B. Konduktor -450-A1/SA1A-54/7
A. Stranded conductor
1 Apropriate standards SPLN T3.001-1;2015 SPLN T3.001-1;2015
2 Designation according SPLN T3.001-1;2007/IEC 61089 450-A1/SA1A-54/7 450-A1/SA1A-54/7
3 Manufacturer's name required, To be mentioned PT JEMBO CABLE COMPANY Tbk
4 Ratio SA1A % 13.0 13.0
5 Sectional area of aluminium mm² 436 436
6 Sectional area of aluminium-clad Steel mm² 56,5 56,5
7 Total Sectional area mm² 492 492
8 Number and diameter of Aluminium wire number/mm 54/3,21 54/3,21
9 Number and diameter Aluminium Clad Steel number/mm 7/3,21 7/3,21
10 Overall diameter approximately mm 28,9 28,9
11 Linear mass (approximately) kg/km 1578,2 1578,2
12 Rated strength (minimum) kN 139,72 139,72
13 DC resisteance at 20°C ohm/km 0,0642 0,0642
14 Modules of elasticity kg/mm² required, To be Mentioned 7470
15 Coefficient of linear expansion per°C required, To be Mentioned 20,5 x 10⁻⁶
16 Length of one drum m 1500-2000 2000
17 Approximate gross weight of one drum kg as required, To be Mentioned 3590
18 Approximate net weight of one drum kg as required, To be Mentioned 3129
19 Dimension of drum (diameter x width) mmxmm as required, To be Mentioned 1980 x 1130
20 Direction of stranding of outermost layer Right-hand lay Right-hand lay