Hand Portable Extinguishers

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

INTRODUCTION

DRY CHEMICAL, DRY POWDER


Anyone who might be expected to use this
fire extinguisher should study and under- IMPORTANT THINGS TO (CLASS D), HALOTRON I, HALOTRON
stand the information in this manual. Please REMEMBER! BRX, HALON 1211, WET CHEMICAL
read it completely and keep it accessible so (CLASS K) AND
that it may be reviewed on a periodic basis. NEVER DISCHARGE A FIRE CARBON DIOXIDE EXTINGUISHERS MONTHLY
OSHA requires training of personnel who might EXTINGUISHER INTO ANYONE’S
FACE INSPECTION RECORD.
be expected to use an extinguisher in the case These extinguishers are shipped factory charged.
of an emergency. Familiarity with this manual Do not test your extinguisher since even a FASTEN TO EXTINGUISHER
and the instruction nameplate on the NEVER THROW AN EXTINGUISHER small amount of discharge could cause it to lose BEFORE INSTALLATION.
extinguisher will contribute to successful use of INTO THE FIRE OR LEAVE IT pressure making it less effective or useless in
the extinguisher. You should know just what it UNATTENDED IF THE FIRE case of a fire.
CAN and CANNOT do, where it is located, how IS NOT OUT DO NOT REMOVE TAG FROM
to use it and how to maintain it. Proper and (Pressure build-up could cause an Dry chemicals are non-poisonous but either EXTINGUISHER.
effective use of any fire extinguisher begins explosion from even a partially full the acidic based (ABC) or alkaline based
with an understanding of the classes of fire. extinguisher) (Regular or Purple K) chemicals could be an
Extinguishers are tested and rated for certain irritant if inhaled. If any physical discomfort is FOLLOW THE INSPECTION
classes and sizes of fires. Some are rated for KEEP FIRE EXTINGUISHERS AWAY experienced, contact a physician immediately. INSTRUCTIONS IN OWNER’S
single classifications, some for multiple FROM CHILDREN
MANUAL AND ON THE
classifications and others constitute a hazard if Dry chemical is not recommended for fires in
used on certain types of fires. delicate electrical equipment or aircraft. Use EXTINGUISHER
of this agent may extinguish the fire but may
Date Inspected By Condition
damage the equipment beyond repair.
TYPES AND CLASSES OF FIRES Neither Halotron I, Halotron BrX nor Halon
1211 should be used in confined areas smaller
CLASSES TYPES OF PICTURE than indicated on the extinguisher nameplate,
food preparation areas or in the presence of
OF FIRES FIRES SYMBOL people with cardiac problems. If problems
occur, quickly remove the person from the
WATER AND WATER MIST area where the gas is present, apply artificial
Wood, paper, EXTINGUISHERS respiration and transport to a physician.

A
cloth, trash and
other ordinary The above referred to models are shipped Never use ABC dry chemical, Halotron I,
materials EMPTY – they must be filled and pressurized Halotron BrX or Halon 1211 fire extinguishers
before being placed into service. on fires involving chlorine containing
oxidizers (example: pool chemicals). A
Model 240 – Never use involving flammable violent explosive reaction could occur with
Gasoline, oil,
liquids or gases or live electrical equipment. The the mixture of chemicals.

B
nameplate on the extinguishers have the
paint and other
international red slash across the Class B and Wet Chemical (Class K) extinguishers are
flammable
Class C symbol designating the hazard of using approved for use for fires involving cooking
liquids
them. media. Do not subject these extinguishers to
conditions where they might freeze.
Models B270, B272 – Water Mist Extinguishers HAVE YOUR EXTINGUISHER PROFESSIONALLY
May be used on
must be charged using deionized water to avoid Carbon Dioxide is discharged as a gas (with MAINTAINED & RECHARGED AFTER ANY USE.

C
fires involving
contaminates. These extinguishers are UL Listed small particles of snow) at extremely low
live electrical HALOTRON BRX EXTINGUISHERS ARE NOT
for Class A and Class C fires. temperatures and will displace oxygen. Care
equipment RECHARGEABLE AND MUST BE REPLACED
should be exercised in confined areas. If AFTER ANY USE.
without danger Never use Water or Water Mist extinguishers problems occur, quickly remove the person
to the operator for fires in cooking media. The water in all from the area where the gas is present, apply
could flash to steam due to the extremely high artificial respiration and transport to a
temperatures and cause serious burns. physician. Avoid skin contact which could IMPORTANT NOTICE TO

D
Combustible cause cold burns. BOAT OWNERS
metals and DO NOT SUBJECT ANY OF THE ABOVE If the extinguisher is to be mounted in your
combustible EXTINGUISHERS OR THE WET CHEMICAL NOTE: As required by OSHA, Safety Data boat, make sure that the proper mounting
metal alloys. (CLASS K) EXTINGUISHERS TO CONDITIONS Sheets (SDS) are available for all chemicals bracket is used. The nameplate (in the area of
WHERE THEY MIGHT FREEZE. contained in Amerex fire extinguishers. the UL manifest) says if it is Coast Guard ap-
NOTE: Only the Model 240 2½ gallon water Contact your Amerex distributor or Amerex proved and the mounting bracket which MUST
extinguisher may be chemically freeze Corporation. In addition, the SDS information be used to complete the approval. You will be

K
Cooking media
(Vegetable or p r o t e c t e d to -40º F with the addition of an is contained in a special section of all cited by the Coast Guard if the correct type of
animal oils and Amerex Model 506B charge. The 506B is not extinguisher labels. All SDS are available on extinguisher and bracket has not been installed.
fats) designed to protect Water Mist or Wet Chemical the Amerex website at www.amerex-fire.com.
extinguishers.
Follow the Mounting Instructions below, HOW TO USE
particularly in public areas where the NOTE: The following instructions are of a
extinguisher might be accidentally dislodged general nature, intended to familiarize the
INSPECTION RECORD user with the basic operating techniques of
Model No: _____________________ from the bracket or have objects placed on it.
Amerex hand portable extinguishers. All
Serial No: _____________________ operate by removing the ring (safety)
Mfg. Date: _____________________ pin and squeezing the handles together.
Date Installed New: _____________ MOUNTING INSTRUCTIONS
Since extinguishers differ, the extinguisher
INSPECTION should be performed monthly UL specifies that a hanging device must withstand a
nameplate must be consulted for specific
or more frequently if circumstances dictate. vertical force of five times the weight of the charged procedures and starting distances.
The extinguisher should be checked to see that extinguisher but not less than 100 pounds. The 1. Hold the extinguisher upright and pull
it is not damaged, the discharge outlet is not extinguisher bracket should be mounted as follows: the ring (safety) pin breaking the plas-
blocked, that it is fully charged, the seal is not Walls where 2"x4" studs can be found – ALL tic seal.
broken and that the operating instructions are SIZES: Mount wall hanger bracket securely to stud
using two #10 x 1¼" long wood screws through the 2. Stand back from the fire (the minimum
clearly visible.
diagonal smaller holes in the bracket. distance stated on the nameplate) and OWNER'S MANUAL
ANNUAL MAINTENANCE is a more
complete inspection of the extinguisher and
Sheetrock – ALL SIZES: Mount a ¾" thick board to
the wall using 3/16" toggle bolts – height and width of
aim at the base of the fire nearest you. HAND PORTABLE
3. Keeping the extinguisher upright,
should be done professionally. It will reveal the the board is dependent on extinguisher size. The
squeeze the handles together to dis- Water
need for hydrotesting which must be done on board should extend a minimum of two inches beyond
Water Mist, Water, Wet Chemical, and Carbon all sides of the extinguisher profile (excluding hose charge and sweep from side to side. Water Mist
Dioxide every FIVE YEARS and Dry Chemical, and horn). Mount wall hanger bracket to board using
two #10 x 1" long wood screws as above.
Move closer as the fire is extinguished Wet Chemical (Class K)
Dry Powder, Halotron I and Halon 1211 but not so close as to scatter the burn-
extinguishers every TWELVE YEARS. Most Cinderblock or Cement – ALL SIZES: Mount wall
ing material or liquid. Dry Chemical
hanger bracket using one ¼" toggle bolt or masonry
local authorities require special tags be
attached to the extinguisher to verify this lead screw expansion anchor through center hole in 4. When the fire is out, back away while Dry Powder (Class D)
service. the bracket. Mount vehicle/marine strap type brackets watching for possible re-ignition. Carbon Dioxide
using two 3/16" toggle bolts or #10 lead screw 5. Evacuate and ventilate the area im-
SIX YEAR MAINTENANCE – Every six expansion anchors. mediately after use. The fumes and Halotron I
years extinguishers requiring a 12 year Concrete or Tile Wall – ALL SIZES – Mount wall
hydrotest shall be emptied and subject to hanger bracket using one ¼" masonry lead screw smoke from any fire may be hazard- Halotron BrX
ous and can be deadly.
thorough examination of mechanical parts,
extinguishing agent and expelling means.
expansion anchor through center hole in wall bracket.
Mount vehicle/marine strap type brackets using two NOTE: Whenever possible, protective Halon 1211
When applicable maintenance procedures are No. 10 masonry lead screw expansion anchors.
Steel Posts or Beams – ALL SIZES: Special tools
clothing and breathing equipment FIRE EXTINGUISHERS
done during periodic recharging or
and fasteners are required – have extinguisher
should be used while fighting a fire.
hydrotesting, the six year requirement will
mounted by a professional fire extinguisher service
begin from that date. Excludes Halotron BrX company.
extinguishers. 1. HOLD EXTINGUISHER UPRIGHT AND
Tile Walls: Locate in joint. PULL THE RING (SAFETY) PIN
RECHARGE should be done professionally
immediately after any use by your local Amerex
Distributor who has the trained personnel,
extinguishing agents and equipment to do it
properly. This extinguisher must be recharged INSPECTION
with the extinguishing agent specified on the Your extinguisher should be inspected monthly,
nameplate. Substitutions could cause damage checking for any possible damage, corrosion,
or injury and will void the warranty. Halotron leakage or obstructions in the discharge outlet. The 2. STAND BACK FROM THE FIRE AND AIM
BrX extinguishers are not rechargeable and tamper seal should be unbroken. The extinguisher AT THE BASE OF THE FIRE NEAREST YOU
shall be removed from service 12 years from should be cleaned so that the instructions on the
the date of manufacture on the UL nameplate. label are always clearly visible.
DISTRIBUTED BY: Carbon Dioxide extinguishers determine fullness by
weighing or hefting.
Water Mist, Water, Wet Chemical, Dry Chemical,
Dry Powder, Halotron I, Halotron BrX and
Halon 1211 extinguisher pressure gauges should be AMEREX LIMITED WARRANTY
checked. The indicator will vary slightly due to tem-
perature, but should always be in the GREEN area if 3. SQUEEZE HANDLES TOGETHER & Amerex warrants its fire extinguishers to be
INSTALLATION & DISTRIBUTION it is fully pressurized. Heft or weigh the extinguisher SWEEP THE EXTINGUISHER STREAM SIDE free from defects in material and workmanship
to determine fullness. TO SIDE
Install, inspect, maintain and test your fire extinguisher from the date of purchase. Visit www.amerex-
in accordance with the National Fire Protection Assoc. fire.com/terms-and-conditions for warranty
IN CASE OF FIRE information.
Standard 10 “‘Portable Fire Extinguishers”. 1. Have everyone evacuate the area immediately.
Your fire extinguisher should be mounted in a clean dry 2. Call the Fire Department even if the fire appears to
area, accessible to possible fire hazards and preferably be small (small fires quickly become LARGE fires).
AMEREX CORPORATION
near an exit. Mount so that for extinguishers having a P.O. BOX 81
The Fire Dept. phone number should be posted at TRUSSVILLE, AL, 35173-0081
gross weight greater than 40 lb ( 18.14 kg ) that the top every phone. Phone: (205) 655-3271 Fax: 1-800-654-5980
is not more than 3 ½ ft ( 1.07 m ) above floor and 40 lb 3. Use your extinguisher properly, according to the e-mail: sales@amerex-fire.com
( 18.14 kg ) or less not more than 5 ft ( 1.53 m ) above instructions on the nameplate and in this manual. A REMEMBER THIS SIMPLE WORD - web page: www.amerex-fire.com
the floor.
Use the mounting bracket furnished with the
large fire should be fought by professionals. Be pre- PASS Printed in U.S.A.
pared to leave the area if the fire cannot be
extinguisher or an approved Amerex vehicle bracket if immediately controlled. PULL AIM SQUEEZE SWEEP P.N. 00914 E’ REV 1/22
required. Fasten to a solid surface using strong screws
or fasteners (not included).