PT PETROKIMIA - DEPT INTERKONEKSI LISTRIK

General information

Station UT-02B Voltage U0 20,00 kV

Number Location HVS00

Switchgeartype Customer

Manufacturer ABB Installationyear

Inspector ANDHIKA DWI MAIYUDHA Measuredate 17/02/2023

Deviceinformation

Megger PD scan 14382980014 Version 1.2.18 Calibrationdate 25/03/2022

Recommendation

MONTHLY ROUTINE CHECK

Ambient information

Temperature 27,00 °C Humidity 73,00 %

Ground noise
Level Pulse per cycle

ContactProbe 8 dBµV 0 ppc

Date Signature

1/7
Plugin Version 1.0
PT PETROKIMIA - DEPT INTERKONEKSI LISTRIK

Measurement data

Testobject Description DEPAN BAWAH

Termination Cable

Measurements Results Ground noise


Level Pulse per cycle Level Pulse per cycle

MAX 7 dBµV 0 ppc 8 dBµV 0 ppc


ContactProbe AVG 7 dBµV 0 ppc 8 dBµV 0 ppc

Evaluation Criticality Criteria


Good Moderate Bad

ContactProbe 0 <=20 21-39 >=40

Recommendation

2/7
Plugin Version 1.0
PT PETROKIMIA - DEPT INTERKONEKSI LISTRIK

Graphs and pictures

ContactProbe Histogram

ContactProbe PRPD

3/7
Plugin Version 1.0
PT PETROKIMIA - DEPT INTERKONEKSI LISTRIK

Measurement data

Testobject Description DEPAN TENGAH

Termination Cable

Measurements Results Ground noise


Level Pulse per cycle Level Pulse per cycle

MAX 8 dBµV 0 ppc 8 dBµV 0 ppc


ContactProbe AVG 8 dBµV 0 ppc 8 dBµV 0 ppc

Evaluation Criticality Criteria


Good Moderate Bad

ContactProbe 4 <=20 21-39 >=40

Recommendation

4/7
Plugin Version 1.0
PT PETROKIMIA - DEPT INTERKONEKSI LISTRIK

Graphs and pictures

ContactProbe Histogram

ContactProbe PRPD

5/7
Plugin Version 1.0
PT PETROKIMIA - DEPT INTERKONEKSI LISTRIK

Measurement data

Testobject Description BELAKANG

Termination Cable

Measurements Results Ground noise


Level Pulse per cycle Level Pulse per cycle

MAX 9 dBµV 0 ppc 8 dBµV 0 ppc


ContactProbe AVG 8 dBµV 0 ppc 8 dBµV 0 ppc

Evaluation Criticality Criteria


Good Moderate Bad

ContactProbe 0 <=20 21-39 >=40

Recommendation

6/7
Plugin Version 1.0
PT PETROKIMIA - DEPT INTERKONEKSI LISTRIK

Graphs and pictures

ContactProbe Histogram

ContactProbe PRPD

7/7