Professional Documents
Culture Documents
ADDAD - 4 Manual
ADDAD - 4 Manual
ADDAD - 4 Manual
Notice
The information contained in this document is subject to change without notice. AEC makes no
warranty of any kind with regard to this material, including, but not limited to, the implied
warranties of merchantability and fitness for a particular purpose. AEC shall not be liable for
errors contained herein or incidental consequential damages in connection with the furnishing,
performance, or use of this material.
This document contains proprietary information which is protected by copyright. All rights are
reserved. No part of this document may be photocopied or otherwise reproduced without consent
of AEC.
Published in a limited copyright sense, and all rights, including trade secrets, are reserved.
The Addad-4 DLMS poly phase smart meter series comprises of 10(100) A, 20(160) A, 1.5(6) A,
1(6) A, 3-Phase-4-Wires, 3-Phase-3-Wires, Direct (Whole current) connection, Transformer
operated CT and CT-VT through connection meters. This Manual is specific for 1(6)A & 5(6)A
3-Phase-4-Wires 3P4W & 5(6)A 3-Phase-3-Wires 3P3W CT,CT-VT through connection meters
with RS485 as a communication media option.
The emerging AMR technologies in the metering industry call for smart meters that have
enormous communication capabilities. The Addad-4 DLMS Smart Meters composite of all
advanced metering functionalities and its robust communication capabilities can easily be an
integral part of the Automatic Meter Reading System (AMR). AEC also provides state of the art
AMR software to manage its smart meters remotely.
All meter types are equipped with a standard built in optical communication interface with DLMS
protocol. Data read out through the communication interface are equipped with the OBIS
identification code. Other communication interfaces like RS485, EURIDIS & GSM are present
according to the meter types.
Notes:
• All default values are configured based on customer request.
• For 3P3W meters phase-B is considered as reference instead of neutral.
LCD
Optical
Communication Scroll Buttons
Port
Pulse LED
Battery Door
Meter Information
Serial number
Optical Port
Optical Link Infrared, 860nm - 950nm
Optical Port Per IEC62056-21
Max. Baud rate 4800 bps
RS485 Port
(For Class 0.2 3P4W Meters only)
Max. Baud rate 9600 bps
Safety Information
General precautions to prevent electric shock
2- Only qualified personnel are allowed to carry out the electrical installation.
AUX
Supply
RL2 RL1
+ -
L N
RL4 RL3
If powered by the VT signals, the meter has three phase power supply to power all electronics
circuitry. This approach insures that the meter is completely functional with single phase. This
guarantee that if two phases goes out for some reason the meter still operate and register
accurately the energy consumed by the existing phase.
If the meter is powered by the auxiliary power supply input at terminal 21 & 25. To use AC power,
connect the line supply wire to the L+ terminal and the neutral supply wire to the N- terminal. To
use DC power, connect the positive supply wire to the L+ terminal and the negative supply wire to
the N- terminal.
The meter contains three voltage sensors and three current sensors as in Fig 4.1 all the sensors
outputs are conditioned using signal conditioning circuit before feeding to analog to digital
converter (A/D) and then feed to power calculation module. This module calculate rms voltage,
current, active power, reactive power, apparent power and frequency, and then generate LED
pulse according to active and reactive power calculated and send this information to
microcontroller that calculates the energy consumption and display Basic and Tariff registers.
The meter measure and display active power, reactive power and apparent power. The
calculations is done as fallows
Active and reactive power can be import (+) or export (-) depending on the angle between voltage
and current as in Fig 4.2
II I
Φ= 180º Φ= 0º
III IV
Φ= 270º
Figure 4.3
The meter calculates each phase alone then sum the total according to below formulas
(3P4W METERS)
(3P3W METERS)
The meter calculates each phase alone then sum the total according to below formulas
(3P4W METERS)
The meter calculates each phase alone according to active and reactive power for each phase
then sum the total according to below formulas
(3P4W METERS)
(3P3W METERS)
The meter calculates amount of power consumed during a period of one hour, kilo Watt hour
(kWh), kilo Var hour (kVarh) and kilo VoltAmp hour (kVAh).
For 3P4W Meter-type, the meter examine each phase individually, phase measuring positive
power is considered as import and phase measuring negative power is considered as export.
Import energy is registered in import registers and export energy is registered in export registers.
For 3P3W Meter-type, the meter examines power for all phases together as a total power, it sums
up all three phase power together, the resultant determines the type of energy flow, positive
power is considered import and negative power is considered export. According to the type of
energy it will be stored in respective register, if it is Import then energy is registered in import
registers or if it is export then energy is registered in export registers.
The Meter calculates the demand by accumulating the power (kW, kvar or kVA) for Active,
Reactive & Apparent Powers over a specified period of time, called integration period, and then
the Power is divided by the integration period to get the average over this period. The Meter
supports block and sliding window methods for calculating the demand with programmable
integration periods of 15, 30 or 60 minutes. And fixed sub interval of 5 minutes for sliding window
method. The end of last demand period in a day will match 00:00 hours. The Meter can be
programmed with Block or Slide to use any of this method to calculate the demand. The Meter
will display the method used when scrolling to any of the demand screens. Demand calculation is
explained in detail as below.
All the following values represent an average for one of the energy components in a user
specified integration period. They are calculated according to two different methods (will be
described later). The target of the demand calculation is to watch the load behavior over a certain
period. In some countries the demand has an effect to the customer bill.
The active energy demand is the average of active power during one integration period. It is
updated according to the following equation:
[Demand (W ) = consumption / duration]
Where:
• Consumption is the sum of the active power consumed during the integration interval.
• Duration is the interval in minutes.
The reactive energy demand is the average of reactive power during one integration period. It is
updated according to the following equation:
[Demand (VAR) = consumption / duration ]
Where:
• Consumption is the sum of the reactive power consumed during the integration interval.
• Duration is the interval in minutes.
The apparent energy demand is the average of apparent power during one integration period. It is
updated according to the following equation:
Demand (VA) = consumption / duration
Where:
• Consumption is the sum of the apparent power consumed during the integration interval.
• Duration is the interval in minutes.
Demand represents the average of the energy component over a programmable integration
period. There are two methods for demand calculation used:
• Block method.
• Sliding window method.
In the block method the demand is averaged and updated every integration period as in the figure
below (assuming the integration period is 30 minute):
…
00:00
00:30
01:00
01:30
Sliding Window Method:
In the sliding window method the demand is averaged and updated every sub-interval which is
fixed to 5 minutes for the last integration period as in the figure below (assuming the integration
period is 30 minute):
… …
00:00
00:05
00:10
00:15
00:20
00:25
00:30
00:35
00:40
00:45
00:50
00:55
01:00
01:05
01:10
01:15
01:20
01:25
01:30
Every second the system sums each energy component in its own sum registers. Each register
will hold the sum of five minutes and then stored in a circular buffer. The demand is calculated as
follow:
Block method:
At the end of every integration interval the demand is calculated by summing the past sub-
intervals and dividing the result by number of seconds in the integration period.
At the end of every sub-interval (5 minutes) the demand is calculated by summing the past sub-
intervals and dividing the result by number of seconds in the integration period.
At the end of each integration period, the Meter examines the demand value to check for
maximum value. If the Demand value is greater than the Maximum Demand value, the Meter will
replace the previous maximum with the new maximum with date and time stamp.
For Minimum Power Factor Lag & Minimum Power Factor Lead there are two separate registers
and does not influence each other & each register works independently. The Meter examines the
PF (Lag or Lead) value to check for minimum value. If the current PF (Lag or Lead) value is
smaller than the minimum registered PF value (Lag register or Lead register), the Meter will
replace the previous minimum value with the new minimum value with date and time stamp.
Figure 4.2B
Updating of Minimum Lag & Lead take place under following cases:
The meter provides a variety of registers; all of the registers are stored in the EEPROM that have
data retention of 20 years and does not required battery to keep data during power off so that
data are not lost during power outage. Available registers are as follows.
All The Meter identification registers are only access through the communication ports. Moreover
the Meter serial number is printed on the Meter name plate and can also be read through the
LCD.
4.2.2.1 Schedule
4.2.2.2 Demand
4.2.2.3 Display
4.2.2.4 Meter Security Codes
4.2.2.5 Transformer Ratios
4.2.2.6 Relay
4.2.2.7 Time & Date
We start by Normal Peak we can select any tariff name from the 8 tariffs we can select
T5 we can define as below schedule note that week included days has Thursday and
Friday is off because we don’t want this tariff to switch in holidays.
Then we can select another name for summer peak. We can select T2 as in below
schedule note that switch time is defined to start in 12:00 and year with xxxx (means
every year).
Then we can select another name for Holidays (week ends). We can select T8 as in
below schedule note week included days only Thursday and Friday. Another note that T8
will fill the gap that was created by T5.
Then we can select another name for Holidays (Eid and National days). We need to
define the Eid holidays in Hijrah calendar as in table below. We can select T6 as in below
schedule. Note that special day 1 is enabled which defines the national day for all years.
Special Day
YYYY:MM:DD
Max 10 , Min 0
D1 xxxx.09.23
D2 2007.10.12
D3 2007.10.13
D4 2007.10.14
D5 2007.10.15
D6 2007.12.19
D7 2007.12.20
D8 2007.12.21
D9 2007.12.22
D10 2007.12.23
4.2.2.2 Demand
Demand can be set for the method (Block or Slide) and Integration period (15, 30 or 60) Default is
Slide with Integration period 30 minutes. For register details refer to Measurement Registers
section.
4.2.2.3 Display
The Meter has 148 screens all of them can be configured as fallows
Association
ASSOCIATION LLS
No. Association Description
Type Password
Range
Security code for
Max 10 , Min
programming (setting)
4, can be any
the meter including
Full Write combinations
1 resetting the meter
access + Reset alpha or
through the
numerals or
communication ports.
both
Max 10 , Min
Security code for 4, can be any
Full Read
reading the complete combinations
2 Access
meter registers through alpha or
the communication ports numerals or
both
Security code for Max 10 , Min
Reading and writing to 4, can be any
Restricted
the meter registers but combinations
3 Write/Read
excluding the reset alpha or
access
through the numerals or
communication ports both
No security code used
for it. It is used to read
4 Default access the measurement meter N/A
registers only through
the communication port.
Current Transformer (CT): The ratio shall only be in format of xxxxx:5 or xxxxx:1, with minimum
value of 00001:1 and maximum value of 10000:5. The primary value shall be always greater than
or equal the secondary value. Note that Secondary can either be 5 or 1 only. The default CT ratio
is set to 5:5
Voltage Transformer (VT): The ratio shall be in format of vvv.v:y.yyy kV, with minimum value for
vvv.v of 000.1kV and maximum value of 655.3kV. For y.yyy, minimum value of 0.100 and
maximum value of 0.999.The primary value shall be always greater than or equal the secondary
value. The default VT ratio is set to 0.1: 0.100
Example: CT = 500, VT = 30
¾ Date: In the format YYYY:MM:DD, where: YYYY from 2001 to 2099 MM from 1 to 12, DD
from 1 to 31. Weekday (1-7), 1 is Monday.
¾ Time: In the format HH:MM, where: HH: from 00 hours to 23 hours, MM: from 00 to 59.
All measurements registers can be viewed on the LCD and through the communication ports. The
values sent through the communication are always primary values.
The meter has 10 Basic registers as in table 1.3. Range is from 000000.00 to 999999.99, then roll
over to 000000.00 if the LCD is configured to display six digits with two decimal places.
Basic register are those registers which continuously accumulates the consumption at all times,
the user has no control on the basic registers and are not affected by the TOU programming.
Table 1.3
The meter has 8 Tariffs and each Tariff has 10 Registers as in table 1.4. The roll over range will
be always linked with the number of digits as basic registers.
The following registers displays Instantaneous measurements, the refresh rate is one seconds.
These registers stores & displays the maximum demand (highest value) from the demand
calculation module at the end of the demand integration period as explained in section 4.1.6 with
date and time stamp as follows:
No. Measurement
1 Total 3 phase Maximum Active demand
2 Date stamp for Maximum Active demand
3 Time stamp for Maximum Active demand
4 Total 3 phase Maximum Reactive demand
5 Date stamp for Maximum Reactive demand
6 Time stamp for Maximum Reactive demand
7 Total 3 phase Maximum Apparent demand
8 Date stamp for Maximum Apparent demand
9 Time stamp for Maximum Apparent demand
10 Total 3 phase Minimum Lag Power Factor
11 Date stamp for Minimum Lag Power Factor
12 Time stamp for Minimum Lag Power Factor
13 Total 3 phase Minimum Lead Power Factor
14 Date stamp for Minimum Line Power Factor
15 Time stamp for Minimum Line Power Factor
1. Auto reset at predefined time and date. (enabling auto reset will disable manual
reset)
2. Manual Reset by pressing the sealed push button. A reset message is displayed on
LCD when reset button is pressed. There is 15 minutes gap after pressing the first
reset, so the second manual reset can only be done after 15 minutes. (disabling auto
reset will enable manual reset)
3. Reset by using communication
The reset will clear all maximum demand values to zero and minimum lag and minimum
lead Power factors to 1.0 and date and time stamp will change to the reset time. Old Maximum
demand values will be stored in history file and all consumption registers including tariff registers
will be stored in history file as explained in section 4.13.
The illustration below shows all segments (shown in 14 groups) that can appear on the display in
different screens:
14 1 2
- 8.8.8:8:8.8:8.8
Hz
S/N 5
11 MkVVArh
9 8 7
4.4.1.1 Group #1
4.4.1.3 Group #3
4.4.1.5 Group #6
4.4.1.6 Group #7
END RESERVED
4.4.1.10 Group # 14
These indicators will depend upon the type of meter, if the meter has one or more of these
feature then it will appear/displayed in all screens.
The display system is divided into 2 modes: Normal & Dial Test Mode.
The next programmed screen will last for the programmable Idle time period minimum of 5
seconds and maximum of 5 minutes after which the screen will go back to screen number 1. The
programmable period will be applied for all screens. The default is 5 minutes.
The number of digits and decimal points for displaying the consumption registers are
programmable. The meter will reject any setting that will cause any register to lose part of register
value.
For all screens, when scroll button is pressed, the meter will show the next programmed screen.
Pressing and holding the scroll buttons (Right + Down) for more than 2 seconds and releasing it
will cause the display automatically sequence through the programmed screens list. Each screen
will be visible for programmable period (Auto Scroll Period), default 5 seconds. (Minimum 1
seconds, maximum 255 second). Pressing any button will stop scrolling.
Pressing and holding the scroll buttons (Left + Down) for more than 2 seconds and releasing it
will cause the display to show all segment ON (see Fig 4.3) for 5 seconds, then return back to the
screen it was showing.
Figure 4.3
A lithium backup battery keeps the RTC running in the event of power OFF or meter storage in
the utility warehouse. The battery offers back-up power for at least 10-year continuous operation
and 1 year continuous operation after 10 years storage.
Forward Adjustment:
If the time is adjusted the meter will clear demand.
Backward Adjustment:
***CAUTION***
If the backward time adjustment in minutes is greater than the demand integration period
(15 minutes), then the Meter will perform the following:
Time synchronization:
Any backward time adjustment below 15 minutes is considered as Time synchronization
and will result only a clear of demand registers. Two consecutive time backward
synchronization cannot be accepted by the meter (the second one will be rejected) until
the time crosses the old time before synchronization.
Setting range:
3P4W 1(6): Programmable threshold. Range: 40V to 86.6V
3P3W 5(6): Programmable threshold. Range: 60V to 140V
3P4W 5(6): Programmable threshold. Range: 90V to 250V
Setting range:
3P4W 1(6): Programmable threshold. Range: 10% to 600% of basic current to Imax.
3P3W 5(6): Programmable threshold. Range: 2% to 120% of basic current to Imax.
3P4W 5(6): Programmable threshold. Range: 2% to 120% of basic current to Imax.
However the Relay will operate if following conditions are met first.
• All 3-phase currents are greater than or equal the minimum current
• All 3-phase Voltages are greater than or equal 30 Volt.
• Power Flow Direction: Completely Import, i.e. all phases in import
direction.
• Hold the checking if any of the above condition not granted.
• If there is any power off then Rest every thing
• Checking started immediately after power on
The meter is protected against tampering or accidental wrong wiring. The meter provides the
following protections:
The meter detects & logs the date & time for occurrence & restoration for several events, up to
200 events and when the event log become full the new log will replace the oldest event. For the
following events:
• Missing potential
• Current Reversal
• Low Power Factor
• Top Cover Opened
• Time before change
• Time after change
• Invalid time
• Parameters changed
• Reset
The meter waits for 30 minutes from power-up before recording the events and there is a 10
minute delay to ensure that it is a real event, this is to avoid transient events,. (Except for the
events Top Cover Opened, Time after and before change, Invalid time, Parameters changed and
reset)
4.8.2.9 Reset
The meter will record the old time and date for any type of resets (Auto Reset, manual Reset and
Reset by communication).
4.10 CT VT Log
Setting CT (Primary and Secondary), VT (Primary and Secondary) ratio will log the new
setting & old settings with date and time. The size of the file is 40 events and then rolls
over.
Load profile reading is done through the optical port or remote reading using communication.
The meter keeps historical data recording in the log for the following registers:
• Number of times the meter has been programmed. Maximum up to 65000 before
resetting to zero.
• Date and time of last meter programming.
• Number of times the meter has been powered down. Maximum up to 65000 before
resetting to zero.
• Date and time of last power down.
• Number of resets. Maximum up to 65000 before resetting to zero.
• Date and time of last reset.
• Date of battery install.
• Date and time of battery fail.
• Date and time of last reverse run.
• Date and time of last phase loss.
Table 4.1
The optical port is a standard communication port for all types, other ports depend on the
ordering part number (see section 6.0 ordering information). The available communication ports
as follows.
On the LCD, there are two error screens available for displaying error types as shown in figure
5.3.1, dash means no error. Please contact the Supplier if one of these errors are discovered.
¾ (Reserved)
¾ Phase A current overload
¾ Phase B current overload
¾ Phase C current overload
¾ Low Battery
The battery offers back-up power for at least 5-year continuous operation and 1 year continuous
operation after 10 years storage. To replace the battery please apply below steps:
Picture 5.1
Picture 5.2
Picture 5.3
Picture 5.4
Picture 5.5
Picture 5.6
Picture 5.7
Picture 5.8
10. Power ON the meter and set the date and time
Examples:
3P4W (3x 57.7/100 ~ 69.3/120 VAC) 1(6)A CL0.2s: AD-442T2O4DNPXN
3P4W (3x 127/220 ~ 220/380 VAC) 5(6)A CL0.2s: AD-422C2O4DNPXN