ISO9001:2015  

INSTRUCTION MANUAL
OF
SERIES LIQUID COOLERS

PLEASE READ CAREFULLY BEFORE USE.

THANKS FOR CHOOSING LABER LIQUID COOLER,

PLEASE READ THIS MANUAL CAREFULLY BEFORE USE SO AS TO

HELP YOU OPERATE THE LIQUID COOLER CORRECTLY.

Baoji Laber Precision Industries Co., Ltd.


CONTENTS

1 APPLICATIONS AND NOTES 5 SERVICE AND MAINTENNANCE

2 INSTALLATION 6 TROUBLESHOOTING

3 PANEL OPERATION 7 WARRANTY

4 TRIAL RUNNING 8 APPENDICES

1 Applications and notes

1. 1 Applications

The series products can be

Environment temp.(℃)
widely applied for CNC aggregate
machining centers, various
machining equipment, such as high
precision lathes, grinding machines,
Temp. range
sawing machines, etc., and can be applicable
applied for hydraulic machineries
and special machineries as well.
1.2 Applicable temperature range
The series liquid coolers are
designed to operate under a temperature Inlet oil temp.(℃)
range given in fig.1, and can’t be used ig.1 Applicable temp range for the Oil Cooler
under conditions where the temperature is
out of the given range. The environment temperature in this manual means room temperature.
1.3 Applicable liquids
The series liquid coolers are only applicable for cooling liquid, hydraulic liquid, grinding liquid,
lubricating liquid and cutting liquid, and are not applicable for following liquids:
a. Water and water soluble liquids (except LO/W-C type);
b. Flammable hydraulic liquid;
c. Fuels, such as gasoline, etc.
d. Liquids of medicines or foods;
e. Any kinds of poisonous or corrosive liquids.
1.4 Notes on safety
1.4.1 Please do cut off the power during routine service, maintenance and examination.
1.4.2 When the cooler needs to be welded,
a. Please remove the cooling system from the main body and drain the liquid completely from
the cooler.
b. Please conduct repairing in a well ventilated place where there is no danger of fire and the
discharge of refrigerant will not affect the surrounding persons.
c. Welding process should observe relevant safety regulations and provisions, and care should be
taken so as to prevent other parts or components from being burnt.
d. Welding should be conducted by personnel from the manufacturer or by qualified special
professionals.
2 Installation
2.1 Moving
During the moving of the unit, care should be taken to prevent it from being damaged due to
impact from external force or excessive bumping, and prevent it from being slant and upside down.
For above reasons, it is recommended to store the original packing. During the lifting, the center of
gravity should be controlled carefully.
2.2 Environment requirement for the place of installation
2.2.1 The cooling unit should be horizontally installed in a well ventilated, dry place and far from
dust and liquid fog. The air inlet and outlet ports should be at least 1m from the walls and other
objects, and necessary service clearance should be kept.

2.2.2 There should be no corrosive, flammable and explosive gas around the unit; and near the

installation spot, there should be no high temperature heating source and other heating objects. Besides,

the unit should not be directly exposed to the sunlight.

2.2.3 The installation spot should be decided by the customers according to type and model of the

unit selected. The structure of the installation spot should be strong enough to endure the weight of the

unit and the force passed when the unit is working.

2.3 Liquid piping


Normally, the pressure of the liquid cooler at the pumping side is about -0.3bar, and the pressure
at delivery side is about 5bar. Select liquid pipes in reference of the pressure level, and ensure that the
piping is rational, the installation is handy and simple, and the loss of pressure of the piping is as less
as possible.
2.3.1 Size of the piping
Steel pipes or flex liquid-resistant pipes with inner diameter no smaller than the sizes specified
should be selected according to the model of the liquid cooler. The inside of the pipes should be dry,
clean, and free of corrosion, dust and grease, etc.
2.3.2 Pipe joints
The number of pipe joints used should be as small as possible so as to reduce the resistance
caused by them.
2.3.3 Valves
Don’t use valves unless it is necessary, because the pressure in the piping loses considerably
even if they are fully open.
2.3.4 Length of the pipes
The length of the piping should be decided according to the characteristics of the cooling
liquid, such as viscidity, temperature, etc., and should be as short as possible. Normally, the length
of the piping should not exceed 5 m.
2.3.5 Assembling of the piping
The connection of the pipes should be reliable, well sealed; and stick tapes should be used at
the joints to prevent the air from entering and the liquid from leaking. Heat insulation material
shall be applied for the liquid piping when it is deemed necessary.
2.4 Intake filter
An liquid intake filter with size of 100~150 should be installed to improve the cooler’s heat
exchanging efficiency and to extend its working life( The filter should be provided by the customer).
2.5 Liquid tank
2.5.1 To ensure the high temperature liquid mixes with the low temperature liquid thoroughly, the
dimensions of the liquid tank, the inside separation, pipes connection, etc., should be carefully worked
out.
2.5.2 To prevent air from entering the liquid circulation, the lowest liquid level in the tank should
be above the inlet of liquid delivery pipe.
2.5.3 The positions of the inlet and outlet liquid pipes should be arranged rationally according to
fig. 2.
2.5.4 For immersion liquid cooler, the clearance between the liquid surface and the top of the
liquid tank shouldn’t exceed 100 mm.

Machanical Machanical
apparatus apparatus
LIQUID COOLER LIQUID COOLER

(bad) (good)
Fig.2 Pipe connection of liquid cooler and machanical apparatus
2.6 Power supply connections
Power supply connecting should be conducted according to the electrical connection diagram and in
observance of relevant electrical regulations and specifications.
2.6.1 Power supply and the fuses should conform to requirements and specifications of the instruction
manual and of the product nameplate. Operation voltage fluctuation of ±10% is permissible.
a. For model LO/W(R)-15~LO/W(R)35and LO/W-C series coolers, 3-phase 5-line power supply
system (3N~380V 50Hz) with neutral line (zero line ) shall be adopted. If there is no neutral line on
the power board and it is needed to use a grounding line instead, set an exclusive line as grounding
line, the resistance of which shall be smaller than 4Ω and the section area of which shall be greater
than 6 mm2, and in this case, the leaking protection switch shouldn’t be used in the circuit.
b. For model LO/W(R)-50~LO/W(R)-600 series coolers, 3-phase 4-line power supply system (3P~
50Hz /380V) shall be adopted, and the grounding line should be well earthed.
c. For model LO/W(R)-15~LO/W(R)35 and LO/W-C series coolers, if 3-phase 5-line power supply
system (3N~380V 50Hz) is to be adopted, remove the covering plate of the cooler in advance, find
the connection terminal row, remove the jump between terminals marked “PE” an “N” on the rows.
2.6.2 The section area of power supply lines shall meet the requirement of the electrical diagram. The
momentary starting current of the compressor is 5~10 times of the rated operating current. The
power supply shall meet the current requirements; otherwise, the liquid cooler will not start
normally.
2.6.3 The power supply circuit shall be equipped with an air-switch or breaker (fuse) independently, the
specifications of which shall match the current value on the nameplate.
2.6.4 It is not allowed to discretionally change the electrical connections inside the control cabinet, and it
is forbidden to close the A.C. contactors coercively.
3 Panel operation
3.1 Panel functions and operation

电源 液泵 故障 电源 制热 故障
POWER COMP PUMP ALARM POWER COMP HEAT ALARM

液体温度 PV 设定温度 SV 液体温度 PV 设定温度 SV

设置 向上 向下 启动/停止 设置 向上 向下 启动/停止
SET UP DOWN ON/OFF SET UP DOWN ON/OFF

Conventional models Heating function models


Fig.3 Panel functions and operation
State indicators
① MODE indicator: illuminates in room temperature co-adjustment control mode; goes
out in thermostatic control mode.
② COMP indicator: goes out while the compressor not in operation and the conditions
for starting not satisfied; flickers while in starting delay period when the condition for
the compressor starting is satisfied; illuminates after the compressor is started.
③PUMP indicator: illuminates while the pump is in operation; goes out when the pump
stops operating.
Model with heating function HEAT indicator light: when heating is on, the indicator light
is on; When the heating stops, the indicator goes out;
④ALARM indicator: flickers in troubled state; goes out after reset successfully from
trouble.
3.2 Primary interface

【Note:The left numeric display indicates the liquid temperature (press <UP> button to display the
ambient temperature value); while the right one indicates the target temperature ( the SET
TEMPERATURE in thermostatic mode or a value of the ambient temperature plus room temperature
co-adjustment temperature difference in co-adjustment mode).
3.3 Quick modification of the set temperature
On primary interface, press <SET> button for 3 seconds to enter the interface for setting control
temperature/room temperature co-adjustment difference, the procedures are given in the following
diagrams;

Note: If there is no other operation on the setting interface for 5 seconds, the setting will be saved
automatically and exit.
Description of the parameters Factory default value Setting range

Temperature setting for thermostatic mode 25℃ 15~45℃

Room temperature co-adjustment difference setting for room


0℃ -9.9~9.9℃
temperature co-adjustment mode

3.4 Press down <UP> and <DOWN> simultaneously to check the value of amperage, proceed as follows:
[Note]:Query current value when the function of compressor or pump current is enabled.
3.5Check/reset from trouble
When any trouble is detected, for temperature-probe absent trouble, the trouble code and the
temperature value will be displayed alternatively; while for trouble with the temperature probe still working,
the trouble code will be displayed alternatively. The controller will reset automatically when trouble is
eliminated.
3.6Control logic
3.6.1 fixed temperature mode
Table 1
Cooling control conditions Heating control conditions (dual-system)

Cooling starts Cooling stops heating starts heating stops


RT1 works fine RT1 is not working RT1 works fine RT1 is not working
And RT1≥ (TS+ 1) ℃ properly And RT1 10 ℃ or less properly
And the delay time is ≥ Or RT1≤ (ts-1) ℃ And the delay time is Or RT1 13 ℃ or higher
3min Or there is an alarm ≥3min Or there is a fault signal
And no alarm signal input signal input And no alarm signal input
At the same time to meet When any of the above input When any of the above
the above conditions, the conditions occur, the At the same time meet conditions occur, the
beginning of refrigeration. refrigeration stops. the above conditions, heating is stopped.
start heating.
[note] : RT1 -- liquid temperature measuring sensor TS -- user set value
3.6.2 room temperature homology mode Differential temperature control type
Table 2
Cooling control conditions Heating control conditions (dual-system)

Cooling starts Cooling stops heating starts heating stops


RT1 and RT3 work ormally RT1 or RT3 are not working RT1 works fine RT1 is not working
And RT1≥RT3+(TS+1) properly And RT1≤ 10 ℃ properly
℃ Or RT1≤RT3+ (ts-1) ℃ And the delay time Or RT1≥ 13 ℃
And RT1 15 ℃ or higher Or there is an alarm signal is ≥3min Or there is a fault
And the delay time is ≥ input And no alarm signal signal input
3min When any of the above input When any of the
And no alarm signal input conditions occur, the At the same time above conditions
When the above conditions refrigeration stops. meet the above occur, the heating is
are met at the same time, conditions, start stopped
refrigeration begins. heating.

[note] : RT1 -- liquid temperature measurement sensor TS -- user set value (room temperature and
uniform temperature difference) RT3 -- environmental temperature measurement sensor
[attention] : every time the compressor goes through the open-> stop action, the next time it starts again,
it needs to go through a time delay of 3min (protection against frequent compressor startup).
3.7 Passive contactors
The electrical control system features a function of outputting by a group of passive contactors, which
comprises the closing contactors of the relays. When the liquid cooler works normally, the output
contactors are engaged; and when the liquid cooler
Oil cooler
is not electrified or is abnormal, the output passive contactor User I/O
contactors will be disengaged. Whether the RC filter

contactors are engaged or disengaged, the output R1


+
100Ω/2W
contactors are not charged. When the passive
R2
R1
contactors are needed, the userneeds to provide 1μf/250VAC 820Ω/2W

power or control signals. E


+ - -
An RC filter should be added between the passive
DC 5~24V
contactor and the I/O port so as to improve the
anti-interference ability, refer to fig.4.
Additionally, in order to prevent the interference signal from being picked, when the alarm signal (low
potential is valid) is received, another 3 seconds are
delayed; if the potential of the signal received is still
low, then the alarm signal is judged valid. Figure 4 Passive contactor circuits
3.8 remote control (special customization is
required)
When using the unit with remote control, the unit will not start automatically when it is powered on,
the remote switch input "close" will start the unit, the remote switch input "disconnect" will stop the
unit, and the digital tube displays "OF".
4 Trial running
4.1 Check before operation to make sure,
a. Power supply is correct, and the grounding line is earthed reliably;
b. Pipes sizes are appropriate, and there is no air seeping and liquid leaking;
c. Liquid input and output direction is correct, all valves in the piping are fully open, and the liquid
flows unimpeded and smoothly;
d. Liquid level in the liquid tank meets the depth requirements and the liquid intake port is below
the surface of the liquid.
Special remark:
a.It is forbidden to start the unit, when the liquid is short (Otherwise, the liquid pump will suffer
damage.)
b. Prevent the air from entering the piping. (Otherwise, big noise will be resulted.)
c. When high viscidity liquid is used or there is excessive pressure loss in the liquid piping, larger
sized liquid pipes are deemed necessary.
d. For model LO/W-□□(without liquid pump), the Liquid Cooler and the system’s liquid pump
should be interlocked and operate simultaneously.
e. For liquid coolers with the fan at the top, don’t start when the front, back and side covering
boards are not installed completely.
Precautions for water cooling machine:
If no water comes out during the first water supply, the following methods can be adopted:
a. First check whether the phase sequence alarms and whether the pump steering is correct;
b. Lw-pt model should first fill the water tank with water;
c. Add a hose to the outlet, raise the water supply, and open the exhaust plug at the upper end of the
pump until water flows out of the vent hole;
d. Tighten the exhaust plug and refill water until there is water flowing out of the suction port. Then
start the pump and the water will circulate automatically;
e water nozzle external machine can save c, d steps.
Water cooling machine filling liquid recommendations
(used for cooling motorized spindle, torque motor, linear motor, large and medium-sized
water-cooled motor, laser, plasma equipment, etc.) :
a, lw-□ PT/ lwl-□ type liquid cooling machine with pure water, distilled water;
b, additives are recommended to use car antifreeze (ethylene glycol), adding 30% ~ 40%.
4.2 Switch on and start to operate
4.2.1 Power on and check to make sure the phase order of the power supply is correct. If the phase
order of the power supply is not correct, the ALARM indicator will illuminates, and the numerical
display will indicate trouble code “E04”. Turn off the switch of the power supply for the liquid
cooling unit and master switch of the circuit, exchange the positions of any two phases of the power
supply, re-energize the liquid cooling unit, the phase order trouble will be eliminated and it will
enter normal operation mode
4.2.2 Turn on the power switch, the pump or agitator will start to operate, the indicator for the liquid
pump will illuminate, and the liquid will start circulating. When the cooling unit starts operating, the
work machinery of the customer should operate simultaneously.
Note: when the liquid pump is running, check whether there is liquid inhalation and discharge
in the pipeline, and whether the amount of liquid in the liquid box is enough!
4.2.3 in the debugging process of LO/ w-pt /P2T model, the ball valve at the inlet and outlet can be
adjusted according to the needs to control the flow, achieving the best effect.
4.2.4 after the normal operation of the unit for a period of time, the actual liquid temperature
displayed by the digital tube on the control panel shall gradually decrease.
4.2.5 temperature control mode
a. Fixed temperature type: When certain temperature value is preset, the liquid cooler will keep the
temperature within the set temperature range automatically.
b. Differential temperature control type: This type controls the operation of the liquid cooler
automatically according to variation of room temperature. When the set temperature is “﹢X℃”, the
liquid temperature is maintained at a value X℃ higher than room temperature;and when the set
temperature is “﹣X℃”, the liquid temperature is maintained at a value X℃ lower than room
temperature.
In general, the recommended liquid temperature setting value is: fixed temperature: about 25℃ ~ 35
℃; Homology at room temperature: about -5℃ ~ +2℃.
4.2.6 refrigeration/heating operation
When the operating conditions in table 1 or table 2 are met, the liquid cooling unit performs
refrigeration or heating.
When cooling starts, the "PUMP" light on the control panel lights up, and the compressor and fan
motors work simultaneously. After the liquid cooling unit runs for a period of time, the liquid
temperature displayed by PV digital tube will decrease accordingly.
When the HEAT PUMP is started, the "PUMP" indicator light on the control panel is on, and the
compressor and fan motors are working. Meanwhile, the "HEAT" indicator light on the control panel
is on, and the four-way valve is started for heating. After the liquid cooling unit runs for a period of
time, the liquid temperature displayed by PV digital tube will rise accordingly.
4.2.7 in the unit operation process, attention should be paid to check whether the system has abnormal
sound or phenomenon. When abnormal conditions occur, the power should be immediately
disconnected, find the cause and eliminate.
4.2.8 since the liquid cooling machine is equipped with the compressor delay protection function, the
cooling will not start immediately after the power supply of the unit or after the compressor stops.
This phenomenon is normal and does not belong to the fault of the unit.
5 Maintenance
The cooling unit should be maintained regularly so as to maintain its working efficiency, and
extend its working life. The maintenance can only be done after the power is switched off and 1 hour
later after the unit stops working.
5.1 After the liquid cooler working for about 2 weeks, open the discharge port on the liquid tank
to drain the liquid so as to clear the impurities taken into the cooler and water at the bottom of the
tank. The cooling cliquid of model LO/W-C cooling unit should be cleared periodically to prevent
the degrading of cooling capacity. During the clearing, the bottom of the liquid tank should be
cleaned thoroughly and care should be taken to avoid damaging the cooling cliquid.
5.2 Clean the air filter once every 2 weeks (clean it once every week when the environment
condition is poor). For cleaning, remove the filter; clear the dust by a cleaner or an air spraying gun. If
there are excessive dirt and dust, clean air filters with warm water featuring a temperature lower than
40℃ and neutral detergent. Air-dry completely after cleaning, reinstall in the original position.
5.3 According to the cleanness of the liquid, examine and clean the liquid intake filter periodically
to avoid it being blocked or jammed.
5.4 When the surface of the unit is dirty, clean it by wiping with soft cloth dipped with neutral
detergent or high quality soap. Attention should be paid not to use petroleum, acidic solvents, grinding
powders, steel brush, sand paper, etc., so as not to damage the plastic coated surface.
5.5 Before resuming after not being used for a long time, or after working for a long period (about
half a year), the liquid cooler should be checked to see if the heat exchanger is jammed by dust or dirt.
Clean the surface of the heat exchanger by compressed dry air, dust cleaner or fluffy brush when it is
deemed necessary. During the cleaning, pay attention not to damage the fins of the heat exchanger.
5.6 If the liquid cooler is left unused for a long time, switch of the liquid cooler, disconnect the
power supply, and cover it with a protection enclosure to prevent dust, liquid fog and water from
entering.
6 Troubleshooting
6.1 Solutions of the malfunctions indicated by failure codes
Any inspection and maintenance shall only be carried out under the premise that safety and protection
conditions are met, and relevant safety specifications and regulation are observed.

(1) Causes and solutions for malfunction with code F1/F2 displayed

Causes Liquid temperature sensor RT1 open circuited or short circuited


※Check the resistance of liquid temperature sensor RT1;
Checking ※Check to see if the plug of the liquid temperature sensor contacts well or
procedures is short circuited;
※ Check to see if the lead of the liquid temperature sensor is broken.
※ Keep the plug of the liquid temperature sensor contacting well;
Solutions
※Change the troubled liquid temperature sensor.

(2) Causes and solutions for malfunction with code F3/F4 displayed

Causes Open circuit or short circuit of room temperature sensor RT3


※ check the resistance value of room temperature sensor RT3;
Checking ※ check whether the plug of the temperature sensor is in good contact or
procedures short circuit;
※ check whether the lead of the temperature sensor is broken.
※ Keep the plug of the overcool protection sensor contacting well;
Solutions
※Change the troubled overcool protection sensor.

(3) Causes and solutions for malfunction with code E02 displayed

Causes Compressor current overload, contactor KM2 circuit breaker QF2/FR2 trip
※ Check voltage of the power supply;
※ Check to see if the condensing fan works and if the revolving direction is
correct;
Checking
※ Check the air filter;
procedures
※ Check to see if the wind inlet and outlet of the cooler are expedite, and if
the environment temperature is too high;
※ Check to see if the heat /Wading of the equipment is excessive.
Solutions ※ Adopt a power supply connection system and external power supply wires
which meet the specifications;
※ Apply the specified power supply voltage;
※ Adjust the revolving direction of the fan;
※ Clean up the air filter;
※ Improve operating environment conditions;
※ Choose a suitable cooling system compatible with heat loading;
※ after troubleshooting, open the front cover plate (or top cover plate) of the
cooling unit, press the green button under QF2/FR2 to reset QF2/FR2.

(4) Causes and solutions for malfunction with code E03 displayed

The pressure in the refrigeration circuit is higher than the specified value, and
Causes
the high pressure protector jumps away
※ Check voltage of the power supply;
※ Check to see if the air filter is blocked;
Checking
※ Check the revolving direction of condensing fan;
procedures
※ Check to see if the environment temperature is too high or too low and if he
wind inlet and outlet of the cooler is expedite;
※ Adopt a power supply system and power voltage which meet the
specifications;
※ Clean up the air filter;
Solutions ※ Adjust the revolving direction of the fan;
※ Improve operating environment conditions of the liquid cooler;
If the high/low pressure protector trips frequently, please contact the
manufacturer.

(5) Causes and solutions for malfunction with code E04 displayed

The phase order of the power supply is not consistent with the specified phase
Causes
order of the liquid cooler.
※ Check the three-phase order of the power supply;
Checking ※ Check to see if the three-phase power supply lacks a phase;
procedures ※ Check the three-phase power supply to see if its voltage is the specified
value.
※ Exchange the positions of any two lines of three-phase power supply;
Solutions
※ Apply the specified power voltage.

(6) Causes and solutions for malfunction with code E05 displayed

Causes The liquid flow is smaller than the specified value


※ Check the liquid level in the liquid tank;
Checking ※ Check to see if the liquid piping is expedite;
procedures ※ Check to see if the inner diameter of the liquid pipes connected externally
matches that of the intake and delivery ports of the liquid cooler.
※ Keep the liquid level in the specified range;
Solutions ※ Clear the liquid piping;
※ Connect external liquid pipes which meets the specifications.

(7) Causes and solutions for malfunction with code E06 displayed

The pressure in the refrigeration circuit is lower than the specified value,
Causes
and the low-voltage protector jumps off
※ check the liquid level of the liquid tank and whether the liquid pipeline
is unblocked;
Checking procedure ※ check whether there is any leakage in the cooling system of the cooling
unit;
※ check air path
※ add liquid or dredge liquid path to liquid tank;
※ repair and supplement fluorine when fluorine leakage occurs in
Solutions refrigeration system.
If frequent high and low voltage protector off phenomenon, please contact
the manufacturer

(8) Causes and solutions for malfunction with code E07 displayed

Causes Liquid level in liquid tank is below the specified lower limit
Checking procedures ※ Check the liquid level in the liquid tank;
Solutions ※ Keep the liquid level above the specified lower-limit ;

(9) Causes and solutions for malfunction with codeLL displayed

Causes Liquid temperature too low, no output alarm


Checking ※ liquid temperature ≤5℃ does not affect normal operation;
procedures
Solutions ※ automatic elimination when liquid temperature >5℃

(10) Causes and solutions for malfunction with code HH displayed

Causes The liquid temperature is higher than the set alarm temperature
Checking ※ check whether the liquid temperature has reached the set overtemperature
procedures alarm temperature before the cooling unit works;
※ check whether the cooling unit works normally;
※ check whether the air filter, ambient temperature and ventilation conditions
are normal;
※ check whether the liquid temperature sensor RT1 is normal;
※ check whether the load capacity of the cooling machine is less than the
actual heat load.
※ enables the cooling unit to operate simultaneously with the mechanical
equipment generating heat source;
※ if the cooling unit does not work normally, it shall be handled with
reference to the above clauses; If it is working normally, check whether its
working current is within the rated range;
※ Clean air filter, improve environmental conditions and maintain good
Solutions
ventilation around;
※ determine whether the liquid temperature displayed by PV is significantly
different from the actual liquid temperature, and judge whether the liquid
temperature sensor works normally.
※ select the model with load capacity matching the actual thermal load;
※ contact the manufacturer if necessary.
(11) Causes and solutions for displaying trouble codes E11/E12
Cause of trouble To high or too low operating amperage of the compressor
※ Check the voltage of the power supply;
※ Check if the condensation fans works normally and if its direction is
correct;
Check procedures ※ Check the air filtering screen;
※ Check if the cooling unit’s inlet and outlet air ports are unblocked, if
the ambient temperature is too high;
※ Check if the heat load of the equipment is too excessive
※ Apply the specified power system and external power cables with
specified wire gauges;
※ Apply the specified power voltage ;
Solutions ※ Adjust the direction of the fan
※ Clean the air filtering screen;
※ Improve the ambient condition for operation
※ Select a unit appropriate for the heat load.
(12)Causes and solutions for displaying trouble codes E13/E14
Cause of trouble Too high or too low amperage through the liquid pump’s motor
※ Check the voltage of the power supply;
Check procedures
※ Check if the liquid circulation is blocked.
※ Apply the specified power voltage
Solutions
※ Clear the liquid circulation

(13 Causes and solutions for displaying trouble codes E15/E16


Cause of trouble Compressor running current is out of phase or unbalanced
※ check whether the compressor power supply circuit is connected
correctly;
Check procedures
※ check whether the terminals of the compressor power supply circuit
are secure.
※ correct wiring;
Solutions
※ tighten the terminals or replace the ones with good contact.
(12)Causes and solutions for displaying trouble codes E17/E18
Cause of trouble Liquid pump motor running current is out of phase or unbalanced
※ check whether the power supply circuit of the liquid pump motor is
connected correctly;
Check procedures
※ check whether the terminals of the liquid pump motor power supply
circuit are firm.
※ correct wiring;
Solutions
※ tighten the terminals or replace the ones with good contact.

[note 1] : the above faults include other faults except "E05, E13, E14, E17 and E18". If the machine is
running before the failure, the machine will automatically run after the failure is reset.

[note 2] : the above faults, except "E05, E06, E15, E16, E17 and E18" faults, will alarm after 8
seconds.

[note 3] : if there are multiple faults at the same time, each fault sequence number will be displayed in
turn (if there is no fault of temperature probe, each fault sequence number and temperature value will
be displayed in turn).

6.2 Other common troubles and solutions

(1)The power is switched on,but the control panel displays nothing

※ The fuse of control circuit is broken, or the external power is not


Causes
supplied properly to the cooler.
Checking
※ Check the fuse and power supply conditions.
procedures
※ Replace the fuse;
Solutions
※ Ensure the power is properly supplied.
(2)The liquid pump works,but there is no liquid flow, or the flow of the liquid circulation is
very small (the pump has abnormal noise)

※ Air seeps for the liquid return pipe;


※ The liquid return filter is jammed;
Causes ※ The liquid level in the liquid tank is too low;
※ Too excessive pressure resistance or too small diameter for external
liquid pipes connected.
※ Check the tightness of the liquid return pipes;
Checking ※ Check to see if the liquid return filter is jammed;
procedures ※ Check the liquid level in the liquid tank;
※ Check the diameter of the external liquid pipes connected.
※ Improve the sealing of the liquid return pipes;
※ Clear the liquid return filter;
Solutions ※ Add liquid to the liquid tank;
※ Increase the diameter, or shorten the length of the external pipes
connected. (Normally, the length shouldn’t exceed 5 meters)

(3)The set temperature isn't reached, but the compressor stops cooling

※ The monitor temperature of overcool protection sensor RT2≤6℃,the


cooling system enters protection mode;
Causes ※Unstable power supply voltage;
※Alarm failure codes E1~E7 displayed;
※ The liquid temperature sensor loosens, and doesn’t contact well.
※ Check the revolving direction of the liquid pump and check the liquid
piping to see if it is expedite.
※ Check to see if the liquid return filter is jammed;
Checking ※ Check to see if the power supply voltage and the electrical connection
procedures is normal;
※ Check to see if the component corresponding to the failure code is
normal;
※ Check to see if the connection of the temperature sensor is reliable.
※ Keep the liquid pump operating normally and the liquid piping
expedite and unimpeded;
※ Clear the liquid return filter;
Solutions
※ Ensure the power supply is normal and the voltage meet the
specifications;
※ Eliminate the troubles of the component corresponding to the failure
code.
※ Make the temperature sensor connected reliably.

(4)The cooling conditions are met,but the compressor does not work

※ Incorrect power supply system for Model LO/W-15~35;


Causes ※ Insufficient load capacity of the power supply;
※ The electrical control panel troubled.
※ 3N ~ 380V power supply system should be applied for Model
LO/W-15~35;
Checking
※ Check the load capacity of power supply;
procedures
※ Operate according to the panel’s operating instruction, observe if it
displays normally.
※ Apply the specified power supply system;
※ Provide a power supply that makes the cooling system operate
Solutions
normally;
※ Change the control panel.

(5)Compressor doesn't stop when the set liquid temperature is reached

※ Liquid temperature sensor RT1 contacts poorly or is troubled;


※ If indicator “COOLER” on the control panel goes out, contactor KM2
Causes
is troubled.
※ Control electric circuit board failed.
※ Switch off the cooler, and switch it on again to see if it works
normally.
※ Check to see if contact of the plug of the liquid temperature sensor
Checking
and the jack is well, if the resistance is appropriate.
procedures
※ Check to see if contactor KM2 is sound.
※ Operate according to the panel’s operating instruction, observe if it
displays normally.
※ Make the plug of the liquid temperature sensor contact the jack well,
or change the liquid temperature sensor.
Solutions
※ Change contactor KM2
※ Change operating panel

6.3 Consulting the manufacturer for trouble eliminating solutions

If the following incidents experienced, stop the liquid cooler immediately, and consult the
manufacturer for solutions:
① Fuses or breakers break frequently, or the failure indicator alarms frequently;
② The compressor starts and stops repeatedly;
③ The compressor works normally, but the liquid pump or the fan doesn’t work simultaneously;
④ The liquid pump or the fan works normally, but the compressor doesn’t work after a long
time.
⑤ There is abnormal sound during the operating of the liquid cooler.

7 Warranty

7.1 Our company, based on the invoice, provides free service or replacement for the complete unit
for one year (according to the date on the invoice) in case the unit doesn’t work normally
because of manufacturing defects on condition that the user observes the instruction given in
this manual.

7.2 Damages caused by not observing the instruction given in this manual or due to inappropriate
external conditions (e.g. the power supply voltage fluctuation exceeds the permitted range, the
environment temperature is too high, etc.) are not covered by the warranty.

7.3 The company is not responsible for free service for products which the user has disassembled,
modified, or repaired by itself without informing the manufacturer.

7.4 Damages caused due to human faults, such as impact happened during the installation,
transportation and operation, are not covered by free service and free replacement warranty.

7.5 Related expenses (including travel cost) for services and repairs not covered by the warranty
or after the expiry date of the warranty shall be paid by the customer.
Appendix A YL-7K Control board

Alarm
Liquid temp.
AC220V Environment temp.
Pump
Compressor
COM
Heater
Low/Oil pressure swicth
Compressor high pressure
Compressor Overload
Liquid Level switch
Flow switch
Remote switch
Three-phase power
Power supply AC10V

Current wiring Current wiring

① Pump A phase ① Compressor A phase


L1 GW122B L1 GW122B
CUR L2
② CUR L2

Pump B phase Compressor B phase
Appendix B External structure drawings

ir out

Power switch Air filter Control panel


Power supply Control panel
lead ir in ir in
Air out Air filter
Air out Power switch
Air filter
Power supply
lead
Oil outlet
Oil inlet Oil outlet

Oil discharge Oil inlet


port
Oil discharge
port

LO-10/10P 70/70P LO-100/100P 600/600P

ir out

Power switch Air filter


Power supply Control panel
Control panel
lead
ir in ir in

ir out Power switch Air filter


Air out
Air filter
Power supply
lead

Oil level gauge Oil outlet Oil level gauge


Oil outlet Oil discharge Oil discharge
port Oil inlet port
Oil inlet

LO-10PT 70PT LO-100PT 600PT


ir out
Power switch

ir in
Air out ir out ir in
Power switch
Control panel Air filter
Control panel
Power supply
Air filter
lead Power supply
Air filter
lead

Cooling coil
Cooling coil

LO-15C 70C LO-100C 150C


APPENDIX B SCHEMATIC RAWING OF THE COOLING SYSTEM

EXPANSION VALVE FILTER DRIER

LIQUID OUTLET RESERVOIR

EVAPORATOR
FAN

CONDENSOR
LOW-PRESSURE HIGH-PRESSURE
PROTECTOR PROTECTOR
LIQUID INLET P< P>

COMPRESSOR

SCHEMATIC DRAWING OF THE COOLING SYSTEM FOR


MODEL LO/LW LIQUID COOLER

COOLING
EXPANSION VALVE FILTER DRIER
HEATING

LIQUID OUTLET
EVAPORATOR

CONDENSER

FAN

4-WAY
VALVE

LIQUID INLET LOW-PRESSURE HIGH-PRESSURE


PROTECTOR PROTECTOR
P< P>

GAS/LIQUID COMPRESSOR
SEPARATOR

SCHEMATIC DRAWING OF THE COOLING SYSTEM FOR


MODEL LOR/LWR LIQUID COOLER
APPENDIX C PARAMETERS LIST

MODEL LO-15PTB

Cooling Capacity(W) 1500

Main power supply 3P~380V 50Hz

Total Power(W) 1490

Total Current(A) 4

Controlled temperature For fixed temperature type: 15~45℃/Type. For differential temperature
rang control type: room-temperature ±9℃. Control precision: ±1℃
composers

Power supply 3P~380V 50Hz

Rated powe r ( W) 905

Pump max flow (L/min) 10

Refrigerant t R22

External dimensions (mm)


450×1120×470
(Width×Height×Thickness)

Pipes size (inner thread) G1/2″


APPENDIX D Electrical principle Diagram

F
PACKAGE LIST

No. Name Quantity Note

1 Liquid Cooler one

2 Operation Manual one

3 Product Certificate one


PRODUCT QUALITY CERTIFICATE

PRODUCT NAME: LIQUID COOLER

MODEL NUMBER: L -

MANUFACTURING NUMBER:

This product is designed and manufactured according to the related


technical standards.

The electrical elements meet the requirement of the national standard


(GB4701.1).

The pressure vessels accord with the requirement of the working


environment.

This product has been passed through the test and factory inspection,
and all the performance data meet the requirement of the technical
specification & regulation.

Approved by our company quality assurance department, this product


is acceptable, and can be put into use.

Laber warrants its products for one year from the date of delivery.
During the warranty period, if a product malfunctions in normal use,
the company will repair the product without any charge. For a product
which has expired the warranty period, reasonable fee is needed.

QUALITY ASSURANCE DEPARTMENT


QUALITY CONTROL MANAGER:
DATE:
Add: 3rd Flr., E. Annex, Enterprise Bldg., 6 Torch Rd., Baoji, Shaanxi, China

Tel: (0917) 3605353 3605355 3605356

Fax: (0917) 3605350

Homepage: www.bjlaber.com

Postcode: 721006