Generator and Transformer Protection

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Sheet 4

5
𝑖1 = 320 + 𝑗0 ∗ = 4 + 𝑗0 𝐴 = 4 0 𝐴
400

5
𝑖1 = 304 + 𝑗0 ∗ = 3.8 + 𝑗0 𝐴 = 3.8 0 𝐴
400

𝑖1 +𝑖2
𝑖1 − 𝑖2 = 4 − 3.8 = 0.2 𝐴 = 3.9 𝐴
2
𝑖1 +𝑖2
𝑠𝑙𝑜𝑝 ∗ = 0.1 ∗ 3.9 = 0.39 A
2

𝑖1 + 𝑖2
∵ (𝑖1 −𝑖2 ) < 𝑠𝑙𝑜𝑝 ∗
2

∴ 𝑇ℎ𝑒 𝑟𝑒𝑙𝑎𝑦 𝑤𝑖𝑙𝑙 𝑛𝑜𝑡 𝑜𝑝𝑒𝑟𝑎𝑡𝑒


11 ∗ 1000ൗ
𝑉𝑏 3
𝑍𝑏𝑎𝑠𝑒 = = = 31.75 Ω
𝐼𝑏 200

𝑢𝑛𝑝𝑟𝑜𝑡𝑒𝑐𝑡𝑒𝑑 𝑋 = 0.1 ∗ 0.15 ∗ 31.75 = 0.476 Ω

𝑍𝐼𝑜 𝑍 ∗ 200
𝑢𝑛𝑝𝑟𝑜𝑡𝑒𝑐𝑡𝑒𝑑 𝑤𝑖𝑛𝑑𝑖𝑛𝑔 = ∗ 100 = ∗ 100
𝑉𝐿 6.35 ∗ 1000

∴ 𝑍 = 3.175 = 𝑟2 + 𝑋2 = 𝑟 2 + 0.4762

∴ 𝑟 = 3.14 Ω
𝐼2 𝑉1 𝑦𝑖𝑒𝑙𝑑𝑠 𝑉1 33
= 𝐼2 = 𝐼1 = 𝐼1 = 5𝐼1
𝐼1 𝑉2 𝑉2 6.6

5 5 𝐼1
𝑖2 = 𝐼2 = 5𝐼1 =
300 300 12

1 𝐼1
𝑖1 = 𝐼1 ∗ 3 ∗ =
𝐶. 𝑇.2 12

12 ∗ 3 60
∴ 𝐶. 𝑇.2 = = 20.785 =
1 5ൗ
3

You might also like