Garansi Teknis (TPG) Konduktor Transmisi 150 kV/275 kV/500 kV

B. Konduktor -450-A1/SA1A-54/7

NO. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

A. Stranded conductor
1 Apropriate standards SPLN T3.001-1;2015 SPLN T3.001-1;2015
2 Designation according SPLN T3.001-1;2007/IEC 61089 450-A1/SA1A-54/7 450-A1/SA1A-54/7
3 Manufacturer's name required, To be mentioned PT JEMBO CABLE COMPANY Tbk
4 Ratio SA1A % 13.0 13.0
5 Sectional area of aluminium mm² 436 436
6 Sectional area of aluminium-clad Steel mm² 56,5 56,5
7 Total Sectional area mm² 492 492
8 Number and diameter of Aluminium wire number/mm 54/3,21 54/3,21
9 Number and diameter Aluminium Clad Steel number/mm 7/3,21 7/3,21
10 Overall diameter approximately mm 28,9 28,9
11 Linear mass (approximately) kg/km 1578,2 1578,2
12 Rated strength (minimum) kN 139,72 139,72
13 DC resisteance at 20°C ohm/km 0,0642 0,0642
14 Modules of elasticity kg/mm² required, To be Mentioned 7470
15 Coefficient of linear expansion per°C required, To be Mentioned 20,5 x 10⁻⁶
16 Length of one drum m 1500-2000 2000
17 Approximate gross weight of one drum kg as required, To be Mentioned 3590
18 Approximate net weight of one drum kg as required, To be Mentioned 3129
19 Dimension of drum (diameter x width) mmxmm as required, To be Mentioned 1980 x 1130
20 Direction of stranding of outermost layer Right-hand lay Right-hand lay

B. Individual Wires

For Aluminium Wires


1 Apropriate standards IEC 60889
2 Material Hard-drawn aluminium Hard-drawn aluminium
3 Designation according to IEC 61089 A1
4 Diameter mm 3,21 3,21
5 Tolerance of diameter mm ±1% ±1%
6 Resistivity at 20 ⁰C ( corresponding to 61,0% IACS conductivity) nΩm 28,264 28,264
7 Density at 20 ⁰C kg/dm3 2,703 2,703
8 Coefficient of linear expansion per°C 23 x 10⁻⁶ 23 x 10⁻⁶
9 Constant-masa temperature coefficient of resitance at 20⁰C per°C 0,00403 0,00403
10 Minimum tensile strength Mpa 165 165
11 Final Modulus of elasticity Gpa Required 73,2
For Aluminium-Clad Steel Wires
1 Apropriate standards IEC 61232
2 Material Aluminium-clad steel Aluminium-clad steel
3 Designation according to IEC 61089 SA1A SA1A
4 Diameter mm 3,21 3,21
5 Tolerance of diameter % ± 1,5 ± 1,5
6 Resistivity at 20 ⁰C ( corresponding to 20,3% IACS conductivity)max. nΩm 84,8 84,8
7 Density at 20 ⁰C kg/dm3 6,59 6,59
8 Coefficient of linear expansion per°C 13 x 10⁻⁶ 13 x 10⁻⁶
9 Constant-masa temperature coefficient of resitance at 20⁰C per°C 0,0036 0,0036
10 Minimum tensile strength Mpa 1340 1340
11 Final Modulus of elasticity Gpa Required 158,87
12 Minimum thickness of aluminium covering (% nominal wire radius) % 8 8
13 Final Modulus of elasticity (Practical) Gpa 162 162