NOTES:

THESE DETAILS REPRESENT A MINIMUM REQUIREMENT


16 DIA STEP BAR CAST INTO AND MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT
COVER SLAB WITH TOE HOLE PROJECT REQUIREMENTS. THEY ARE EXPECTED TO BE
DUCTILE IRON COVER INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
COVER SLAB DETAIL AS SPECIFIED UV RESISTANCE EPOXY AS SPECIFIED UV RESISTANCE EPOXY COATING
TO ALL SURFACES ABOVE GROUND
DRAWING SET.
FOR UNPAVED AREA COATING TO ALL SURFACES ABOVE
200 GROUND
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE
CL CL 2. ALL CONCRETE TO BE CLASS B UNLESS OTHERWISE STATED.
FGL FGL FGL FGL 3. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND TO BE

100

100
200
4. ALL INTERNAL FACES OF CONCRETE TO BE COATED WITH
EPOXY COATING AS SPECIFIED.

300
5. UNLESS OTHERWISE STATED ALL INLET AND OUTLET PIPES OF
MANHOLES SHALL BE LAID SOFFIT TO SOFFIT.
6. ALL COVERS IN OPEN AREA TO BE PROVIDED WITH 1No. GRAB
GRP LADDER 7. MANHOLES SHALL BE PROVIDED WITH REINFORCED CONCRETE
REINFORCED RINGS (2Nos. AS MINIMUM). THE LOWER RING SHALL BE 250mm

DEPTH VARIES-MAX 4200mm FOR PIPE DIA. FROM 2500mm - 3000mm


CONCRETE HEIGHT AND THE UPPER RING TO VARY ACCORDING TO FINAL
GROUND LEVEL.

DEPTHVARIES-MAX3200mmFORPIPEDIA.FROM1500mm-2400mm
WALL
8. MANHOLES TO BE PROVIDED WITH SAND TRAP 500mm DEEP
9. THE MANHOLES AND CHAMBERS ARE DESIGNED USING FULL
GROUND WATER LEVEL CONDITION WITH 1.1 FACTOR OF SAFETY
EPOXY FOR FLOATATION AND BEARING PRESSURE NOT EXCEEDING
COATING TO 200kpa AT FORMATION LEVEL.
ALL INTERNAL 10. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
SURFACES CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER ROOF
SLAB HAS BEEN INSTALLED.
11. ALL STRUCTURAL DETAILS TO BE VERIFIED BY DESIGNERS /
CONSULTANTS.
LEGEND
C C REINFORCED CONCRETE
SOIL COMPACTED TO 95% MDD
STAINLESS
STEEL PLAIN CONCRETE
SAFETY CHAIN FGL FINAL GROUND LEVEL
AND FIXINGS FL FINAL ASPHALT / INTERLOCKED TILE LEVEL
IL
DIA DIAMETER
PVC WATER STOP CL COVER LEVEL

(SEE NOTE 8)
IL INVERT LEVEL OF OUTLET PIPE

500
TANKING MEMBRANE CONSTRUCTION
400

GA GENERAL ARRANGEMENT
AND PROTECTION BOARD JOINT

1000
REINFORCED

500
CONCRETE
BASE

50mm THK. CEMENT/SAND SCREED 50mm THK. CEMENT/SAND SCREED


900 1500 900 TANKING MEMBRANE 400 A = OUTLET PIPE INTERNAL DIAMETER + 1200 400 TANKING MEMBRANE
75mm THICK C20 BLINDING 75mm THICK C20 BLINDING
1000 GAUGE POLYETHYLENE SHEET 1000 GAUGE POLYETHYLENE SHEET
SECTION A-A SECTION B-B
- DUCTILE IRON COVER AND FRAME
TO SUIT 900 DIA. OPENING IN ALL
NOTE : THIS DRAWING APPLIES WHERE DEPTH FROM UNDERSIDE OF MANHOLES ON STORM WATER
TOP SLAB TO INVERT OF OUTLET PIPE IS AS FOLLOWING : PIPELINES WITH DIAMETER
B · NOT GREATER THAN 3200mm FOR PIPE DIA FROM 1500mm TILL RANGING FROM 1500 TO 3000.
2400mm. - GRP COVER WITH ADEQUATE
3300 · NOT GREATER THAN 4200mm FOR PIPE DIA FROM 2500mm TILL FRAME IS ACCEPTABLE SUBJECT
3000mm. TO THE ENGINEER'S APPROVAL.
900 1500 900
FOR DEEP MANHOLES SEE DRAWING No. 205
REFERENCE DRAWINGS AND DOCUMENTS
STANDARD DRAWING - TANKING DETAILS - 801
STANDARD DRAWING - CONSTRUCTION AND MOVEMENT 1001
JOINT

400

± STANDARD DRAWING - MISCELLANEOUS DETAILS


2 0° - 207
1 FOR MANHOLES
AT 1000


STANDARD DRAWING - REINFORCEMENT DETAILS

750
EN
±
OP (SERIES)
°
90
STANDARD DRAWING - STORM WATER MANHOLE FRAME - 213
AT

AND COVER DETAILS


K
C
LO
A = OUTLET PIPE INTERNAL DIAMETER + 1200

SEE DETAIL A FOR HINGE


DETAILS

DETAIL A
HINGE DETAILS
A No. REVISION-2 APP'D 2021
NOTE : THIS DRAWING APPLIES WHERE DEPTH CLIENT
FROM UNDERSIDE OF TOP SLAB TO INVERT OF OUTLET
PIPE IS AS FOLLOWING :
· NOT GREATER THAN 3200mm FOR PIPE DIA FROM
1500mm TILL 2400mm.
· NOT GREATER THAN 4200mm FOR PIPE DIA FROM
2500mm TILL 3000mm.
FOR DEEP MANHOLES SEE DRAWING No. 205 75 THICK PRECAST CONCRETE
COVER SLAB DETAIL
SEATING RINGS BEDDED IN 1 PART FOR PAVED AREA PLAN AT COVER LEVEL TITLE
CEMENT / 2 PART SAND MORTAR STANDARD DRAWINGS
DUCTILE IRON COVER
10 DOWEL DRILLED AND SET INTO
16 DIA STEP BAR CAST INTO COVER
STORM WATER WORKS
COVER SLAB AT 300 CENTERS
SLAB WITH TOE HOLE
150 CLASS B
DRAWING TITLE
FINISHED LEVEL OF
CARRIAGEWAY (FL) CL CONCRETE SURROUND
STANDARD DRAWING G.A. OF
400

(MIN.)
450

MAX
600

SHALLOW STORM WATER MANHOLE


ON PIPELINES 1500 - 3000mm DIA.
300

B DRAWN - SCALE 1 : 50
CHECKED - DATE -
COVER SLAB DETAIL FOR CARRIAGEWAY &
SECTION C-C APPROVED - SIZE A1
PARKING AREAS
PROJECT DWG.
No. - No. 204

THIRD EDITION - APRIL 2022