Connection procedure
WARNING! The supply modules are heavy and have a high centre of gravity. Be careful when
manoeuvring the modules.

Removal of module:
(1) Turn the supply (rectifier) module switch-disconnector handle to open
position.
(2) Release the door handle and open the supply unit door.
(3) Remove the fastening screws at the top of the module.
(3b) Units with marine construction (+C121) only: Remove fan (see page
107 for instructions) and the two fastening screws at the rear bottom of the
3
module frame.
(4) Loosen the connector locking screw (hexagonal socket head).
(5) Place the module pull-out ramp against the cabinet base. Make sure 4
the ramp is secured to the cabinet frame.
(6) Pull the module carefully out of the cabinet along the ramp. 6

3b

Remove the plastic insulators covering the input power terminals.


Lead the cables into the inside of the cabinet. Make the 360° earthing
arrangement at the cable entries as shown below.

Grommet (in
IP54 units only)

Connect the cables as follows:


• Twist the cable shields to bundles and connect to cabinet PE (ground)
busbar. Connect the separate ground conductors/cables to cabinet PE
(ground) busbar.
• Connect the phase conductors to the input power terminals (U1.1 …).
Depending on the cable size, use cable lugs or dual-cable screw lug
connectors. For details on the terminals and tightening torques, see
Technical data – Input power connection on page 122, and section Use of
the dual-cable screw lug connector below.

Refit the plastic insulators onto the input power terminals.

Push the module back in – mind your fingers – and tighten the fastening screws. Tighten the connector
locking screw to 4 Nm (3 lbf.ft). Please note that the module can only mate with the quick connector when
the switch-disconnector is in open position.

Remove the module pull-out ramp and close the cubicle doors.

Electrical installation

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com


82

Connection procedure
WARNING! The inverter modules are heavy and have a high centre of gravity. Be careful when
manoeuvring the modules. In order to minimise the danger of toppling over, keep the support legs
of the modules extended whenever manoeuvring the modules outside the cabinet.

Extract each inverter module from the cubicle as follows:


(1) Open the door of the inverter cubicle.
(2) Remove the shroud covering the upper part of the cubicle.
(3) Open the transparent cover on the front of the inverter module and disconnect the fibre optic cables.
Move the cables aside.
(4) Remove the L-shaped DC busbars on top of the module.
(5) Disconnect the terminal block (X50) next to the DC busbars.
(6) Remove the two module fastening screws (6a) at the top. At the base of the module, loosen the two
fastening screws (6b) but leave them in place; lift the bracket (6c) into the up position.
(7) Insert the module pull-out ramp under the two screws at the base of the module and tighten.
(8) Pull the module carefully out of the cubicle along the ramp. Make sure the wires do not catch.
(9) Extend the support legs of the module. Keep the legs extended until the module is about to be inserted
back into the cubicle.

6a

4
3
8

9a 9b
6c

6b

Electrical installation