Download as pdf or txt
Download as pdf or txt
You are on page 1of 30

2020-03-24

LOAD CHARACTERISTICS

EPM412

1
CONTENTS
Relationship between the Load and Loss Factors

2020-03-24

 Maximum Diversified Demand

 Examples

2
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 Assume that the primary feeder shown in Figure is

2020-03-24
connected to a variable load.

3
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 The load factor is:

2020-03-24
4
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 The loss factor is:

2020-03-24
where
 PLS,av is the average power loss
 PLS,max is the maximum power loss
 PLS,2 is the peak loss at peak load

5
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS

2020-03-24
 From Figure:

where
 PLS,1 is the off-peak loss at off-peak load
 t is the peak-load duration
 T − t is the off-peak-load duration

6
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 The copper losses are the function of the associated loads.

2020-03-24
Therefore, the off-peak and peak loads can be expressed,
respectively, as

7
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 Case 1: Off-peak load is zero. Here,

2020-03-24
 since P1 = 0. Therefore,

 That is, the load factor is equal to the loss factor, and they
are equal to the t/T constant.

8
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 Case 2: Very short-lasting peak. Here,

2020-03-24
 That is, the value of the loss factor approaches the value of
the load factor squared.

9
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 Case 3: Load is steady. Here,

2020-03-24
 That is, the difference between the peak load and the off-
peak load is negligible. For example, if the customer’s load
is a petrochemical plant, this would be the case.

10
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 That is, the value of the loss factor approaches the value of

2020-03-24
the load factor . Therefore, in general, the value of the loss
factor is

 Therefore, the loss factor cannot be determined directly


from the load factor.
 The reason is that the loss factor is determined from losses
as a function of time, which, in turn, are proportional to the
time function of the square load.
11
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS

2020-03-24
12
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 Example1

2020-03-24
 Assume that the annual peak-load input to a primary
feeder is 2000 kW. A computer program that calculates
voltage drops and I2R losses shows that the total copper
loss at the time of peak load is I2R = 100 kW. The total
annual energy supplied to the sending end of the feeder is
5.61 × 106 kWh.

 a. determine the annual loss factor.


 b. Calculate the total annual copper loss energy and its
value at $0.06/kWh.

13
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 Solution

2020-03-24
 a. The annual loss factor is

14
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 Solution

2020-03-24
 b. The annual loss factor is

15
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 Example2: Assume that a DT supplies three primary

2020-03-24
feeders. The annual maximum demands and corresponding
power factor per feeder are listed in the following table,

 Assume a diversity factor of 1.15 among the three feeders


for both real power (P) and reactive power (Q).

16
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 a. Calculate the annual maximum demand on the

2020-03-24
substation transformer in kilowatts and in kVAs.

17
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 a. Calculate the annual maximum demand on the

2020-03-24
substation transformer in kilowatts and in kVAs.

18
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 b. Find the load diversity in kilowatts.

2020-03-24
19
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 c. Select a suitable substation transformer size if zero load

2020-03-24
growth is expected and if a 25% short-time overloads on
the distribution substation transformers is allowed . sizes
available are :

1. 2500/3125 kVA self-cooled/forced-air-cooled


2. 3750/4687 kVA self-cooled/forced-air-cooled
3. 5000/6250 kVA self-cooled/forced-air-cooled
4. 7500/9375 kVA self-cooled/forced-air-cooled

 It is appropriate to choose the transformer with the


3750/4687-kVA rating since with the 25% short-time
overload, it has a capacity of
4687 × 1.25 = 5858.8 kVA 20
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 d. Now assume that the load will increase at a constant

2020-03-24
percentage rate per year and will double in 10 years. If the
7500/9375 kVA-rated transformer is installed, in how many
years will it be loaded to forced-air-cooled rating?

 Load growth equation

where
 Pn is the load at the end of the nth year

 P0 is the initial load

 g is the annual growth rate

 n is the number of years

21
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS
 find the increase (g) per year,

2020-03-24
22
RELATIONSHIP BETWEEN THE LOAD AND LOSS
FACTORS

2020-03-24
 Therefore, if the 7500/9375 kVA-rated transformer is
installed, it will be loaded to its fans-on rating in about 7
years.

23
MAXIMUM DIVERSIFIED DEMAND

 Estimating Distribution Transformer loads in residential

2020-03-24
areas by the diversified demand method:

1. Determine the total number of appliances by multiplying


the total number of customers by the per-unit saturation.

2. Read the corresponding diversified demand per customer


from the curve for the given number of appliances.

3. Determine the maximum demand, multiplying the demand


found in step 2 by the total number of appliances.

24
MAXIMUM DIVERSIFIED DEMAND

2020-03-24
A, clothes dryer;
C, water heater
D, range; 25
E, lighting
MAXIMUM DIVERSIFIED DEMAND

 Example: Assume a typical DT that serves six

2020-03-24
residential loads. Suppose that there are a total
of 150 DTs and 900 residences supplied by this
primary feeder. assume that a typical residence
contains a clothes dryer, a range, a refrigerator,
and some lighting and miscellaneous appliances.
Determine the following:

 a. The maximum diversified demand on the DT.


 b. The maximum diversified demand on the
entire feeder.

26
MAXIMUM DIVERSIFIED DEMAND

 when the number of loads is six, the average

2020-03-24
maximum diversified demands per customer are:

27
MAXIMUM DIVERSIFIED DEMAND

 when the number of loads is 900 (note that, due

2020-03-24
to the given curve characteristics, the answers
would be the same as the ones for the number of
loads of 100), then the average maximum
diversified demands per customer are

28
MAXIMUM DIVERSIFIED DEMAND

 Hence,

2020-03-24
 This discrepancy is due to the application of the
appliance diversities. 29
MAXIMUM DIVERSIFIED DEMAND(CEDC)

 Hence,

2020-03-24
 This discrepancy is due to the application of the
appliance diversities. 30

You might also like