Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

CSM-321S

CS2-RL PULSE (FREQ.) Indicator


„ DESCRIPTION
CS2-RL RPM Indicator has been designed with high accuracy

CS2-VA
measurement, display and communication of pulse (Frequency).
; The innovation feature is auto-range input from 0.01Hz~ 100KHz
(option ~140KHz) and the display resolution will auto-change to
show the highest according to input frequency.
They are also building in 4 Relay outputs, 3 External Control Inputs, 1
Analogue output and 1 RS485(Modbus RTU Mode) interface with

CSM- CSM-321S CSM-


versatile functions such as control, alarm, re-transmission and
communication for a wide range of testing and machinery control
applications.

„ FEATURE
● Measuring Frequency AUTO RANGE 0.01~100KHz / ~140KHz(optional) / Contact, NPN, PNP, Voltage pulse
can be switch on rear of meter
● Accuracy: ± 0.005%; Display range: 0~99999; Decimal Point auto moving according to input frequency
● 4 relay can be programmed individual to be a Hi / Lo / Hi Latch / Lo Latch / Go energized with Start Delay /
Hysteresis / Energized & De-energized Delay functions, or to be a remote control.
● Analogue output and RS 485 communication port in option
● 3 external control inputs can be programmed individual to be Tare (Relative PV) / PV Hold / Maximum or
Minimum Hold / DI (remote monitoring) / Reset for Relay Energized Latch….

CS2-RL
● CE Approved & RoHS
„ ORDERING INFORMATION
CS2−RL− Input
Mode
Input
level −
Relay
Output −
Analogue
Output − RS 485 Port

AUX.
POWER −
*Optional Customize function is welcome. Please contact with our
Function sales for detail.

CSM-321S CSM- CSM-321S CSM- CSM-321S CSM-


OPTION 1 OPTION 2 OPTION 3

CODE INPUT MODE CODE REALY OUTPUT CODE ANALOG O/P CODE RS 485 PORT CODE AUX. POWER
C 00 Contact N None N None N None A AC115/230V
N NPN R2 2 Relay 0(1) ~ 5 V 8 RS 485 OPTION 4
V 0 ~ 10 V
P PNP R4 4 Relay AC 85~264V
ADH DC 100~300V
Input mode and level V Voltage Pulse 0 ~ 10 mA
I 0(4)~20 mA
can be changed by 05 5V pulse ADL DC 20~56V
dip switches on rear 12 12V pulse
of meter Please specify the range
24 24V pulse
of amplitude, if the input
O xx Specify mode has specified to be
U P Pick Up sensor pick up sensor.

Compensation factor: Compensate error from 0.001~9.999


„ TECHNICAL SPECIFICATION Over range indication: ovfl, when input is over 20% of input range Hi
Input Max / Mini recording: Maxi & Mini Value of PV storage during power on.
Input Frequency Input Mode Input Level Display functions: PV / Max(Mini) Hold / RS 485 programmable
0.01Hz ~ 50 Hz Mech. Contact Front key functions: Relative PV / PV Hold / Reset for maxi(mini) hold /
NPN High Level: 8~12V; Low Level: 0.0~4.0 V Reset for relay energized latch programmable
0.01Hz ~ 50 Hz (with excitation supply 12Vdc)
PNP Low cut: Settable range: -19999~29999 counts
0.01Hz ~ 100KHz
High Level: over 2/3 of input level Digital fine adjust: pVzro: Settable range: 0~+99999
0.01Hz ~ 140KHz Voltage Pulse
Low Level: under 1/3 of input level pVspn: Settable range: 0~+99999
(optional)
Pick Up Sensor Specified by order
Input Mode(NPN, PNP, Contact) & Level(5Vp, 12Vp, 24Vp) Reading Stable Function
changeable by dip switch of rear terminal block. Average: Settable range: 1~99 times
Moving average: Settable range: 1(None)~10 times
Calibration: Doesn’t need calibration Digital filter: Settable range: 0(None)/1~99 times
Input range: Auto range: 0.01Hz ~ 100KHz (~140KHz in option);
Accuracy: ≤± 0.005% of FS± 1C; Control Functions(option)
Sampling time: 15 cycles/sec(≥15Hz); Set-points: Four set-points
f cycles/sec(≤15Hz) Control relay: Four relays
Response time: ≤100 m-sec(when the AvG = “1”) Relay 2 & Relay 3: Dual FORM-C, 5A/230Vac, 10A/115V
Time out function: Auto, Manual programmable, In manual mode, the period Relay 1 & Relay 4: Dual FORM-A, 1A/230Vac, 3A/115V
of time out can be set 0.0 sec~999.9sec D.P. of set point: Programmable from 0 / 0.0 / 0.00 / 0.000 / 0.0000
Relay energized mode: Energized levels compare with set-points:
Display & Functions Hi / Lo / Go.12 / Go.23 / Hi.HLd / Lo.HLd; programmable
LED: Numeric: 5 digits, 0.8”(20.0mm)H red high-brightness LED DO function: Energized by RS485 command of master.
Relay output indication: 4 square red LED Energizing functions: Start delay / Energized & De-energized delay / Hysteresis /
RS 485 communication: 1 square orange LED Energized Latch
E.C.I. function indication: 3 square green LED Start band(Minimum level for Energizing): 0~9999counts
Max/Mini Hold indication: 2 square orange LED Start delay time: 0:00.0~9(Minutes):59.9(Second)
Display type: RPM / RPS / Linear line speed / Frequency programmable Energized delay time: 0.00.0~9(Minutes):59.9(Second)
Display range: 0.0000~99999 with auto moving of decimal point De-energized delay time: 0.00.0~9(Minutes):59.9(Second)
Resolution of PV: Decimal point will Auto-changed according to input Hysteresis: 0~5000 counts
(Auto-Moving for d.p.) Auto / Semi-Auto / Fix; 3 mode programmable

CS2-RL-2010-10-15 C2-11-1/9
CSM-321S

External Control Inputs(ECI)


Input mode: 3 ECI points, Contact or open collect input, Level trigger
„ DIMENSIONS
Functions: Relative PV (Tare) / PV Hold / Reset for Max or Mini. Hold /
CS2-VA

DI / Reset for Relay Energized latch


Debouncing time: Settable range 5 ~255 x (8m seconds) FRONT VIEW 48.0

Analogue output(option)
Accuracy: ≤± 0.1% of F.S.; 16 bits DA converter 96.0 100.0
Ripple: ≤± 0.1% of F.S. 8.0 12.0
Response time: ≤100 m-sec. (10~90% of input)
CSM- CSM-321S CSM-

Isolation: AC 2.0 KV between input and output Dimensions: 96mm x 48mm x 120mm
PANEL CUT-OUT 44.0+0.2 Panel Cutout: 93mm x 45mm (advise)
Output range: Specify either Voltage or Current output in ordering
Voltage: 0~5V / 0~10V / 1~5V programmable
Unit: mm
Current: 0~10mA / 0~20mA / 4~20mA programmable 92.0+0.2
Output capability: Voltage: 0~10V: ≥ 1000Ω;
Current: 4(0)~20mA: ≤ 600Ω max
aOhs(output range high): Settable range: -19999~29999
Functions:
aOls(output range Low): Settable range: -19999~29999
„ INSTALLATION
aOlmt (output High Limit): 0.00~110.00% of output High The meter should be installed in a location that does not exceed the
Digital fine adjust: aOzro: Settable range: -38011~+27524 maximum operating temperature and provides good air circulation.
aOspn: Settable range: -38011~+27524

RS 485 Communication(option)
Modbus RTU mode
COM
Protocol: R
RL
R
C
C
R

1200/2400/4800/9600/19200/38400 programmable
C
Baud rate:
8 bits
2
Kg/cm
Data bits: ENT/FN ? ? ?
CS2-RL

Parity: Even, odd or none (with 1 or 2 stop bit) programmable


FIX HOLDER:
Address: 1 ~ 255 programmable PANEL CUT-OUT: 104 mm(L) / W M3
Remote display: to show the value from RS485 command of master 92+0.2(W) x 44+0.2(H) mm
1.0~8.0 mm
Distance: 1200M
Terminate resistor: 150Ω at last unit.
„ CONNECTION DIAGRAM
CSM-321S CSM- CSM-321S CSM- CSM-321S CSM-

Electrical Safety
Relay 1 Relay 2 Relay 3 Relay 4 RS 485 Analogue
Dielectric strength: AC 2.0 KV for 1 min, Between Power / Input / Output / Case port output
Insulation resistance: ≥100M ohm at 500Vdc, Between Power / Input / Output Terminal blocks:
a c b c a b c a a c A B 10A/300Vac, M2.6,
Isolation: Between Power / Input / Relay / Analogue / RS485 / E.C.I.
EMC: EN 55011:2002; EN 61326:2003 21 22 23 24 25 26 27 28 29 30 31 32 33 34 M2.6, 1.3~2.0mm2
(16~22AWG)
Safety(LVD): EN 61010-1:2001
ECI1 ECI2 ECI3 COM

Environmental 11 12 13 14 15 D-S
3 4 5 6 7 8 9 10
Dip-Switch
Operating temp.: 0~60 ˚C
Operating humidity: 20~95 %RH, Non-condensing AC115V
D-S 1 2 3 4 5
AC230V AC 86~265V
+IN

0V
+V

Temp. coefficient: ≤100 PPM/˚C NPN ON


FG
PNP ON ADH DC 100~300V
Storage temp.: -10~70 ˚C Frequency/Pulse M.C. ON ON External
ADL DC 20~56V
5VP Control
Enclosure: Front panel: IEC 549 (IP54); Housing: IP20 SIGNAL INPUT 12VP
24VP
ON
ON Input AUX. POWER
D-S is on, when it is
on down side.
Mechanical
Dimensions: 96mm(W) x 48mm(H) x 120mm(D) Please check the voltage of power supplied first, and then connect to
Panel cutout: 92mm(W) x 44mm(H) the specified terminals. It is recommended that power supplied to the
Case material: ABS fire-resistance (UL 94V-0) meter be protected by a fuse or circuit breaker.
Mounting: Panel flush mounting Power Supply
Terminal block: Plastic NYLON 66 (UL 94V-0)
10A 300Vac, M2.6, 1.3~2.0mm2(16~22AWG) 7 8 9 10
Weight: 550g / 350g(Aux. Power Code: ADH or ADL) 1A Fuse
L L AC115/230V
N N AC85~264V
Power
G G
Power supply: AC115/230V,50/60Hz; Filter or Transformer
Optional: AC 85~264V, DC 100~300V, DC 20~56V
Excitation supply: DC12V/24V, 30mA maximum in standard
Sensor input connection Please change the dip-switch on rear
Power consumption: 5.0VA maximum of meter to match the input mode and
Back up memory: By EEPROM level.
11 12 13 14 15
D-S 1 2 3 4 5
NPN ON
+IN

+V

0V

„ FRONT PANEL +Vdc


PNP
Mech. Contact
Voltage pulse 5VP
ON
ON
ON
Out
0V Voltage pulse 12VP ON
+Vdc Voltage pulse 24VP ON
Relay status Max. Hold status Out D-S is on when it is in down site
0V
Indication RL1 COM
M.H
Comm. status
RL 2 CI11
2
RL3
RL4
CI2
CI3
Control Input
M.H status
Display screen
ENT/FN ? ? ? RPM Mini. Hold status
Operation Key
Engineer Unit

C2-11-2/9 CS2-RL-2010-10-15
Remote Display by RS485 command rs485 :
RS485 Communication Port
The meter will show the value that received from RS485
sending. In past, The meter normally receive 4~20mA or

CS2-VA
Max. Distance: 1200M 0~10V from AO or digital output from BCD module of PLC.
Terminate Resistor
(at latest unit): We support a new solution that PV shows the value from
A B 120~300ohm/0.25W RS485 command of master can so that can be save cost and
(typical: 150ohm)
wiring from PLC.
30 31 32 Other functions : The meter is also support relative PV (∆PV) and PV hold
RS485 Port functions that set in [ eci group]. Please refer to
explain of ECI functions.

CSM- CSM-321S CSM-


„ FUNCTION DESCRIPTION
Input Functions
Input range: Auto-Range: 0.01Hz~100.00KHz(option 140KHz), Low cut: Settable range from -19999~+99999 counts.
The meter has been designed very wide input auto-range from The users can set the value range.
0.01Hz~100.00KHz (Option: 0.01Hz~140.00KHz) that can cover almost 1. If set the positive value (X1) here to display "0" which it
any application for RPM, Linear Line Speed and Frequency. User doesn’t expressed to be low-cut the PV between "+X1 (plus)" &
need to specify the input range. "-X1(minus)" /absolute value
Auto range display: programmable between Auto Range / Semi-Auto Range / PV< l Setting value (X1) l, the display will be shown 0
manual range, The description as below, EX: Low Cut is set for 0.50. If the display is from
Auto range auto: The decimal point will be auto changed according to the input -0.50~+0.50, that will be 0.
frequency so that keep reading in the highest resolution. Low Cut set to be +0.50
Semi-Auto range semi: Present PV according
The decimal point will be auto changed according to the input Value to input signal

frequency to keep reading in the highest resolution under [ lOcut]

CS2-RL
)50 0.50
setting position of decimal point, According to the setting of X1
decimal point. So, it’s possible to show “overflow”, if the input
X1 Low cut
frequency is over the display range. -0.50 function
Manual range manul: The decimal point will be fixed
Time out of input: Low Cut is set for 0.50, if the PV is
from -0.50~+0.50, that display will be 0.
In the case of low frequency, the meter can not to identify that is low

CSM-321S CSM- CSM-321S CSM- CSM-321S CSM-


frequency and no input until the next pulse input. Sometimes, it takes a 2. If set the negative value (X2) here to display "X2" which it
long period. expressed to be low-cut the PV that it's under the X2 setting
The meter builds in a time out function to cut out the reading to be “0”. value;
There are two modes manul / auto can be programmed. PV< Setting value(X2), the display will be shown X2.
Manual manul: There is a period named ito can be set from 0.0 sec ~ EX: Low Cut is set for -0.01. If the display is < -0.01, and all
999.9 sec. The reading will display “0”, when the next pulse the display will be -0.01.
doesn’t input during the setting time. Low Cut set to be -0.10
Auto range auto: The reading will display “0”, when the next pulse doesn’t input Present PV according
during the time that gave by formula of meter’s firmware. Value to input signal

Period of time out: Settable: 0.0 sec~999.9sec [ lOcut]


-)10
If the time out mode [itOmd] set to be manul, it’s will be
show out.
X2 -0.10
Low cut
function

Display & Functions Low Cut is set for -0.10, if the PV is


under (< = -0.10), that display will be -0.10.
Max / Mini recording: The meter wills storage the maximum and minimum value in
[ user level] during power on in order to review drifting of PV. Digital fine adjust: Settable range: -19999~+29999
Display functions: PV / Max(Mini) Hold / RS 485 programmable in [dsply] Users can get Fine Adjustment for Zero & Span of PV by front key of the
(Please refer to step A-07) function of [input group] meter, and “Just Key In” the value which user want to show in the
Present Value pv: The display will show the value that Relative to Input signal. current input signals.
Maximum Hold maXhd / Minimum Hold miNhd : Especially, the [pVzro] & [pVspn] are not only in zero & span of PV, but
The meter will keep display in maximum(minimum) value also any lower point for [pVzro] & higher point for [pVspn]. The meter
during power on, until manual reset by front key in [User will be linearization for full scale.
level], rear terminal is close [External Control Input(ECI) ] The adjustment can be clear in function [ZSclr]
or press front down or up key to reset (according to setting,
Default Input:[ lOsc]: )00, [ hIsc]: 19(99
please refer to the function of the ECI Group) Digital fine adjustment:
X Please find the M.H sticker that enclosure the package input 2.75V, [pVzro]set to be 8)00
of the meter to stick on the right side of square orange LED SCALE input 9.00V, [pVspn]set to be 17)00
Display: Low point from 55.00 to 80.00
Max. ( Mini.) Hold & Reset [ h Isc ] High point from 180.00 to 170.00
19(99
M axim um Hold
Present 18)00
Value 17)00

10)00
8)00
Reset the Max
(M ini) H old by
Level O 5%00
EC I or F. Key Trigger N
[ l Osc ]
)00 INPUT _
0V 2.75V 5V 9.00V 10V

CS2-RL-2010-10-15 C2-11-3/9
CSM-321S

Compensation factor: Settable range: 0.001~9.999 Go-1.2 go-!2: This function is programmable in Relay 4 only.
The factor is compensation of display. There are some applications that If the Relay 4 set to be Go function, the relay will compare with
are indirect detection of sensor as like as Gear, wheel. User can set the [ry!sp] and [ry@sp].
CS2-VA

factor to compensate the display. Go relay energized when the condition is


User installs the proximity switch to detect the RPM of left wheel, and want [ry!sp] (Hi) > PV > [ry@sp] (Lo)
to show the right wheel. It’s easy to set the factor to do it. Go-2.3 go-@3:. This function is programmable in Relay 4 only.
Frequency: 50Hz; Left wheel: diameter: 1M; Right wheel: diameter: 0.35M If the Relay 4 set to be Go function, the relay will compare with
[ry@sp] and [ry#sp].
Go relay energized when the condition is
CSM- CSM-321S CSM-

[ry@sp] (Hi) > PV > [ry#sp] (Lo)


Hi / Lo / Go Relay Energized
Set:
PV. type pVtyp to be RPM rpm. Hi Setting

Pulse/Rotation ppr to be 1 1 Pulse/Rotation


The meter will show 1480RPM of left wheel.
Set: factr to be 2.857(1M/0.35M), then the meter will show 4228.5RPM for Lo Setting
right wheel
Hi Relay Energized ON

Reading Stable Function Lo Relay Energized ON


Go Relay Energized ON ON ON
Average display:
Jittery Display caused by the noise or unstable signal. User can set the times to average Hi.HLd hIhld (Lo.HLd lOhld) :
the readings, and to get smoothly display. The relay energized with latched function is for electrical
The meter’s sampling is 15cycle/sec. If the [ avg](Average) set to be 3 to safety and human protection.
express the display update with 5 times/sec. The meter will calculate the sampling 1-3 For example, a current meter relay installed for the over
and update the display value. At meantime, the sampling 4-6 will be processed to current alarm of motor. Generally, over current of motor
calculate. caused by over load, mechanical dead lock, aging of insulation
Average set to be 3 and so on.
CS2-RL

Sample 1 Sample 2 Sample 3 Sample 4 Sample 5 Sample 6 ……. ……. Above cases will alarm in the meter, if the user doesn't figure
out the real reason and re-start the motor. It may damage the
Display Update Value = Display Update Value = motor. The functions of Hi.HLd & Lo.HLd are designed must
(Sample 1 + Sample 2 + Sample 3)/3 (Sample 4 + Sample 5 + Sample 6)/3
be manual reset the alarm after checking out and solving the
Remark: The higher average setting will cause the response time of issue. It's very important idea for electrical safety and human
Relay and Analogue output slower. protection.
CSM-321S CSM- CSM-321S CSM- CSM-321S CSM-

Moving average: As the PV Higher (or lower) than set-point, the relay will be
Jittery Display caused by the reasons as like as noise or unstable signal. User can set energized to latch except manual reset by from key in [ user
the times to average the readings, and get smoothly display. level] or [ eci](ECI) set to be rYrst is closed.
The meter’s sampling is 15cycle/sec. If the [ Mavg](Moving Average) set to be 3 Hi(Lo) Energized Latch & Reset
expressed the display update with 15 times/sec., [ry_.sp] Hi Setting
In the first updated display value will be same as average function. In the next updated
display value, the function will get the new fourth sample (sample 4) then throw away the
first sample (sample 1) that the newest 3 samples(sample 2,3,4) will be calculated for the [ry_.md]
updated display value. hIhld Hi.HLd(H igh H old)
Relay Energized ON
Moving Average set to be 3
[ ecI_] Reset the relay Hold ON
Sample 1 Sample 2 Sample 3 Sample 4 Sample 5 Sample 6 ……. ……. Level Trigger
rYrst by ECI or Front Key
In first 3 samples, Display Update Value
= (Sample 1 + Sample 2 + Sample 3)/3 DO function do: The function has been designed not only a meter but also an
Display Update Value
I/O interface. In the case of motor control cabinet can't get the
= (Sample 2 + Sample 3 + Sample 4)/3 remote function. It's very easily to get the ON/OFF status of
Display Update Value switch from CS2 series with RS485 function.
= (Sample 3 + Sample 4 + Sample 5)/3 If the [ry_.md] had been set do, the relay will be
Display Update Value energized by RS485 command directly, but no longer to
= (Sample 4 + Sample 5 + Sample 6)/3 compare with set-point.
Remark: The higher moving average setting wouldn’t cause the Start delay band and Start delay time:
response time of Relay and Analogue output slower after first 3 The functions have Been designed for,
samples. ► To avoid starting current of inductive motor (6 times of rated current)
Digital Filter: The digital filter can reduce the magnetic noise in field. with alarm.
The digital filter can reduce the influence of spark noise caused by ► If the ry_.md relay energized mode had been set to be lo(Lo) or
magnetic of coil. lOhld(Lo & latch). As the meter is power on and no input to display
If the values of samples are over digital filter band (fix in firmware and about the "0" caused the relay will be energized. User can set a band and
5% of stable reading) 3 times (Digital Filter set to be 3) continuously, the delay time to inhibit the energized of relay.
meter will admit the samples and update the new reading. Otherwise, it Start band rYsb (Fig.2-c): Settable range from 0~9999 Counts
will be as treat as a noise and skip the samples. Start delay time rYsd (Fig.2-d): Settable range from 0.0(s)~9(m)59.9(s);
Start Delay Fig.2
Control Functions(option) Inhibit
Relay energized mode: Hi / Lo / Go-1.2 / Go-2.3 / Hi.HLd / Lo.HLd / DO programmable Inhibit
Hi hi(Fig.1-c): Relay will energize when PV > Set-Point [ry_.sp] Hi Setting

Lo lo(Fig.1-d): Relay will energize when PV < Set-Point


[ rYsb] Start Band
Hi / Lo Relay Energized Fig.1
c Relay
[ry_.sp] Hi Setting Energized Start Delay Time ON

d[ rYsd]

[ry_.sp] Lo Setting
[ry_.md]
hi Hi Relay Energized c ON
lo Lo Relay Energized ON d

C2-11-4/9 CS2-RL-2010-10-15
CSM-321S
Hysteresis ry_.hy (Fig.3-c): Settable range from 0~9999 Counts Hi(Lo) Energized Latch & Reset
As the display value is swing near by the set point to cause the relay on [ry_.sp] H i Setting
and off frequently. The function is to avoid the relay on and off frequently

CS2-VA
such as compressor…….etc.,
Relay energized delay ry_.rd (Fig.3-d): Settable range from 0.0(s)~9(m)59.9(s);
[ry_.md]
The function is to avoid the miss action caused by noise. Sometime, the hIhld H i.H Ld(High H old)
R elay Energized ON
display value will swing caused by spark of contactor…etc.. User can set
a period to delay the relay energized. [ ecI_] Reset the relay Hold ON
Level Trigger
rYrst by ECI or Front Key
Relay de-energized delay ry_.fd (Fig.3-e): Settable range from 0.0(s)~9(m)59.9(s);
Energized / De-energized Fig.3 Debouncing time:

CSM- CSM-321S CSM-


Delay & Hysteresis The function is for avoiding noise signal to into the meter. And The basic
[ry_.sp] period is 8mseconds. It means you set the number that has to multiple 8
Hi Setting m-seconds.
[ry_.hy]
Energized delay time For example:

De-energized
Hysteresis
c

delay time
[debnc]set to be 5, it means 5 x 8mseconds = 40mseconds
[ry_.rd] [ry_.fd]
d e Analogue output(option)
Relay Please specify the output type either a 0~10V or 4(0) ~ 20mA in ordering.
Energized ON
The programmable output low and high scaling can be based on various
display values. Reverse slope output is possible by reversing point positions.
Output range: Voltage: 0~5V / 0~10V / 1~5V programmable
External Control Inputs(ECI) Current: 0~10mA / 0~20mA / 4~20mA programmable
The three external control inputs are individually programmable to perform Functions: Output High / Low scale, output limit, fine adjustment
specific meter control or display functions. All E.C.I. have been designed in Output range high [ aOhs]:
level trigger actions. Please pay attention, the ECI1 or ECI2 input will be To setting the Display value High to versus output range
disable while UP or Down Key has been set to be “YES”. High(as like as 20mA in 4~20)

CS2-RL
Functions: Relative PV / PV Hold / Reset Max or Mini. Hold / DI / Reset Output range low [ aOls]:
for Relay Energized latch programmable. To setting the Display value Low to versus output range
Relative PV reLpv or Tare: Low(as like as 4mA in 4~20)
The [ ecI_] can be set to be reLpv function. When the Set Scaling: [ lOsc]: 0.00, [ hIsc]: 199.99;
E.C.I. is closed, the reading will show the differential value. SCALE Output: [ aOls]: 50.00(Display Value Low),
[ aOhs]: 150.00(Display Value High)
Relative PV E C I_ has closed, and 199.99

CSM-321S CSM- CSM-321S CSM- CSM-321S CSM-


Prese nt
then P V g oe s to “0” [ aOhs]
Value 150.00

R elativ e PV 100.00
E C I_ has opened, [ aOls ]
a nd then displa y
s how s PV 50.00
R elativ e
P V(?PV ) b y Level ON [ ecI_] 0.00
ECI or F.Key Trig ger r eL pv 0.00% 50.00% OUTPUT 100.00%
PV Hold pVhld: The [ ecI_] can be set to be pVhld(PV Hold) function. The range between [ aOhs] and [ aOls] should be over
PV Hold & Reset 20% of span at least; otherwise, it will be got less resolution of
analogue output.
Present PV Hold
Value Output High Limit [ aOlmt]:
0.00~110.00% of output High User can set the high limit of
output to avoid a damage of receiver or protection system.
Set Scaling: [ lOsc]: 0.00, [ hIsc]: 199.99;
Reset PV Hold Output: [ aOls]: 50.00(Display Value Low),
by E.C.I. or
O ON Level ON [ ecI_]
N Trigger SCALE [ aOhs]: 150.00(Display Value High)
Front Key pVhld [aOlmt]: 80.00%( of Output Range)
199.99
Reset for Maximum or Minimum Hold Mrst: [ aOhs] Ao.LMt: 80.00%
When the [dsply] function in [input group] selected 150.00
maXhd or miNhd, the display will show Maximum or
100.00
Minimum value. [ aOls ]
The [ ecI_] function can be set to be Mrst 50.00
function to reset the maximum and minimum value 0.00 OUTPUT
in [User Level] by terminals of ECI (close). Please refer 0.00% 50.00% 80.00% 100.00%
[aOlmt]
to the figure as below.
Max. ( Mini.) Hold & Reset Fine zero & span adjustment:
M axi in User Level Users can get Fine Adjustment of analogue output by front key of the
Prese nt
Value meter. Please connect standard meter to the terminal of analogue output.
To press the front key (up or down key) of meter to adjust and check the
Reset the max storage output.
when ECI has closed
Zero adjust [aOzro]: Fine Zero Adjustment for Analog Output;
Reset the Max. [ ecI_]
(M ini.) storage
L evel O Settable range: -38011~27524;
by E.C .I. Trigg er N M rst
Span adjust [aOspn]: Fine Span Adjustment for Analog Output;
DI di : The E.C.I can be set to be di function, when the meter Settable range: -38011~27524;
building in RS485 port. It is easier to get remote monitoring a
switch status through the meter as like as DI of PLC.
Reset for Relay Energized Latch rYrst:
If the relay energized mode has been set to be
hIhld(Energized latch), and the [ ecI_] can be set to be
rYrst(Reset the Relay energized latch). When the PV
meets the condition of relay energizing, the relay will be
energized and latch until the ECI is to be closed.

CS2-RL-2010-10-15 C2-11-5/9
CSM-321S

RS 485 communication(option) Remote Display:


CS2 series supports Modbus RTU mode protocol to be used as Remote The meter will show the value that received from RS485 command. In
Terminal Unit (RTU) for monitoring and controlling in a SCADA past, The meter normally receive 4~20mA or 0~10V from AO or digital
CS2-VA

(Supervisor Control And Data Acquisition) system. The baud rate can be output from BCD module of PLC .We support a new solution that PV
up to 38400 bps. It's not only can be read the measured value and DI shows the value from RS485 command of master so that can be save
(external control inputs) status but also controls the relays output (DO) cost and wiring from PLC.
by RS485 communication ports. When the [ dsply] set to be RS485, it means, the PV screen will show the
CS2-PR & SC2-RL APPLICATION MEASURING & RS485 COMMUNICATION number from RS485 command & data. The data(number) will be same as
RS485 wiring 1.2KM maximum
Terminate Resistor: PV that will compare with set-point, analogue output and ECI functions so
RS 485 Modbus RTU Mode (up to 38400bps)
CSM- CSM-321S CSM-

Analog Output 0~10V/0(4)~20mA


that is to control analogue output, relay energized and so on.
CS2 APPLICATION FOR REMOTE DISPLAY FROM RS485 COMMAND
4 Relay outputs:
Functions: Hi(Lo) alarm / Hi(Lo)
energized hold / Go RS 485 Modbus RTU Mode (up to 38400bps)
function / DO function
R L1
COM
RL1
COM RS485 wiring 1.2KM maximum
R L2
RL3
RL4
ECI1
ECI2
ECI3
RL2
RL3
RL4
ECI1
ECI2
ECI3
Terminate Resistor:
ENT/FN ◄ ▲ ▼ Kg/cm2 ENT/FN ◄ ▲ ▼ Kg/cm2

3 External Control Inputs:


Functions: Relative PV / PV hold / Reset for
Max(Mini) / Reset for relay latch / DI
Application: Leakage test / Thermal Switch /
Circuit Breaker / Push Button / … RL1
RL2
COM

ECI1
RL1
RL2
COM

ECI1
RL3 ECI2 RL3 ECI2
RL4 ECI3 RL4 ECI3

2 2
ENT/FN ◄ ▲ ▼ Kg/cm ENT/FN ◄ ▲ ▼ Kg/cm

Calibration System calibration by front key. The process of calibration,


please refer to the operating manual

Optional Function
Customize function with quantities is welcome. Please contact with our
sales for detail. The appendix code of optional function will be added
CS2-RL

behind the code of auxiliary power as like as xxx-A-HSM(High speed mode.

„ ERROR MESSAGE
BEFORE POWER ON, PLEASE CHECK THE SPECIFICATION AND CONNECTION AGAIN.
SELF-DIAGNOSIS AND ERROR CODE:
CSM-321S CSM- CSM-321S CSM- CSM-321S CSM-

DISPLAY DESCRIPTION REMARK


ovfl Display is positive-overflow (Signal is over display range) (Please check the input signal)

-ovfl Display is negative-overflow (Signal is under display range) (Please check the input signal)
ADC is positive-overflow (Signal is higher than input range
ovfl high 20%)
(Please check the input signal)
ADC is negative-overflow (Signal is lower than input range low
-ovfl -20%)
(Please check the input signal)

eep fail EEPROM occurs error (Please send back to manufactory for repaired)

aiCng pv Calibrating Input Signal do not process (Please process Calibrating Input Signal)

aic fail Calibrating Input Signal error (Please check Calibrating Input Signal)

aoCng pv Calibrating Output Signal do not process (Please process Calibrating Output Signal)

aoc fail Calibrating Output Signal error (Please check Calibrating Output Signal)

C2-11-6/9 CS2-RL-2010-10-15
CSM-321S
„ FRONT PANEL:
Max. Hold status „ Operating Key: 4 keys for Enter(Function) / Shift(Escape) /

CS2-VA
Relay status
Indication R L1 COM
M.H
Comm. status Up key / Down key
RL2 CI11
2
RL3
RL4
CI2
CI3
Control Input Setting Status Function Index
M.H status Increase number Go back to previous
Display screen Up key
ENT/FN ? ? ? RPM Mini. Hold status function index
Operation Key
Engineer Unit Down key Decrease number Go to next

CSM- CSM-321S CSM-


function index
Shift key Shift the setting Go back to this function
„ Numeric Screens position index, and abort the setting
0.8”(20.0mm) red high-brightness LED for 4 2/3 digital present value.
„ I/O Status Indication Enter/Fun Setting Confirmed From the function index to
● Relay Energized: 4 square red LED key and save to EEProm get into setting status
RL1 display when Relay 1 energized; „ Pass Word Pcode: Settable range: 0000~9999;
RL2 display when Relay 2 energized; User has to key in the right pass word so that get into【Programming
RL3 display when Relay 3 energized; Level】. Otherwise, the meter will go back to measuring page. If user
RL4 display when Relay 4 energized; forgets the password, please contact with the service window.
● External Control Input Energized: 3 square green LED „ Function Lock: There are 4 levels programmable.
ECI1 display when E.C.I. 1 close(dry contact) ● None none: no lock all.
ECI2 display when E.C.I. 2 close(dry contact) ● User Level user: User Level lock. User can get into
ECI3 display when E.C.I. 3 close(dry contact) User Level for checking but setting.
● RS485 Communication: 1 square orange LED

CS2-RL
● Programming Level eng: Programming level lock.
COM will flash when the meter is receive or send data, and COM flash User can get into programming level for checking but setting.
quickly means the data transient quicker. ● ALL all: All lock. User can get into all level for checking but
● Max/Mini Hold indication: 2 square orange LEDs setting.
CO M.H displayed: When the display function has been selected in „ Front Key Function
Maximum or Minimum Hold function. ● The Key can be set to be the same function as the setting of ECI1.

CSM-321S CSM- CSM-321S CSM- CSM-321S CSM-


„ Stickers: Ex. The ECI1 set to be pVhld and the function [E1=up] set to be
Each meter has a sticker what are functions and engineer label yes in [ eci group]. When user presses Key, the PV will hold
enclosure. as like as ECI1 close.
● Relay energized mode: H H H i L o L L D O ● The Key can be set to be the same function as the setting of ECI2.
● E.C.I. functions mode: Ex. The ECI2 set to be reLpv and the function [E2=dn] set to be
PV.H(PV Hold) / Tare / DI(Digital Input) yes in [ eci group]. When user presses Key, the PV will show
M.RS(Maximum or Minimum Reset) / relative value as like as ECI2 close.
R.RS(Reset for Relay Latch) X If the front key function has been set, the terminal input for ECI
● Engineer Label: over 80 types. will be disabling.

CS2-RL-2010-10-15 C2-11-7/9
CSM-321S

„ OPERATING DIAGRAM (The detail description of operation, please refer to operating manual.)
User Level
CS2-VA

Power ON
Press for 1 sec. can back to Measuring
If the [dsply]
***** Self-diagnosis
299(9 10000 ry$sp: Relay 4
no Mrst: Reset the

0−0−1

0−4

0−8
function has Set-point saved value of
pv been set rs485 ry$sp -19999~29999 Mrst Maximum &
CSM- CSM-321S CSM-

pv: Present Minimum


Value yes / no
Show the model ry!sp: Relay 1 rYrst: Reset model number
cs@rl 10000 no ver!4
0−1

0−5

0−9
number Set-point for energized firmware
ry!sp -19999~29999 rYrst Latch of Relay cs@rl version
Checking only
yes / no

ver!4 Show
10000 ry@sp: Relay 2
)0000 min: the
299(9 Cyclic to first
0−2

0−6

0−0−1
the firmware Set-point Minimum value page
version ry@sp -19999~29999 min of PV saving pv
Checking only
MEASURING
10000 ry#sp: Relay 3
29999 max: the
0−3

0−7
PAGE
299(9 ry#sp
Set-point Maximum value
ENT
Press 1sec -19999~29999 max of PV saving
Checking only
Press 1sec
Enter the
enter password to
CS2-RL

access Engineer
Pcode Level
ENT

NO
Pass Code Programming Level
YES

Default:1000 Press for 1 sec. can back to Measuring



CSM-321S CSM- CSM-321S CSM- CSM-321S CSM-

input relay eci ao



INPUT RELAY EXTERNAL ANALOGUE
GROUP GROUP CONTROL OUTPUT


group group group INPUT (E.C.I)
group GROUP
ENT ENT ENT ENT
GROUP
pVtyp: Present rYsb: Start band ecI1: External aOtyp: Analogue
lNspd Value type 0 for Relay reLpv Control Input 1 A4-20 Output type
A−1

B−1

C−1

D−1

energized selection
pVtyp lNspd /
rps /
rpm /
hz /
rYsb 0~9999counts
ecI1 none / reLpv /
pVhld / Mrst /
aOtyp V0-10 / V 0-5 /
khz rYrst / di V 1-5 / A0-10 /
A0-20 / A4-20
If [pVtyp] has rYsd: Start delay ecI2: External aOls: Analogue
1 )0)0 pVhld )0
A−2−1

B−2

C−2

D−2

been selected time for Relay Control Input 2 Low Output


hz or khz, This energized versus Low
ppr function will be rYsd 0.00.0~
ecI2 none / reLpv /
pVhld / Mrst /
aOls Scale
hidden 9(M).59.9(S) -19999~29999
PPr: rYrst / di
Pulse/rotation
1~99999
If [pVtyp] has ry!md: Relay 1 ecI3: External aOhs: Analogue
m/mn hi Mrst 100)0
A−2−2

B−3

C−3

D−3

been selected energized mode Control Input 3 High Output


lNspd, This versus High
Eunit function will be ry!md off / lo /
hi / lOhld /
ecI3 none / reLpv /
pVhld / Mrst /
aOhs Scale
showed out -19999~29999
hIhld / do rYrst / di
Eunit:
Engineer Unit
m/mn / cm/mn /
yd/mn / ft/mn
If [pVtyp] has ry!hy: Relay 1 debnc: aOzro: Fine Zero
)1000 0 12 0
A−2−3

B−4

C−4

D−4

been selected Hysteresis Debouching of Adjustment for


lNspd, This Analogue Low
diamt function will be ry!hy 0~5000 counts debnc external control
Input
aOzro Output
showed out 5~255(x8ms) -38011~27524
diamt:
Diameter
0.0001~9.9999M
dp: Decimal ry!rd: Relay 1 E1=up: ECI.1 set aOspn: Fine
0 )0)0 no 0
A−3

B−5

C−5

D−5

Point of energized delay to be UP Key Span Adjust. for


set-point time Analogue High
dp 0~0.0000
ry!rd 0.00.0~
E1=up function
yes / no
aOspn Output
9(M).59.9(S) -38011~27524
Next Page Next Page Next Page Next Page

C2-11-8/9 CS2-RL-2010-10-15
CSM-321S
factr: ry!fd: Relay 1 E2=dn: ECI.2 set ZSclr: Zero &
!000 )0)0 no none
A−4

B−6

C−6

D−6
Compensation de-energized to be Down Key Span Clear for
Factor delay time Adjustment
factr 0.001~9.999
ry!fd 0.00.0~
E2=dn function
yes / no
ZSclr none / aOzro /

CS2-VA
9(M).59.9(S) aOspn / both
pVspn: Fine ry@md: Relay 2 aOlmt: Analog
0 hi 11)00
A−5

B−7

D−7
High point energized mode Output High
Adjustment for Limit
pVspn PV display
ry@md off / lo /
hi / lOhld /
aOlnt 0.00~110.00%
0~+99999 hIhld / do

CSM- CSM-321S CSM-


Sclr: Clear Fine ry@hy: Relay 2
no 0
A−6

Span B−8 Hysteresis


Adjustment for
Sclr PV display
ry@hy 0~5000 counts

yes / no
dsply: Display ry@rd: Relay 2
pv )0)0
A−7

B−9

Function energized delay


time
dsply pv / miNhd /
maXhd / rs485
ry@rd 0.00.0~
9(M).59.9(S)
lOcut: Low Cut ry@fd: Relay 2
0 )0)0 rs485 RS485
A−8

B−10

Function de-energized
delay time GROUP
lOcut 0~99999
ry@fd 0.00.0~
group
ENT
9(M).59.9(S)
itOmd: Input ry#md: Relay 3 adres: Device
auto hi 1
A−9

B−11

CS2-RL
time out Mode number of the

E−1
energized mode
meter
itOmd auto / manul
ry#md off / lo / adres 1~255
hi / lOhld /
hIhld / do
If [itOmd] has ry#hy: Relay 3 baud: Baud
)0 0 9600
A−10

B−12

E−2
been selected Hysteresis rate
ito manul, This
ry#hy 0~5000 counts baud 1200 / 2400 /

CSM-321S CSM- CSM-321S CSM- CSM-321S CSM-


function will be 4800 / 9600 /
showed out 19200 / 38400
ito: How long
will be time out
0.0~999.9sec
range: Reading ry#rd: Relay 3 prity: Parity
auto )0)0 NstB2
A−11

B−13

E−3

Range with energized delay NstB1 / NstB2 /


decimal point time
range switching.
ry#rd 0.00.0~
prity odd / even

auto / semi / 9(M).59.9(S)


manul
avg: Average ry#fd: Relay 3
5 )0)0
A−12

B−14

update for PV de-energized


delay time
avg 1(None)~
99 times
ry#fd 0.00.0~
9(M).59.9(S)
Mavg: Moving ry$md: Relay 4
1 hi
A−13

B−15

Average energized mode


update for PV
Mavg 1(None)~
ry$md off / lo /
hi / lOhld /
10 times hIhld / do /
go-!2 / go-@3
Dfilt: Digital ry$hy: Relay 4
0 0
A−14

B−16

filter Hysteresis
Dfilt 0(None)/1~
99 times
ry$hy 0~5000 counts

dNkey: Down ry$rd: Relay 4


none )0)0
A−15

B−17

key function energized delay


time
dNkey none / reLpv /
pVhld / Mrst /
ry$rd 0.00.0~
rYrst 9(M).59.9(S)
Pcode: Pass ry$fd: Relay 4
0 )0)0
A−16

B−18

Code for enter de-energized


Engineer Level delay time
Pcode 0000~9999 ry$fd 0.00.0~
9(M).59.9(S)
Flock: Function
none
A−17

Level Lock
Flock none / user /
eng / all

X Plesae refer to operating manual for detail description

CS2-RL-2010-10-15 C2-11-9/9

You might also like