HHP Natural Gas Engine & Generator Controls

MODULE 4

Genset Controls
Refresh: Genset Layout
GIB

GIB (v.2) Contents:


• A/C MCB’s & Contactors
• VDC Interfaces & Controls
• Engine Control (CM700)
• Genset Control (PCC 3.3)
• VDC Primary Supply
• Customer Connections
• HMI (HMI320 & HMI114)
• Customer I/O Modules
(AUX101’s #3 & #4)
• Alternator Mains Decoupling
Relay (Optional)

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 2
GIB Components
External
HMI320

HMI114

VDC
Isolator

E-Stop

VAC
Isolator Harness
Connections

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 3
GIB Components
Internal (Doors Removed) Service
VDC Termination Rail Rail
VAC Termination Rail
PCC3300

Rail for
Optional Customer
Mains Termination
Decoupling Rail
Relay

VAC Aux Termination Rail


CM700
AUX101 AUX101 (ECM)
(3) (4)

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 4
GIB Components
VAC Termination Rail

VAC Supply from VAC Isolator

37

38
39

42

43

44
31
32
33
34
35
36

40
41

45
46
47
48
49
50
7 8

Battery
1 2 3 4 5 6 PSU Check
Module KM’s
VDC Source
MCB’s Management &
Isolator

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 5
GIB Components
VAC Termination Rail – MCB’s

COMPONENT MODULE RATING

Contactor 12A @ 440VAC


MCB1
- MCB5 Class 10 for 3Ph Motors
Circuit Breaker
Bus Bar input from VAC Isolator Set Range: 3 to 12A

Contactor 32A @ 440VAC


MCB6 Class 10 for 1Ph Motors
Circuit Breaker
Set Range: 4.5 - 18A

MCB7 Circuit Breaker 3 Pole, 2A

MCB8 Circuit Breaker 6A

1 2 3 4 5 6 7 8

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 6
GIB Components
VAC Termination Rail – MCB’s
Contactor + CB Assemblies (MCB’s 1 Æ 6)

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 7
GIB Components
VAC Termination Rail – MCB’s
Contactor + CB Assemblies (MCB’s 1 Æ 6)
- Continued -

CB Trip Position

CB Off Position CB On Position

CB Reset Position
CB Trip Test

Thermal / Magnetic
Trip Settings

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 8
GIB Components
VAC Termination Rail – MCB’s
Contactor + CB Assemblies (MCB’s 1 Æ 6)
- Continued -
L3
Source L2
L1

DC
A/C

N.O. Auxiliary
N.C. Contacts
Contactor
Source +
Controls Controlled
Ground -

L1
Output L2
CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 9
L3
GIB Components
Refresh: VAC Termination Rail

VAC Supply from VAC Isolator

37

38
39

42

43

44
31
32
33
34
35
36

40
41

45
46
47
48
49
50
7 8

Battery
1 2 3 4 5 6 PSU Check
Module KM’s
VDC Source
MCB’s Management &
Isolator

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 10
GIB Components
VAC Termination Rail – VDC Source
Genset & Engine Control Systems

VAC Isolator Input Battery


380Æ500VAC 3Ph Check
50/60 Hz Module

Diagnostics
PSU:
Output: 20A
24VDC 480W

VDC + Æ VDC Iso.

VDC +
VDC Back-up
Batteries
CAUTION: This system is not
intended to be the VDC source (2 x 12VDC in Series)
to the Genset electronic starter
motors.
CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 11
MCB7
VAC Supply

L1 L2 L3
GIB Components Battery
VAC Termination Rail – VDC Source Check
Genset & Engine Control Systems Module

Batt. In Out

+ + +
PSU
DC
- - -
A/C + + - -
To Diagnostic
Relay Contact
(Not Used)

VDC Source
(Not Backed Up)
(Not Used)
SDC Iso. Switch
VDC Source
(Backed Up)

+ - + - + - + -

Backup Backup
Battery #1 Battery #2

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 12
GIB Components
VDC Source Backup Battery Location

• Cover

• Battery Pack (x2)

• Genset Skid

VDC Source Backup w/ Cover On


DO NOT use as a step!

VDC Source Backup w/ Cover On


Side Profile

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 13
GIB Components
VAC Termination Rail – VDC Source (Backup Batteries)
Genset & Engine Control Systems

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 14
GIB Components
VAC Termination Rail – KM’s
COMPONENT RATING

Input (max): 24VDC±20% 6.6mA 160mW


VDC Response / Drop: 15.4V / 6.5V
KM31 - KM36,
IDC Pickup / Drop: 4mA / 1.2mA
KM39 - KM41,
KM45 - KM50
Switch (max): 250VAC, 6A Input from
Switch (min): 12V, 100mA VAC Isolator
Input (max): 24VDC±10% 16mA 400mW
VDC Response / Drop: 16.8V / 2.4V
KM37 - KM38,
KM42 - KM44
Switch (max): 250VAC, 10A
Switch (min): 10V, 100mA

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 15
GIB Components
VAC Termination Rail – KM’s
KM’s 31 – 36, 39 – 41, 45 - 50

Green LED
On = Coil Energized

Relay
(Pluggable)

Relay
Base

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 16
GIB Components
VAC Termination Rail – KM’s
KM’s 37, 38, 42 - 44

Relay
(Pluggable)

Relay
Base

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 17
GIB Components
VDC Termination Rail

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 18
GIB Components
VDC Termination Rail
100’s

4 Wire Connections
COMPONENT RATING per Terminal
Surge Voltage (Max): (excluding Jumper Bar)
- IEC: 8kV
Nominal Voltage (Max):
- IEC = 800V
100's
- UL / CSA = 600V
(all)
Nominal Current (Max):
- IEC / CSA = 27A
- UL = 25A
CSA / UL: AWG 30 - AWG 12

Insert Jumper
Bar Here

Jumper Bar Jumper Bar


N1 N2
CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 19
GIB Components
VDC Termination Rail
Fuses (F)
COMPONENT RATING
Surge Voltage (Max):
- IEC: 6kV
Nominal Voltage (Max):
- IEC = 400V
Fuse Block's
- UL / CSA = 300V
(all)
Nominal Current (Max):
- IEC / UL = 30A
VDC+ Red LED - CSA = 25A
Jumper Bar CSA / UL: AWG 22 - AWG 10
VDC Isolator On = Open Fuse
F2 – F15

Spade Type
Fuses
F1
F2
F3
F4
F5
F6
F7
F8
F9
F10
F11
F12
F13
F14
F15

VDC+ out
Control Circuit

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 20
GIB Components
VDC Termination Rail
S’s

S3

S5

S7

S11

S13

S19

S21

S23
S4

S6

S8

S10

S12

S20

S24
S1

S2

S9

S14

S15

S16

S17

S18

S22
CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 21
GIB Components
VDC Termination Rail
CM’s

Resistor

COMPONENT RATING
Resistor 120Ω, 0.33W

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 22
GIB Components
VDC Termination Rail
KM’s

KM15
KM22
KM16

KM12

KM14

KM17

KM18

KM19

KM11
KM20

KM21

KM13
CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 23
GIB Components
VDC Termination Rail
KM11 & KM13

COMPONENT RATING
Coil: 24VDC, 69mA, 350Ω
Contact (pf = 1): 110VAC 10A, 24VDC 10A
- Carry Current: 10A
- Switching Voltage (Max): 250VAC, 125VDC
Relay - Switching Current (Max): 10A
KM11 - Switching Power (Max): 1100VA, 240W
KM13 Contact (pf = 0.4): 110VAC 7.5A, 24VDC 5A
- Carry Current: 10A
- Switching Voltage (Max): 250VAC, 125VDC
- Switching Current (Max): 10A
- Switching Power (Max): 825VA, 120W

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 24
GIB Components
VAC AUX Termination Rail

V4 – V3

V8 – V7

V12 – V11
T4 – T3
T6 – T5
V2 – V1

V6 – V5

V10 – V9
T2 – T1
AC1 through AC25

VAC
Isolator

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 25
GIB Components
VAC AUX Termination Rail
AC1 through AC25

COMPONENT RATING
Surge Voltage (kV) (Max):
- IEC: 8
Nominal Voltage (V) (Max):
- IEC / UL / CSA = 800 / 600 / 600
Terminal Block Nominal Current (A) (Max):
- IEC / UL / CSA = 24 / 25 / 27
Wire Size (AWG) (Min - Max) :
- CSA: 22 - 10
- UL: 30 - 12

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 26
GIB Components
VAC AUX Termination Rail
T1 through T6, V1 through V12

Odd #
Connections

Even #
Connections

COMPONENT RATING
Surge Voltage (kV) (Max):
- IEC: 6
Nominal Voltage (V) (Max):
- IEC / UL / CSA = 500 / 300 / 300
Terminal Block Nominal Current (A) (Max):
- IEC / UL / CSA = 20 / 10 / 10
Wire Size (AWG) (Min - Max) :
- CSA: 26 - 12
- UL: 30 - 12

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 27
GIB Components
VAC AUX Termination Rail
VAC Isolator

VAC Supply
To GIB

COMPONENT RATING
Nominal Voltage (V) (Max):
- IEC = 440
VAC Nominal Current (A) (Max):
Isolator Isolation Switch - IEC / UL & CSA = 100 / 100
Motor Load Rating (HP) (Max):
- UL & CSA (240V): 25
- UL & CSA (480V): 40
VAC Supply
From Customer
380 – 440VAC
50 Hz 3Ph

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 28
GIB Components
Customer Terminal Rail

Genset
Connections

M1 through M4
(paired)
C93 through C100

C301 through C304


110 / 240 VAC
Euro / US Socket
Customer
Connections

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 29
GIB Components
Customer Terminal Rail
C1 through C76

Odd #
Connections

Even #
Jumper Bar Connections
N3

Jumper Bar
Connection

C1 through C76
(paired)

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 30
GIB Components
Customer Terminal Rail
C77 through C92
Jumper Bar

Jumper Bar
Connection

COMPONENT RATING
Surge Voltage (Max):
- IEC: 8kV
Nominal Voltage (Max):
- IEC = 800V
- UL / CSA = 600V
Terminal Block
Nominal Current (Max):
- IEC = 24A
- CSA = 27A
- UL = 25A
UL: AWG 30 - AWG 12

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 31
GIB Components
Customer Terminal Rail
C93 through C100

Odd #
Connections
Jumper Bar
Even #
Connections

Jumper Bar
Connection

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 32
GIB Components
Customer Terminal Rail
R1 through R18, M1 through M4
Jumper Bar
Connection

Resistor

R1 through R18 COMPONENT RATING


Resistor 120Ω, 0.33W

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 33
GIB Components
Customer Terminal Rail
Euro / US Socket

COMPONENT RATING
Socket 250 / 125 VAC - 2P+E 10 / 15A

Euro / US Socket
110 / 240 VAC

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 34
GIB Components
Customer Terminal Rail
C301 through C304

Odd #
Connections
Jumper Bar
Even #
Connections

Jumper Bar
Connection

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 35
GIB Components
Customer Terminal Rail
C322 through C327 (CT Shorting)

Slider
(Engage in jumper to
connect with locked block)

Jumper

Lock
(Retains the engaged
position for one
disconnect terminal)

C322
through
C327
COMPONENT RATING
Nominal Voltage (V) (Max):
- IEC / UL / CSA = 500 / 300 / 300
Nominal Current (A) (Max):
Disconnect Terminal - IEC / UL / CSA = 57 / 45 / 45
Wire Size (AWG) (Min - Max) :
- CSA: 20 - 8
- UL: 20 - 8

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 36
GIB Components
Customer Terminal Rail
C101 through C150

Odd #
Connections

Even #
Connections

Jumper Bar
Connection

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 37
GIB Components
Service Rail

Engine Aux Oil Pump Stay-In-Boot J1939 R232


Push-Button Switch (CM850) (Cense)
On = Button Depressed On = 1 Service Tool Connection
INSITE™
ECM Keyswitch
Switch
On = 1

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 38
GIB Components
Service Rail
STCC & STCD

STCC STCD
J1587 / J1939 INSITE Service Tool Connector Socket RS-232 CENSE Software Download
Connector Plug - Shown w/ Mounting
Screws for Connector Pattern Identification
A
24VDC (–)
100

D
J1939 (–)
BLACK 303

C RS232 TX –
J1939 (+)
CLEAR 309
E
J1939
RED 302 RS232 RX –

SCREEN 304 B
24VDC (+)
RED 308

156

F
J1587 (+)
RED 318

I
NOT USED
RS232 GND –

G
J1587 (–)
BLACK 310

BLACK 319
H
NOT USED

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 39
GIB Components
Internal (Doors Removed)
Service
VDC Termination Rail Rail
VAC Termination Rail
PCC3300

Rail for
Optional
Customer
Mains
Termination
Decoupling
Rail
Relay

VAC Aux Termination Rail


CM700
AUX101 AUX101 (ECM)
(3) (4)

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 40
GIB Components
PCC3300 – Refresh

TB15
TB10 J14 TB9

Genset Control
TB7 • Isochronous or droop governing
TB8 • Remote start / stop / e-stop
• Temperature variable in governing algorithm
• Local e-stop
CT1
• Sleep mode
CT2
Engine Control
TB5 • SAE J1939 CAN communications & control
• Cycle cranking limits
CT3
• Time delay (start & stop) for cool down

J12
Alternator Control
TB3 • Digital output voltage regulation: 3Ph L-L via shunt or PMG
• Droop voltage regulation
TB1 • Torque matched V / Hz overload control
J22 • Fault current regulation

J26 J25 J20 CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 41
GIB Components
PCC3300 – Refresh – Cont’d
Paralleling Control
TB15 • First Start Sensor™
TB10 J14 TB9
• Digital synchronization of:
• frequency
• slip frequency
• phase
• voltage
• kVAR & kW load sharing
TB7 • Load govern mode
B8 • Sync check for breaker closure
• Genset & utility AC bus metering
• Power transfer control (PTC)
CT1 • over / under voltage / frequency protection
• Phase loss / rotation protection
CT2 • Genset breaker trip sensing
• Start / stop / transfer / re-transfer / programmed transition
delay & maximum parallel time control
B5 • Utility & genset CB control & diagnostics
CT3 • Extended paralleling mode
• Exercise clock
J12
Applications
B3
• Standalone
• Synchronizer Only
B1 • Isolated Bus
J22 • Utility Single / Multiple

• Protective Functions
• Battle short mode
• Derate
• Customer configurable alarms & state inputs

J26 J25 J20 CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 42
GIB Components
PCC3300 – CT’s

Standard Function Connection LBNG Function

1 Genset Bus or Utility L1 Current C311 & C312 Utility CT1 (L1) Output Current Sense

2 Genset Bus L2 or Neutral or Utility L2 Current C313 & C314 Utility CT2 (L2) Output Current Sense

3 Genset Bus or Utility L3 Current C315 & C316 Utility CT3 (L3) Output Current Sense

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 43
GIB Components
PCC3300 – TB1 Basic

Standard Function Connection LBNG Function

1 PCCNet A (+) RS485 R5 PCCNet A (+) RS485

2 PCCNet B (-) RS485 R4 PCCNet B (-) RS485

3 PCCNet Sheild R3 PCCNet Sheild


Low Side Driver: Ready to
4 Load O/P KM45-A2 Return: KM45 Relay Coil (Ready to Load)

5 Supply: Fused 3A B+ - Supply: Fused 3A B+

6 Config O/P #1 - Relay NO KM31-A2 Return: KM31 Relay Coil (Common Warning)

7 Config O/P #1 - Relay COM TB1-9 Return: TB1-6

8 Config O/P #2 - Relay NO KM32-A2 Return: KM32 Relay Coil (Common Shutdown)
TB1-7 & TB1-
9 Config O/P #2 - Relay COM 13 Return: TB1-8
Return: Fused 3A B+ /
10 Remote Start (Wake Up) - Return: Fused 3A B+

11 I/P: Remote Start (Wake Up) R7 & C27 Supply: Remote Start

12 Config I/P #1 C7 Config I/P #1

13 Config I/P (Common) TB1-7 Return: Config I/P #1 & #2

14 Config I/P #2 C9 Config I/P #2

15 Local E-Stop Return KM18-1 (11) Return: KM18-1 Contact (Remote E-Stop)

16 Local E-Stop (Wake Up) KM18-1 (14) Supply: KM18-1 Contact (Remote E-Stop)

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 44
GIB Components
PCC3300 – TB3 Customer I/O

Standard Function Connection LBNG Function

1 Return - Return

2 Master CAN Shield C79 Master CAN Shield

3 Master CAN L C78 Master CAN L

4 Master CAN H C77 Master CAN H

5 Config O/P #20 State KM47-A2 Return: KM47 Relay Coil (Start Inhibit Event)

6 Config O/P #21 State - Config O/P #21 State

7 - - -
Return: KM41 Relay Coil (Engine @ Idle
8 Config O/P #22 State KM41-A2 Speed)

9 Config I/P #20 - Transfer Inhibit C57 Transfer Inhibit (PTC)

10 Config I/P #21 - Retransfer Inhibit C59 Retransfer Inhibit (PTC)

11 Master First Start O/P State C29 First Start Arbitration

12 Return - Return

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 45
GIB Components
PCC3300 – TB5 Circuit Breaker Control
TB7 Genset Bus Voltage

Standard Function Connection LBNG Function

1 Genset Bus or Utility L1 Voltage C301 Utility L1

2 Genset Bus or Utility L2 Voltage C302 Utility L2

3 Genset Bus or Utility L3 Voltage C303 Utility L3

4 Genset Bus or Utility Neutral Voltage C304 Utility Neutral

Standard Function Connection LBNG Function

1 Genset CB Close KM38-A1 Supply: KM38 Relay Coil (Genset CB Close)

2 Genset CB Close Return TB5-4 Return: TB5-1

3 - - -

4 Genset CB Open State KM37-A1 Supply: KM37 Relay Coil (Genset CB Open)

5 Genset CB Open State Return TB5-7 Return: TB5-4

6 Utility CB Close State KM43-A1 Supply: KM43 Relay Coil (Utility CB Close)

7 Utility CB Close State Return TB5-9 Return: TB5-6

8 Utility CB Open State KM44-A1 Supply: KM44 Relay Coil (Utility CB Open)

9 Utility CB Open State Return S22 Return: TB5-8

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 46
GIB Components
PCC3300 – TB8 Premium

Standard Function Connection LBNG Function


Return: Fault Reset
1 (Wake Up) - Return

2 Return: Start Type - Return


Low Side Driver: Delayed
3 Off O/P - Return: Delayed Off
Low Side Driver: Switched
4 B+ (Run) O/P KM39-A2 Return: KM39 Relay Coil (Run)
Supply: Fault Reset
5 (Wake Up) C25 & R8 Supply: Fault Reset

6 Supply: Start Type C33 Supply: Start Type

7 Supply: Config I/P #3 C11 Supply: Config I/P #3

8 Supply: Config I/P #4 C13 Supply: Config I/P #4


Low Side Driver: Config Return: KM48 Relay Coil (Common
9 O/P #4 KM48-A2 Fault)
Low Side Driver: Config Return: KM33 Relay Coil (Common
10 O/P #3 KM33-A2 Controlled Shutdown)
Low Side Driver: Load Return: KM46 Relay Coil (Load
11 Dump O/P KM46-A2 Dump)

12 Discrete I/P Return - Return

13 Discrete I/P Return - Return

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 47
GIB Components
PCC3300 – TB9 Analog I/O

Standard Function Connection LBNG Function

1 Config Analog I/P #1 - kW Load Set Point C81 Sense: kW Load Set Point

2 Analog Return C82 & C83 Return: kW & kVAR Load Set Point
Config Analog I/P #2 - kVAR Load Set
3 Point C84 Sense: kVAR Load Set Point

4 Config Analog O/P #2 - Voltage Bias C85 Speed Bias

5 Config Analog O/P #1 - Speed Bias C88 Voltage Bias

6 Analog Return C86 & C87 Return: Speed & Voltage Bias

7 kW Load Share Level C89 Return: kW Load Share

8 - C90 kW Load Share

9 Load Share Shield C80 Return: TB9 Wire Shields

10 kVAR Load Share Level C91 Return: kVAR Load Share

11 - C92 kVAR Load Share

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 48
GIB Components
PCC3300 – TB10 CB Status

Standard Function Connection LBNG Function

1 Return - Return

2 Return - Return

3 Utility CB Position (A) C37 Utility CB Position (A)

4 Config I/P #23 - Utility CB Position (B) - Utility CB Position (B)

5 Utility CB Tripped C39 Utility CB Tripped

6 Config I/P #25 - Utility CB Inhibit C41 Utility CB Inhibit

7 Genset CB Position (A) C43 Genset CB Position (A)

8 Config IP #26 - Genset CB Position (B) - Genset CB Position (B)

9 Return - Return

10 Genset CB Tripped C45 Genset CB Tripped

11 Config I/P #28 - Genset CB Inhibit C47 Genset CB Inhibit

12 Config I/P #29 - Utility Single Mode Verify C49 Utility Single Verify

13 Config I/P #30 - Sync Enable C51 Sync Enable

14 Config I/P #31 - Load Demand Stop C53 Load Demand

15 Congif I/P #32 - Extended Parallel C55 Ramp Load / Unload

16 Return - Return

17 Return - Return

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 49
GIB Components
PCC3300 – TB15 Modbus (RS485) / PC Tool
& J12 Genset Current

Standard Function Connection LBNG Function

1 RS485 Shield - RS485 Shield

2 - - -

3 RS485 Data A - RS485 Data A

4 RS485 Data B - RS485 Data B

5 System Wakeup R6 System Wakeup

Standard Function Connection LBNG Function

1 Genset L1 CT1-X1 See AVR WD's Genset L1 CT1-X1

2 Genset L2 CT2-X1 See AVR WD's Genset L2 CT2-X1

3 Genset L3 CT3-X1 See AVR WD's Genset L3 CT3-X1

4 Genset L1 CT1-X2/X3 (Common) See AVR WD's Genset L1 CT1-X2/X3 (Common)

5 Genset L2 CT2-X2/X3 (Common) See AVR WD's Genset L2 CT2-X2/X3 (Common)

6 Genset L3 CT3-X2/X3 (Common) See AVR WD's Genset L3 CT3-X2/X3 (Common)

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 50
GIB Components
PCC3300 – J14 Modbus / PC Tool
J22 Genset Voltage

Standard Function Connection LBNG Function

1 - - -

2 RS232 (R) - RS232 (R)

3 RS232 (T) - RS232 (T)

4 - - -

5 RS232 (G) - RS232 (G)

6 - - -

7 - - -

8 - - -

9 - - -

Standard Function Connection LBNG Function

1 Alternator Terminal U (R) See AVR WD's Alternator Terminal U (R)


PT’s employed where
L-L Voltage > 600VAC 2 Alternator Terminal V (Y) See AVR WD's Alternator Terminal V (Y)

3 Alternator Terminal W (B) See AVR WD's Alternator Terminal W (B)

4 Alternator Terminal Neutral See AVR WD's Alternator Terminal Neutral

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 51
GIB Components
Standard Function Connection LBNG Function
1 Chassis Ground GND Chassis Ground

2
PCC3300 - J20 Genset
Return: B+ S18 Return: B+

3 Relay Driver: Switched B+ (Run) Control - Switched B+ Low Side Driver

4 Return: B+ S18 Return: B+

5 Return: Config Digital I/P #3 (Low Coolant Level Switch / Wake Up) KM21-2 (21) Return: Fire Shutdown

6 Return: Config Digital I/P #4 (Fuel Level Switch / Wake Up) - Return: Earth Fault

7 Return: B+ S18 Return: B+

8 Supply: Config Digital I/P #12 (Rupture Basin Switch / Wake Up) S17 Return: Differential Fault Shutdown

9 Fused B+ - Control Fused B+ Supply

10 Fused B+ S17 Control Fused B+ Supply

11 Starter Disconnect I/P - Starter Disconnect I/P

12 Return: B+ S18 Return: B+

13 Relay Driver: B+ Oil Priming Pump Control - Relay Coil B+ Supply

14 Relay Driver - FSO Control S19 Relay Driver - FSO

15 Relay Driver - Starter Control - Relay Driver - Starter

16 Relay Driver - Oil Priming Pump Control - Relay Driver - Oil Priming Pump

17 Supply: Config Digital I/P #3 (Low Coolant Level Switch / Wake Up) KM21-2 (24) Supply: Fire Shutdown

18 Supply: Config Digital I/P #4 (Fuel Level Switch / Wake Up) C61 Supply: Earth Fault

19 Supply: Config Digital I/P #12 (Rupture Basin Switch / Wake Up) C63 Supply: Differential Fault Shutdown

20 Fused B+ S17 Control Fused B+ Supply

21 Fused B+ S17 Control Fused B+ Supply

22 Alternator Flash I/P - -


CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 52
GIB Components
PCC3300 – J25 Display

Standard Function Connection LBNG Function

1 - - -

2 I/P (Wake Up on Open) KM17-1 (14) Supply: KM17 Contact 1 (Local E-Stop)

HMI320 J29-2
3 PCCNet B (-)
HMI114 J1-4
PCCNet B (-)

HMI320 J29-1
4 PCCNet A (+)
HMI114 J1-3
PCCNet A (+)

HMI320 J29-3
5 System Wake Up
HMI114 J1-5
System Wake Up

6 Return: I/P (Wake Up on Open) KM17-1 (11) Return: KM17 Contact 1 (Local E-Stop)

7 Return: Discrete I/P - -

HMI320 J6-2
8 Return: B+
HMI114 J28-3
Return: HMI320 & HMI114 B+

9 PCCNet Shield - PCCNet Shield

10 Run (Wake Up) HMI320 J29-6 Run (Wake Up)

11 Auto (Config Wake Up) HMI320 J29-4 Auto

HMI320 J28-1
12 HMI Fuse B+
HMI114 J6-1
Supply: HMI Fuse B+

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 53
GIB Components
PCC3300 – J26 Interconnect (AVR & Engine)

Standard Function Connection LBNG Function

1 J1939 Shield ? J1939 Shield

2 Backup Start Disconnect AUX103 J19-3 Backup Start Disconnect

3 AVR PWM - AUX103 J19-9 AVR PWM -

4 - - -

5 Return: AVR Fused B+ AUX103 J19-8 Return: AVR Fused B+

6 - - -

7 Field Current (-) AUX103 J19-10 Field Current (-)

8 - - -

9 Supply: AVR Fused B+ AUX103 J19-1 Supply: AVR Fused B+

10 J1939 (-) ? J1939 (-)

11 J1939 (+) ? J1939 (+)

12 - - -

13 - - -

14 Field Current (+) AUX103 J19-4 Field Current (+)

15 ECM Keyswitch KM22-A2 Return: KM22 Relay Coil (ECM Keyswitch)

16 AVR PWM + AUX103 J19-2 AVR PWM +

17 - - -

18 - - -
CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 54
GIB Components
AUX101-3 & 4

# Rating
Relay O/P’s
1
2
3
30VDC
4 250VAC
5 NO: 5A
6
NC: 3A
Analog I/P’s
7
# Rating
8
1
Sense I/P: + / - 5V
2
3
4 Sense I/P: 0 - 5V
Current O/P: 5VDC,
5
20A Max
6
7
Sense I/P: 0 - 38V
8

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 55
GIB Components
AUX101-3 & 4

J1 J2 J3 J4
1 Relay 1 O/P NO Relay 5 O/P NO Relay 7 O/P NO
2 Relay 1 O/P Common Relay 5 O/P Common Relay 7 O/P Common
3 PCCNet A (+) Relay 1 O/P NC Relay 5 O/P NC Relay 7 O/P NC
4 PCCNet B (-) Relay 2 O/P NO Relay 6 O/P NO Relay 8 O/P NO
5 System Wake-Up Relay 2 O/P Common Relay 6 O/P Common Relay 8 O/P Common
6 Relay 2 O/P NC Relay 6 O/P NC Relay 8 O/P NC
7 Relay 3 O/P NO
8 Relay 3 O/P Common
9 Relay 3 O/P NC
10 Relay 4 O/P NO
11 Relay 4 O/P Common
12 Relay 4 O/P NC

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 56
GIB Components
AUX101-3 & 4

J10 J11 J14


1 J1939 H Analog I/P #1: Sense Supply (B+): AUX101
2 J1939 L Analog I/P #1: Sense Return Return (B-): AUX101
3 Analog I/P #3: Current Return Analog I/P #2: Sense
4 Analog I/P #4: Current Return Analog I/P #2: Sense Return
5 Analog I/P #5: Current Return Analog I/P #3: Sense
6 Analog I/P #6: Current Return Analog I/P #3: Sense Return
7 5VDC Supply #1 (20A Max) Analog I/P #4: Sense
8 5VDC Supply #2 (20A Max) Analog I/P #4: Sense Return
9 Analog I/P #3: Current Supply Analog I/P #5: Sense
10 Analog I/P #4: Current Supply Analog I/P #5: Sense Return
J14
11 Analog I/P #5: Current Supply Analog I/P #6: Sense
12 Analog I/P #6: Current Supply Analog I/P #6: Sense Return
13 Analog I/P #7: Sense
14 Analog I/P #7: Sense Return
15 Analog I/P #8: Sense
16 Analog I/P #8: Sense Return

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 57
GIB Components
AUX101-3 & 4

AUX101-3 AUX101-4
1 Derate Authorization C35 GIB Isolator Open VAC Isolator

2 Start System Trip C31 Alternator Heater On KM6 (14)

3 Vent Fan Trip C3 Alternator DE Bearing Temperature See AVR WD's

Analog 4 Louvres Closed C1 Gearbox Oil Pressure 1-B


I/P 5 Radiator Fan Trip C5 Gearbox Oil Temperature 1-D

6 Start Inhibit N1 C17 Engine DC PSU Unavailable VDC Reg Alarm 4

7 Start Inhibit N2 C19 Alternator Heater Trip MCB6-SD (95)

8 Start Inhibit N3 C21 - -

1 - - Alternator Heater Control (NO) MCB6-A2

2 - - Emergency Stop P/B (NO) KM18-2 (24)

3 Vent Fan Control (NO) KM35-A1 - -

Relay 4 Louvres Control (NO) KM36-A1 - -


O/P 5 Radiator Fan Control (NO) KM34-A1 - -

6 - - - -

7 - - - -

8 - - - -

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 58
GIB Components
AUX101-3, 4 & 5 – Default Functions

Warning
Key: Digital Input (H=active high, L=active low) Key:
Analogue Input Shutdown
I/O Type Digital Output
Shutdown Type Controlled Shutdown

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 59
GIB Components
Internal (Doors Removed)

PCC3300

Rail for
Optional
Mains
Decoupling
Relay

CM700
AUX101 AUX101 (ECM)
(3) (4)

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 60
GIB Components
Mains Decoupling Relay (Optional)

Purpose:
ƒ Protect the Genset’s alternator from the utility
ƒ Protect the utility from the Genset’s alternator
ƒ Meet utility protection requirements (VDEW, G59) for utility paralleling applications

Space allotted to fit one mains decoupling relay:


Manufacturer: Woodward SEG
Model: XRN2-1

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 61
GIB Components
Mains Decoupling Relay
(Optional)

XRN2-1 Protection Features:


Over / under voltage
TIME (SECONDS)

Over/ under frequency


Vector Surge

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 62
GIB Components
Mains Decoupling Relay
(Optional)

FAULT INDICATORS FAULT INDICATORS SELECTION OF TEST TRIPPING


(Parameter) (Phase & Function) FUNCTION & & SOFTWARE
RESETTING OF VERSION
LED illuminates when the respective LED illuminates when the respective
DEVICE ENQUIRY
adjustment value has been selected measuring value has been selected
(GREEN when setting / RED after (GREEN normal / RED tripped ).
activation value reached ).

ON
ALHA NUMERIC KEYS FOR KEY FOR STORING DIP SWITCHES - OFF
LED INDICATOR CHANGING SET ‘SET’ VALUES
VALUES
Woodward XRN 2 – 1 Fascia
CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 63
GIB Components
Mains Decoupling Relay
(Optional)

XRN2-2 Terminal Connections

Voltage Analogue I/P


(A1& A2) Not used?
Blocking
Input

U/V U/F ∆Ө Self


TRIP ALARM ALARM ALARM Supervision
External
Reset

External Tripping - All Indication of over Indication Indication Indication self Network
reset & 11, 12, 14 and & under voltage of over & of df/dt- supervision Connection
blocking I/P 21, 22, 24 alarm. under alarm (internal fault To PCC
Not used ? 31, 32, 34 and 41, frequency 61, 62, of the unit) Net or not
42, 44 (N/O) alarm. 64 (N/O) 71, 72, 74 used ???
Set o/p to AUX config I/P and configure 51, 52, 54 (N/C)
(N/O)
CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 64
GIB Components
Mains Decoupling Relay
(Optional)

XRN2 - 1Adjustments and Setting.


Four DIP Switches are located on the front panel. Their function is shown in the table
below. Switch 4 has no function assigned.
Manual RESET of alarm RELAY is Manually carried out by pushing the “SELECT/RESET”
button on the relay fascia for approximately 3 seconds.
Factory default Password is “++++” and should not be changed. Enter this code to make
changes to parameter settings for up to 5 minutes (auto time out).
After password press “ENTER” to call up the Parameter Menu. Press “SELECT/RESET” to
reach parameter to be set. Press “+”/”-” to change setting then “ENTER” to save new
setting.
After entering the password the “TRIP” button may be used to test the output Alarm relay
circuits (both tripping & signaling contacts operate).

CPG DIP
Default
1- OFF

2 - ON

3 - OFF

N/A

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 65
Refresh: Genset Layout
Alternator Control Box (Rear of Genset)
Shown on Frame 8 Alternator – Cover Removed

Alternator
AVR AUX101
(AUX105) (5) Termination
Rails

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 66
Protocol and Interface Standards
Modbus is the Industry standard microprocessor communications package protocol.
Modbus communication is used to communicate between PCC3300, B&R HMI, I-watch (RMS) and any
customer interface that may be required .
Modbus can operate on RS422 or RS485 Interface connections. We run Modbus on RS485 interface.
150Ώ Line terminating resistors required – polarity sensitive.
RS 232
INTERFACE
RX RX RS232 Interface Standard connection

TX TX
Error checking by multi transmit (parity check),
if not received shuts down.
GND GND Maximum communicating distance 5 mtrs.

9 PIN ‘D’ Baud rate for a RS232 / 422 9 PIN ‘D’ RS422 Interface Standard connection
Connectors
Connectors interface is 2,400 to 19,600 baud.
RS 422 Error checking by collision detection and
INTERFACE RX1 parity check, both lines work in parallel
RX1
allowing higher power transmission.
TX1 TX1

RX2 RX2 Maximum communicating distance 15 mtrs.


TX2 TX2

RS485 Interface Standard connection


Baud rate for RS485
9 PIN ‘D’ 9 PIN ‘D’
Connectors interface is 250K baud. Connectors
RS485 uses the new RS222 connection (2
RS 485
wire as RS232) which is then electrically
INTERFACE enhanced to give RS422 type operation.
RX RX

TX TX
CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 67
MODBUS PCC3300
(1900 baud)

Network Data Links Slave


Master \ Slave
Cummins (Point to Point)
Peer to Peer J1939 Proprietary Peer to Peer Data Link
(Multi-tasking) CAN 2.0B (Multi-tasking)
Data Link (250K baud) Genset Control (500K baud) Data Link
System
(PCC3300/AUX101) Master
CENSE on H/E
SERVICE TOOL QSK 60G
CONNECTOR
CM700 Customer
Options
CM700 (PLC/HMI)
J1
93

CM558
CM558
9
Sy

C
A
st

N
em

CM558

N
(+) CM558

et
B

(-)

w
us

or
N

(SHIELD)

k
et

B
w

ac
or

Networks constructed

kb
k

CENSE on

on
B

with twisted two core standard


ac

e
shielded cable.
kb

QSK 60G
on

External terminating
e

resistors fitted where


indicated CONNECTION CHECKS
120 Ohm - J1939 / CAN 2.0B Polarity - Terminating Resistors - Shield Connections
150 Ohm - MODBUS CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 68
PCC Net Overview
Protocol
PCC Net is a communication system that uses a standardized
proprietary protocol unique to Cummins Power generation.

Interface
ƒ 2-wire, RS-485 Data Connection TB1-1 & TB1-2 Shielded
ƒ 2-wire Power Connection. twisted pair

ƒ Data terminals are polarity sensitive TB1-5 (B+) & TB1-3 (B-)
ƒ PCC Net Must use a “daisy chain” topology for data connections
ƒ Up to 4,000 feet network data length
ƒ No Termination Required
ƒ Total of 20 PCCNet devices on one network

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 69
Control System Network Line Diagram
J1939 +
PGI BUS J1939 Network
120Ω 120Ω
(250K baud)
J1939 –

Note: When CM850’s


System CENSE fitted in place of
PCC3300 Inputs / CM700 CM558-A CM558-B OR CENSE they connect
to the CAN network
Outputs CM850 as shown.
150Ω
CAN 2.0B +
120Ω CAN 2.0 B Network
120Ω
(500 K baud)
CAN 2.0B –

OPTIONAL Cummins Customer


DEVICES I-watch (RMS) PLC
MODBUS +
MODBUS link
150Ω
PCC Net (19,200 baud)
(19,200 baud) MODBUS –

Signal
- 24v dc
+ 24v dc
Note A; Network devices are designed to be
‘Daisy Chain” connected as shown.
AUX HMI114 HMI320 OPTIONAL DEVICES
( PHII Release )
101/2 Bargraph Display
Note B; PHII release J1939 “System Bus network”
to other PCC3300 controllers not shown.
CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 70
Auxiliary Control

AUXILIARY DATA DESCRIPTION DATA SOURCE DATA OUPUT


PCC3300 CM700 HMI320 MODBUS

Alternator Heaters Off 9 z z

Alternator Heaters Requested 9 z z

Coolant Circulating Pump Off 9 z z


This table shows
the controlling
Coolant Circulating Pump Requested 9 z z
device and the
Coolant Heaters Off 9 z z available output
GIB Isolator Open 9 z z data sources for
GIB Isolator Closed 9 z z
each system
Lube Oil Low 9 z z

Lube Oil Priming Pump Off 9 z z

Lube Oil Priming Pump Requested 9 z z

Oil Heater Off 9 z z

Oil Heater Requested 9 z z

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 71
Generic PCC Net Devices
REMOTE HMI 320 HMI 114
HMI 320

HMI 112

AUX 101/102 – for PCC Net


Aux boards to be added in
the next software release
which will enable HMI113
customers to add remote Future development
I/O that can be configured for LBNG
for any system alarm with
ease

* The device list is subject to change as more devices are added or removed
CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 72
Operator Interface & Data Displays
HMI320
Overview
HMI 320 – Main Operator Interface
ƒ Manual / Start / Stop / Auto / Reset
selection, circuit breaker command, system
display and menu navigation.
ƒ Protocol / Interface connection – RS485 /
PCC NET HMI 114

HMI 114 – Bar Graph


ƒ Graphic Digital Display of A,V,PF and Hz.
ƒ Protocol / Interface connection – RS485 /
PCC NET

These components will be covered in detail in Module 6.

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 73
AUX103 AVR Driver Module

Features:
‰ 12 and 24vdc Operation
‰ InPower Compatible (PC Based Service J17
Field Output
Tool)
‰ The AVR receives digital signals from
the PCC3300 base board to switch /
control the level of power supplied for
Alternator excitation.
‰ Power for Alternator excitation comes J18
Power Input
from the Permanent Magnet Generator
(PMG).
‰ The AUX103 also provides starter
disconnect using the output frequency J19
Connection to PCC33000
from the Alternator. Ground / Earth base board (J26).
Wire
‰ The AUX103 is located in the
Alternator box.

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 74
Alternator Box Layout

ƒ The Alternator box houses


the Aux 101-5 Alt I/O module
and the AUX103 AVR Driver
Module.
ƒ The alternator box also
provides access to the
interconnection terminals. No
additional fusing or protection
is provided for these
components.
ƒ A flexible harness connects
the Alternator box to the GIB.
AVR Driver AUX Board Interconnection Flexible
Module (101-5) Alt Terminal Block Harness
(AUX103) (TB x – xx)

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 75
Understanding Control Configuration & Set Up

• ISLAND MODE PARALLELING


- ISOCHRONOUS LOAD SHARING FOR
MULTIPLE GENERATORS.
- DROOP LOAD SHARING FOR MULTIPLE
GENERATORS. ( WHEN PARALLELING WITH
NON CUMMINS SUPPLIED GENERATORS).

• UTILITY PARALLELING MODES


- GENERATORS SUPPLY A PERCENTAGE OF
THEIR RATED POWER BASED ON THE ZERO
TO 5 vdc. LOAD SET INPUT SIGNAL APPLIED
(KW/Kvar). CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 76
UTILITY PARALLELING MODES:

- BASE LOAD MODE.


Generators provide base load power up to their total rating.
Power above this rating is supplied by the utility.

- PEAK SHAVE MODE.


Utility provides base load power. Generators provide
additional power above a pre-set level.

- IMPORT / EXPORT MODE.


Generators provide their rated power. Utility is used as a
buffer to supply additional power as required (Import) or as
a load (Export) for excess power generated.

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 77
PCC 3300 Utility Parallel -
Modes of Operation

„ The PCC3300 is configurable via HMI 320 panel or the InPower service tool
to operate in either Island Mode or one of two different modes of utility
paralleling: Multiple Mode and Single Mode.

„ Selection of the Multiple Mode allows the Genset to operate in both isolated
bus load sharing mode and utility paralleling mode.

„ The Single Mode is a special mode of software designed for single Genset to
single utility supply/breaker. Selecting Single Mode will disable load sharing
capability.

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 78
Utility Single Mode

PCC3300 Control

Single Mode - ONLY used in the configuration 3300

shown. i.e.. Single set with bus sensing on


live (Utility side) of the Utility breaker. Generator
Sensing
Utility
Sensing
Selection of Single Mode enables the G2

PCC3300 synchronizer to run when the genet


breaker is closed. The genset can therefore
re-synchronize with the utility on mains From Utility
Source
restoration.
The single set power transfer mode is the U1

ONLY configuration where the PC3.3 will 52-G2

directly Control the Utility breaker on mains


restoration. All other configurations will utilize
a PC3320 DMC board to control the utility
breaker when required. 52-UM

NOTE: To ensure Single Mode is not selected


advertantly Single Mode verify terminals must
be linked for single mode operation (CXX &
CXX) in HHP Gas GIB Panels. To
Loads

L1,L2 & L3 Sensing Voltages

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 79
Overview of PCC3300 modes
of operation with associated
active control features

PH 2 ONLY

GENSET APPLICATION
(Mode)

F
E - M/F
A
T
U
R
E
S

Understanding Genset application type is of primary importance for configuring and adjusting
paralleling features and general for system troubleshooting.

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 80
PCC3300 Isochronous Load
Sharing for Island Mode

2.5v @ f/load
LOAD SHARE LINE
PCC3 PCC3 INTERCONNECTIONS
300 300
#N #1
PCC3.3 Terminal Block 9

Terminal Block 9
TB9 - 7 = KW ( - )
PCC3 PCC TB9 - 8 = KW (+ )
300 3300 TB9 – 10 = KVAR ( - )
#3 #2 TB9 – 11 = KVAR ( + )
TB9 – 9 = RETURN

PCS #1
sensed kW Example of kW error
(VkW1) circuit, a similar circuit is
used to derive VAR error.

Error signals are used to


Ve = Vpwr - VkW1
adjusts voltage regulation
Ve kW Error kW Error Ve for VAR match and fueling
to PCS #1 to PCS #NINC TRAINING - Gas Engine
CUMMINS, for kW
Controls match.
/ Genset Controls / KDL / 10 - 2009 / REV 1.1 81
PCC3300 - Integrated
Synchronizer & Sync Check
„ The Synchronizer is Enabled when all of the following conditions are
met:

- Bus Voltage % (L1L2, L2L3 and L3L1) is 60-110% of Genset Nominal


Voltage
- Bus Frequency is 60-110% of Alternate Frequency Switch
- If Genset CB Fail to Close Standalone Mode Enable is set to Enable,
Warning fault 1452 (Genset Breaker Fail to Close) is Inactive
- The PCC is not raising the engine speed to idle speed or rated speed, or
lowering the engine speed to idle speed
- Event 1465 (Ready to Load) is Active
- If the PCC is in Manual Mode, Sync Disable is Inactive
- If Fail to Sync Lockout is Enabled, event 1457 (Fail to Synchronize) is
Inactive
- Synchronizer Speed Control Method is not External, Synchronizer Voltage
Control Method is not External, or both are not External

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 82
PCC3300 - Integrated
Synchronizer & Sync Check

Paralleling Frequency Reference Offset:


The PCC adjusts the speed reference (bias) to make the Genset frequency match the Bus
frequency. The PCC may also try to make the Genset phase match the Bus phase. This
adjustment is the Paralleling Frequency Reference Offset.
The PCC uses one of two methods to calculate the Paralleling Frequency Reference Offset:
ƒ Slip Frequency synchronizing control logic: Selected when:-
- It is important that the power flows in the desired direction when the Gensets are
first connected in parallel.
- The Genset cannot be controlled well enough to make the Genset phase match
the Bus phase (for example, with Gas Gensets).
ƒ Phase Matching synchronizing control logic: Selected when:-
- A phase difference exists between the Genset and the Bus (for example, if there is
a delta/wye transformer in the system).
The PCC3300 default setting for synchronizing control is Slip Frequency control logic

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 83
PCC3300 - Integrated
Synchronizer & Sync Check
Slip Frequency Synchronizing Control Logic: The PCC attempts to drive a fixed frequency
between the two sources.

„ The following conditions must all occur before the permissive function will
allow automatic or manual closure of the Genset breaker:
0
– a) The difference between the Genset frequency and the Bus frequency is
-10° +10° equal to or less than 10 degrees.
– b) Voltage difference between Genset and Bus is less than 5% (voltage
matching is standard on PCC)
– d) Phase rotation between Genset and Bus is correct after other sync
conditions are met
– e) All of the above conditions are met for greater than 100 milliseconds
– f) Phase angle must be moving towards zero (in either direction) and less
than 1 degree

„ If a breaker “close” signal is given and the phase difference moves out of
the permissive window, then the breaker close signal is removed until the
conditions are re-established.

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 84
PCC3300 - Integrated
Synchronizer & Sync Check
Phase Matching Synchronizing Control Logic: The PCC attempts to drive the Phase
Error to zero.
„ The following conditions must all occur before the permissive function will
allow automatic or manual closure of the Genset breaker:
– a) Phase difference (Error) between the Genset and the Bus must be less
0 than 5 degrees (adjustable from front keypad between 5 and 20 degrees)
-5° +5° – b) Voltage difference between Genset and Bus is less than 5% (voltage
matching is standard on PCS)
– d) Phase rotation between Genset and Bus is correct after other sync
conditions are met
– e) All of the above conditions are met for greater than 0.5 seconds
(adjustable from 0.5 to 5 seconds)
– f) Phase angle must be moving towards zero (in either direction) and less
than 1 degree

„ If a breaker “close” signal is given and the phase difference moves out of
the permissive window, then the breaker close signal is removed until the
conditions are re-established.

IMPORTANT NOTE: If changing from ‘Slip Sync’ to ‘Phase Matching’ synchronizing control logic, the
Permissive Phase Angle MUST be changed from the default setting of 10° to the preferred setting of 5°.
This can be changed via the PCC3300 front panel or via InPower.
CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 85
Speed/Load Bias to CM700
„ Speed bias can influence base engine
NOTE: PCC3300 TB9 – 4 / TB9 - 5 is a customer
speed between – 10% to + 10% of
Speed Bias signal output only (+10/-10Vdc).
nominal.
„ The speed bias is a digital signal
transmitted from the PCC3.3 to the CM700
over the J1939 System Bus.
„ When no speed bias is required, the PC3.3 Customer GIB Alt
digital output is Zero, commanding NO Inteface
AUX101
Intefa
AUX101
ce
box
AUX101
Intefac
PCC3300
speed change from the CM700 governed MODBUS / I/O I/O e
I/O
nominal speed (i.e. no speed correction InPower
(MON)
J1939
from it’s current base speed set-point). Tool Con.
(on board)
System Bus (250KBPS)
J1587
„ The PC3.3 synchronises the Genset by PWM
(250KBPS)
CM700
varying the digital output (positive and AUX103
negative) , thereby biasing (changing) the AVR
CM558L
J1587 Service
Tool Connector
base governed speed of the engine to CAN
2.0B
match the Genset and bus voltage CM558R
waveforms.
CENSE or J1939 Service
„ The PC3.3 controls multiple Gensets for 2 x CM850 Tool ConnectorCM850
core 2 module ONLY
set-to-set load sharing and kW load
against the utility in the same way.
„ Failure of the J1939 System Bus causes
an Immediate critical shutdown.

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 86
PCC 3.3 Utility Parallel –
Import/Export Operation
„ This figure shows the utility load set analog
5.0 voltage input versus kW load govern reference
4.185 produced by that voltage.
„ The kVAR load reference is determined by the
Volts kW reference and the PF level set in the
control.
Load Track
„ Voltages between 0.5 and 1.0 represent a
0%kW reference. A voltage of 4.185 or greater
1.5 (up to 24 VDC) represents 100% output.
1.0 „ The kW Reference % for voltages between 1.0
Zero kW
0.5 and 4.185 are represented by the equation:
0% 50% 100% kW% = 31.4 x (Load Set Volts -1)
kW Output % e.g. Load set = 2.0v
Load set voltage signal : The load set voltage kW output = 31.4 x ( 2 - 1 )
must be “Conditioned” so that change is “ramped” = 31.4%
rather than stepped. The load set voltage must be
OR, 3v = 62.8%, etc.
applied BEFORE the UTILITY PARALLEL
contact is closed and the set signaled to run. PCC3300 TB9 – 1/ 3, TB9- 2 RETURN

Utility Parallel Mode is Activated by linking the Utility Parallel Enable Terminals in the GIB. This is
often achieved using an Auxiliary contact on the Utility Breaker. Utility Parallel enable contact selects
CM700 utility governor gain table and signals PCC to load control via the 0-5v load set (demand)
signal up to max load and Power Factor set on the HMI 320 Operator Panel.
CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 87
Master First Start Control
for Multi-Set Applications

Master First Start Connection Feature.


The master first start feature is designed to prevent two or more
generator circuit breakers closing onto a “dead bus” at the same
time.
When a Genset reaches 90% Speed and Volts it is considered
ready to close its output breaker to the bus. At this time each
PCC3300 boards sends a series of random bursts (1- 8 ms each)
for 800 ms. If another genset receives these signals when up to
speed and volts it holds off for closing for another 2.5 seconds.
A set that sees no MFS pulses closes its breaker onto a dead bus
after 800 ms and at the same time supplies a first start connection TB3
to prevent any other gensets from receiving permission to close. If
two or more reach 90% speed and volts at the same time this MFS Connection :
process is called arbitration and all other units are locked out until PCC3300 TB3 – 12
synchronous conditions have been met. Terminals must be “daisy
Chain” connected between
First Start Backup Timer – Used to give PCC authority to close generators in order for the MFS
function to operate.
it’s circuit breaker should the MFS feature fail for any reason.
Ensure First Start Backup time is set differently on each
generator PCC3300 board.
CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 88
Circuit Breaker Control
The level of control the PCC has over the Genset circuit breaker depends on the Genset application type or
mode.

Standalone and Synchronizer Only


If Genset CB Shunt Trip Enable is set to Enable, the PCC may be connected to the Genset circuit breaker to
trip the circuit breaker when there is a shutdown fault or a shutdown with cool down fault.

Isolated Bus Only, Utility Single and Utility Multiple


The PCC is connected to the Genset circuit breaker to open and close the circuit breaker. The PCC sends an
open signal and a close signal to the Genset circuit breaker. The logic is arranged so that one of the signals is
on at almost all times and so that the open signal has higher priority than the close signal.

Power Transfer Control ( 2nd release only)


The PCC controls the Genset circuit breaker and the utility circuit breaker. Transition type controls the way the
PCC transfers load from one source to the other. Typically used on Diesel Genset systems only.

Genset CB Inhibit Signal


This signal may come from any of these sources.
• PCC Genset CB Inhibit Switch connection
• PCCNet devices
• Modbus network

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 89
Circuit Breaker Control

The level of control the PCC has over the Genset circuit breaker depends on the Genset
application type. Note: This section applies only if Genset Application Type is set to
Utility Single, Utility Multiple, or Power Transfer Control.

Genset CB Close Request

A Genset CB close request comes from one of these sources:

• Dead Bus process


• First Start process
- Dead Bus Gen CB Close Request indicates that the Dead Bus process or First
Start process is generating a Genset CB Close Request.
• Synchronize
- Sync Gen CB Close Request indicates that the synchronizer is generating a
Genset CB Close Request.

ƒ The PCC will display “ Breaker Failed To Close” if :-


- The output breaker fails to close when PCC commands it to.

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 90
Circuit Breaker Control
The level of control the PCC has over the Genset circuit breaker depends on the Genset
application type. Note: This section applies only if Genset Application Type is set to
Utility Single, Utility Multiple, or Power Transfer Control.

Genset CB Open Request


There is a Genset CB open request when at least one of these conditions are met:
• The PCC is in Manual mode, Excitation Disable Override is set to Excitation Off, or the CB
Open button is pressed on the Operator Panel.
• If the PCC is not in Manual mode, the Genset CB inhibit signal is active.
• The Genset is not running at rated speed and voltage.
• The engine is running at rated speed in one of the following stop sequences; the PCC is
running the load govern kW ramp unload process; and Load Govern kW Reference is zero.
• There is an idle request from engine or Genset control.
• There is an active Shutdown fault.
• If Genset CB Fail To Close Standalone Mode Enable is set to Enable, Warning fault 1452
(Genset Breaker Fail To Close) is Inactive, or the PCC has stopped the Genset for any
reason other than a Shutdown fault since Warning fault 1452 became Active.
• It has been less than Genset CB Recharge Delay since the close signal became active.
ƒ The PCS will display “ Breaker Failed To Close” if :-
- The output breaker opens when the PCS did not tell it to.
CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 91
Circuit Breaker Control

Additional circuit breaker control can be instigated through a circuit breaker inhibit
command.

Genset CB Inhibit Signal

This signal may come from any of these sources.

• PCC Genset CB Inhibit Switch connection

• PCC Net devices

• Modbus network

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 92
GIB – Harness & Service Connector Layout

PLAN VIEW OF BASE OF GIB – INSIDE PANEL


(Photograph required + add connector circuit numbers)

Gear Box Harness J1939 Service J1587 Service tool connector.


LB & RB Genset
when fitted. tool connector TO CM700 ONLY.
Harness connectors
(Protections)
(Multi-Pin Harting)

Twin Solenoid Gas Valve


Harness Connector

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 93
PCC3300 / AUX103 AVR / CM700 Control & Sensing Logic
Woodward
ProAct
CM558R MCM700
CAN/Proprietary Datalink
Connector A
A 12V 3kHz signal is used to ‘trigger’ the Woodward 4 13 3 16 6
AVR, allowing transformed PMG power to CM558L
ProAct
the exciter windings. This is ‘% Regulator’
viewed on the PCC HMI. 304 Jumper Bar – S16 Speed
Field Current (-)
● ● 4 3 Sensor
Field Current (+) 303 Jumper Bar – S15
AVR PWM (-)
● ●
302 Jumper Bar – S14
AVR PWM (+) ● ● Flywheel

J1939 Shield
Return Speed Bias Signal (Sync, load share or

J1939 (+)
J1939 (-)
parallel with grid) communicated via
AVR Fused (+)
J1939 Comms
Backup Start Disconnect

14 3 10 4 9 2 8 1 2 7 14 3 16 5 9 1 10 11 15 Utility Current Sensing


J19 J19 J26 PCC3300
AUX103 AVR
J18 J17 J12 J22 TB7 CT3 CT2 CT1

494

493

490
495

491
492
3 2 1 2 1 2 5 1 4 3 6 U V W N L3 L2 L1 N

C316 C315 C314 C313 C312 C311


P2 P3 P4 13 14 ACB Terminal Rail 42 43 40 41 44 45 U V W N C303 C302 C301 C304 Customer Terminal Rail

12 – 50 VDC C326 C325 C324 C323 C322 C321


0.55A
0.55A

0.55A

(12V = No Load,

0.55A
0.55A

0.55A
50 V = Overload) Breaker

● W ●
CTA CT1
PMG Exciter Alternator ● V ●
CTA CT2
PMG Output:
1200RPM/60Hz 170VAC
● U ●
1500RPM/50Hz 195VAC Rotating CTA CT3
1800RPM/60Hz 220VAC
Diode Pack
● N ●
There are 6 diodes (3 +ve, 3 –ve), 2 per phase. At Full Load, the Exciter outputs approximately 42 amps through each diode. Each diode has a capacity of 72
amps. If the PCS is not correctly calibrated (L-L, L-N imbalances), or the set is crash synchronised, then circulating currents can be present in the main
alternator stator winding, which try to back-feed through CUMMINS,
the diodes.INCThese
TRAINING - Gas Engine
circulating Controls
currents can/ Genset Controls
be as high as /300
KDL amps.
/ 10 - 2009 / REV 1.1 94
Module 4 - Genset Control Systems

Team Tasks…
Group Practical Exercises

Cummins, Inc Training

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 95
Team Tasks… Group Practical Exercises

Split into groups of 2 or 3 people and carry out the following tasks.
Using the appropriate wiring diagrams, determine the Control Logic for
Relays, Fuses, Power Supply, etc. for the following systems -
• Oil Pre-Lube Pump
• Coolant Circulation Pump
• Engine Coolant Pre-Heaters
• Alternator Bearing Temperature

CUMMINS, INC TRAINING - Gas Engine Controls / Genset Controls / KDL / 10 - 2009 / REV 1.1 96
HHP Natural Gas Engine & Generator Controls
(M700 & PCC3300)

Module 4 - Genset Control Systems

End