Evacuation Procedures

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 109

EVACUATION PROCEDURES

Unitary Mid Range

Applied
S Evacuation Procedures Service Training INTSE-TRG-VAC1
Course Contents
: Reasons for Evacuation
: Factors Affecting Evacuation
: Correct Evacuation Procedures

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


EVACUATION
Upon Completion of this Course you will be able to:
: Describe the damage occurring in an air conditioning
system due to contamination.
: Describe the factors which affect evacuation.
: Select the proper vacuum pump for a particular system.
: Demonstrate the correct method for connecting and
disconnecting a vacuum pump from the system.
: Explain the reason a vacuum pump requires frequent oil
changes

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Section 1

WHY
WHY DOES
DOES A
A
REFRIGERATION
REFRIGERATION
SYSTEM
SYSTEM NEED
NEED TO
TO
BE
BE EVACUATED
EVACUATED …..
…..

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


MOISTURE
Public Enemy #1

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


MOISTURE IN A REFRIGERATION SYSTEM

Moisture = Ice and Corrosion

R
= &
SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1
ICE

Refrigerant Ice

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


CORROSION

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


CORROSION

Moisture + Refrigerant = ACID

+ =

Moisture + Heat + Refrigerant = MORE ACID

+ + =

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


CORROSION

Brass

Steel

Copper

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


CORROSION

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


CORROSION

Refrigerant + Water - Enters Oil = Acid

=
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


CORROSION
SLUDGE

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


CORROSION
SUMMARY
Acid Attacks Ferrous and Non-Ferrous Metals
Acid
Brass +
Steel
Oil

=
Copper

R
Sludge

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


HOW DOES MOISTURE GET IN ?
Atmospheric Pressure

Must Remove moisture


R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


THE VACUUM PUMP

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


MOISTURE REMOVAL BY EVACUATION

EXHAUST

VAPOUR

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


BOILING POINT OF WATER IN RELATION TO ALTITUDE

At 2.2 Miles (3.5Km) above sea level


P = 8.32 PSI (57.36Kpa)
Boiling water = 184°F (84.4oC)

At Sea Level = 0 ft (0m)


MT.
P = 14.7 PSI (100.1Kpa) WHITNEY
Boiling water = 212°F(100oC)

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


BOILING POINT OF WATER BY ELEVATION
82oc 88oc 93oc 99oc 104oc 110oc
12,000 3,700
11,000 3,400
10,000 3,000

ALTITUDE IN METERS
ALTITUDE IN FEET

9,000 2,700
8,000 2,400
7,000 2,100
6,000 1,800
5,000 1,500
4,000 1,200
3,000 900
2,000 600
1,000 300
Sea Level Sea Level
180of 190of 200of 210of 220of 230of
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


BOILING POINT OF WATER UNDER VACUUM
Boiling Point Microns* Inches Boiling Point
Water Vacuum Water

100oc 759,968 00 212of

60oc 150,368 24 141of


56oc 124,968 25 133of
52oc 99,568 26 126of
46oc 74,168 27 115of
38oc 48,768 28 101of
27oc 23,368 29 80of
14oc 10,668 29.5 58of
* Remaining Pressure in the System in Microns
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Section 2

FACTORS
AFFECTING SPEED
OF EVACUATION

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


5 FACTORS AFFECTING SPEED OF EVACUATION

1 Vacuum Pump Type and Condition

2 Vacuum Pump Capacity V System Internal Volume

3 Amount of Moisture in the System

4 Ambient Temperature

5 Internal and External Restrictions

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Vacuum Pump Type and Condition 1

HAVE
HAVE II GOT
GOT THE
THE
CORRECT
CORRECT TYPETYPE
VACUUM
VACUUM PUMPPUMP
AND
AND IS
IS IT
IT IN
IN GOOD
GOOD
CONDITION
CONDITION ….. …..
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Vacuum Pump Type and Condition 1

MAKE SURE YOU


ARE USING THE
CORRECT VACUUM
PUMP TYPE

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Vacuum Pump Type and Condition 1

EXHAUST INTAKE

ROTARY VANE
VACUUM PUMP

Rotary Vane - Deeper Vacuum Than Piston Type


R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Vacuum Pump Type and Condition 1

EXHAUST INTAKE

Second First

TWO STAGE VACUUM PUMP


R Higher Ultimate Vacuum - as Low as 1 Micron
SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1
Vacuum Pump Type and Condition 1 MAINTENANCE

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Vacuum Pump Type and Condition 1 MAINTENANCE

USE THE CORRECT OIL

R
THINGS TO WATCH
SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1
Vacuum Pump Type and Condition 1 MAINTENANCE

KEEP THE BELTS CORRECTLY TEST ELECTRICS


TENSIONED AND IN GOOD CONDITION REGULARLY FOR SAFETY
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Vacuum Pump Capacity 2

HAVE II GOT
HAVE GOT THE
THE
CORRECT SIZE
CORRECT SIZE
VACUUM PUMP
VACUUM PUMP FOR
FOR
THE SYSTEM
THE SYSTEM
INTERNAL VOLUME
INTERNAL VOLUME
…..
…..
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Vacuum Pump Capacity 2 UN
ITA
RY

PUMP SIZE Vs SYSTEM SIZE

Size of System
Vacuum Pump
in Tons
= Capacity Required
In CFM
7

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Vacuum Pump Capacity 2 UN
ITA
RY
PUMP SIZE Vs SYSTEM SIZE
Example Calculation

7 Tons
= 1.0 CFM
7

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Vacuum Pump Capacity 2 UN
ITA
RY
VACUUM PUMP Vs SYSTEM SIZE
Table
System Size Minimum Capacity

Up to 7 Tons 1.0 CFM


7 - 10 Tons 1.5 CFM
10 - 15 Tons 2.2 CFM
15 - 20 Tons 2.9 CFM
20 - 30 Tons 4.3 CFM
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Vacuum Pump Capacity 2
MI
D
RA
PUMP SIZE Vs SYSTEM SIZE N GE
MID RANGE UNITS 60 Tons - 200 Tons

5CFM - 10CFM
(141LPM - 283LPM)

Vacuum Pump
Capacity Required
In CFM

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Vacuum Pump Capacity 2 AP
P LIE
PUMP SIZE Vs SYSTEM SIZE D
LARGE UNITS Above 200 Tons

10CFM - 20CFM
(283LPM - 566LPM)

Vacuum Pump
Capacity Required
In CFM

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Amount of Moisture in the System 3

HAS
HAS THE
THE SYSTEM
SYSTEM BEEN
BEEN
LEFT
LEFT OPEN
OPEN FORFOR A
A
LONG
LONG TIME
TIME OROR HAS
HAS
THERE
THERE BEEN
BEEN A A TUBE
TUBE
FAILURE
FAILURE ...
...

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Amount of Moisture in the System 3

Sweep The
System With
Dry Nitrogen

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Amount of Moisture in the System 3

Dismantle and
Dry Off the
Internal Parts

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Amount of Moisture in the System 3

Use a Freezeout Chamber To Stop


Moisture Entering the Vacuum Pump
Vacuum Suction Line From Evaporator Refrigeration Type Shut Off Valve

Refrigerant Drum

Vacuum Pump

Dry Ice

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Amount of Moisture in the System 3

WHY AND
WHEN TO
USE GAS
BALLAST
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Amount of Moisture in the System 3

TYPICAL GAS
BALLAST VALVES

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Amount of Moisture in the System 3

WET DRY GAS BALLAST

MIXING WET AND DRY AIR

z Lowers “Relative Humidity”


z Keeps Moisture from Condensing Inside Vacuum Pump
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Temperature 4

IS
IS THE
THE TEMPERATURE
TEMPERATURE
AROUND
AROUND THE
THE UNIT
UNIT
WARM
WARM ENOUGH
ENOUGH

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Temperature 4

70oF (21oC)

When Evacuating
an AC Unit the
temperature should
be at least …..
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Temperature 4

If The Temperature Is Too Low …… Add Heat

Cover (Tarpaulin)

68oF (20oC) minimum

Vacuum Pump

Heater
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


mm Mercury
4 In. Mercury o
Temp oF Microns Temp C
Temperature PSIA
Absolute Absolute

212 14.796 29.921 759.99 759,990 100


205 12.770 26.000 660.40 660,400 96
195 10.386 21.150 537.14 537,140 91
175 6.717 13.676 347.37 347,370 79
160 4.742 9.656 245.25 245,250 71
FACTORS 140 2.890 5.884 149.46 149,460 60
AFFECTING 120 1.693 3.449 87.57 87,570 49
SPEED - 105 57.00 57,000 41
1.102 2.244
TEMPERATURE
85 .596 1.214 30.83 30,830 29
80 .507 1.032 26.22 26,220 27
75 .430 .875 22.23 22,230 24
70 .363 .739 18.77 18,770 21
65 .306 .622 15.80 15,800 18
60 .522 .522 13.25 13,250 16
45 .147 .300 7.63 7,630 7
30 .081 .165 4.18 4,180 -1
20 .050 .103 2.61 2,610 -7
5 .024 .049 1.24 1,240 -15
-24 .0049 .01 .254 254 -31
-35 .00245 .005 .127 127 -37
R
-60 .00049 .001 .0254 25.4 -51
-70 .00024 .0005 .0127 12.7 -56
SERVICE EXCELLENCE -90 .000049 .00254 Service Training
.0001Evacuation Procedures 2.54 -68
INTSE-TRG-VAC1
Internal and External Restrictions 5

HAVE ALL INTERNAL


AND EXTERNAL
RESTRICTIONS BEEN
ELIMINATED …...

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Internal and External Restrictions 5 UN
ITA
MI RY
D
RA
NG
E
Gauges
Hoses

Schrader
Valves

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Internal and External Restrictions 5

VACUUM PUMP HOOK - UP

R
Use Shortest Hoses Possible
SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1
Internal and External Restrictions 5 UN
ITA
MI RY
D
RA
NG
E
3.2 CFM Vacuum Pump Time

Direct 3/8” NPT Hose 5 Minutes

Through Manifold. High and Low 121


Sides Open. Valve Cores in Place Minutes

As Above but with Valve Cores Removed 65 Minutes

You can only pull a vacuum on a system as quickly as


the smallest orifice will allow.
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Internal and External Restrictions 5 UN
ITA
MI RY
D
RA
NG
E

Evacuate system from both the high and low side so


that any internal restrictions are eliminated.
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Internal and External Restrictions 5

Connect to as many points as possible

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Section 3

WHAT EQUIPMENT IS
REQUIRED, AND WHAT
SAFETY PROCEDURES
NEED TO BE
FOLLOWED TO DO A
SAFE AND EFFECTIVE
JOB …..
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


HAND TOOLS SAFETY EQUIPMENT

HI VACUUM PUMP
R
TEST EQUIPMENT
SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1
SA
FE
TY

WHAT IS YOUR
MOST
IMPORTANT
JOB….

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


EVACUATION PROCEDURES SA
FE
TY
Pressure Test Safety

R
Remember Safety Is Your Most important Job
SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1
EVACUATION PROCEDURES SA
FE
TY
Pressure Test Safety

R
Remember Safety Is Your Most important Job
SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1
EVACUATION PROCEDURES SA
FE
TY
Pressure Test Safety

Remember Safety Equipment is supplied to you


for your use… Make sure you wear it

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Section 4

UNITARY
EVACUATION
PROCEDURES
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


UN 1
ITA
RY

R
ADDITION OF NITROGEN
SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1
UN 1
EVACUATION PROCEDURES ITA
RY
Pressure Test Procedures
• Use Nitrogen plus a Trace Gas (R22)
• Use Dalton’s law of Partial Pressures to
calculate the amount of trace gas Required.
Total pressure = sum of all the partial pressures

• 10% to 20% of refrigerant is usually


sufficient

• Add Gas to Both High and Low Sides


R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


1
Imperial Units EVACUATION PROCEDURES UNIT
A RY
Example
Test Pressure Required = 165psig
Trace Gas Required = 15% Dalton’s law of Partial
(all pressures for the calculation are absolute) Pressures
(Using Imperial Measurements)

Calculation
15% Trace Gas = 15% Refrigerant and 85% Nitrogen
180 psia (165psig) x 15% = 27 psia (12.3psig)
27
= 0.15 = 15%
180

First Break vacuum or pressurize the system to 12.3 psig (27 psia ) with R22
Next Pressurize the system to 165psig (180 psia) with nitrogen.
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


1
Metric Units EVACUATION PROCEDURES UNIT
A RY
Example
Test Pressure Required = 1137 Kpa
Trace Gas Required = 15% Dalton’s law of Partial
(all pressures for the calculation are absolute) Pressures
(Using Metric Measurements)
Calculation
15% Trace Gas = 15% Refrigerant and 85% Nitrogen
1237Kpa (1137Kpa) x 15% = 286Kpa (186Kpa)
286
= 0.15 = 15%
1237 To convert gauge pressure to absolute add 100Kpa

First Break vacuum or pressurize the system to 186Kpa (286Kpa absolute )


with R22
Next Pressurize the system to 1137Kpa (1237Kpa absolute ) with nitrogen.
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


UN 2
ITA
RY

LEAK TEST THE UNIT


R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


UN 2
ITA
RY

R
SOAP BUBBLES
SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1
UN 3
ITA
RY

BLANK OF TEST
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


UN 4
ITA
RY

CONNECTING UP YOUR VACUUM PUMP


R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


UN 4
ITA
“T” IN CENTER HOSE RY

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


UN 5
ITA
RY

IF NECESSARY OPEN GAS BALAST

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


UN 6
ITA
RY

1 2
0.5 5

10
20
MILLIMETERS OF MERCURY

1000 MICRONS
0
500 MICRONS
300 MICRONS

100 MICRONS

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


EVACUATION PROCEDURES
UN
ITA
RY

If Unit passes the


Standing Test then
Effective Evacuation
has been achieved.

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Applied Unit evacuation Procedure Review. UN
ITA
RY
1 Pressure test the unit using Dry Nitrogen
and 10% to 20% of trace gas.

2 Leak Check unit.

3 Remove all dry nitrogen from the system.

4 Perform “blank off” test on vacuum pump.

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Applied Unit evacuation Procedure Review. UN
ITA
RY
5 Connect the vacuum pump to the unit.

6 Start Vacuum Pump.

7 Begin evacuating with the gas


ballast valve open if the system has
been contaminated with water.
8 Let the vacuum pump run until the micron gauge reads
350 microns or lower.

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Applied Unit evacuation Procedure Review. UN
ITA
RY
9 Close the vacuum pump isolation valve
and observe the micron gauge. It should
not rise above 500 microns within one
minute. If it does, continue the process
10 When a 500 micron or lower
vacuum can be maintained,
evacuation is complete. Close the
valve to the vacuum pump and
turn it off.

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Section 5

APPLIED
EVACUATION
PROCEDURES
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


AP 1
EVACUATION PROCEDURES PL
IE
D

If Necessary
Pressure Test
The Unit using
Dry Nitrogen
and 10% to 20%
trace gas.

Local Regulations Permitting.


R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


AP 1
EVACUATION PROCEDURES PL
IE
D
1) Use as little trace gas as possible.

2) Never use compressed air, oxygen or a flammable gas to pressurize


the system! Use compressed, dry nitrogen.

3) Always use a regulator when adding nitrogen to a system.

4) Add nitrogen to the system slowly, to allow better mixing with the
trace gas and prevent sweeping the trace gas from the access port.

5) Do not exceed the rating of any relief valve. Never exceed a


placarded low-side test pressure.

6) When possible, pressure test only the part of the system that
requires testing.

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


AP 1
EVACUATION PROCEDURES PL
IE
D
Pressure Test Procedures
• Use Nitrogen plus a Trace Gas (R22)
• Use Dalton’s law of Partial Pressures to
calculate the amount of trace gas Required.
Total pressure = sum of all the partial pressures

• 10% to 20% of refrigerant is usually


sufficient

• Add Gas to Both High and Low Sides


R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


2
EVACUATION PROCEDURES APP
LIE
D

R
Leak Test the Unit
SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1
3
EVACUATION PROCEDURES APP
LIE
D
Remove The Dry Nitrogen

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


EVACUATION PROCEDURES AP 4
PL
IE
D

R
“BLANK OFF” TEST
SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1
AP 5
EVACUATION PROCEDURES PL
IE
D

Typical
Hookup

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


EVACUATION PROCEDURES AP 5
PL
IE
D

CONNECT VACUUM
GAUGE TO UNIT

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


EVACUATION PROCEDURES AP 5
PL
IE
D
APPLY A DEEP VACUUM

THINGS TO WATCH
25,000
Vacuum Microns

Pull Down
20,000

15,000
Moisture Removal
10,000

5,000 Final Degassing

Time
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


6
EVACUATION PROCEDURES APP
LIE
Open ballast if system has been contaminated with D
water or high levels of moisture.

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


7
EVACUATION PROCEDURES APP
LIE
D
Remember change the oil in the pump every 12 hours.

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


8
EVACUATION PROCEDURES APP
LIE
D
After a period of 12 hours check vacuum with the
micron gauge.

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


EVACUATION PROCEDURES APP 9
LIE
D

If system was
contaminated with water
or high levels of
moisture and vacuum is
difficult to achieve, flush
with dry nitrogen.

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Pressure Rise Test AP 9
PL
IE
D
3500

Time
3000

2500
MICRONS

2000

1500

1000

500

0
5

5
5

14

22

33

37

42

53
2

.
7.

16

27

46
TIME- minutes

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


EVACUATION PROCEDURES AP 10
PL
IE
After 24 hours check vacuum and perform a D
standing test.

s e
Pressure Rise

Pressure Rise
Ri
ure Levels Off
ss
re

e
P

is
nt

R
a
st

re
su
n
Co

es
LEAK MOISTURE

Pr
Time Time

R
Final Degassing

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


AP 10
Centravac Vacuum Test PL
IE
D
2500

2000

1500
MICRONS

1000

500

0
1 2.5 3.75 10 15 20 25 30 35

TIME - Hours

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


AP 10
Centravac Rise Test PL
IE
D
2500

2000
Microns

1500

1000

500

0
3.75

24.5
2.5

15

25

30

32

35
10

24

26

31

33
1

Hours

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


AP 10
Centravac Rise chart PL
IE
2500 D

MICRONS 2000

1500

1000

500

0
1 2.5 3.75 10 15 24 24.5 25 30

HOURS

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


EVACUATION PROCEDURES
AP
PL
IE
D

If Unit passes the


Standing Test then
Effective Evacuation
has been achieved.

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Applied Unit evacuation Procedure Review. AP
PL
IE
D
1 If necessary, pressure test the unit using
Dry Nitrogen and 10% to 20% of trace gas.

2 Leak Check unit.

3 Remove all dry nitrogen from the system.


(Bleed the dry nitrogen from the lowest
point of the evaporator so that any waste oil
may also be removed.)

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Applied Unit evacuation Procedure Review. AP
PL
IE
D
4 Prove vacuum pump efficiency by
performing a blank off test

5 Connect a copper line from the vacuum


pump to the charging valve on the base of
the evaporator. Copper pipe size should
be a minimum of 1/2 inch. Connect
micron gauge to the unit. Start Vacuum
Pump.
6 Open the ballast if the system has been contaminated
with water or high levels of moisture.
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Applied Unit evacuation Procedure Review. AP
PL
IE
D

7 Remember to change the oil in the pump every 12 hours.

8 After a period of 12 hours check


vacuum with the micron gauge.

9 If system was contaminated with water


or high levels of moisture and vacuum
is difficult to achieve, flush with dry
nitrogen.
10 After 24 hours check vacuum and perform a standing test.
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


Section 6

LOGGING THE UNIT


EVACUATION
PROCEDURES
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


RECORD THE INFORMATION

PLOT IT

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


VACUUM ANALYZER
3500

3000

2500
MICRONS

2000

1500

1000

500

0
0 10 20 30 40 50 60
TIME

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


REVIEW

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


EVACUATION REVIEW
Evacuation Removes Moisture & Non Condensibles:
 Moisture Can Cause Internal Restrictions
 Moisture Causes Acid & Sludge to Form
 Moisture Causes Bearing Wear
 Acid Can Cause Both Mechanical & Electrical Failures
 Non-Condensables Reduce Capacity and Cause
Inaccurate Measurements .
Time Required for Evacuation Depends On:
 Vacuum Pump Capacity VS System Size
 Internal Restrictions
 External Restrictions
 Amount of Moisture
R

 Temperature
SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1
EVACUATION REVIEW
Evacuation Procedures for both large and small units:
 Pressure Test the unit.
 Check for Leaks.
 Prove the vacuum pump efficiency by performing a blank off test.
 Make sure that the connection between your vacuum pump and the.
unit is of adequate size and unrestricted.
 Open the ballast if the system has been contaminated with water or
has high levels of moisture.
 Remember to change the oil in the pump frequently.
 Check vacuum with a micron gauge.
 Carry out a standing test.
 Log your results.
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


CUSTOMER SERVICE

Always keep the customer informed of what you are doing:

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


THINK SAFETY

To You And Those


Around You This Is
Your Most Important
Job:
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1


ANY QUESTIONS?
THE
END
R

SERVICE EXCELLENCE Evacuation Procedures Service Training INTSE-TRG-VAC1

You might also like