Regional Contest Package in EIM NC II

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Cordillera Administrative Region

Contest Area: Industrial Arts- Grade Level: 10-12 Number of Participants: 2


CONTEST PACKAGE ASSESSMENT PROCEDURE/SPECIFICATION RESOURCES
Electrical Installation and Criteria Percentage PRELIMINARY ACTIVITIES Contestant Organizer
Maintenance NC II
TIME ALLOTMENT Functionality 40% a .Contest registration of coaches and contestants. Long nose plier

Tools and Personal Protective Equipment


4 Hours b. Submission of required documents for the Combination plier
Description Workmanship 40% contest. Side Cutting plier
Electrical installation of two c. Ocular inspection of the contest venue. Philip/Flat tip Screw Driver
d. Briefing orientation of coaches with the contest Pull push rule
lamps connected in parallel
controlled by two 4-way and administrator a day before the competition. Wire striper
Try square
two 3-way switches in four Time 10% DURING
Claw hammer
different locations, three lamps Management
Spirit level or Chalk line
each controlled by a single pole Safety 5% a.Briefing of coaches with the contest
Portable Impact drive or electric drill
switches, two power outlets administrator (10 minutes)
Hacksaw /PVC Pipe Cutter
and one special power outlet. Communication 5% b.Final instruction of coaches with their Heat Gun / Butane gas with regulator
Skills contestants (5 minutes) Multi tester,
c.Final inspection of contest materials and tools Helmet, Gloves, respirator, Shoes, Goggles
ILLUSTRATION
d.Other instruction
Working Plan Total 100% AFTER 50 m 2.0 mm2 THHN/THWN 1 PC

MATERIALS
Employability or Business Attachment a.Coaches shall serve as judges 10 m 3.5 mm2 THHN /THWN Wiring
Opportunity 4 m 5.5 mm2 THWN Board
b.All outputs should be endorsed to the
2 m 8.0 mm2 THHN /THWN
Building Wiring Electrician Analytic Performance secretariat by the contest administrator ¾”x 4’x4’
2 pcs PVC pipe ½” Ø
/Maintenance Electrician Scoring Rubrics c.All endorsed output shall be displayed until the 1 pc PVC Pipe ¾” Ø
USE duration of the skills competition. 3 pcs PVC adopter with locknut ¾” Ø
29 pcs PVC adopter with locknut ½” Ø
Form of Judging NOTES 1 pc Entrance Cap ¾”
Compatriot Judging a. With regards to the provision of resources, the 3 pcs PVC Clamp ¾” Ø
school, division and regional organizer may opt to 18 pcs PVC Clamp ½”
deviate. 1 pc Meter Base
1 set Breaker panel with 4 holes (40A,30A,20A,15A)
b. The wiring design with dimensions shall be
2 sets 2-gang Power Outlet -Flush/ grounding type
given by the contest administrator to the 1 Set Special power outlet-Flush type
contestant and coaches before the contest proper. 3 pcs Single pole switch-Flush type
c. The wiring job must conform to the given wiring 2 pcs Three Way switch-Flush type
design. 2 pcs Four way switch - Flush type
d. Only flush type materials shall be used in the 3 pcs Two gang switch plate
1 pc One gang switch plate
circuit. 5 pcs Amco/Utility box
e. There shall be no pre-cut wires and PVC pipes 5 pcs Junction box-Plastic
before the start of the competition. 2 pcs Square box -Plastic
f. All types of tools can be used in the competition 5 pcs Lamp Socket –Flush type (4”Ø )
but borrowing from other contestants is 1 pc Electrical tape big
5 pcs Incandescent lamp/CFL/LED lamp
prohibited.
40 pcs wood screw
1 pc steel bar/square/round bar 12mm ( 1 foot)
Scoring rubrics Electrical Installation and Maintenance NC II
CRITERIA PERFORMANCE INDICATORS
1)FUNCTIONALITY 40%
1.1)Special Purpose Switching on the main breaker 40A and 20A, S P O has power 4% S 1 A, bulb A Function 4%
Outlets Switching on CB 20A, 1st PO has power 4% S 4w B , bulb B function 4%
1.2) Power Outlet 2nd PO has power 4% S1 C, bulb C function 4%
Switching on CB 15A and S 3w B , bulb B off 4%
1.3)Lighting Outlets S 3w B, bulb B function 4% S 1 D, bulb D function 4%
S 4w B, bulb B Off 4%
2)WORKMANSHIP40%
2.1) Bending of Rigid All Offset and 90 degrees bend were accurately done in accordance with the prescribed procedure and work requirements. 0.33 shall be deducted for every bend with kinks or worn
Non-Metallic Conduit out.
10%
2.2) Dimensions of All dimensions should be measured from center to center. 0.5 shall be deducted for every item mark that deviates from the tolerance of +/-3mm.
Mounted Fixture 6%
3 2 1 0.5
2.3) Adapter and All entries in the box were provided with 1-5 entries in the box were loosely 6- 10 entries in the box were loosely 11-20 entries in the box were loosely attached
Locknut 3% PVC adapter and locknut firmly attached. attached or not provided with PVC attached or not provided with PVC or not provided with PVC adapter and locknut.
adapter and locknut. adapter and locknut.
2.4) Mounting of Rigid All Rigid non-metallic Conduit were secured 1-3 rigid non-metallic Conduit were not 4-6 rigid non-metallic Conduit were not 7-11 rigid non-metallic Conduit were not
Non-Metallic Conduit with a clamp in one run of conduit when secured with a clamp in one run of secured with a clamp in one run of secured with a clamp in one run of conduit when
3% stability requires it. conduit when stability requires it. conduit when stability requires it. stability requires it.
2.5) Fastening of All fixtures and accessories such as breaker 1-5 fixtures and accessories are not 6-10 fixtures and accessories are not 11-22 fixtures and accessories are not firmly
Fixtures & Accessories panel, bulb receptacles, firmly mounted/attached. firmly mounted/attached. mounted/attached.
3% square/junction/utility boxes, switches,
special power outlet, power outlets and
entrance cap are firmly mounted/attached.

2.6) Wire Splices and All rat tail joints are in accordance with the 1-5 rat tail joints are not in accordance 6-10 rat tail joints are not in accordance 11-18 rat tail joints are not in accordance with
Joints 3% code requirements as to its mechanical and with the code requirements as to its with the code requirements as to its the code requirements as to its mechanical and
electrical characteristics. mechanical and electrical characteristics mechanical and electrical characteristics electrical characteristics or deviated from the
All lengths from the point of the skinned or deviated from the required or deviated from the required required measurement.
wire to the tip of the joint without electrical measurement. measurement.
tape are from 35- 50mm.
2.7) Allowance of Wire All allowance of wire from the center of the 1-5 Allowance of wire from the center of 6-10 Allowance of wire from the center 11-18 Allowance of wire from the center of the
inside Boxes boxes up to the tip of the joint without the box deviated from the required of the box deviated from the required box deviated from the required measurement.
3% electrical tape are from 150 - 160 mm. measurement. measurement.
2.8) Terminal All terminal connections or wire loops on 1-5 terminal connections or wire loops on 6-10 terminal connections or wire loops 11-30 terminal connections or wire loops on
Connections bulb receptacles, circuit breakers and bulb receptacles, circuit breakers and on bulb receptacles, circuit breakers and bulb, circuit breakers and switches did not follow
3% switches followed the tightening direction switches did not follow the tightening switches did not follow the tightening the tightening direction or not properly
and properly connected. direction or not properly connected. direction or not properly connected. connected.

2.9) Conductors and Able to use all the correct size of conductors Is not able to use 1 incorrect size of Is not able to use 2-3 incorrect size of Is not able to use 4-6 incorrect size of
Over Current for SE,ground, SPO, conductors and current ratings of circuit conductors and current ratings of circuit conductors and current ratings of circuit
Protective devices 3% P O, L.O , and the breakers for main and each branch. breakers for main and each branch. breakers for main and each branch.
Current ratings of circuit breakers for main
and each branch.
2.10) Economy of No wasted materials. 1-3 materials were wasted. 4-6 materials were wasted. 7 or more materials were wasted
Materials and Working place is clean and orderly Working place is clean and orderly Working place is not clean and orderly Working place is not clean and orderly
Housekeeping 3%
3. Time Management Able to finished the output: 10-14 minutes before the time 6
10% 30 minutes or more before the time 10 5-9 minutes before the time 5
25- 29 minutes before the time 9 1-4 minutes before the time 4
20-24 minutes before the time 8 Within the time 3
15-19 minutes before the time 7 Unfinished 0

4. Safety Shows the following standards: (5%) Shows only three of the given standards. Shows only two of the given standards. Shows only one of the given standards OR
5% -Use of complete PPE (Respirator, Gloves, 4% 3% If Slight Injury was noticed to the contestant
Tool holster, Helmet, goggle and shoes) while the contest is in progress. 2%
-Proper use and handling of tools
-Followed safety procedures
-Make final check to ensure that work
conform to job requirements.
5. Communication Able to clearly discuss/explain with Able to clearly discuss/explain with Able to clearly discuss/explain with Able to clearly discuss/explain with confidence 1
Skills confidence all of the following: confidence 3 of the following: confidence 2 of the following: of the following:
5% a. process a. process a. process a. process
b. function of tools, materials and b. function of tools, materials and b. function of tools, materials and b. function of tools, materials and
equipment equipment equipment equipment
c. cost of production c. cost of production c. cost of production c. cost of production
d. employability or business opportunity d. employability or business d. employability or business opportunity d. employability or business opportunity
opportunity