Precast Compound Wall - 14.02.2023 - Commented

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

1. ALL DIMENSIONS ARE IN MM UNITS, UNLESS OTHERWISE SPECIFIED.

2. ADDITIONAL COLUMNS FOR EXPANSION JOINT SHALL BE PROVIDED AT


A. EVERY 15 NOS OF COLUMNS.
B. EVERY 300MM CHANGE IN GROUND LEVEL.
3. HORIZONTAL PRECAST SLAB CONCRETE GRADE SHALL BE OF M 30.
4. VERTICAL PRECAST COLUMN POST CONCRETE GRADE SHALL BE OF M 30.
BEFORE LAYING OF PCC.
THIS DOTTED LINE SHOULD NOT BE THERE IF IT IS
AN ANGLE MEMBER
5. THE GRADE OF CONCRETE FOR VERTICAL POST UNDER GROUND
SHALL BE M 20.
6. STRUCTURAL MS STEEL SHALL CONFIRM TO IS - 2062.
7. BARBED WIRE SHALL CONFIRM TO IS 2721. 4
8. PRECAST/PRESTRESSED SLAB S1 BE REINFORCED WITH 3 NOS OF
3MM WIRON OF STANDARD MAKES. 4
CHECK THE
DIA 9. PRECAST/PRESTRESSED SLAB S2 BE REINFORCED WITH 3 NOS OF
4MM WIRON OF STANDARD MAKES.
10. ALL NUT, BOLTS, ANGLES AND BASE PLATE SHALL BE MS AND
PROVIDED WITH 2 COATS OF SILVER PAINT WITH RED OXIDE.

1. PRECAST/PRESTRESSED SLAB BE REINFORCED WITH 4 NO'S OF 3MM WIRON


OF STANDARD MAKES, KINDLY CHANGE IT IN SECTION C-C.
2. 6 NOS OF 300MM PRE CAST SLAB REQUIRED.

1. CORNER POST DETAILS TO BE SHOWN.


2. HOW TO INSTALL THE BIRBED WIRE THROUGH THE CIRCLE. PLEASE CHECK IF CAN BE
POSSIBLE WITH INCLINED OPEN SLOT.
3. SHOW THE CONNECTION DETAIL OF MS BASE PLATE WITH 12 DIA MS BOLT.
4. MENTIONED THE DIA OF BARBED WIRE TO BE USED.
5. INCREASE THE DEPTH OF COLUMN SUPPORTED PILE ATLEAST TO 1000MM.

4 NOS OF 3MM WIRON

150

CLIENT: RADIANCE RENEWABLE PVT LTD


EPC CONTRACTOR: INSOLARE ENERGY PVT LTD
DEVELOPER: TS WIND POWER DEVELOPER

PROJECT DESCRIPTION: 150MW SOLAR POWER PLANT, MOL-MANJARWADI, PHALTAN.


TITLE: PRE-CAST COMPOUND WALL
SHEET NO: 01 OF 01

SCALE REV NO
N.T.S 01

DRAWING NO: TSWPD/RAD/COM WALL/MM/001