GENERAL NOTES:

ALL ELECTRICAL WORKS HEREIN WERE DONE IN ACCORDANCE WITH THE PROVISION OF THE LATEST EDITION OF THE NATIONAL ELECTRICAL
CODE, THE LAW ORDINANCES OF THE LOCAL CODE ENFORCING AUTHORITIES AND THE REQUIREMENTS OF THE LOCAL POWER AND
TELEPHONE COMPANY.

1. ALL WORKS HEREIN SHALL COMPLY WITH THE LATESTPROVISION OF THE FIRE CODE OF THE PHILIPPINES.

2. ALL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF REGISTERED ELECTRONIC ENGINEER.

3. ALL MATERIALS AND EQUIPMENT TO BE USED SHALL BE NEW AND APPROVED TYPE FOR LOCATION OF PURPOSES.

4. A CIRCUIT BREAKER BRANCH SOLELY DEDICATED AS MAIN POWER SUPPLY FOR THE FIRE ALARM CONTROL PANEL ( FACP ) SHALL BE PROVIDED.
THIS SITE

5. EQUIPMENT SPECIFICATION

a). A ONE BRAND SYSTEM SHALL BE IMPLEMENTED ON FIRE ALARM EQUIPMENT. BRAND MUST BE COOPER, GST OR APPROVED EQUAL.

b). FIRE ALARM CONTROL PANEL SHALL BE ADDRESSABLE TYPE UL LISTED.

c). THE COVERAGES OF FIRE ALARM ZONE SHALL BE CLEARLY INDICATED ON THE FACP AND ANNUNCIATORPANEL ( AP ). THIS INDICATION
MUST BE ENGRAVED LABELS, FORMAL DIRECTORIES, GRAPHIC DISPLAY OR BOOTH.

YVALUEXVALUE
YSIZE
XSIZE

d). THE BOTTOM OF THE BOXSHALL BE POSITION 3.5 -5 FT FROM FINSH FLOOR LEVEL.

e). ALARM BELL OR HORN SHALL BE INSTALLED 7.5 FEET FROM FLOOR LEVEL OR BELOW OF THE FINISH CEILING OF NOT LESS THAN 6 INCHES.

NN
N
AI
DR
V-
G
TIN
IS
EX

f). ANNUNCIATOR TO BE USEDSHALL BE OF LISTED TYPE AND ANNUNCIATOR PANEL COMPATIBLE TO THE BRAND OF FACP BEING USED.

IN
RA
V-D
ING
IST
EX
6. WIRING SHALL COMPLY WITH THE NEW STANDARD ELECTRONIC COLOR CODING SCHEMES AS FOLLOWS:
DETECTORS AND MANUAL PULL STATION --- ( + ) RED ( - ) BLACK
BELL AND STROBE LIGHTS ------------------------ ( + ) YELLOW ( - ) BLUE

ANNUNCIATOR ------------------------------------------- ( + ) WHITE ( - ) GREEN L O C A T I O N M A P


N O T T O S C A L E

7. ALL WIRING SHALL BE PROPERLY LABELED WITH APPROVED TYPE MARKERS IN EVERY TERMINAL ENDS.

8. WIRE CONNECTION AT ALL DETECTOR BASED, MANUAL PULL STATION, HORNS OR BELL, AND ANNUNCIATOR PANEL SHALL BE TERMINATED
USING TERMINAL LUGS.

9. AFTER COMPLETION OF THE PROJECT, THE IMPLEMENTING BODY SHALL SUBMIT TO ARCHITECT AND ENGINEER FOR THE FOLLOWING.

a). A COPY OF CERTIFICATE OF ACCEPTANCE.

b). TWO COPIES OF MAINTENANCE MANUAL OF THE SYSTEM INSTALLED AND MANUFACTURER'S TECHNICAL LITERATURE ALL PARTS OF THE SYSTEM.

c). TWO COPIES OF AS-BUILT AND SINGLE LINE DIAGRAM INCORPORATING THE WIRE COLOR CODE AND SHOWING INTERCONNECTION OF THE SYSTEM. CEILING BRACKET

NOTES FOR FDAS


CAMERA
1. ALL FIRE DETECTION ALARM SYSTEM WORKS SHALL COMPLY WITH NFPA 72 CODES, GOVERNING
LAWS, FIRE CODE OF THE PHILIPPINES (FCP) AND APPLICABLE LOCAL & NATIONAL BUILDING CODE.
2. CONDUITS SHALL BE SIZED AND SHALL BE NOT MORE THAN 40% CABLE RATE AND A MINIMUM
CONDUIT DIAMETER OF NO LESS THAT 34"
3. ALL PULL BOXES AND JUNCTION BOXES SHALL BE PROVIDED WITH COVERS.

4. USE SAME BRAND OR SINGLE BRAND SHALL BE USED FOR INITIATING DEVICE AND NOTIFICATION CEILING - MOUNTED BULLET CAMERA
APPLIANCES TO AVOID INCOMPATIBILITY ISSUES.
5. THE CONTRACTOR SHALL CLEAN AND THOROUGHLY CHECK ALL INSTALLED WORK PRIOR TO
CONCEALING TO ARCHITECTURAL FINISHING
CCTV BULLET TYPE CAMERA
CEILING MOUNTING DETAIL
N O T T O S C A L E

ENGINEERING DEPARTMENT
ARCHITECT PLANNERS CONSULTANT INTERIOR DESIGN

FONTANA LEISURE PARKS & CASINO - CLARO M. RECTO HIGHWAY, CLARK SPECIAL ECONOMIC ZONE, CLARKFIELD,
PAMPANGA. POSTAL CODE 2009 TELEPHONE NO. 045-599-5000 LOC. 8810, FAX NO. 045-599-6979

LEGEND:

I BULLET TYPE ANALOG


CAMERA (INDOOR)

BULLET TYPE ANALOG O OUTDOOR OPEN AREA


O TERRACE
CAMERA (OUTDOOR)

CABINET FOR POWER I CASHIER


DVR
FOR AMPLIFIER & I

TO DVR
CCTV DIGITAL VIDEO
RECORDING I DINING AREA - 1
I
I

CCTV WIRE TO DVR


TO DVR
I

CONNECTION TO DVR I DINING AREA - 4

I KITCHEN
DVR
FOR
CCTV

1-RG6 SIAMESE CABLE IN 20mmØ PVC


1-RG6 SIAMESE CABLE IN 20mmØ PVC
1-RG6 SIAMESE CABLE IN 20mmØ PVC
1-RG6 SIAMESE CABLE IN 20mmØ PVC
1-RG6 SIAMESE CABLE IN 20mmØ PVC

TO DVR

DIGITAL VIDEO
RECORDER
(DVR)

VILLA 3142-ELECTRONICS PLANS

RISER DIAGRAM
NTS

VILLA 3142 - ELECTRONICS PLANS

CCTV LAYOUT
SCALE 1:100 MTS

ENGINEERING DEPARTMENT
ARCHITECT PLANNERS CONSULTANT INTERIOR DESIGN

FONTANA LEISURE PARKS & CASINO - CLARO M. RECTO HIGHWAY, CLARK SPECIAL ECONOMIC ZONE, CLARKFIELD,
PAMPANGA. POSTAL CODE 2009 TELEPHONE NO. 045-599-5000 LOC. 8810, FAX NO. 045-599-6979

You might also like