Star-Delta Motor Starter Selection

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 5

3-PHASE STAR-DELTA STARTER SELECTION CHART

FULL LOAD
CIRCUIT BREAKER CONTACTOR RATING
3-PH MOTOR 3-PH MOTOR PHASE
SL.NO (MCB/MCCB)
KW HP CURRENT
RATING
(Amps)
MAIN
1 5.5 7.5 6.6 EZ9F56340 LC1D09U7
2 7.5 10 8.9 EZ9F56363 LC1D09U7
3 11 15 12.7 EZC100F3100 LC1D12U7
4 15 20 17.3 EZC250F3125 LC1D18U7
5 18.5 25 20.8 EZC250F3125 LC1D25U7
6 22 30 24.8 EZC250F3160 LC1D25U7
7 30 40 32.3 EZC250F3200 LC1D38U7
8 37 50 64.3 EZC250F3200 LC1D40U7
9 45 60 48.5 EZC250F3250 LC1D50AU7
10 55 75 57.2 EZC400N3400N LC1D65AU7
11 75 100 77.4 EZC400N3400N LC1D80U7
12 90 125 92.8 EZC400N3400N LC1D95U7
13 110 150 113.4 EZC630N4500N LC1D115U7
14 130 175 135.3 EZC630N4500N LC1D150U7
15 150 200 155.2 EZC630N4500N LC1F330
DELTA STARTER SELECTION CHART

CONTACTOR RATING ENCLOSURE SIZE (HxWxD) in


OVERLOAD RELAY RATING
MM

DELTA STAR
LC1D09U7 LC1D09U7 LRD12 (5.5-8.0A) 500X400X200
LC1D09U7 LC1D09U7 LRD14 (7.0-10.0A) 500X400X200
LC1D12U7 LC1D09U7 LRD16 (9.0-13.0A) 600X500X200
LC1D18U7 LC1D12U7 LRD21 (12.0-18.0A) 600X500X200
LC1D25U7 LC1D18U7 LRD22 (16.0-24.0A) 600X500X200
LC1D25U7 LC1D18U7 LRD32 (23.0-32.0A) 600X500X200
LC1D38U7 LC1D25U7 LRD35 (30.0-38.0A) 700X500X200
LC1D40U7 LC1D32U8 LRD340(30.0-40.0A) 700X500X200
LC1D50AU7 LC1D40AU7 LRD350 (37.0-50.0A) 700X500X200
LC1D65AU7 LC1D40AU7 LRD365 (48.0-65.0A) 1000X600X200
LC1D80U7 LC1D50AU7 LRD3363 (63.0-80.0A) 1000X600X200
LC1D95U8 LC1D50AU7 LRD3365 (80.0-104.0A) 1000X800X250
LC1D115U8 LC1D65AU7 LRD4367 (95.0-120.0A) 1200X800X250
LC1D150U8 LC1D80U7 LRD33696 (110.0-140.0A) 1200X1000X250
LC1F330 LC1D95U7 LR9F (132.0-220.0A) 1200X1000X300
RUN AND TRIP PUSH BUTTON OR STAR
INDICATION - EACH SELECTOR SWITCH DELTA
ONE TIMER
1NO&1NC OFF/ON
1 2 1 1
1 2 1 1
1 2 1 1
1 2 1 1
1 2 1 1
1 2 1 1
1 2 1 1
1 2 1 1
1 2 1 1
1 2 1 1
1 2 1 1
1 2 1 1
1 2 1 1
1 2 1 1
1 2 1 1
HP TO KW CONVERSION STEP-1
Input of Motor HP 2 HP
HP to Kw Conversion 1 Kw
KW CALCULATION STEP-2
Input of Motor kW 60 kW
Efficiency% %
System Voltage 415 V
Phase 3Ø
System P.F 0.8
Full Load Current Line #DIV/0! A
Full Load Current Phase #DIV/0!
Mccb/Mcb Rating #DIV/0!
Main Contactor #DIV/0! 1/1.732 of FLC = 58% of FLC
Delta Contactor #DIV/0! 1/1.732 of FLC = 58% of FLC
Star Contactor #DIV/0! 1/3 of FLC = 33% of FLC
O/L Relay Min #DIV/0! 80% of FLC Phase
O/L Relay Max #DIV/0! 130% of FLC Phase
O/L Relay Setting #DIV/0! 110% of FLC Line
Step-1
Conversion for HP to KW.
Step-2
Kw values can be given in cells either converted(from
step-1) or directly. as well as the motor efficiency
needed to provide in the cell. Certain values are
locked.