Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Selection guide

Surge protection

Commercial/industrial applications OEM applications

Audible alarms, Form C contacts 1- or 3-phase 1-phase


and filtering parallel wiring series wiring

Surge counter, >50 dB filtering, 40 dB 50–100 kA <50 kA


200 kA SCCR, internal disconnect filtering per phase protection

Power XpertT SPD—Advanced


monitoring display, Ethernet
communications over ModbusT
TCP/IP and BACnet/IP, time/date
stamped surge events

>400 kA 50–400 kA 50–200 kA DIN rail


per phase per phase per phase mounting

SPM SPD SPC CVX SP1 AEGIS™ surge


series series series series series and filtering

Peak kA 100–800 kA 50–400 kA 50–200 kA 50–100 kA 50 kA Up to 80 kA


rating per per phase
phase
Typical panel Unlimited Up to 4000 A Up to 1000 A Up to 400 A Up to 200 A Up to 60 A
current rating
Nominal 120–600 Vac 120–600 Vac 120–600 Vac 120–600 Vac 120–600 Vac 100–240 Vac
voltage 24, 48 Vdc
ULT 1449 type 1 and 2 1 and 2 1 and 2 1 1 2
Enclosure NEMAT 4 and 4X A NEMA 1, 4 and 4X NEMA 4X NEMA 4X NEMA 4 Open
Warranty 20 years B 15 years B 10 years B 5 years 2 years 10/15 years B
A Optional Power Xpert SPD available on some models.
B With online registration.

SPM series SPD series SPC series CVX series SP1 series AEGIS series
SPD series SPC series
Flagship line offering superior protection, a wide Value line offering solid protection for many
range of features and industry-leading safety. applications.
SPD 250 480Y 2 K SPC 200 208Y 8 P

Surge rating kA rating Enclosure


050 = 50 kA per phase 050 = 50 kA per phase P = NEMA 4X
080 = 80 kA per phase Enclosure 080 = 80 kA per phase
100 = 100 kA per phase K = NEMA 1 enclosure 100 = 100 kA per phase
Features
120 = 120 kA per phase L = NEMA 1 flushmount enclosure 120 = 120 kA per phase
160 = 160 kA per phase 150 = 150 kA per phase Options SPD
M = NEMA 1 enclosure with application
200 = 200 kA per phase internal disconnect 160 = 160 kA per phase
250 = 250 kA per phase N = NEMA 4 enclosure 200 = 200 kA per phase 1 = No options (standard configuration) Type 1
300 = 300 kA per phase O = NEMA 4 enclosure with 2 = Filtering, UL 1283 7th Edition Type 2
400 = 400 kA per phase internal disconnect 3 = Audible alarm Type 1
Voltage code
P = NEMA 4X enclosure 4 = Form C relay Type 1
120N = 120 V single-phase (2W +G) 5 = Audible alarm and Form C relay Type 1
Voltage code (stainless steel) 240N = 240 V single-phase (2W +G)
Q = NEMA 4X enclosure with internal 6 = Filtering and audible alarm Type 2
230L = 230 single-phase 277N = 277 V single-phase (2W +G) 7 = Filtering and Form C relay Type 2
disconnect (stainless steel) 480N = 480 V single-phase (2W +G)
240S = 120/240 single split-phase 8 = Filtering, audible alarm and Type 2
208Y = 120/208 wye (4W + G) 240S = 120/240 V split-phase (3W +G) Form C relay
220Y = 127/220 wye (4W + G) Feature package 240D = 240 V delta (3W + G)
400Y = 230/400 wye (4W + G) 480D = 480 V delta (3W + G)
1=B
 asic A Available optional equipment Catalog number
480Y = 277/480 wye (4W + G) 600D = 600 V delta (3W + G)
2=S
 tandard AB
600Y = 347/600 wye (4W + G) 240H = 240 V high leg delta (4W + G) Flushmount plate for P1 FLUSHMNTPLATE13
3=S
 tandard + surge counter ABC
240D = 240 delta (3W + G) 208Y = 120/208 V wye (4W + G) enclosure
4=P
 ower Xpert SPD ABCD
480D = 480 delta (3W + G) 415Y = 240/415 V wye (4W + G)
Flushmount plate for P2 FLUSHMNTPLATE14
600D = 600 delta (3W + G) 480Y = 277/480 V wye (4W + G)
enclosure
240H = 240 delta high leg (4W + G) on ‘B’ phase 600Y = 347/600 V wye (4W + G)

SPM series CVX series


Innovative safety features with high surge ratings Branch circuit and control panel protection.
and redundant/field-changeable surge modules.
CVX 050 – 208Y
SPM 600 480Y 3 Y

Surge rating Voltage code


050 = 50 kA 230L = Single-phase—200, 208, 220, 230, 240, 277
Voltage code 100 = 100 kA 480L = Single-phase—480
230L = 230 single-phase 600Y = 347/600 wye (4W + G) 240S = Split-phase—100/200, 110/220, 120/240
240S = 120/240 single split-phase 240D = 240 delta (3W + G) 240H = Three-phase high leg delta—120/240
208Y = 120/208 wye (4W + G) 480D = 480 delta (3W + G) 208Y = Three-phase wye (star)—100/174, 110/190, 120/208, 127/220
220Y = 127/220 wye (4W + G) 600D = 600 delta (3W + G) 480Y = Three-phase wye (star)—220/380, 230/400, 240/415, 277/480
400Y = 230/400 wye (4W + G) 240H = 2 40 delta high leg 600Y = Three-phase wye (star)—305/525, 347/600
480Y = 277/480 wye (4W + G) (4W + G) on ‘B’ phase 240D = Three-phase delta—200, 208, 220, 230, 240
480D = Three-phase delta—380, 400, 415, 440, 480
600D = Three-phase delta—525, 600 (600D available in 50 kA only)
Surge rating Feature package
100 = 100 kA per phase 320 = 320 kA per phase 1=B
 asic A
120 = 120 kA per phase 400 = 400 kA per phase 3=S
 tandard + surge counter ABC SP1 series F
160 = 160 kA per phase 500 = 500 kA per phase 4=P
 ower Xpert SPD ABCDE Basic protection SP1 – 240S
200 = 200 kA per phase 600 = 600 kA per phase
250 = 250 kA per phase 800 = 800 kA per phase
300 = 300 kA per phase
Voltage code
240S = 120/240 single 480Y = 277/480 wye 480D = 480 delta
Enclosure
split-phase 600Y = 347/600 wye 600D = 600 delta
R = NEMA 4 steel enclosure with disconnect and one module E 208Y = 120/208 wye 240D = 240 delta
S = NEMA 4 steel enclosure with disconnect and two modules
T = NEMA 4 steel enclosure with terminal block and one module E
U = NEMA 4 steel enclosure with terminal block and two modules
V = NEMA 4X stainless steel enclosure with disconnect and one module
W= NEMA 4X stainless steel enclosure with disconnect and two modules Note: For AEGIS information, see the documentation tab
X = NEMA 4X stainless steel enclosure with terminal block and one module at Eaton.com/aegis. For DIN rail OEM surge offering, please
Y = NEMA 4X stainless steel enclosure with terminal block and two modules reference our OEM surge guide PA158009EN.
A Dual-colored protection status indicators for each phase and neutral-ground protection mode.
B Audible alarm with silence button, Form C relay contact and EMI/RFI filtering.
C Surge counter with reset button.
For more information on
D Power Xpert SPD with advanced monitoring display and communication capabilities. Not available with NEMA 4X enclosure.
Eaton’s surge products, go to
E R and T suffix SPM series with Power Xpert SPD option are available in NEMA 1 enclosures only.
F SP1MNTGKIT = optional wall or DIN rail mounting kit (order separately—not included with SP1 unit). Eaton.com/spd
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com

© 2022 Eaton
All Rights Reserved Eaton is a registered trademark. To contact our surge technical team,
Printed in USA call Eaton’s Technical Resource Center
Publication No. SA01001006E / Z26547 All other trademarks are property at 1.800.809.2772, option 5, option 2
July 2022 of their respective owners. or email us at spd@eaton.com.