TANK INSPECTION REPORT
CUSTOMER NAME JAKSON KEPL/F/TIR/01
WO NO 22/5987
QUANTITY 02 no's.
DATE:17/02/2023
PRODUCT NAME 50KVA TRANSFORMER TANK
Sl.No. Tank Critical Dimension Tol. Measured Result
1 Transformer Base Chennel
a) Tank base channel - L-590 x W-100 x H-50 ±1.0mm 591*100*50 Within Limit
b) Wheel mounting pitch to pitch-410*410 ±1.0mm 410*410 Within Limit

2 Tank Over all Dimension


a) Tank inside Length-L-665 x W-280 x H-635 ±1.0mm 680*290*680 Within Limit
b) Tank base sheet thickness- 4 ±0.2mm 3.99 Within Limit
c)tank side sheet thickness-3 ±0.2mm 3.05 Within Limit

3 LV Chamber
a) Length-390x Width-65xHeight139 ±1.0mm 391*65*140 Within Limit
b) LV Terminal plate- L-470 x W-216 x Tk-6 ±1.0mm 471*215*6 Within Limit
c) LV Terminal plate hole Ø-28, Qty-4 No's & pitch-92 ±1.0mm Ø-28,4no's&92 Within Limit
d) LV Cable box Length-320 x Width-470 x Height-420 ±1.0mm 320*471*421 Within Limit
e) LV Cable box gland plate - L- 470 x W-318 x T-4 ±1.0mm 471*319*4 Within Limit

4 HV Chamber
a) Length- 384x Width-100 x Height-130 ±1.0mm 385*100*131 Within Limit
b) HV Terminal plate Length-470 x Width-216 x Thck-6 ±1.0mm 471*217*6 Within Limit
c) HV Terminal plate hole-ɸ 38 and pitch 130 ±1.0mm ɸ 38 & 130 Within Limit
d) HV Cable box Length- x Width- x Height- ±1.0mm 371*471*421 Within Limit
e) HV Cable box gland plate - L-470 x W-368 x T-3 ±1.0mm 470*368*3 Within Limit

5 Lifter Width 110 x Height135 x Thck 12 ±1.0mm 111*135*12 Within Limit

6 Top Cover
a) Length-776 x Width-386 x Thck-4 ±1.0mm 777*387*4 Within Limit
b) Filling & darin Boss ɸ-3/4'' ±1.0mm ɸ-3/4'' Within Limit

7 Conservator
a) Length-500 x ID-200 x Thck-2 ±1.0mm 501*ɸ201*2 Within Limit
b) Conservator POG Plate OD-264 & Thck-4 ±1.0mm 265*4 Within Limit
c) Conservator closing plate-ɸ205& 2 thick ±1.0mm ɸ206*2 Within Limit

8 PAINT INSPECTION
a) Paint Shade RAL 5012 RAL 5012 Ok
b) Paint Thickness Min 100 100-125µ Ok
c) Finishing Painting Painting Ok

9 Pressure Test
Tank subjected to a pressure of 2.5 kg/cm² over ambient
2.5 kg/cm² No leakages found Ok
pressure

10 Visual check for workmanship Found ok

NOTE: All dimensions are in "mm"


Accepted P Pavan
Rejected Checked By
KEPL/F/TIR/01 REV-00 Date:01-01-2018
KALPA ELECTRIKAL PVT,LTD.
H.O : Rajajinagar,Bangalore.
TRANFORMER TANK INSPECTION REPORT Doc No:KEPL/F/TIR/01
(Pressure Test & Vacuum Test) Rev No:00
Date:01-01-2018
CUSTOMER NAME JAKSON
WO No 22/5987
DRAWING No.: KE-3PH-TK-56-22
VACUUM PRESSURE TEST AIR PRESSURE TEST
DATE: 17/2/23 DATE: 17/2/23
DURATION: 60 Mnts DURATION: 60 Mnts
VACCUM APPLIED: 250MM MERCURY PRESSURE APPLIED: 0.35kg/cm²
STARTING TIME: 10.00am STARTING TIME: 11.15am
ENDING TIME: 11.00am
DEFLECT
ENDING TIME: 12.15pm
DIMENSIONS(mm) ION DIMENSIONS(mm)
1 2 AFTER 1
TEST POINT LOCATION RELEASI TEST POINT LOCATION
INITIAL AFTER NG AIR INITIAL
READING READING PRESSUR READING
E
A1 168.51 169.72 1.21 A1 169.92
HV SIDE HV SIDE
A2 169.83 170.8 0.97 A2 170.83

A1 129.35 130.28 0.93 A1 130.07


LV SIDE LV SIDE
A2 130.07 131.31 1.24 A2 131.21

A1 144.46 144.97 0.51 A1 145.16


LSH LSH
A2 144.86 145.12 0.26 A2 144.86

Note: All dimensions are in'mm' PAVAN


Result: Pass Tested By

KEPL/F/TIR/01 REV NO -00 Date:01/01/2018


LTD.
Doc No:KEPL/F/TIR/01
Rev No:00
Date:01-01-2018

SURE TEST
17/2/23
60 Mnts
0.35kg/cm²
11.15am
12.15pm DEFLECT
DIMENSIONS(mm) ION
2 AFTER
RELEASI
AFTER NG AIR
READING PRESSUR
E
168.12 1.8
169.29 1.54
129.41 0.66
130.02 1.19
144.95 0.21
144.02 0.84