Short Circuit Page - Power Grid Page 2 of 6
Grounding
Connection
The connection of the power grid can be selected by clicking on the connection buttons until the desired
connection is displayed. The available connections are Wye and Delta. Note that this option is available only
for 3 phase power grids.
Note: In unbalanced load flow studies this connection is ignored and the utility is considered grounded if
“Unbalanced” is selected in the rating page.
Grounded
This checkbox is available only for 1 phase power grids. Check this box if the power grid is grounded.
mk:@MSITStore:C:\ETAP%202101\Etaps.chm::/Short_Circuit_Page_PG.htm 3/1/2023
Short Circuit Page - Power Grid Page 3 of 6
Earthing Type
The earthing type menu is available when the Power Grid voltage is 1 kV or less. The available earthing types
are dependent on the Grounding selection and they reflect the source’s earthing method.
Distributed Neutral
This option is available only when the Grounded option is not checked in 1 phase Power Grid or if Grounding
selection is ungrounded in 3 phase Power Grid. Check this box if the neutral is distributed for the IT arthing
type. This field is only utilized when running the Electric Shock feature from within the Cable Editor/Manager.
It is not utilized for modules such as Short Circuit, Load Flow, Arc Flash, and etc.
Rg
This field will only be visible if the Power Grid is 1 kV or less and TT earthing type is selected. It is for the
inclusion of the Power Grid earthing in Electric Shock calculation only. This field reflects both the source’s
Ground Grid (Earthing Mat) and the soil resistance between this Power Grid and the load service entry point.
The Rg result from ETAP’s Ground Grid module can assist in determining this value. This field can be left as
zero if the Ze field in the Earth/Ground Fault Loop Impedance is populated.
SC Rating
The section is enabled only for 3 phase power grids.
MVAsc
Specify the short-circuit MVA for three-phase and single-phase (line-to-ground) faults. As you enter or modify
MVAsc or X/R, ETAP recalculates the corresponding short-circuit impedance values.
The short-circuit MVA for three-phase and single-phase (line-to-ground) fault currents are calculated from the
following equations:
Where I3P and I1P are three-phase and single-phase short-circuit currents (kAsc). These values are calculated
and displayed. Also, the MVAsc for 1-phase calculations based on Vln if it is displayed as well.
kAsc
Enter the short-circuit contribution from the power grid. This value is updated if the MVAsc and X/R are
specified.
X/R
mk:@MSITStore:C:\ETAP%202101\Etaps.chm::/Short_Circuit_Page_PG.htm 3/1/2023
Short Circuit Page - Power Grid Page 4 of 6
Enter the following X/R ratios for the positive and zero sequence impedances:
3-Phase X/R = X/R ratio for positive sequence impedance of the power grid.
1-Phase X/R = X/R ratio for zero sequence impedance of the power grid.
* The Ze and X/R are only typical values and actual values from the local power supplier should be acquired.
MVAsc
Specify the short-circuit MVA for line to line faults. As you enter or modify MVAsc or X/R, ETAP recalculates
the corresponding short-circuit impedance values.
The short-circuit MVA for line-to-line fault currents are calculated from the following equations:
MVALL = kV * ILL
X/R
Enter the X/R ratio for power grid impedance to a line to line fault.
kAsc
Enter the short-circuit contribution from the power grid. This value is updated if the MVAsc and X/R are
mk:@MSITStore:C:\ETAP%202101\Etaps.chm::/Short_Circuit_Page_PG.htm 3/1/2023
Short Circuit Page - Power Grid Page 5 of 6
specified.
MVAsc
Specify the short-circuit MVA for line to ground faults. As you enter or modify MVAsc or X/R, ETAP
recalculates the corresponding short-circuit impedance values. For current ETAP release, these fields are used
in the electric shock calculation only.
The short-circuit MVA for line-to-ground fault currents are calculated from the following equations:
MVALG = kV * ILG
X/R
Enter the X/R ratio for the power grid impedance to a line to ground fault.
kAsc
Enter the short-circuit contribution from the power grid. This value is updated if the MVAsc and X/R are
specified.
For current ETAP release, these fields are used in the Electric Shock calculation. This section is enabled for
only 1-Phase power grids.
mk:@MSITStore:C:\ETAP%202101\Etaps.chm::/Short_Circuit_Page_PG.htm 3/1/2023
Short Circuit Page - Power Grid Page 6 of 6
* The Ze and X/R are only typical values and actual values from the local power supplier should be acquired.