Tabel 3.

1 Hasil Pengamatan HRP FOKUS 804

DATA Correct charge Reduce Capacity Blocked Capilary Overcharge Undercharge High Discharge Pressure
o
Ambient Temperature ( C) 29,1 29,2 29,2 29,5 29,6 29,5
Suction Pressure (oC/bar) -8 /1.2 9 /3 -40 /0.6 0 /2 -18 /0.4 24 /5.2
o
Temp. 1 ( C) 4,2 28,3 24,9 -0,8 22,2 17,2
o
Temp. 2 ( C) 46,9 54,1 34,3 50 41,8 45,2
o
Temp. 3 ( C) 30,6 30,4 24,3 31,1 30,4 30,8
Temp. 4 (oC) -3,1 10,7 21,1 2,5 -11,6 19,2
Discharge Pressure (oC/bar) 40 /9 34 /7.5 32 /7 46 /11 34 /7,5 50 /12
Condenser Outlet Temp. (oC) 30 29 29 29 29 33
Sight glass (%) 100%Cair 50%Cair 100%gas 100%Cair 70%cair 100%cair
Comp. Operation Conditions Bunyi Halus Desis Dengung berkala dengung dengung desis halus
Evap. Frost (%) 100% 0% 0% 50% Belakang 50% depan 0%
Superheat -5,5 9,3 23 0,3 21,9 22,8
Tabel 3.2 Hasil Perhitungan HRP FOKUS 804

Pengujian h1 (kJ/kg) h2 (kJ/kg) h3 (kJ/kg) h4 (kJ/kg) Wcomp (kJ/kg) Qcond(kJ/kg) Qevap (kJ/kg) COP
Correct Charge 406 428 241 241 22 187 165 7,50
Reduced Capacity 422 440 326 326 18 114 96 5,33
Blocked Kapilary 425 419 0 0 -6 419 0 0,00
Overcharge 400 429 244 244 29 185 156 5,38
Undercharge 423 434 353 353 11 81 70 6,36