Professional Documents
Culture Documents
Pt118a 2
Pt118a 2
Pt118a 2
Online Parameterize
Parameter Value Lower Value Upper Value State
Pres -144 Pa ok
AO 10.850 mA ok
LRV -1000 Pa ok
URV 1000 Pa ok
Online Parameterize / Device setup / Diag/Service / Test device / Status / Status group 2
Parameter Value Lower Value Upper Value State
Temperature coefficients 0 ok
checksum error
Software error #3 0 ok
Software error #2 0 ok
Software error #1 0 ok
Sensor board not initialized 0 ok
CPU board not initialized 0 ok
Incompatible CPU board & 0 ok
module
file:///C:/Users/PJBS/AppData/Local/Temp/PACF8B7.tmp.html 19/03/2023
DTM Documentation Page 2 of 9
Online Parameterize / Device setup / Diag/Service / Test device / Status / Status group 3
Parameter Value Lower Value Upper Value State
4k snsr EEPROM error- 0 ok
factory
EEPROM corr warning 0 ok
4k micro EEPROM error- 0 ok
factory
EEPROM corr error 0 ok
1k snsr EEPROM error-user 0 ok
4k micro EEPROM error- 0 ok
user
1k snsr EEPROM error-user- 0 ok
no out
EEPROM non-corr error 0 ok
Online Parameterize / Device setup / Diag/Service / Test device / Status / Status group 4
Parameter Value Lower Value Upper Value State
Press out of limits 0 ok
Press Alert 0 ok
Temp Alert 0 ok
Temp out of Limits 0 ok
Temp Beyond Fail limits 0 ok
Low Flow Cutoff 0 ok
Online Parameterize / Device setup / Diag/Service / Test device / Status / Status group 5
Parameter Value Lower Value Upper Value State
Software Error #4 0 ok
RAM checksum error 0 ok
LCD update failure 0 ok
EEPROM non-corr warn 0 ok
Stuck Key 0 ok
ASIC redundancy config 0 ok
error
Open sensor error 0 ok
Online Parameterize / Device setup / Diag/Service / Calibration / Sensor trim / Sensor trim
file:///C:/Users/PJBS/AppData/Local/Temp/PACF8B7.tmp.html 19/03/2023
DTM Documentation Page 3 of 9
points
Parameter Value Lower Value Upper Value State
Lo snsr trim pt 0 Pa ok
Up snsr trim pt 5000 Pa ok
Online Parameterize / Device setup / Detailed setup / Sensors / Pressure sensor / Process
variables
Parameter Value Lower Value Upper Value State
Pres -121 Pa ok
% rnge 43.930 % ok
file:///C:/Users/PJBS/AppData/Local/Temp/PACF8B7.tmp.html 19/03/2023
DTM Documentation Page 4 of 9
AO 11.029 mA ok
Snsr temp 37.1 C ok
SV -0.00003 unknown ok
PV is Pres ok
Online Parameterize / Device setup / Detailed setup / Sensors / Pressure sensor / Sensor
service
Online Parameterize / Device setup / Detailed setup / Sensors / Pressure sensor / Sensor
service / Sensor trim
Parameter Value Lower Value Upper Value State
Snsr trim cal typ Gage (GP) ok
Online Parameterize / Device setup / Detailed setup / Sensors / Pressure sensor / Sensor
service / Sensor trim / Sensor trim points
Parameter Value Lower Value Upper Value State
Lo snsr trim pt 0 Pa ok
Up snsr trim pt 5000 Pa ok
Online Parameterize / Device setup / Detailed setup / Sensors / Device Temp Sensor
Parameter Value Lower Value Upper Value State
Snsr temp 37.1 C ok
Snsr temp unit C ok
Online Parameterize / Device setup / Detailed setup / Signal condition / Process variables
Parameter Value Lower Value Upper Value State
Pres -144 Pa ok
% rnge 43.930 % ok
AO 10.850 mA ok
Snsr temp 37.1 C ok
SV -0.00003 unknown ok
PV is Pres ok
Online Parameterize / Device setup / Detailed setup / Signal condition / Range values
Online Parameterize / Device setup / Detailed setup / Signal condition / Alarm/Sat Levels
Parameter Value Lower Value Upper Value State
Alarm Direction Hi ok
file:///C:/Users/PJBS/AppData/Local/Temp/PACF8B7.tmp.html 19/03/2023
DTM Documentation Page 5 of 9
Hi Alarm 22.10 mA ok
Low Alarm 3.73 mA ok
High Sat 20.80 mA ok
Low Sat 3.90 mA ok
Online Parameterize / Device setup / Detailed setup / Output condition / Analog output
Parameter Value Lower Value Upper Value State
Alarm Direction Hi ok
Online Parameterize / Device setup / Detailed setup / Output condition / HART output
Parameter Value Lower Value Upper Value State
Poll addr 0 ok
Num req preams 5 2 20 ok
Burst mode 252 ok
Burst option Process variables ok
Online Parameterize / Device setup / Detailed setup / Output condition / Scaled Variable
Parameter Value Lower Value Upper Value State
SV Units ok
SV xfer Function Linear ok
SV Cutoff Mode Off ok
SV Low Flow Cutoff 0.00000 unknown ok
SV Linear Offset 0 Pa ok
Online Parameterize / Device setup / Detailed setup / Output condition / Scaled Variable / SV
Data Points
Parameter Value Lower Value Upper Value State
Press Input 1 5515772 Pa ok
Press Input 2 0 Pa Error144error
SV Output 1 1.000000 ok
SV Output 2 0.000000 Error144error
Online Parameterize / Device setup / Detailed setup / Output condition / Process Alerts
file:///C:/Users/PJBS/AppData/Local/Temp/PACF8B7.tmp.html 19/03/2023
DTM Documentation Page 6 of 9
Online Parameterize / Device setup / Detailed setup / Output condition / Variable Remapping
Parameter Value Lower Value Upper Value State
PV is Pres ok
SV is Snsr temp ok
TV is SV* ok
file:///C:/Users/PJBS/AppData/Local/Temp/PACF8B7.tmp.html 19/03/2023
DTM Documentation Page 7 of 9
Online Parameterize / Device setup / Detailed setup / Device information / Field device
info / Revision #'s
Parameter Value Lower Value Upper Value State
Universal rev 5 ok
Fld dev rev 9 7 253 ok
Software rev 2 ok
Online Parameterize / Device setup / Detailed setup / Device information / Sensor information
Parameter Value Lower Value Upper Value State
Meas typ Diff (DP) ok
Module config type Std coplanar (C) ok
Isoltr matl 316 SST ok
Fill fluid Silicone oil ok
Process Connector Coplanar ok
Process Conn Matl 316 SST ok
O ring matl PTFE ok
Drain vent matl 316 SST ok
Online Parameterize / Device setup / Detailed setup / Device information / Diaphram seal info
Parameter Value Lower Value Upper Value State
# of diaph. seals None ok
Seal type Unknown ok
Seal fill fluid Unknown ok
RS isoltr matl Unknown ok
file:///C:/Users/PJBS/AppData/Local/Temp/PACF8B7.tmp.html 19/03/2023
DTM Documentation Page 8 of 9
file:///C:/Users/PJBS/AppData/Local/Temp/PACF8B7.tmp.html 19/03/2023
DTM Documentation Page 9 of 9
file:///C:/Users/PJBS/AppData/Local/Temp/PACF8B7.tmp.html 19/03/2023