Professional Documents
Culture Documents
SAES-B-801 Editorial Revision (10-27-2021)
SAES-B-801 Editorial Revision (10-27-2021)
SAES-B-801 Editorial Revision (10-27-2021)
SAES-B-801
Saudi Aramco Fire Code
Document Responsibility: Loss Prevention Standards Committee
Contents
Summary of Changes..................................................................................................... 5
1 Scope ....................................................................................................................... 9
2 Conflicts And Deviations .......................................................................................... 9
3 References ............................................................................................................. 10
3.1 SAUDI ARAMCO REFERENCES .............................................................................. 10
3.2 INDUSTRY CODES AND STANDARDS ..................................................................... 12
4 Terminology ........................................................................................................... 14
4.1 ACRONYMS ........................................................................................................ 14
4.2 DEFINITIONS ....................................................................................................... 16
5 Modifications To Saudi Fire Code (SBC-801) ........................................................ 16
5.1 CHAPTER 1 - ADMINISTRATION ............................................................................. 16
5.2 CHAPTER 2 - DEFINITIONS ................................................................................... 20
5.3 CHAPTER 3 – GENERAL REQUIREMENTS ............................................................... 23
5.4 CHAPTER 4 – EMERGENCY PLANNING AND PREPAREDNESS................................... 23
5.6 CHAPTER 5 – FIRE SERVICE FEATURES ................................................................ 24
5.7 CHAPTER 6 – BUILDING SERVICES AND SYSTEMS ................................................. 32
5.8 CHAPTER 7 – FIRE AND SMOKE PROTECTION FEATURES ....................................... 33
5.9 CHAPTER 8 – INTERIOR FINISH,DECORATIVE MATERAILS AND FURNIISHING ............ 33
5.10 CHAPTER 9 - FIRE-PROTECTION SYSTEMS............................................................ 33
5.11 CHAPTER 10 - MEANS OF EGRESS ...................................................................... 61
5.12 CHAPTER 11 – CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS ............. 61
5.13 CHAPTER 12 THROUGH 19 – RESERVED .............................................................. 61
5.20 CHAPTER 20 – AVIATION FACILITIES ..................................................................... 62
5.21 CHAPTER 21 – DRY CLEANING ............................................................................ 62
5.22 CHAPTER 22 – COMBUSTIBLE DUST-PRODUCING OPERATIONS .............................. 62
5.23 CHAPTER 23 – MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES ......... 62
5.24 CHAPTER 24 – FLAMMABLE FINISHES ................................................................... 62
5.25 CHAPTER 25 – FRUIT AND CROP RIPENING .......................................................... 62
5.26 CHAPTER 26 – FUMIGATION AND INSECTIDAL FOGGING ......................................... 62
5.27 CHAPTER 27 – SEMICONDUCTOR FABRICATION FACILITIES .................................... 62
© Saudi Aramco Oil Company, 2021
Page 2 of 75
Summary of Changes
Combustible Dust-Producing
- CHAPTER 22 Modified
Operations
Motor Fuel-Dispensing
- CHAPTER 23 No Change
Facilities and Repair Garages
Hazardous Materials –
- CHAPTER 50 No Change
General Provisions
Hazard Categories
- APPENDIX E No Change
(Informational Only)
1 Scope
The 2018 Saudi Fire Code (SBC-801) of the National Committee of Saudi
Building Code (NCSBC) in its entirety, with all references, amendments, errata,
and supplements thereto, shall constitute the Saudi Aramco Fire Code (SAFC),
except as modified by this standard. The provisions of the SAFC, hereinafter
referred to as “this Code,” shall apply to the design, construction, alteration,
moving, demolition, repair, and use of Saudi Aramco (SA) buildings and
facilities, except as superseded by B-Series standard for operating plants.
Operational processes and activities addressed in this Code shall also comply
with other company procedure and general instruction requirements.
Most B-Series standards will be reserved for industrial plants as contained in the scoping
sections of those standards. However, some B-Series standards may apply to certain portions
of non-plant facilities, such as but not limited to, confined space areas (SAES-B-008), electrical
area classifications (SAES-B-068) eyewash and shower stations (SAES-B-069) and others.
Additional requirements can be found for specific building types in applicable Mandatory Saudi
Aramco Engineering Requirements (MSAERs) that include, but are not limited to: SAES-M-009
and SAES-B-014 for blast resistant buildings, SAES-B-009 for offshore facilities, SAES-P-119
for substations, 12-SAMSS-014 for pre-engineered metal buildings, SAES-B-055 for plant
layouts, SAES-P-103 for battery rooms, and SAES-R-004 for architectural finishes.
Any conflicts between this standard and any other applicable Mandatory Saudi
Aramco Engineering Requirements (MSAERs), shall be addressed to EK&RD
Coordinator.
Any deviation from the requirements herein shall follow internal company
procedure SAEP-302.
3 References
ASTM International
NFPA 22 Standard for Water Tanks for Private Fire Protection (2018)
NFPA 24 Standard for the Installation of Private Fire Service Mains
and Their Appurtenances (2019)
NFPA 45 Standard on Fire Protection for Laboratories Using
Chemicals (2019)
NFPA 72 National Fire Alarm and Signaling Code (2019)
NFPA 92 Standard for the Installation of Smoke Control Systems
(2018)
NFPA 291 Recommended Practice for Fire Flow Testing and Marking
of Hydrants (2019)
NFPA 495 Explosives Materials Code (2017)
NFPA 655 Standard for Prevention of Sulfur Fires and Explosions
(2018)
Safety and Fire Protection (SAF) through the High Commission for Industrial
Security (HCIS)
4 Terminology
4.1 Acronyms
ASTM: ASTM International, formerly American Society for Testing and Materials
4.2 Definitions
See Section 5.2 and Chapter 2 of the Saudi Building Code (SBC-801).
The following part, chapter and section numbers refer to the Saudi Fire Code
(SBC-801) (First Printing, 2018), which is part of this SAES. The text of each
paragraph below is an addition, modification, exception or deletion as noted.
proponent organization.”
definition in SAES-B-008”
(Addition) Add the following text. “Section 319 from the 2018
IFC shall apply to mobile food preparation vehicles.”
5.5 (Modification) Add the following text to the end of this section.
“See also, Appendix H, Hazardous Materials Management
Plan (HMMP) and Hazardous Materials Inventory Statement
(HMIS) Instructions, in the SBC-801. The HMMP shall
comply with GI-0150.100 for the Hazardous Materials
Communication (HazCom) Program and other Environmental
Protection Department requirements.”
The three 507.2 exceptions allow for a significant reduction for fire flow for
buildings with a reduced size meeting all the conditions of the exception.
These reduction methods account for unique conditions in remote and
other locations. See Table B103.3 for fire flow requirements for Project
Management Construction Camps (PMCCs) as defined in GI-0298.010.
(Addition) Add the following text for this section. “Fire flow
water supply capacity of the required system pressure shall
be provided by a reliable means at all times. Reliability is
achieved by one of the following methods.
No Modification
No Modification
Modifications to the SAES-B-801 Sections 903, 904, 905, 906, 907, 908,
909, 912 and 913 also apply to the modifications of the similar section
numbers in SAES-M-100 that are repeated for the SAES-M-100. The
Section 901 in the SAES-B-801 is unique to the SAES-B-801 and not part
of the SAES-M-100. The following sections are unique to the SAES-B-
801 and apply only to the SAES-B-801: 901, 903.6, 904.1.1, and the
system test and maintenance requirements in 904.5 to 904.12, 905.11,
906.2, 907.8, 907.9, 910.5, 911, 913.5 and 914.
2. Water supply piping for the site with water flow test
information.
11. All control valves, check valves, drain pipes and test
connections, with separate zone control for each
building floor level.
See Section 1103.5.1 for existing buildings with Group A-2 occupancies
with an occupant load of 300 or more.
(Modification) Add this text and the end of the section for fire
sprinkler omission in addition rooms or areas.
(Addition) Add the following text. “If fire sprinkler systems are
required by SAES-M-100 or SAES-B-801, rooms and areas
with telecommunication equipment shall have fire sprinkler
protection. Quick-response, sidewall sprinklers with piping
outside these rooms shall be used for wet-pipe sprinkler
systems, whenever permitted by NFPA 13 and the listing
requirements for the sprinklers. The use of dry-barrel
sprinklers is optional. The use of double-interlock, pre-action
or water mist systems is required for larger, complex areas.”
(Addition) Add this text to the end of Item 1. “UL 1626 listed
residential sprinklers shall be used in all Group I-2 care
recipient sleeping units. All sprinklers installed in these NFPA
13 defined compartments shall be UL 1626 listed residential
sprinklers. Other light-hazard building areas not defined
above shall have quick-response listed sprinklers installed.”
(Addition) Add this text to the end of Item 3. “UL 1626 listed
residential sprinklers shall be used throughout all Group I-1
and Group R dwelling units and sleeping units and their
adjoining corridors in conformance with their listing. All
sprinklers installed in these NFPA 13, NFPA 13R and NFPA
© Saudi Aramco Oil Company, 2021
Page 44 of 75
Minimum
rated single 4-A 4-A 10-A
extinguisher
Maximum
278.7 m2 139.35 m2 92.9 m2
floor area
(3000 ft2) (1500 ft2) (1000 ft2)
per unit of A
Maximum
floor area 1045.2 m2 1045.2 m2 1045.2 m2
Maximum
distance of
22.9 m (75 ft) 22.9 m (75 ft) 15.2 m (50 ft)
travel to
extinguishera
6. Annunciators.
7. Power connection.
8. Battery calculations.
• UL 38 (boxes/pull stations),
• UL 1480 (speakers),
• UL 1711 (amplifiers),
Note:
After June 30, 2022, smoke alarms shall comply with the 8TH Edition of
UL 217. After June 30, 2021, smoke detectors shall comply with the 7TH
Edition of UL 268.
(Modification) Delete the following text, “In areas that are not
continuously occupied,” at the beginning of the first sentence
in this section.”
© Saudi Aramco Oil Company, 2021
Page 54 of 75
1. System purpose.
3. Design approach
8. Design calculations
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
No Modification
5.83 Add a new table for fire flow requirements for Project
Management Construction Camps (PMCCs) as defined in GI-
0298.010.
(2) The table is limited to single story buildings with a maximum of 3.6 meters
in height.
(3) Contractor Camps shall be located more than 500 meters from pipelines,
highways, plants and well sites unless Building Risk Assessment, Quantitative
Risk Assessment or zoning maps requires more space.
(4) Any construction camp that is located more than 30 kilometers distance
away from any firefighting brigade shall have a dedicated trained firefighting
team.
(5) The fire-flow requirements can be reduced by 250 gpm if the contractor
camp does not have any residential buildings.
(6) The maximum building area for this table is 2000 m2. Buildings exceeding
2000 m2 in area shall follow SBC-801-Appendix-B
(8) The fire-flow requirements can be reduced to 500 gpm for 60 minutes if a
NFPA 13 or 13R fire sprinkler system is provided. The reduction of 250 gpm in
item (5) can be applied accumulatively.
(9) The minimum residual pressure at all points in the system is 20 psig (138
kPa).
Table B105.1(1) Required fire-flow for one- and two-family dwellings, Group R-
3 and R-4 Buildings and townhouses
No modification
No modification
No modification
No modification
No modification
Deleted
Deleted
Deleted
Deleted
Document History
26 July 2021 New Saudi Aramco Engineering Standard
27 October 2021 Editorial revision to reflect the correct organization/abbreviation.