General
Step 3: Start the test
OMICRON offers a reference CT (calibration CT
VEHZ0649) for calibrating the CT Analyzer. This
reference CT is delivered together with a calibration
certificate from a national test laboratory. The Step 4: Assessment
calibration CT is a class 0.02% CT and has a ratio of Compare the CT Analyzer test results with the results in
2000:1 and 2000:5. the calibration report delivered with the reference CT.
To do the calibration follow steps 1 to 4. Compare the results at:
100% nominal current and 100% burden and at 50%
Step 1: Connection of reference CT nominal current and 100% burden.