Spaj 144 C Combined Overcurrent and Earth-Fault Relay: User S Manual and Technical Description

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

User´s manual and SPAJ 144 C

Technical description Combined overcurrent


and earth-fault relay

3I >
2 I

f n = 50Hz I n = 1A 5A (I ) 5
I L1 I L2 I L3 I 0 IRF
60Hz I n = 1A 5A (I o )

SPAJ 144 C
80...265V –
~ RESET
I >/I n
18...80V – U aux STEP
t > [s]
k
SPCJ 4D28 I >> / I n
t >> [ s ]
REGISTERS OPER.IND.
I >>> /I n
0 0 0 0 0 t >>> [ s ]

I 0 >/I n
1 I L1 /I n 1 I > Start
2 I L2 /I n 2 I > Trip t 0 > [s ]
k0
3 I L3 /I n 3 I >> Start
I 0 >> / I n
4 t (I > ) [ % ] 4 I >> Trip
t 0 >> [s ]
5 t ( I >>) [ % ] 5 I >>> Start
∆ I > [%]
6 I 0 /I n 6 I >>> Trip
t ∆ > [s ]
7 t (I 0 > ) [ % ] 7 I 0 > Start PROGRAM
8 t ( I 0 >>) [ % ] 8 I 0 > Trip SGF
9 ∆ I [%] 9 I 0 >> Start
SGB
11 I max (15min) /I n 0 I 0 >> Trip
11∆ I > Trip
SGR
A CBFP
TRIP
0303A

0023A

RS 611 Ser.No. SPCJ 4D28

ABB Network Partner


1MRS 750043-MUM EN
SPAJ 144 C
Issued 95-11-02
Version A Combined overcurrent
Checked
Approved and earth-fault relay
Station
Automation
Data subject to change without notice

Contents Features .......................................................................................................................... 2


Description of operation ................................................................................................. 3
Connections ................................................................................................................... 5
Signal diagram ................................................................................................................ 7
Signal abbreviations ........................................................................................................ 8
Start and operation indicators ......................................................................................... 8
Power supply and output relay module ......................................................................... 10
Technical data .............................................................................................................. 11
Examples of application ................................................................................................ 12
Commissioning ............................................................................................................ 18
Testing ......................................................................................................................... 19
Maintenance and repairs ............................................................................................... 20
Spare parts .................................................................................................................... 20
Dimensions for mounting ............................................................................................ 21
Order information ........................................................................................................ 21

The complete manual for the relay SPAJ 144 C contains the following submanuals:

General relay description for SPAJ 144 C 1MRS 750043-MUM EN


Combined overcurrent and earth-fault relay module SPCJ 4D28 1MRS 750093-MUM EN
General characteristics of D-type relay modules 1MRS 750066-MUM EN

Features Three-phase, low-set phase overcurrent unit Built-in circuit breaker failure protection
with definite time or inverse definite minimum
time (IDMT) characteristic Two heavy-duty and four signal output relays
with field-selectable configuration
Three-phase, high-set phase overcurrent unit
with instantaneous or definite time operation Output relay matrix allowing any start or trip
characteristic signal from the protection stages to be routed to
the desired output relay.
Three-phase, superhigh-set phase overcurrent
unit with instantaneous or definite time opera- Local display of measured and set values and
tion characteristic data recorded at the moment of a fault.
Reading and writing of setting values either via
Low-set earth-fault unit with definite time or local display and front panel push buttons or
inverse definite minimum time (IDMT) char- from higher-level systems over the serial inter-
acteristic face and the fibre-optic bus.

High-set earth-fault unit with instantaneous or Self-supervision system continuously monitor-


definite time function ing the operation of the electronics and the
mircoprocessor. When a permanent fault is de-
Phase discontinuity stage with definite time tected the alarm output relay operates and the
characteristic. The phase discontinuty stage can other relay outputs are blocked.
be set out of operation

2
Description of The combined overcurrent and earth-fault relay ers a start signal after a preset (~50 ms) start
operation is a secondary relay to be connected to the time. At the moment the set operate time elapses,
current transformers of the protected object. the earth-fault unit operates. In the same way
The three-phase overcurrent unit and the earth- the phase discontinuity stage starts and delivers
fault unit continuously measure the phase cur- a start signal after a preset (~150 ms) start time,
rents and the neutral current of the protected when the set start value is exceeded. At the
object. On detection of a fault the relay starts, moment the set operate time elapses, the stage
trips the circuit breaker, provides an alarm operates.
signal, records fault data, etc. in accordance with
the application and the relay configuration. The low-set stage of the overcurrent unit and the
low-set stage of the earth-fault unit may be given
When the phase current exceeds the set start definite time or inverse definite minimum time
current of the low-set stage I>, the overcurrent (IDMT) characteristic. When the IDMT char-
unit starts and it delivers, after a preset start acteristic is chosen six time/current curves are
time, a start signal. When the set operate time at available. Four of the curves comply with the BS
definite time operation, or the calculated oper- 142 and IEC 255 and are named "Normal
ate time, at inverse time operation elapses, the inverse", "Very inverse", "Extremely inverse"
overcurrent unit operates. In the same way, the and "Long-time inverse". The two additional
high-set stage I>> of the overcurrent unit starts inverse time curves are called "RI" and "RXIDG".
when the set start current is exceeded and deliv-
ers a start signal after a preset (~40 ms) start By appropriate configuration of the output relay
time. When the set operate time elapses, the matrix, the start signals of the overcurrent and
overcurrent unit operates. The second high-set earth-fault units are obtained as contact func-
stage I>>> of the overcurrent unit operates in tions. The start signals can be used for blocking
the same way as the above stages. It starts when co-operating protection relays, and for signal-
the set start current is exceeded and delivers a ling.
start signal when a preset start time has elapsed.
The relay includes one external binary input,
When the earth-fault current exceeds the set which is controlled by an external control volt-
start current of the low-set stage I0>, the earth- age. The function of the control input is deter-
fault unit starts and it delivers, after a preset start mined by the switch SGB1 of the protection
time, a start signal. When the set operate time at relay module. The control input can be used for
definite time operation, or the calculated oper- blocking the operation of one or more protec-
ate time, at inverse time operation, elapses, the tion stages, for resetting a latched output relay in
earth-fault unit operates. In the same way, the the manual reset mode or for switching between
high-set stage I0>> of the earth-fault unit starts main and second setting banks.
when the set start current is exceeded and deliv-

3
Three-phase definite time
or inverse time low-set 51
overcurrent protection I> SS1

IL1
Three-phase instantaneous
or definite time high-set 50
overcurrent protection I>>
TS1

Three-phase instantaneous
or definite time high-set 50
IL2 overcurrent protection I>>>
SS2
Phase discontinuity protection
with definite time characteristic ∆I>

IL3 Definite time or inverse time TS2


low-set earth-fault 51 N
protection Io>

Instantaneous or definite
time high-set earth-fault 50 N
Io protection Io>> SS3

Remote reset, remote setting


control or blocking input for
the current stages
IRF

Circuit breaker failure 51BF


Blocking protection (CBFP)
or Reset Serial I/O

Serial communication port

Fig. 1. Protection functions of the combined overcurrent and earth-fault relay type SPAJ 144 C

4
Connections

SERIAL
Tx

PORT

Σ = ____
Σ = ____
Σ = ____
Σ = ____
Σ = ____
Σ = ____

Σ = ____

Σ = ____
Σ = ____
Σ = ____
Σ = ____
Rx

(16)
+
SPA-ZC_

5
5
5
5
5
5

5
5
5
5
68 69
SS3
-0

I
-

(8)
4
4
4
4
4
4

4
4
4
4
+

65 66
TS2
0
+

(4)
3

3
3

3
3
80 81
SS2
I

(2)
2
2
2
2
2
2

2
2
2
2
74 75
TS1

(1)
1

SGR11 1

1
1

SGR10 1
SGR9 1
77 78
SS1

SGR1
SGR2
SGR3
SGR4
SGR5
SGR6

SGR7
SGR8
U aux
L1
L2
L3

I/O
IRF
+ (~)
- (~)

Trip

Trip

Trip

Trip

Trip
Start

Start

Start

Start

Trip
Start
70 71 72
IRF

3I>>>
SPCJ 4D28

3I>>

Io>>
3I>

Io>
∆I>

RESET
62 61

+ -
~
63
EXTERNAL
CONTROL
10
11

U2
7 8 9 25 26 27

1A
5A

1A
5A

SPAJ 144 C
1 23 4 5 6

1A
5A

1A
5A
U3
U1

Fig. 2. Connection diagram for the combined overcurrent and earth-fault relay type SPAJ 144 C

Uaux Auxiliary voltage


IRF Self-supervision
SGR Switchgroups for the configuration of output relays
SGB Switchgroup for the configuration of blocking or control signals
TS1, TS2 Trip output relays
SS1, SS2, SS3 Signal ouput relays
U1 Overcurrent and earth-fault relay module SPCJ 4D28
U3 Input module SPTE 4E1
U2 Power supply and output relay module SPTU 240 R1 or SPTU 48 R1
SERIAL PORT Serial communication port
SPA-ZC_ Bus connection module
Rx/Tx Receiver bus terminal (Rx) and transmitter bus terminal (Tx) of the bus
connection module

5
1 61

Rx 2 62
Tx 68 3 63
69
4 65
77
78 5 66

80 6 74

7 75

8 70

9 71
Made in Finland
25 72

26 10

27 11

Fig. 3. Terminal arrangement of the overcurrent and earth-fault relay type SPAJ 144 C

The energizing currents of the overcurrent unit supply module. The permitted auxiliary voltage
are connected to terminals 1-2, 4-5 and 7-8, range of the relay is marked on the relay front
when the rated current of the CT secondary panel.
circuits is In = 5 A. When the rated current of the
CT secondary circuits is In = 1 A, terminals 1-3, Output relays TS1 and TS2 are heavy-duty trip
4-6 and 7-9 are used. The relay can also be used relays capable of controlling most circuit break-
in single-phase or two-phase applications, by ers. The operate signals of the protection stages
leaving one or two energizing inputs unoccu- are routed to the trip relay with the SGR switches.
pied. In single-phase applications the same When the relay is delivered from the factory all
energizing current can be routed through two the protection stages are routed to the trip
energizing inputs, this may increase the operat- relays. Switchgroup SGF4 is used to select
ing speed of the overcurrent unit, especially, at latching of the heavy-duty output relays.
instantaneous operation.
The relay module is also provided with a circuit
The energizing current of the earth-fault unit is breaker failure protection (CBFP), which pro-
connected to terminals 25-26 when the rated vides a tripping signal via TS1 after the set
current In = 5 A and to terminals 25-27 when operation time 0.1...1 s counted from the nor-
the rated current In = 1 A. mal tripping signal TS2, if the fault has not been
cleared within that time. The operation time of
The control input 10-11 can be used in three the circuit breaker failure protection is set in
ways: 1) as the control input for an external Register A, submenu 5.The output contact of
blocking signal, 2) as the control input for the circuit breaker failure protection is normally
unlatching a trip relay, or 3) as the control input used for tripping an upstream circuit breaker.
for the remote control of main/second settings The CBFP can also be used for establishing a
of the relay. The required function is selected redundant trip system by providing the circuit
using switchgroup SGB of the protection relay breaker with two tripping coils one being con-
module. trolled by TS2 and the other by TS1. Output
relay TS1 is used as a trip relay for the circuit
The auxiliary supply voltage of the relay is breaker failure protection (CBFP), when the
connected to terminals 61-62. At d.c. supply CBFP function is used. In this case the trip
the positive lead is connected to terminal 61. signal can be used either to control a circuit
The level of the voltage to be applied to the breaker upstream or to control a second trip coil
terminals depends on the type of power supply on the main circuit breaker to increase the
and output relay module used in the relay. For redundancy of the circuit breaker.
further details, see the description of the power

6
Output relay IRF functions as the output relay The relay connects to the fibre-optic SPA bus via
for the self-supervision system of the protection a bus connection module type SPA -ZC 17 or
relay. Under normal operating conditions the SPA-ZC 21 and the 9-pole, D-type subminiature
IRF relay is energized and the contact gap 70-72 connector located at the rear panel of the relay.
is closed. If a fault is detected by the self- The fibre-optic cables are linked from one relay
supervision system, or on loss of auxiliary sup- to another and to the substation level communi-
ply, the output relay drops off and the NO cation unit.
contact 71-72 closes.

Signal diagram The figure below schematically illustrates how be configured to obtain the required protection
the start, trip, control and blocking signals can functions.

I L1 ∆I> t∆>
I L2 Imax - Imin
SGR 11 / x
Imax
I L3 TRIP ∆I>

SGR 1 / x
50 ms START I>
I>
t>, k
SGR 2 / x
TRIP I> SGF 5/1
SGF1/1... 3 SS1
SGB 1/6 1

SGR 3 / x RESET +
SGB 1/1 SGF 4/1 PROGRAM
30 ms START I>>
I>>
t>> SGF 5/2
SGR 4 / x 2 1 TS1
1
TRIP I>>

SGB 1/2
0.1..1s SGF 5/3
BS1 SGR 5 / x 3 SS2
30 ms START I>>>
I>>> t>>> SGF 4/2
RESET +
PROGRAM

SGR 6 / x SGF 5/4


TRIP I>>> TS2
4 1
SGB 1/3
SGF 4/5
SGR 7 / x
SGF 5/5
50 ms START Iο>
5 SS3
Io>
to>, ko
I0
SGR 8 / x
TRIP Iο>
SGF 1/6... 8
Io>>
SGR 9 / x
30 ms START Iο>> TRIP
SGB 1/4
to>>
SGR 10 / x RESET
TRIP Iο>>
SGB 1/5
Settings (main / 2nd)
SGB 1/7 Reset trip indicators and output relays
SGB 1/8 Reset trip indicators, output relays and
registers SPCJ 4D28

Fig. 4. Signal diagram of the combined overcurrent and earth-fault relay type SPAJ 144 C

The functions of the blocking and operation of the protection relay module. The functions of
signals are selected with the switches of the switches are explained in detail in the user´s
switchgroups SGB and SGR. The checksums of manual of the protection relay module SPCJ
the switchgroups are found in the setting menu 4D28.

Signal IL1, IL2, IL3 Phase currents


abbreviations I0 Neutral current
BS1 Blocking or control signal
SGF1..8 Selector switchgroups for relay functions
SGB1...3 Selector switchgroups for external control signals
SGR1...11 Selector switchgroups for output relays configuration
SS1...SS4, TS1...TS4 Output signals
TRIP Red operation indicator

7
Operation 3I >
A) The indicator TRIP is lit when one of the
indicators 2 I
protection stages operates. When the protection
f n = 50Hz I n = 1A 5A (I ) I L1 I L2 I L3 I 0 IRF
60Hz I n = 1A 5A (I o )
5 stage resets, the red indicator remains lit. The
TRIP indicator is configured with switchgroup
SPAJ 144 C SGF 5.
80...265V –
~ RESET
I >/I n
U aux
18...80V –
t > [s]
STEP
B) If the display is dark when one of the protec-
tion stages I>, I>>, I>>>,I0>, I0>> or ∆I>, oper-
k
SPCJ 4D28 I >> / I n
t >> [ s ]
REGISTERS OPER.IND.
I >>> /I n
t >>> [ s ]
ates, the faulty phase or the earth-fault is indi-
0 0 0 0 0
I 0 >/I n
cated with a yellow LED. If, for instance, the
1 I /I n 1 I > Start
2 I
L1

L2 /I n 2 I > Trip t 0 > [s ]


k0
TRIP indicator glows red, and at the same time
3 I L3 /I n 3 I >> Start
4 t (I > ) [ % ] 4 I >> Trip I 0 >> / I n
t 0 >> [s ]
are the indicators IL1 and IL2 lit, overcurrent has
5 t ( I >>) [ % ] 5 I >>> Start
6 I 0 /I n 6 I >>> Trip
∆ I > [%]
t ∆ > [s ]
occurred on phase L1 and L2.
7 t (I 0 > ) [ % ] 7 I 0 > Start PROGRAM
8 t ( I 0 >>) [ % ] 8 I 0 > Trip SGF
∆ I [%]
9
11 I max (15min) /I n
9 I 0 >> Start
0 I 0 >> Trip
SGB C) Besides operating as a code number at data
11∆ I > Trip
A CBFP
SGR presentation, the leftmost red digit in the dis-
TRIP
play serves as a visual operation indicator. An
0303A

0023A
RS 611 Ser.No. SPCJ 4D28
operation indicator is identified by the red digit
alone being lit. The following table explains the
code numbers used.

Indication Parameter V9 Symbol Explanation

1 1 I> START = Start of overcurrent stage I>


2 2 I> TRIP = Operation of overcurrent stage I>
3 3 I>> START = Start of overcurrent stage I>>
4 4 I>> TRIP = Operation of overcurrent I>>
5 5 I>>> START = Start of overcurrent stage I>>>
6 6 I>>> TRIP = Operation of overcurrent stage I>>>
6 7 I0> START = Start of earth-fault stage I0>
7 8 I0> TRIP = Operation of earth-fault stage I0>
8 9 I0>> START = Start of earth-fault stage I0>>
0 0 I0>> TRIP = Operation of earth-fault stage I0>>
11 11 ∆I> TRIP = Operation of phase discontinuity protection
stage ∆I>
A 12 CBFP = Operation of circuit breaker failure protection

D) The TRIP indications persist when the pro- SGF2/1 = 1 manual reset of I> start indication
tection stage returns to normal. The indicator is SGF2/2 = 1 manual reset of I>> start indication
reset by pushing the RESET/STEP push-but- SGF2/3 = 1 manual reset of I>>> start indication
ton. SGF2/4 = 1 manual reset of I0> start indication
SGF2/5 = 1 manual reset of I0>> start indication
Further, the indicators may be reset by applying
a control voltage to the external control input On delivery of the relay from the factory the
10-11, provided switch SGB1/7 is in position 1. switches SGF2/1…5 are preset at 0.

The basic protection relay functions are not E) Once the internal self-supervision system has
depending on whether the operation indicators detected a permanent relay fault the red IRF
are reset or not. The relay is always alert. indicator is lit and the output relay of the self-
supervision system operates. Further, in most
If a protection stage starts, but does not operate, fault situations, an autodiagnostic fault code is
because the energizing quantity falls below the shown in the display. The fault code is com-
set start current before the operate time circuit posed of a red figure 1 and a green code number
times out, the start indicators are normally which indicates the fault type. The code number
switched off automatically. When required, should always be recorded for maintenance pur-
manual resetting of the start indications is ob- poses.
tained through the following switch settings:

8
Power supply To be able to operate the relay needs a secured panel. The primary side of the power supply
and output relay auxiliary voltage supply. The power supply module is protected with a fuse, F1, located on
module module forms the voltages required by the pro- the PCB of the module.
tection relay module and the auxiliary relays.
The withdrawable power supply and output The power supply unit is a pulse-width modu-
relay module is located behind the system front lated (PWM) dc/dc converter with galvanically
panel, which is fixed by means of four cross- isolated primary and secondary sides. It forms
slotted screws. The power supply and output the dc secondary voltages required by the pro-
relay module contains the power supply unit, tection relay module; that is +24 V, ±12 V and
the output relays, the control circuits of the +8 V. The output voltages ±12 V and +24 V are
output relays and the electronic circuitry of the stabilized in the power supply module, while the
external control inputs. +5 V logic voltage required by the protection
relay module is stabilized in the protection relay
The power supply and output relay module can module.
be withdrawn after removing the system front

+8V Unstabilized logics


1 A slow voltage

Uaux +12V
Operation amplifier
80...265 V ac & dc voltage
-12V
18...80 V dc
Output relay coil
+24V voltage

Fig. 5.Voltage levels of the power supply unit

A green LED indicator Uaux on the system front Insulation test voltage between the primary and
panel is lit when the power supply module is in secondary side and protective earth
operation. The supervision of the voltages sup-
plying the electronics is integrated into the 2 kV, 50 Hz, 1 min
protection relay module. If a secondary voltage
differs too much from its rated value, a self- Voltage ranges of the power supply modules:
supervision alarm will be generated. An alarm - SPTU 240 R1 Uaux = 80...265 V dc/ac
signal is also issued when the power supply - SPTU 48 R1 Uaux = 18...80 V dc
module is withdrawn from the relay case, or on
loss of auxiliary supply. The SPTU 240 R1 module can be fed from an
ac source or a dc source. SPTU 48 R1 is designed
There are two versions of power supply and for dc supply only. The permitted auxiliary
output relay modules available. The secondary voltage range of the relay is marked on the relay
sides and the relay configurations are identical, system front panel.
but the input voltage ranges differ.

9
Technical data Energizing inputs
Rated current In 1A 5A
Thermal withstand capability
- continuously 4A 20 A
- for 10 s 25 A 100 A
- for 1 s 100 A 500 A
Dynamic current withstand, half-wave value 250 A 1250 A
Input impedance <100 mΩ <20 mΩ
Rated frequency fn, on request 50 Hz or 60 Hz

Output contact ratings


Trip contacts
Terminal numbers 65-66, 74-75
- rated voltage 250 V dc/ac
- continuous carry 5A
- make and carry for 0.5 s 30 A
- make and carry for 3.0 s 15 A
Breaking capacity for dc, when the trip circuit
time-constant L/R ≤ 40 ms, at 48/110/220 V dc 5 A/3 A/1 A
Contact material AgCdO2

Signal contacts
Terminals 70-71-72, 68-69, 77-78, 80-81
- rated voltage 250 V dc/ac
- continuous 5A
- make and carry for 0.5 s 10 A
- make and carry for 3.0 s 8A
Breaking capacity for dc, when the signal circuit
time-constant L/R ≤ 40 ms, at 48/110/220 V dc
signal circuit voltage 1 A/0.25 A/0.15 A
Contact material AgCdO2

External control inputs


Blocking, remote reset or remote setting input (BS1)
- terminal numbers 10-11
Control voltage level 18...265 V dc or 80...265 V ac
Control current of activated input 2…20 mA

Auxiliary power supply and output relay module


Voltage ranges of power supply modules:
SPTU 240R1:
- rated voltage Un = 110/120/230/240 V ac
Un = 110/125/220 V dc
- operative range U = 80...265 V ac/d
SPTU 48R1
- rated voltage Un = 24/48/60 V dc
- operative range U = 18...80 V dc
Power consumption, under quiescent/
operation conditions ~4W /~8W

Combined overcurrent and earth-fault relay module SPCJ 4D28


- see "Technical data" in the manual for the module. (1MRS 750093-MUM EN)

10
Data communication
Transmission mode Fibre-optic serial bus
Data code ASCII
Data transfer rate, selectable 4800 Bd or 9600 Bd
Electrical/optical bus connection module
powered from the host relay
- for plastic core cables SPA-ZC 21BB
- for glass fibre cables SPA-ZC 21 MM
Electrical/optical bus connection module
powered from the host relay or from an
external power source
- for plastic core cables SPA-ZC 17BB
- for glass fibre cables SPA-ZC 17 MM

Test voltages *)
Dielectric test voltage (IEC 255-5) 2 kV, 50 Hz, 1 min
Impulse test voltage (IEC 255-5) 5 kV, 1.2/50 µs, 0.5 J
Insulation resistance (IEC 255-5) >100 MΩ, 500 V dc

Disturbance tests *)
High-frequency (1 MHz) disturbance test (IEC 255-22-1)
- common mode 2.5 kV
- differential mode 1.0 kV
Electrostatic discharge test (IEC 255-22-2
and IEC 801-2), class III
- air discharge 8 kV
- contact discharge 6 kV
Fast (5/50 ns) transients
- IEC 255-22-4, class III
- IEC 801-4, level IV
- power supply inputs 4 kV
- other inputs 2 kV

Mechanical environmental test


Vibration test (IEC 255-21-1) class 1
Chock/bump test (IEC 255-21-2) class 1

Environmental conditions
Service temperature range -10...+55°C
Transport and storage temperature range (IEC 68-2-8) -40...+70°C
Temperature influence 0.2%/°C
Damp heat test (IEC 68-2-30) 93...95%, +55°C, 6 cycles
Degree of protection by enclosure of
flush mounting relay case (IEC 529) IP 54
Weight of fully equipped relay 3.5 kg

*) The insulation and disturbance tests do not apply to the serial port, which is used for the bus
connection module only.

11
Examples of The combined overcurrent and earth-fault relay tripping and signalling facilities. The overcur-
application SPAJ 144 C is intended to be used for the rent and earth-fault relays can also be used for
selective short-circuit and earth-fault protection other applications requiring single-, two-, or
of radial feeders in solidly earthed, resistance three-phase overcurrent protection. The com-
earthed or impedance earthed power systems. bined overcurrent and earth-fault relay also in-
The integrated protection relay includes an over- cludes a phase discontinuity stage and circuit
current unit and an earth-fault unit with flexible breaker failure protection.

I0>
SPAJ
TS 2
3I> 144C

3I>> Example 2
SS 1

TS 1

TS 2

Blocking Signal 3I>


SPAJ
3I>>
144C

I0 Example 1
Tripping Signal

Fig. 6. The combined overcurrent and earth-fault relay SPAJ 144 C used for substation protection.
For reasons of clarity remote control equipment and other protection relays have been omitted.

The short circuit protection is based on blockings can be extended to include the transformer
between successive protection stages. In such an feeding the busbar system.
arrangement the relay located nearest to the
fault gives, when starting, a blocking signal Current asymmetry, if any, does not have to be
backwards to the relay that is closest to the allowed for in the current settings, because due
object supplying the short-circuit current. If to the peak-to-peak measurement method em-
there is no blocking, the relay perceives the fault ployed by the SPACOM relays asymmetry does
as being within its own protection area and trips not affect the operation of the protection.
the circuit breaker. When required the blocking

12
feeder
Example 1.
Overcurrent and
earth-fault protec-
tion of an outgoing

L1

feeder
L2
L3 0
-

- I

I 0
+ +
Rx Tx

+ (~)
SPA-ZC_

U aux +
- (~)
Circuit breaker
alarm
Overcurrent

Blocking signal
failure protection

External to the infeeder


alarm
Earth-fault

control IRF SS1 TS1 SS2 TS2 SS3


input
SERIAL
1 23 4 5 6 7 8 9 25 26 27 11 10 63 62 61 70 71 72 77 78 74 75 80 81 PORT
65 66 68 69

5A
5A
1A
5A
1A

1A
+

5A
1A
~ + + + + +

+ -
U2

SPCJ 4D28 IRF


3I> Start SGR1 1 2 3 4 5 Σ=0
U3 5
Trip SGR2 1 2 3 4 Σ = 12
SGR3 1 2 3 4 5 Σ=0
3I>> Start
Trip SGR4 1 2 3 4 5 Σ = 12
3I>>> Start SGR5 1 2 3 4 5 Σ=1
Trip SGR6 1 2 3 4 5 Σ=0
∆I> SGR11 1 2 3 4 5
Trip Σ=8

Io> SGR7 1 2 3 4 5 Σ=0


Start
Trip SGR8 1 2 3 4 5 Σ = 24
SGR9 1 2 3 4 5 Σ=0
Io>> Start
Trip SGR10 1 2 3 4 5 Σ = 24
RESET I/O
SPAJ 144 C (1) (2) (4) (8) (16) U1

13
Fig. 7. The combined overcurrent and earth-fault relay SPAJ 144 C used for protecting an outgoing
Overcurrent The overcurrent relay module SPCJ 4D28 in- The operation of the low-set stage of the over-
protection cludes three overcurrent stages. By using all current relay can be based on definite time
three stages and giving each overcurrent stage its characteristic or inverse time characteristic. The
own operate value and operate time good selec- operation characteristic is selected with the SGF1
tivity with short operate times can be obtained. switchgroup. When definite time characteristic
Normally, two-stage overcurrent protection is has been selected, the operate time of the relay is
sufficient. However, when the short-circuit current independent. At inverse time character-
protection is based on blockings between the istic, on the contrary, the operate time is a
successive protection stages, the high-set stage function of the fault current level; the greater the
I>>> can be used for blocking purpose and so fault current, the shorter the operate time. There-
the blocking level can be freely selected. This fore, the operate time is short at close faults.
means that when starting, the I>>> stage of the
overcurrent relay module of the feeder provides In this example the definite time characteristic is
a blocking signal to the I>> stage of the overcur- used. Definite time characteristic can be used to
rent relay module of the infeeder. When no obtain constant time grading steps over a wide
blocking signal is received, the infeeder overcur- current range and it offers faster tripping times
rent relay module perceives the fault as being than inverse time protection at low multiples of
within its own protection zone and trips the current settings.
circuit breaker. When required, the blocking
functions can be extended to include the relay of
the infeeder.

Earth-fault protection The earth-fault relay provides two-stage earth- The earth-fault relay is provided with two stages,
fault protection. The neutral current can be a high-set stage and a low-set stage. The low-set
measured either via a set of three phase current stage satisfies the sensitivity requirements of the
transformers in a residual connection or a core- protection and the high-set stage the operate
balance current transformer. The above applica- time requirements. The two-stage relay also
tion can be used in cases with high earth-fault enables selective protection in such cases, where
currents, moderate sensitivity requirements and the fault current generated by the feeder during
small current transformer ratios. In solidely a fault somewhere else in the network exceeds
earthed networks or networks earthed over a the set start current of the low-set stage but not
low-resistance resistor or low-impedance coil, that of the high-set stage. Definite time opera-
the earth-fault current is high enough to guaran- tion has been used in this example, but inverse
tee sufficient accuracy of the residual current time characteristic can be selected for the stage
connection for measuring the earth-fault cur- I0> as well.
rent. The accuracy of the residual current con-
nection depends on electrical similarity of the The operation of a non-directional neutral over-
current transformers. To secure selectivity and current relay can be stabilised with a residual
stability at high fault current levels, current voltage relay. During a no-fault situation the
transformers with high accuracy limit factors are residual voltage relay provides a blocking signal
recommended, especially, if the high-set stage is which is routed to the non-directional earth-
to operate instantaneously. fault relay. At an earthfault the residual voltage
relay starts, the blocking signal disappears and
the neutral overcurrent relays are allowed to
operate.

Earth-fault current In figure 2, a core-balance current transformer is The advantage with the core-balance current
measured with a core- used instead of the residual current connection. transformer is that only one CT core is used in
balance transformer In isolated neutral networks and in networks place of three phase current transformers. In this
earthed over a resistor the core-balance current way the CTmagnetizing current at relay opera-
transformer is preferred to ensure stable and tion is reduced by approximately three-to-one,
sensitive earth-fault protection. At an earth- an important consideration in sensitive earth-
fault situation, the healthy network supplies fault protection. Furthermore the number of
fault current to the faulty feeder. Therefore, secondary turns does not need to be related to
non-directional earth-fault relays like SPAJ 144 the cable rated current because no secondary
C are best suited for the earth-fault protection of current would flow under normal balanced con-
networks with rather short feeders, for instance, ditions. This allows the CT to be choosen such
motor and transformer feeders of industrial as to optimize the effective primary pick up
switchgear. current.

14
Phase discontinuity The phase discontinuity stage ∆I> has a tripping disconnected. The phase discontinuity protec-
protection function when used for protecting overhead tion is of special importance in overhead lines
lines. In cable networks, where phase disconti- and in overhead lines with isolated phase wires.
nuity does not cause dangerous situations, the
∆I stage can be given an alarming function. The The start setting value of the stage ∆I> is the
phase discontinuity protection can be used irre- difference between the minimum and the maxi-
spective of earthing principle. mum phase current measured, expressed as per-
centage (∆I=(Imax-Imin)/Imax x 100%). The set
Health and safety is an important consideration start value of the stage depends on the normal
for protecting against phase discontinuity faults. unbalance in the network. This has to be consid-
An example can be a broken phase wire, that has ered when selecting the setting value. Since this
fallen down on such a place that the resistance type of protection cannot be graded with other
towards earth is very high, for example, a dry systems, it is confined to a supplementary role
road. the earth-fault protection alone is not able by the use of a long time delay, adjustable from
to detect the fault and thus the voltage is not 1s up to 300s.

Configuration In the case described in example 1 the switches


of feeder protection relay SPAJ 144 C can be
configured as follows:

Switch- Serial comm. Checksum Operation


group parameter

SGF1 S53 000 Definite time operation


SGF2 S54 000 All stages used, automatic resetting of start indicators
SGF3 S55 000 ∆I stage operates, resetting time of I> & I0> = 40 ms
SGF4 S56 016 No self-holding for TS signals, the TS2 signal starts
the circuit-beaker failure protection
SGF5 S57 008 Signal TS2 controls the TRIP LED
SGF6 S58 000 Not used in SPAJ 144 C
SGF7 S59 000 Not used in SPAJ 144 C
SGF8 S60 000 Not used in SPAJ 144 C

SGB1 S61 000 No blocking/control by the BS1 signal


SGB2 S62 000 Not used in SPAJ 144 C
SGB3 S63 000 Not used in SPAJ 144 C

SGR1 S64 000 I> start not linked to the output contacts
SGR2 S65 012 I> trip linked to contacts TS2 and SS2
SGR3 S66 000 I>> start not linked to the output contacts
SGR4 S67 012 I>> trip linked to contacts TS2 and SS2
SGR5 S68 001 I>>> start linked to alarm contact SS1
SGR6 S69 000 I>>> trip not linked to output contacts
SGR7 S70 000 I0> start not linked to output contacts
SGR8 S71 024 I0> trip linked to contacts TS2 and SS3
SGR9 S72 000 I0>> start not linked to output contacts
SGR10 S73 024 I0>> trip linked to contacts TS2 and SS3
SGR11 S74 008 ∆I> trip linked to output contacts TS2

15
Fig. 8. The combined overcurrent and earth-fault relay SPAJ 144 C used for protecting an infeeder
0 -
L1
from the relays of the

L2
- I
Incoming blockings

L3
outgoing feeders

I 0
Rx Tx
+ +
Overcurret

Earth-fault

SPA-ZC_
alarm

alarm
+ (~)
U aux
- (~)
+
IRF SS1 TS1 SS2 TS2 SS3
- SERIAL
PORT
1 23 4 5 6 7 8 9 25 26 27 11 10 63 62 61 70 71 72 77 78 74 75 80 81 65 66 68 69
5A
1A

5A
1A

5A
1A

5A
1A

~ + + + + + +
+ -
U2
SPCJ 4D28 IRF
U3 3I> Start SGR1 1 2 3 4 5 Σ=0
Trip SGR2 1 2 3 4 5 Σ = 12
3I>> Start SGR3 1 2 3 4 5 Σ=0
Trip SGR4 1 2 3 4 5 Σ = 12
3I>>> Start SGR5 1 2 3 4 5 Σ=0
Trip SGR6 1 2 3 4 5 Σ = 12
∆I>
Trip SGR11 1 2 3 4 5 Σ=0
Io> Start SGR7 1 2 3 4 5 Σ=0
Trip SGR8 1 2 3 4 5 Σ = 24
Io>> Start SGR9 1 2 3 4 5 Σ=0
Trip SGR10 1 2 3 4 5 Σ = 24
(1) (2) (4) (8) (16) (1)
RESET I/O
SPAJ 144 C U1
tion of an infeeder
earth-fault protec-
Overcurrent and
Example 2.

16
Overcurrent In the application example 2, the stages I> and time settings on the outgoing feeders do not
protection I>>> of the overcurrent relay module SPCJ affect the operation, because each relay has a
4D28 operate as back-up protection for the separate CBFP function. The disadvantage of
outgoing feeders and the busbar system and the the CBFP function is that it requires external
I>> stage is used for the short-circuit protection wiring from the protection relays of the outgo-
of the busbar system. In this way the back-up ing feeders to the relay of the infeeder.
protection has two stages and the current set-
tings can be the same as those used on the If an operate time of less than 100 ms is required
outgoing feeders. The set operate time of a back- on the busbar protection system and non-selec-
up protection stage is calculated from; the fault tive operation can be allowed, one possibility is
current interrupting time of the circuit breaker to use the second high-set stage I>>> with an
(~150ms) plus a safety margin (~100ms), plus instantaneous operate time. Then the start cur-
the operate time of the protection relay of the rent value shall be set to such a level that the fault
outgoing feeder. most probably is within the busbar system. The
second high-set stage I>>> can be given a set
If a fault occurs on the feeder, the overcurrent value up to 40 times the rated current. The
relay module of the outgoing feeder provides a advantage is that a fault on the busbar system
blocking signal to the overcurrent relay module does not cause serious damage due to the instan-
of the infeeder. Should the fault occur on the taneous trip of the busbar system. On the other
busbar system no blocking signal will be issued hand, it is difficult to find the right setting value
and the I>> stage of the overcurrent module of since a close-up fault on a feeder can cause the
the infeeder provides a trip signal to the infeeder circuit breaker of the infeed to trip instead of the
circuit breaker. Thus it is possible to use a feeder protection relay.
minimum operate time of 100 ms at busbar
system faults. The blocking arrangement can be In a double busbar system where the busbar
extended to include the HV side overcurrent circuit breaker is closed and two main trans-
relay of the main transformer. formers are connected in parallel, the breaking
capacity of the circuit breakers of the feeders
Busbar protection and the co-operation of the may not be sufficient and so tripping should be
relays between the different protection levels carried out by the circuit breaker of the infeeder.
can be arranged in many ways and varies quite a Then the current setting of the second high-set
lot between different applications. Below a few stage I>>> is set to the the same level as the
examles of how the application described can be breaking capacity of the feeders. This means
changed using some of the features of the relay that if the fault current exceeds the breaking
SPAJ 144 C. capacity if the outgoing feeders the tripping is
performed by the protection of the infeeder. An
The back-up protection can also be made with external control signal can be used for shifting to
the circuit breaker failure protection function of the second settings when the transformers are
the protection relay of the outgoing feeder. used in parallel operation. Then the stage I>>>
Then a faster back-up function can be achived as is active in parallel operation and inhibited or
since the safety margin can be omitted when has other settings when parallel operation not is
setting the CBFP time. Furthermore, different used.

Eart-fault protection The earth-fault stages can be used in different In networks with arc supression coil compen-
ways dependig of the earthing principle used. In sated neutral point the earth-fault stages can be
this example with a low-resistance earthed net- used to protect the coil. Should the coil not be
work the two stages are used as back-up earth- dimensioned for continuous service, the protec-
fault protection and earth-fault protection of tion can be designed so that the low-set stage I0>
the busbar system. The low-set stage of the is alarming and stage I0>> is tripping.
earth-fault protection serves as back-up protec-
tion for the outgoing feeders and the high-set
stage as the primary earth-fault protection of the
busbar system.

17
Configuration In the case described in example 2 the switches
of feeder protection relay SPAJ 144 C can be
configured as follows:

Switch- Serial comm. Checksum Operation


group parameter

SGF1 S53 000 Definite time operation


SGF2 S54 000 Automatic resetting of start indicators
SGF3 S55 000 Stage ∆I operates, resetting time of I> & I0> = 40 ms
SGF4 S56 016 No self-holding or CBFP
SGF5 S57 008 Signal TS2 controls the TRIP LED

SGB1 S61 002 The BS1 signal blocks stage I>>

SGR1 S64 000 I> start not linked to the output contacts
SGR2 S65 012 I> trip linked to contacts TS2 and SS2
SGR3 S66 000 I>> start not linked to the output contacts
SGR4 S67 012 I>> trip linked to contacts TS2 and SS2
SGR5 S68 000 I>>> start not linked to the output contacts
SGR6 S69 012 I>>> trip not linked to output contacts
SGR7 S70 000 I0> start not linked to output contacts
SGR8 S71 024 I0> trip linked to contacts TS2 and SS3
SGR9 S72 000 I0>> start not linked to output contacts
SGR10 S73 024 I0>> trip linked to contacts TS2 and SS3
SGR11 S74 000 ∆I>trip not linked to output contacts

Commissioning When commissioning a SPAJ 144 C all settings tage of using a PC is that the settings are more
can be entered either via the push buttons on the easily entered and the final settings can be saved
Settings front panel or via the serial communication to a file on a disk for future reference, or a
using a PC program, e.g. SMS 010. An advan- permanent record can be printed on paper.

Inspection Examine the relay case carefully to see that no relay diagram. Ensure that the case earthing
damage has occurred since installation. Check connection (terminal 63) is used for connecting
that the external wiring is correct to the relevant the relay to the local earth bar.

Wiring In the trip test mode the outputs can be acti- display (register 0) of the relay module to receive
vated one by one to test the circuit breaker the blocking signal that it arrives properly. When
operation etc. The external wiring of the block- the I>>> stage of the overcurrent module of the
ing circuits is also easily tested. To test the outgoing feeder is started (signal SS1), the right-
blocking circuit, the stage of the relay module most digit of register 0 will be 1 (= blocking
issuing the blocking signal is activated (see sec- signal BS1 is activated) on the relay of the
tion "General characteristics of D-type SPC infeeder.
relay modules") and then it is checked from the

18
Testing The relay should be subjected to regular tests in can be extended to include additional setting
accordance with national regulations and in- values.
Periodic structions. The manufacturer recommends an
maintenance tests interval of five years between the tests. As the settings of the relay modules vary in
different applications, these instructions present
The test should be carried out as a primary test, the general features of the test procedure. Ordi-
which includes the whole protection arrange- nary current and voltage supply units and in-
ment from the instrument transformers to the struments for measuring current, voltage and
circuit breakers. time can be used for the tests.

The test can also be carried out as a secondary During the test procedure the relay records
injection test. Then the relay has to be discon- currents, voltages and relay operations. If the
nected during the test procedure. However, it is recorded data are used for the collection of
recommended to check the condition of the information for longer time periods (for exam-
signal and trip circuits as well. ple, AR counters), these registers should be read
before the test is started. After the test the
Note! registers are reset and, if required, the readings
Make sure that the secondary circuits of the of the AR counters can be restored.
current transformers under no condition open
or are open, when the relay is disconnected and The relay settings may have to be changed
during the test procedure. during testing. A PC program is recommended
to be used to read the relay settings before
The test is recommended to be carried out using starting the test to make sure that the original
the normal setting values of the relay and the settings are being restored when the test has
energizing inputs used. When required, the test been completed.

Testing of over- The protection stages used (I>, I>>, I>>>, I0>, - start time
current and earth- I0>> and ∆I>) are tested as follows: - trip time
fault relay module - trip indication, output relay operation and
SPCJ 4D28 - start value (the high-set stages for all three signalling
phases) - circuit breaker failure protection (CBFP)
General

Start value Test the start value by raising the current, start- When multi-stage protection relays are tested,
ing from zero, until the relay starts. Record the it is often necessary to inhibit or delay the
current value required for starting. The value operation of the low-set stages, to be able to test
should be within the permitted tolerances. the operation of a high-set stage. In such a case
it is recommended to start from the highest stage
To test the resetting value, if required, raise the and then proceed to the lower stages. The ad-
current until the relay starts and then reduce the vantage of this method is that the original set-
voltage, until the relay resets. tings of the stages really are restored, because
otherwise the test cannot be carried out success-
fully.

Start and trip times Switch a current 2...2.5 times the setting value When inverse times are measured the measure-
of the protection stage to the relay. Measure the ment can be made with different supply cur-
operate time, i.e. the time from the closing of the rents, for example, 2 times and 10 times the
switch until the relay operates. The operate time setting value, if required. The resetting time can
should be within the permitted tolerances, ex- be measured from opening of the current switch
cept when the injected current is below 2 times until resetting of the relay.
the setting value. In such a case the protective
algorithm adds about 20 ms to the operate
times.

19
Maintenance When the feeder protection relay is used under If the relay malfunctions or the operating values
and repairs the conditions specified in "Technical data", the differ from those specified, the relay should be
relay requires practically no maintenance. The overhauled. Minor measures can be taken by
feeder protection includes no parts or compo- the customer but any major repair involving the
nents that are sensitive to physical or electrical electronics has to be carried out by the manufac-
wear under normal operating conditions. turer. Please contact the manufacturer or his
nearest representative for further information
Should the temperature and humidity at the about checking, overhaul and recalibration of
operating site differ from the values specified, or the relay.
the atmosphere contain chemically active gases
or dust, the relay should be visually inspected in The protection relay contains circuits sensitive
association with the secondary testing of the to electrostatic discharge. If you have to with-
relay. This visual inspection should focus on: draw a relay module, ensure that you are at the
same potential as the module, for instance, by
- Signs of mechanical damage to relay case and touching the case.
terminals
- Collection of dust inside the relay case; remove Note!
with compressed air Protective relays are measuring instruments and
- Signs of corrosion on terminals, case or inside should be handled with care and protected
the relay against moisture and mechanical stress, espe-
cially during transport.

Spare parts Three-phase overcurrent and earth-faultmodule SPCJ 4D28

Power supply and output relay module


Uaux = 80...265 V ac/dc SPTU 240 R1
Uaux = 18...80 V dc SPTU 48 R1

20
Dimensions for The relay is housed in a normally flush-mounted panel surface, when the relay is panel mounted.
mounting case. The case is made of an extruded, beige The relay case is complete with a hinged gasketed,
aluminium profile. When semi-flush mounting clear, UV-stabilized polycarbonate cover with a
is required, raisings frames can be used to reduce sealable fastening screw. The degree of protec-
the mounting depth. Three types of raising tion by enclosure of the cover is IP 54 as well.
frames are available:
SPA-ZX 111, 40 mm A terminal strip and two multi-pole connectors
SPA-ZX 112, 80 mm are mounted on the back of the relay case to
SPA-ZX 113, 120 mm facilitate input and output connections. To
each heavy-duty terminal, i.e. measuring input,
For surface mounting a case SPA-ZX 110 is power supply or trip output, one 6 mm2, one
available. 4 mm2 or one or two 2.5 mm2 wires can be
connected. No terminal lugs are needed. The
A cast aluminium alloy mounting collar with a signalling outputs are available on a six-pole
rubber gasket provides a degree of protection by detachable connector and the serial bus connec-
enclosure to IP 54 between the relay case and the tion is using a 9-pin D-type connnector.

250
142
216 34
30 186

136
162

129 ±1 a b
139 ±1

Panel cut-out

Raising frame a b
SPA-ZX 111 176 74
SPA-ZX 112 136 114
SPA-ZX 113 96 154

Order information Example


1. Quantity and type designation 15 relays type SPAJ 144 C
2. Rated frequency fn = 50 Hz
3. Auxiliary voltage Uaux = 110 V dc
4. Accessories 15 bus connection modules SPA-ZC17 MM
2 fibre optical cables SPA-ZF MM 100
14 fibre optical cables SPA-ZF MM 5
5. Special requirements —

21
22
23
Meter & Load
Information Management
Management
Services

Network
Management

Station
Automation

Communications

Panorama is the standard for a comprehensive range


of integrated solutions for efficient and reliable
management of power networks. Using innovative
information technology, Panorama delivers total control
of the power process, from generation to consumption.
The Panorama standard covers six application areas,
each offering specific solutions.

1MRS 750043-MUM EN

ABB Transmit Oy
Relays and Network Control
P.O.Box 699
FIN-65101 VAASA
Finland
Tel. +358 10 224 000
Fax. +358 10 224 1094

You might also like