Professional Documents
Culture Documents
Line Sizing
Line Sizing
LINE SIZING
CONTENTS
654307908.doc 1
1.0 SCOPE
3.0 GENERAL
1.0 SCOPE
654307908.doc 2
1.1 This Process Engineering Design Guideline outlines the general process requirements
for piping systems.
1.3 These design guidelines are intended to provide a simple, standard method to
facilitate the accurate sizing of lines within a plant or the accurate determination of
pressure drop for a specific Line. For a more detailed analysis of Fluid Flow
calculations refer to Crane.
3.0 GENERAL
c. The economic sizing of lines to insure the hydraulic integrity of the process.
d. Co-ordination with the piping design discipline to insure that the detail design
does not interfere with the process design.
The design pressure of a line shall be carried through to, and include, the last block valve
which can be used to shut in the system. Line design pressure shall be determined from the
maximum of the following:
4.1 Design pressure based on maximum operating pressure. This should take into
account all modes of operation and shall be set based on the table below
654307908.doc 3
Full or Partial Vacuum 3.5/ Full Vac
0.0 - 0.4 3.5/Full Vac
0.4 - 2.5 3.5
2.5 - 20.0 MOP +2
> 20.0 1.1 x MOP
4.2 The set pressure of the relief valve when mounted on the line.
4.3 The set pressure of the relief valve on equipment when connected to the line plus the
static head and friction loss.
4.4 The maximum pressure that a piece of equipment can generate, such as the shutoff
head of centrifugal pumps or the stalling pressure of reciprocating pumps.
a For horizontal centrifugal pumps, the assumed shutoff pressure shall be the
normal suction pressure plus 125% of the differential pressure at normal
capacity, or the maximum suction pressure plus the differential pressure at
normal capacity, whichever is greater. Maximum suction pressure is taken at
the relieving pressure of the suction vessel.
b. For some high head and vertical pumps, the shutoff pressure may be higher
than 125% of the normal. The Mechanical Engineer should be consulted for
an adequate allowance.
c. For reciprocating pumps the following table shall be used to establish the
setting for the relief valve in the pump discharge, this also sets the design
pressure of the discharge piping. The factor shall be applied to the normal
pump discharge pressure.
5.1 The design temperature for piping shall be set at the maximum operating temperature
plus 30°C. The maximum operating temperature shall take into account all
temperature excursions. In hot climatic conditions a design temperature of some
minimum value may be necessary.
5.2 Minimum design temperatures shall be set based on the table below:
654307908.doc 4
Ambient to -10 Min op minus 1 5°C
-10 to -25 -30 °C
-25 to -60 Min op minus 5°C
Below -60 Min op
5.3 Additionally, the following shall be considered and applied where appropriate:
c. Lines subject to steam-out will have the steam out temperature stated.
(Minimum design temperature 105°C)
d. The design temperature on the outlet side of an exchange shall be the normal
inset temperature to the exchanger or the outlet temperature plus 30°C
whichever is the greater.
f. The control setting for steam or electrically traced lines: shall be considered
for operating temperatures.
g. The design temperature on the outlet side of an air cooler shall be the normal
inlet operating temperature minus one third of the normal temperature drop
across the air cooler. or the normal outlet temperature plus 30°C whichever
the greater
654307908.doc 5
6.1 Single Fluid Lines
6.1.2 THEORY
When a fluid flows through a tube or over a surface, the pattern flow will
vary greatly with the velocity, the physical properties of the fluid and the
geometry of the surface. There are two fundamental types of flow, namely
Laminar or Streamline and Turbulent.
Laminar flow refers to a flow pattern in which elements of the fluid pass
along the pipe axis without intermixing. Turbulent flow is characterised by
random movement of fluid across the pipe axis accompanied by eddies.
654307908.doc 6
The head lose of a Liquid or gas flowing in a round pipe is given by the
generalised Darcy-Weisbach equation:
h = F. L . v2
d 2g
For the turbulent flow, the friction factor F can be expressed as a function of
two dimensionless groups, the Reynolds Number and the relative roughness
of the surface
d
and in the laminar flow region
F= 64
Re
p = 64.42 F W2
d5 S
This equation can be used for any single phase Newtonian fluid but for gases
it is more practical to re-write S in terms of pressure (bar), absolute
temperature (T °K) and molecular Weight (MW such that
p = 5459 FW 2T
d5 p (MW)
and for turbulent or transitional flow Re > 2700 F can be read from Moody
friction factor charts as a function of Re and /d
Re = 354 W
d
6.1.4 Roughness
Limitations
For practical purposes the economic pipe size can be selected using criteria,
which have been established, based on fluid velocity or pressure drop per
Unit length of pipe. For initial pipe size selection use the Meare circular
calculator with the appropriate criteria. The following criteria are to be used
for the selection of pipe sizes. However, for each case, consideration may be
given to the effects of increasing or decreasing pressure drop to utilise the
highest-pressure drop, which can be tolerated without sacrificing economy or
safe operation. There will therefore be cases when individual judgement will
indicate deviation from the following criteria and these cases should be
discussed with the Process Design Manager.
For more viscous fluids the basic equations can still be used to assess p
though they become less accurate at higher viscosities. Viscous fluid
velocities should be approximately within following values (in m/s)
654307908.doc 8
Pressure Drop Velocity
bar/100m m/s
Steam Condensate
Based on liquid .025
volume
Size liquid lines from vessels to control valves according to the pump suction
criteria above.
* The related line size should be carefully checked to ensure that the NPSH
requirement for a particular pump is satisfied.
In cases where the fluid viscosity is moderate to large it is often difficult to conform
with the recommended pump suction line p and have a practical line size. In such
cases of viscous flow the moat important criterion to fulfil is the provision of
654307908.doc 9
adequate NPSH. Generally, 2 - 3m NPSH is required for pump of up to l00m 3/hr
capacity although this should be checked with Vendors for more specific calculations.
A margin of l to 2 m liquid should be added to the manufacturers required NPSH for
the purpose of pump suction line calculations.
By following the guidelines in 5.2 for viscous liquids, line pressure drops greater than
0.035 bar/100m may be encountered This is acceptable provided that:
a) NPSH is satisfactory.
In general the vapour Pressure of the viscous fluid will have a very small effect on the
NPSH calculation and the largest contributor to NPSH losses will be suction line
pressure drop. Care must, therefore, be taken to properly assess the pipework and
fittings for pump suction calculations.
Piping allowable velocities and pressure drops shall be within the following limits:
6.2.2 Steam
<5 bar a 0.06 - 0.25 Maximum of 9.1 m/s
5 - 12 bar a 0.25 - 0.35 25 mm of pipe dia.
> 12 bar a 0.25 - 0.5 Between 80 mm and
150 mm diameter, 61
m/s
Short leads (steady 0.34 - 0.91 for saturated steam and
flow to equipment) 76 m/s for superheated
over 3.4 barg steam
654307908.doc 10
may be allowed, providing that any control value in the circuit has sufficient
pressure drop across it to give good control, i.e., at least 30% of the particular
system pressure-drop.
To avoid noise problems for gases and vapours flowing in lines the following
maximum velocities should be considered
For gaseous oxygen services, the velocity must not exceed 20 m/s under any
circumstances.
6.3.1 Piping allowable velocities and pressure drops shall be within the
following limits
a. Feed lines on entry to columns should be sized to meet the following criteria:
v= 122
p
b. Liquid side draw-off lines should be sized using the free orifice region of
Figure 16.1. After a vertical drop of 6000 mm (19.7 ft) which is preferably
straight the line size should be swedged down to the pump suction line size.
654307908.doc 11
a Outlet lines from columns to reboilers should be sized on 0.01 to 0.05
bar/100m with a maximum velocity of 0.9 m/s .
b. The two-phase return line should be sized using the two phase criteria under
section 6.3.
6.6 Flare and Relief Valve Outlet Lines
Flare Headers
Flare system in large facilities require detailed analysis but for most applications
may be sized using the same criteria as for process fluids. Care should be taken not
to make flare lines too small and sonic velocities which are likely to occur at
Pressure drops in excess of 2 bar per 100m must be avoided.
For API-ASME code conditions, the line must be sized such that when the valve is
relieving at full capacity, the outlet pressure does not exceed 10% of the relief
valve set pressure. If a balanced bellows valve is used up to 50% back pressure can
often be accepted, however, a conservative value of 30 % should be wed for sizing
purposes.
If other codes are used these conditions may be changed as appropriate for the
code.
Laminar Flow (Re < 2000) through straight pipe is covered by the general pressure
drop equation given above. However, for pressure drop attributes to valves and
fittings it is advisable to use another more accurate method such as the
“Two-K” method.
The 2Two-K” method involves the use of two K-values, one corresponding to R e = 1
and the other to Re = , i.e.
25.4
K = K1 + K1
d
v2
P = 0.00001
2
K
for a straight length of pipe
FL
K =
d
64
where F =
Re
For pipe entrance and exit losses the following equation applies:
654307908.doc 12
K1
K = K
Re
where the constants are
K1 K
normal pipe entrance 160 0.5
normal pipe exit 0 1.0
7.1 Battery limit block valves shall consist of a single gate valve with a bleed valve
upstream and downstream.
7.2 Start-up and shut-down bypass and circulation lines should be considered for each
unit. Lines that are normally used only during start ups and shut downs should be
double valued out of service. Bypass and circulation lines shall be sized for 1/2 of
normal flow.
7.3 Facilities for air feeding units before introduction of hydrocarbon (or hydrogen) feed
streams should be provided.
7.5 A cooler shall be used when hot liquid samples are taken so that flashing or loss of
vapour will not occur when drawing samples. A single cooler can be used to serve
several streams. Gas samples shall be drawn into a bomb.
7.6 Recirculating samplers are the preferred type ~ These require a circulation line
across a pressure differential, such as a control valve or a pump
7.7 When sampling corrosive liquids, flush sample to an appropriate recovery sump. A
drain funnel to the appropriate sewer (oily water, chemical etc.) shall be: provided at
all sample connection points.
The two preliminary line sizing charts (FIGURES I and 2) are provided to give an easy fix on
the line sizes which should be selected for detailed examination.
The following examples have been detailed in a stepwise manner to illustrate the route taken
in building up a pressure drop analysis However the standard calculation sheet is ultimately
the short cut path to laying out the calculation.
Example 1
Main Header
Try mid range velocity
say 3 m/s
360 x 354
Size = = 206 mm say 200 mm
3
Assume turbulent flow. From crane for 200 and 250 mm pipe at full turbulent flow F =
0.014
64.42 x 360000 2 x 0.014
p = = 0.365 bar/100m
200 5 x1
this is on the high side
try 250 mm pipe
Branch Line
Size lies between 100mm /150 mm
Assume full turbulence
Pressure drop for 100mm line is excessive, therefore use 150mm for Branch Line.
Example 2
Find pump suction and discharge line sizes for the following information:
These sizes are only Preliminary and should be checked in detail. In particular the suction line
should be checked to ensure that there is sufficient NPSH for the pump. In many cases it may
be found that the next larger size of pipe is required.
Example 3
Find the correct line size and calculate the pressure drop per 100m of line for the following
conditions:
Example 4
Calculate system pressure drop for sketch below based on conditions in Example
654307908.doc 15
6m
2m
3m
19 m 2m
41 m
Straight length 80 m
5m
2m
From FIGURE 4
Example 5
Find the pressure drop for the following laminar flow system
Straight pipe
FL 40
K = = 0.582 x = 447.69
di 0.052
90° Bends
K1 25.4
K = 10 + K1 +
Re 52
800 25.4
K = 10 + 0.25 1 + = 76.45
110 52
Ball Valves
K1 25.4
K = 3 + K1 +
Re d
500 25.4
K = 3 + 0.15 1 + = 14.31
110 52
K1 25.4
K = + K1 +
Re d
654307908.doc 17
1500 25.4
K = 3 + 1.5 1 + = 15.87
110 52
The equivalent length of pipe for various types of fittings is given in the following table as a function
of pipe diameter.
Type R/d n
180 ° Bends
Mitre Bends
654307908.doc 18
45 ° 1 cut 0.015
60 ° 1 cut 0.03
90 ° 1 cut 0.06
90 ° 2 cut 0.02
90 ° 3 cut 0.015
Tees
Valves
Type n
Gate 0.007
Globe 0.333
Angle .167
Swing Check .08 3
Butterfly Ball .04
Ball .01
Cock .02
3 Way Cock (straight through) .'05
.08
.06
654307908.doc 19
.04
.02
The above is a convenient way of calculating equivalent pipe lengths. In some cases the relevant n
value may not be available in the above table. Vendors literature often expresses fitting resistances
(Crane Manual) in terms of equivalent K values. To convert 'K' values to 'n' values the following
equation may be used:
K = F x n x 1000
For example the 'K' value for a Globe Stop Check value b 400.Ft
Assuming we have a 80mm bore pipe with complete turbulent we get F~0.018 and thus
n = K = 7.2 = 0.4
1000F 1000 x 0.018
Fitting Type K1 K
Standard (R/D = 1), screwed 800 0.40
Standard (R/D = 1), Flanged/welded 800 0.25
Long Radius (R/D - 1.5), all types 800 0.20
654307908.doc 20
90° Mitered elbows : 1 weld (90° angle) 1000 1.15
(R/D =1.5 ) : 2 Weld (45° angles) 800 0.35
: 3 Weld (30° angles) 800 0.3
: 4 Weld (22 ½ ° angles) 800 0.27
: 5 Weld (18° angles) 800 0.25
Elbows Standard (R/D = 1), all types 500 0.20
Long Radius (R/D = 1.5), all types 500 0.15
45° Mitered , 1 weld, 45° angle 500 0.25
Mitered, 2 weld, 22 ½° angles 500 0.15
Standard (R/D = 1), screwed 1000 0.60
180° Standard (R/D = 1), Flanged/welded 1000 0.35
Long Radius (R/D - 1.5), all types 1000 0.30
Used Standard (R/D = 1), screwed 500 0.70
as Long Radius, screwed 800 0.40
elbows Standard, Flanged/welded 800 0.80
Tees Stub-in type branch 1000 1.00
run- Screwed 200 0.10
Through Flanged or welded 150 0.50
tee Stub- in type branch 100 0.00
Gate Full line size, = 1.0 300 0.1
Ball Reduced Trim, = 0.9 500 0.15
plug Reduced Trim, = 0.8 1000 0.25
Globe Standard, 1500 4.00
Valves Globe angle or Y-type 1000 2.00
Diaphragm dsm type 1000 2.00
Butterfly 800 0.25
Lift 2000 10.00
Check Swing 1500 1.50
tilting disk 1000 0.50
654307908.doc 21