11: Measuring voltage across test points TP3 & TP4
Warning: The controlled source document of this document is stored within the Product Data Management (PDM) System Any paper version of
this document is uncontrolled and should be compared with the source document at time of use to ensure it is up-to-date.
PDM # 101179210
Revision: AA
Date: 27-AUG-2012
INSTRUCTION-PROCEDURE Page: 13 of 16
TITLE: CALIBRATION PROCEDURE, CROWCON XGARD GAS DETECTORS
Schlumberger Private
Figure 12: Zeroing the Type 5 detector
5.5.6 Install the Calibration Adaptor (Crowcon P/N C03005) to the detector.
Warning: The controlled source document of this document is stored within the Product Data Management (PDM) System Any paper version of
this document is uncontrolled and should be compared with the source document at time of use to ensure it is up-to-date.
PDM # 101179210
Revision: AA
Date: 27-AUG-2012
INSTRUCTION-PROCEDURE Page: 14 of 16
TITLE: CALIBRATION PROCEDURE, CROWCON XGARD GAS DETECTORS
5.5.7 Connect the 2ft clear tube (Crowcon P/N CRWS1003) to the 0.5L/min flow regulator
Schlumberger Private
Crowcon P/N CRWS1001). Then connect the regulator to CH4 gas can (Crowcon P/N
CRWS0082).
Warning: The controlled source document of this document is stored within the Product Data Management (PDM) System Any paper version of
this document is uncontrolled and should be compared with the source document at time of use to ensure it is up-to-date.
PDM # 101179210
Revision: AA
Date: 27-AUG-2012
INSTRUCTION-PROCEDURE Page: 15 of 16
TITLE: CALIBRATION PROCEDURE, CROWCON XGARD GAS DETECTORS
5.5.8 Connect the loose end of the 2ft clear tube (Crowcon P/N CRWS1003) to either of the
nipples on the calibration adapter.
Schlumberger Private
Figure 16: Calibrating the CH4 detector
5.5.10 Remove the gas and allow the sensor to stabilize then re-check the zero setting.
Close the junction box ensuring it is securely tightened then tighten the grub-screw.
Warning: The controlled source document of this document is stored within the Product Data Management (PDM) System Any paper version of
this document is uncontrolled and should be compared with the source document at time of use to ensure it is up-to-date.
PDM # 101179210
Revision: AA
Date: 27-AUG-2012
INSTRUCTION-PROCEDURE Page: 16 of 16
TITLE: CALIBRATION PROCEDURE, CROWCON XGARD GAS DETECTORS
Schlumberger Private
Warning: The controlled source document of this document is stored within the Product Data Management (PDM) System Any paper version of
this document is uncontrolled and should be compared with the source document at time of use to ensure it is up-to-date.