Professional Documents
Culture Documents
V-2158-0201-A-8002 - 3 - 0030 VFD Acs5000
V-2158-0201-A-8002 - 3 - 0030 VFD Acs5000
154
原図 3N4-S4293202
ABB
155
原図 3N4-S4293202
ABB
Table of contents
Copyright notice 1
Document identification 1
Contact information 1
Equipment covered by the manual 1
Structure of the user documentation 2
Target groups and required qualifications 2
Relevant chapters of the manual 3
User’s responsibilities 4
Intended equipment use 4
Quality certificates and applicable standards 4
Writing conventions 5
Meaning of icons 5
Text conventions 5
Related documentation 6
Items covered by delivery 6
Identifying the delivery 8
Identifying transport units 8
Mechanical installation 1
Electrical installation 1
Main circuit breaker (MCB) 2
Input transformer (if applicable) 2
Motor 2
Insulation tests 2
Power supply 3
Miscellaneous 3
Maintenance schedule
Cluster A cluster is a synonym for a group of hardware modules of the drive control system.
Drive system The drive system includes all equipment used to convert electrical into mechanical power
to give motion to the machine.
DriveDebug DriveDebug is part of ABB’s DriveWare® software tools for drives using the DDCS
communications protocol. DriveDebug runs on computers with Windows® operating
systems. DriveDebug is a specialist’s tool used to diagnose, tune and troubleshoot ABB
drives.
DriveMonitorTM DriveMonitor is a monitoring and diagnostics system that allows secure access to the
drive via the internet from a remote location. DriveMonitor provides long-term monitoring
functions that allow to infer equipment status and improve equipment performance.
Ground Earth
To ground The conducting path (e.g. conductor) between the electric equipment (e.g. frequency
converter) and the earth. The electric equipment is connected to the earth, e.g. by a
grounding set or a grounding switch.
INU Inverter unit of the drive. The INU converts the DC voltage to the required AC motor
voltage and frequency.
I/O device Term of ABB’s S800 I/O system. An I/O device consists of a module termination unit
(MTU) and one I/O module.
I/O module Term of ABB’s S800 I/O system. The I/O module is an active input or output device for
digital or analog signals.
I/O station Term of ABB’s S800 I/O system. The I/O station typically consists of a bus modem and
several input and output devices.
Line voltage RMS voltage of the main power supply of the drive
ModuleBus Term of ABB’s S800 I/O system. The ModuleBus is an electrical bus for the
interconnection of I/O devices.
PCC Point of common coupling. The PCC is the point in the electrical power supply system
where the responsibility of the utility changes to the industrial customer. The utility is
responsible to provide clean voltage and current with respect to harmonic distortion up to
the PCC. The industrial customer is responsible not to distort voltage and current by its
electrical systems.
PE Protective earth
Power cell The power cell is an assembly of wired components including power semiconductors and
circuit boards that serves as a standardized building block for the rectifier and inverter of
the drive.
S800 I/O The S800 I/O is a distributed process input output system that can be connected to
various process controllers from ABB and other companies.
Zero speed threshold Used in the manual to indicate that the drive has reached the value “zero speed” that is
set in a parameter. The value can be set in the range of 0 and maximum speed (the unit
for the speed is rpm).
Trademarks
Names that are believed to be trademarks of other companies and organizations are designated as
such. The absence or presence of such a designation should however not be regarded as an offence
of the legal status of any trademark. The following registrations and trademarks are used in this
manual:
Copyright notice
The information in this manual is subject to change without notice.
This manual and parts thereof must not be reproduced or copied, or
disclosed to third parties, nor used for any unauthorized purpose without
written permission from ABB Switzerland Ltd, Medium Voltage Drives.
The hardware and software described in this manual is provided under a
license and may be used, copied, or disclosed only in accordance with the
terms of such license.
Document identification
Ownership ABB Switzerland Ltd
Medium Voltage Drives
Revision index B
Contact information
Address ABB Switzerland Ltd
Medium Voltage Drives
CH-5300 Turgi, Switzerland
E-mail mvdrives@ch.abb.com
Mechanical installation The personnel must be qualified to prepare the installation site according
to the site and equipment requirements and to perform the installation
accordingly.
Electrical installation The personnel must have a sound knowledge of the relevant electrical
codes and specifications covering low and medium voltage equipment,
be experienced with electrical wiring principles, and know the electrical
symbols typically used in wiring diagrams.
Operation The personnel include all persons who operate the equipment from the
local operating panel of the drive. The personnel must know the functions
of the operating panel, be adequately trained for the equipment, and know
the driven process. Special knowledge of frequency converter technology
is not required.
General information x x x x
Safety x x x x
Overview x x
Transport x
Mechanical installation x x
Electrical installation x
Operation x
Troubleshooting and x
maintenance
User’s responsibilities
It is the responsibility of those in charge of the equipment to ensure that
each person involved in the installation, operation or maintenance of the
equipment has received the appropriate training and has thoroughly read
and clearly understood the instructions in this manual and the relevant
safety instructions.
Writing conventions
The following icons and text conventions are used in the manual.
Meaning of icons
Text conventions
• Bulleted list
Used to list items or steps in a procedure, where the sequence does
not matter.
• Bulleted list of a subsection following a main paragraph
Used to list items or for procedures, where the sequence does
not matter.
1 Steps of a procedure, to be followed in the specified order (e.g. 1, 2,
3.....)
1 Figure legend, numbers identify the items referred to in the illustration
above (e.g. 1, 2, 3.....)
Arial Bold is used to highlight switches to be operated, status messages
shown in a display and special terms.
UPPERCASE letters refer to a parameter.
Italic is used for references to illustrations, chapters and supplementary
documentation.
Packaging -
3 3
2 1
Packing list Transport units which belong to a particular drive are identified with the
help of the commodity description on the packing lists. The identical
column of the packing list states the number of the drive to which the
transport unit belongs (see the section of packing list in Figure 2).
the nearest Lloyd's agent may be contacted. Please also inform the contact person with ABB Schweiz AG
shown on this packing list.
list. The item number in column ’ABB Item / Customer item’ provides the
necessary information (see the section of packing list in Figure 3).
the nearest Lloyd's agent may be contacted. Please also inform the contact person with ABB Schweiz AG
shown on this packing list.
The number in this place (4th digit from right) states the drive to which
the accessories belong. In this example they belong to drive 1.
Packing label The packing labels on the back walls of a transport unit can also be used
to identify the drive to which the transport unit belongs (see Figure 4).
The main circuit breaker (MCB) is a major protection device of the drive.
If a serious fault occurs in the drive, the MCB must disconnect the main
power supply to the drive immediately. The main power supply must be
disconnected without delay on an open or trip command from the drive to
prevent hazard to the personnel and further damage to the equipment.
Depending on the main power supply configuration of the drive system,
the MCB is either located on the primary side of the input transformer or
on the primary side of the drive if the drive is connected directly to the line
(DTL).
MCB
Protection CT
relay
Input
transformer
Higher-level
Drive control system
Local MCB control
Motor M
Short-circuit occurs
Maintenance recommendation
The MCB trip circuits should be checked once yearly.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result
in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could
result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to personal injury.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 1-1 (6)
184
原図 3N4-S4293202
Chapter 1 - Safety ABB
1.2 General safety information
To maintain safety and minimize hazards observe the following:
1-2 (6) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
185
原図 3N4-S4293202
ABB Chapter 1 - Safety
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 1-3 (6)
186
原図 3N4-S4293202
Chapter 1 - Safety ABB
1.4 Safety labels and signs
Fire fighting The sign explains the procedure when fighting fire in electrical equipment.
The sign should be installed well visible near the drive.
1-4 (6) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
187
原図 3N4-S4293202
ABB Chapter 1 - Safety
Dimensions: 50 x 30 cm
Pacemaker The magnetic field of the drive can influence the functioning of
pacemakers. The sign should be installed at the entrance to the drive
room or at a minimum distance of 6 meters (20 ft.) from the drive to stop
personnel with pacemakers approaching the drive.
Diameter: 32 cm
High voltage The sign should be installed clearly visible at the main circuit breaker in
the switchgear room. The sign alerts personnel to the high voltage which
can be present on the secondary side of the input transformer until the
main circuit breaker has been opened and secured and the drive has been
de-energized and grounded.
Dimensions: 20 x 10 cm
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 1-5 (6)
188
原図 3N4-S4293202
Chapter 1 - Safety ABB
1-6 (6) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
189
原図 3N4-S4293202
ABB
2.1 Overview
The air-cooled ACS 5000 is a general purpose frequency converter for the
control of standard induction and synchronous motors.
See the Technical specifications and / or the Rating plate of the drive for
information on the power and voltage range of your drive.
The following drive configurations are described in the manual:
• ACS 5000 (1) with integrated transformer (2)
2 1
2 1
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 2-1 (18)
190
原図 3N4-S4293202
Chapter 2 - Power electronics and cabinet features ABB
2.2 Power supply configurations
The drive requires the following independent power supplies:
• Main power supply for the power electronic components
• Auxiliary power supply for the control and cooling equipment
Charging voltage
I >>
Main
power supply
2-2 (18) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
191
原図 3N4-S4293202
ABB Chapter 2 - Power electronics and cabinet features
• auxiliary power for the cooling fans and the charging unit (short time
demand) and
• control power for the control hardware and the gate units.
The auxiliary power for the cooling fans and the charging unit is supplied
to the drive by a three-phase AC power supply and the control power by
an Uninterruptible Power Supply (UPS) to a separate single-phase AC in-
put (AC safeline).
Feeding the control power separately by a UPS has the advantage that the
main control hardware will remain energized, the full ride-through capabil-
ities of the drive can be used and the communication to a higher-level con-
trol system will not be lost in the event of an auxiliary power outage.
Optionally, the total auxiliary power can be supplied to the drive by a three-
phase AC power supply. If the power supply is interrupted, drive internal
capacitors provide a backup for the control hardware between 0.5 and 3
sec. The backup enables the drive to ride-through or to perform a con-
trolled shutdown.
In addition to the above power supplies, a separate power supply is need-
ed for
• optional converter space heaters (110 / 230 VAC)
• the excitation unit if present in the line-up and
• the synchronized bypass unit if present in the line-up.
The desired voltage level for the auxiliary power needs to be specified
when ordering the drive.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 2-3 (18)
192
原図 3N4-S4293202
Chapter 2 - Power electronics and cabinet features ABB
2.3 Drive topology
Legend
1 Control compartment
1 2 3 4 5
2 Swing frame
3 Terminal compartment
4 Behind swing frame
5 Rectifer-inverter-compartemnt
6 DC-link capacitors
7 Power cell
8 Rectifier
9 Inverter
10 Grounding switch
11 IGCT power supply units
7 6 8
9 10
2-4 (18) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
193
原図 3N4-S4293202
ABB Chapter 2 - Power electronics and cabinet features
2.3.2 DC link
The DC link consists of:
• the charging unit (1)
• the grounding switches (2)
• the DC capacitors (3)
2
3
Charging The unit charges the DC link capacitors to 90% of the steady state
voltages before the MCB is closed to connect the drive to the main power
supply. Thus, excessive inrush currents are prevented.
The charging unit is fed from an auxiliary power supply.
The charging sequence is started by pressing the SUPPLY ON push-
button on the control compartment door. After the charging sequence has
finished, the charging unit is disconnected from the medium voltage
circuit, the MCB is closed and the DC link will reach its nominal level.
Stand-by mode Once the DC link is charged, it is possible to keep the drive in this state to
facilitate a more rapid start-up procedure. The losses during stand-by
mode are approx. 1% of the nominal power and are caused from small
losses from the rectifiers, the inverters and the auxiliaries.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 2-5 (18)
194
原図 3N4-S4293202
Chapter 2 - Power electronics and cabinet features ABB
2.3.2.2 Grounding switches
The grounding switches are safety devices that enable safe access to the
medium voltage compartments of the drive. There is a grounding switch in
each power cell.
When all three switches are in position grounded, the rectifier, the DC link
and the inverter in each power cell are connected to the PE ground bus.
The switch is electromechanically interlocked with a discharge monitoring
circuit to prevent closing of the switch while the DC link capacitor is still
charged.
Grounding the drive is only possible after the main power supply has been
disconnected and the DC link has discharged. The DC link is regarded as
discharged when the voltage level is below 50 VDC. The lamp grounding
switch unlocked (1) will then light up and the grounding switches can be
turned to position grounded (2).
When the grounding switchs are in position grounded, the door safety
switch of the rectifier-inverter-compartment will be released, and the door
can be opened.
2-6 (18) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
195
原図 3N4-S4293202
ABB Chapter 2 - Power electronics and cabinet features
2
3
Legend
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 2-7 (18)
196
原図 3N4-S4293202
Chapter 2 - Power electronics and cabinet features ABB
2.3.3 INU - Inverter unit
The three inverters convert the DC voltage to the required AC motor
voltage and frequency.
The inverters are self-commutated, 5-level voltage source inverter. As a
result of the multi-level topology, the drive produces a total of nine
switching levels.
10000 V P
P
P
5000 V
P
Time
- 5000 V
P
- 10000 V
P
The resulting waveforms permit the application of standard motors.
2-8 (18) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
197
原図 3N4-S4293202
ABB Chapter 2 - Power electronics and cabinet features
Cable entry The cable entry for the power cables and the ground cable is separated
from that for the auxiliary power cables and control cables.
Entry plates The following types of cable entry plates are available:
• EMC entry plate
• Roxtec cable transit
• Undrilled alluminium plate for the use of cable glands
See Chapter 6 - Electrical installation, 6.6.2 Cable entry plates for detailed
information.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 2-9 (18)
198
原図 3N4-S4293202
Chapter 2 - Power electronics and cabinet features ABB
2.4.1.2 Cable entry for auxiliary power and control cables
The top and bottom cable entry for the auxiliary power and control cables
is fitted with an undrilled plate for the use of cable glands.
2-10 (18) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
199
原図 3N4-S4293202
ABB Chapter 2 - Power electronics and cabinet features
• Non-integrated
The drive and the transformer are installed in different locations. The
maximum possible distance is determined by the maxium allowed
length for the secondary transformer cables.
The transformer is equipped with an additional compartment (1). The
compartment is divided into the control compartment (2), and the
terminal compartment (3) for the power cables. The terminal compart-
ment is located behind a bolted door.
2 3
Protective relays The protective relays monitor the input phase currents of the two primary
winding systems of the 36-pulse transformers. The pick-up values for
overload and short-circuit are set in the factory and must not be changed.
See:
• the List of protective devices for the settings.
• the Appendix D - Wiring diagrams for the associated electric circuits
of the relays.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 2-11 (18)
200
原図 3N4-S4293202
Chapter 2 - Power electronics and cabinet features ABB
• the circuit breaker for the auxiliary voltage (1)
• the starters (2) and auxiliary contactors for the fan units (3)
• the auxiliary power transformer (4)
• the power supply unit for the protective relays (5)
• the customer terminals (6)
1 2
6 3 5 4
Figure 2-7 Control compartment of the transformer
2-12 (18) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
201
原図 3N4-S4293202
ABB Chapter 2 - Power electronics and cabinet features
control compartment door. The different lock inserts ensure that these
doors can only be opened by personnel authorized to do so.
The doors of the is integrated transformer are bolted.
Legend
To open a door:
1 Insert the key and turn the key to the right.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 2-13 (18)
202
原図 3N4-S4293202
Chapter 2 - Power electronics and cabinet features ABB
2 Turn the handle to the right if the door is hinged on the right. Turn the
the handle to the left if the door is hinged on the left.
2-14 (18) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
203
原図 3N4-S4293202
ABB Chapter 2 - Power electronics and cabinet features
When the safety switch is in the normal operating position, the DC link
must be discharged and the auxiliary voltage must be switched on in
order to open the door.
If the auxiliary voltage is switched off and the door is locked, the
safety switch must be unlocked manually as described in the
following section.
Procedure 1 On the roof of the drive, remove the cap of the access hole for the
mechanical release.
2 Insert the supplied triangular nut driver into the triangular counterpart
of the safety switch.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 2-15 (18)
204
原図 3N4-S4293202
Chapter 2 - Power electronics and cabinet features ABB
3 Turn the mechanical release from the locked to the unlocked posi-
tion to release the interlock (the symbols on the safety switch are
visible when looking through the opening at an angle).
2.8 Cooling
2.8.1 Configurations
The standard drive, the integrated transformer, and the external-
integrated transformer can each be equipped with a redundant fan unit.
This redundant configuration ensures that the operation of the drive
system is not interrupted if one of the standard fan units fail.
Note: The number of standard fan units present depends on the drive
power.
Legend
1 2 2 1
1 Fan 1
2 Fan 2 (stand-by unit)
2.8.2 Function
Operation The standard fan unit is switched on by the control system of the drive
when the DC link has been charged. The fan unit continuous to run for a
2-16 (18) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
205
原図 3N4-S4293202
ABB Chapter 2 - Power electronics and cabinet features
preset time after the main power has been switched off to remove the heat
from the interior of the cabinet.
When a standard fan of the drive or a fan of the transformer fails, the
control system of the drive switches on the stand-by fan automatically.
Fault indication The failure of a fan is indicated on the CDP control panel of the drive as
follows:
• CoolCircuit1Alm if a fan of the drive fails
• CoolCircuit2Alm if a fan of the intergrated transformer fails
• The alarm - fault lamp on the door of the control compartment starts
to flash.
Air flow monitoring The air flow through the cabinet of the drive and the cabinet of the
integrated transformer is monitored by air pressure switches.
The air pressure switch of the drive is located above the swing frame
inside the terminal compartment (see Figure 2-11).
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 2-17 (18)
206
原図 3N4-S4293202
Chapter 2 - Power electronics and cabinet features ABB
The air pressure switch of the transformer (see arrow) is located on the
right side wall of the cabinet.
The air flow through the filter mats and the air flow through the cabinets
are monitored by separate air pressure switches in each cabinet.
When the filter mats are clogged and the pressure drop reaches the
specified final pressure loss, the message Conv1CoolAirFilter is
displayed on the CDP control panel and the alarm/fault lamp lights up on
the door of the control compartment.
2-18 (18) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
207
原図 3N4-S4293202
ABB
Chapter 3 - Control system
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 3-1 (14)
208
原図 3N4-S4293202
Chapter 3 - Control system ABB
Legend
MAIN SUPPLY
OFF ON
2
ALARM EMERGENCY OFF
FAULT RESET
3
GROUND. SWITCH
UNLOCKED
4
EMERGENCY OFF
3-2 (14) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
209
原図 3N4-S4293202
ABB Chapter 3 - Control system
6 7
8
9
10
See Appendix D - Wiring diagrams for the devices actually present in the
control compartment.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 3-3 (14)
210
原図 3N4-S4293202
Chapter 3 - Control system ABB
3.2 Control system configuration and main components
This section provides a brief functional overview of the main hardware
components of the control system and their interconnection.
The control system is configured, customized and tuned with a set of
application parameters. The application parameters are organized in
functional groups and have factory-set default values. The default
parameter values are adjusted during commissioning to the specific
application of the drive to activate the specific control, monitoring and
protection functions for the driven process, and to define the signals and
data to be transferred between drive and external equipment.
See Signal and parameter table for detailed information on the parameters
provided for signal allocation, signal type selection, signal inversion,
scaling and filtering, etc.
DriveWare® DriveMonitor®
Higher-level External
control system devices
DDCS
DDCS
Fieldbus S800
adapter I/O devices
RS485
DDCS
Option
Pulse
PPCS
encoder
INU
INT circuit board
INU
ACS 5000
3-4 (14) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
211
原図 3N4-S4293202
ABB Chapter 3 - Control system
Legend
Control tasks The AMC circuit board has specific control and closed-loop tasks assigned
to it.
The AMC circuit board processes drive and status information, performs
the speed and torque control tasks, and monitors the operation of the
drive.
All relevant drive variables (e.g. speed, torque, current, voltage) are
continuously monitored by the control system. Pre-programmed
protection functions ensure that these variables remain within certain
limits in order to maintain safe operation of the drive. These internal
functions are not programmable by the user.
Optionally, the drive offers monitoring of signals from external
equipment.These can be activated and adjusted by parameter settings.
Other general control, protection and monitoring tasks regarding the
whole drive include control and monitoring of:
• The main circuit breaker (MCB)
• The grounding switch
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 3-5 (14)
212
原図 3N4-S4293202
Chapter 3 - Control system ABB
• The door interlocking system
• The cooling system
Main circuit breaker The main circuit breaker (MCB) is an important switching and protection
control device of the drive system. If a serious fault occurs in the drive system, the
MCB must disconnect the main power supply to the drive immediately.
Therefore the MCB must only be controlled and monitored by the drive.
The feedback signals from the MCB upon a close or an open command
from the drive are monitored. These signals must have the correct status
and must arrive within a preset time at the drive:
• If the drive applies a close command and the expected feedback
signal does not arrive after a preset time, the close command is reset
and the MCB is tripped.
• If the open command from the drive to the MCB is a maintained
signal, it is reset after receiving the open feedback signal from the
switchgear. If the feedback signal does not arrive after a preset time,
a trip command to the MCB is issued.
Speed and torque The speed and torque of the motor is controlled by DTC (Direct Torque
control Control). The DTC motor control platform is unique to ABB and has been
proven in all variable speed drives of the ACS product range. DTC
provides accurate speed and torque control, and high dynamic speed
response. DTC is implemented on the AMC circuit board of the INU.
Torque reference
Torque- Torque Switching
or reference flux logic
controller comparator
Speed reference
Speed
controller
Switch
Actual speed positions
Motor
model Voltage
Current
3-6 (14) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
213
原図 3N4-S4293202
ABB Chapter 3 - Control system
Peripheral I/O devices The peripheral input and output devices connected to the AMC circuit
board of the INU include:
• Local CDP control panel
• S800 I/O system for parallel signal transfer to external devices
• Optional fieldbus adapters for serial data transfer to a higher-level
control system
• PC-based service tools comprising:
• DriveWare® software tools
DriveWare® includes software tools such as the commissioning
and maintenance tools DriveWindow and DriveDebug, and
DriveOPC for data transfer between ABB drives and Windows®-
based applications.
• DriveMonitorTM (Option)
DriveMonitorTM is a monitoring and diagnostics tool that allows
access to the drive from any location in the world via a secure in-
ternet connection.
Overview Internal and external, analog and binary I/O signals are connected to the
control system by standard S800 I/O from the ABB Advant control system.
The S800 I/O system is configured from the following interface packages:
Standard package The standard interface package is always part of the drive.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 3-7 (14)
214
原図 3N4-S4293202
Chapter 3 - Control system ABB
Wiring diagram
I/O device Cluster position
designation
Optional packages The optional packages CI1 and CI2 provide additional I/O devices to
control and monitor external equipment such as motor and transformer.
Wiring diagram
Package I/O device Cluster position
designation
I/O devices A complete I/O station comprises the I/O devices and the TB 820 bus
modem. An I/O device consists of an I/O module and a module terminal
unit (MTU).
No. of
I/O module type I/O rating
channels
3-8 (14) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
215
原図 3N4-S4293202
ABB Chapter 3 - Control system
I/O stations
1 Optional I/O station
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 3-9 (14)
216
原図 3N4-S4293202
Chapter 3 - Control system ABB
I/O device identification The I/O devices are identified in the drive and in the wiring diagrams by
their technical designation (e.g. A2511). Additionally, a cluster-position
designation is used in the wiring diagrams and in the software. This
designation has no relevance to the connection of the control cables but
is used to help identify a device in the software and the Signal and
parameter table.
A cluster is a synonym for the group of S800 I/O devices of the control
system. Each I/O device belongs to a cluster (C) and occupies a fixed
position (P) within the cluster. The relation between cluster and position is
expressed by the designation CxPy, with x representing the number of the
cluster and y identifying the number of the position.
All I/O devices used in the drive belong to cluster 1 and each I/O device
occupies a fixed position between 1 and 10.
The fixed position is the reason why their might be empty MTUs in the
control compartment. If, for example, interface package CI2 is not part of
the control compartment, the MTUs of CI2 are present.
Communication with Communication between the AMC circuit board and the S800 I/O system
AMC circuit board is done by the TB 820 bus modem via a fast optical link. The optical link
uses the standard DDCS protocol. Data between the bus modem and the
I/O modules is transmitted through the S800 ModuleBus. A section of the
ModuleBus is contained in each MTU where the I/O module is plugged
into.
Wiring The external I/O signals of the standard S800 I/O station are connected to
separate terminals in the control compartment. The internal wiring
between terminals and I/O modules is made in the factory.
The wires to the optional S800 I/O station are connected to the module
terminal units.
3-10 (14) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
217
原図 3N4-S4293202
ABB Chapter 3 - Control system
Available fieldbuses The drive can be equipped with one of the following fieldbus adapters.
Table 3-1 Fieldbus adapters
Ethernet NETA-01
Modbus NMBA-01
Profibus DP NPBA-12
Communication with The fieldbus adapter is connected to channel 0 of the AMC circuit board
AMC circuit board of the INU via optical fibers.
INU
AMC circuit board
DDCS
Fieldbus
adapter
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 3-11 (14)
218
原図 3N4-S4293202
Chapter 3 - Control system ABB
Location The fieldbus adapter is mounted on a DIN rail on
the swing frame of the control compartment (see
arrow).
The indicated mounting position may vary
depending on the number of optional devices
present in the control compartment.
Overview The NTAC interface is part of the control system of the drive if pulse
encoder feedback is used to control the motor.
Terminals X1 Terminals X2
1 A+ Channel A 1 -V 0V
2 A- 2 -V 24 V
3 B+ Channel B 3 +V
4 B- 4 24/25
5 Z+ Channel Z 5 15
6 Z- 6 24
7 SH Shield 7 0V
8 SH 8 +24 V
Communication with The NTAC module communicates with the AMC circuit board of the INU
AMC circuit board via a fast optical link using the standard DDCS protocol. The optical fibers
are connected to channel 1 of the AMC circuit board.
3-12 (14) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
219
原図 3N4-S4293202
ABB Chapter 3 - Control system
INU
AMC circuit board
DDCS
NTAC
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 3-13 (14)
220
原図 3N4-S4293202
Chapter 3 - Control system ABB
3-14 (14) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
221
原図 3N4-S4293202
ABB
Chapter 4 - Transportation, storage and disposal
4.1 Safety
The drive must only be handled by personnel who are skilled and
experienced in unpacking and transporting heavy equipment.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 4-1 (4)
222
原図 3N4-S4293202
Chapter 4 - Transportation, storage and disposal ABB
• When transporting the cabinet, ensure that no dirt enters. Keep the
doors closed. Metallic dust in particular may cause damage and lead
to malfunction when the cabinet is powered up.
3
1
mm
42
5 in
1. 6
4 4
1 1
4-2 (4) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
223
原図 3N4-S4293202
ABB Chapter 4 - Transportation, storage and disposal
4.5 Storage
The drive can be stored for up to one year in the original packaging as long
as it is not damaged or opened. For information on longer storage periods
contact the ABB service organization.
4.5.2 Storage
If the drive is taken out of service for a longer time proceed as follows:
1 Cover all cable inlets and ventilation slots with an impermeable plastic
or aluminum foil and a wooden panel.
2 Add a desiccant of the appropriate quality:
• 1 unit desiccant (30 g) absorbs 6 g water vapor.
The following quantity is needed when using a polyethylene foil:
• 10 units/m2 foil
3 Close and lock the doors of the cabinet.
4 Use polyethylene or equivalent for packaging:
• 0,3g/m2/24h water vapor diffusion
5 Attach humidity indicators to the packaging.
The storage conditions and the packaging should be checked regularly.
Any damages that occur during the storage period should be repaired
immediately.
NOTICE
Static electricity can damage printed circuit boards.
Apply static-sensitive precautions when handling these components.
Check the spare parts immediately after receipt for damages. Report any
damage to the shipping company and the ABB service organization.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 4-3 (4)
224
原図 3N4-S4293202
Chapter 4 - Transportation, storage and disposal ABB
Observe the following to maintain spare parts in good condition and to
keep the warranty valid during the warranty period:
• Keep spare parts in their original packaging.
• Store printed circuit boards in antistatic bags or boxes.
• Storage temperature range: -5 °C to + 55 °C (23 °F to 131 °F)
• Storage place requirements:
• Free of vibration and shock.
• Protected against dust, sand, vermin and insects.
• Free of corrosive gases, salt or other impurities that could
damage electronic equipment.
• Dry; no condensation
Relative air humidity: 5 to 85%
If in doubt whether the maximum allowed humidity is exceeded,
protect the spare parts by an external heater.
• Do not touch a component without wearing a wrist grounding
strap.
• Put the component on a grounded working surface protected
against electrostatic discharges.
• Hold the component only at the edge.
4-4 (4) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
225
原図 3N4-S4293202
ABB
Chapter 5 - Mechanical installation
5.1 Safety
All installation work must be carried out by qualified personnel according
to the site and equipment requirements and in compliance with local
regulations.
NOTICE
When working on the drive ensure that foreign matter cannot enter the
cabinet. Close the doors and cover openings completely when work is
discontinued. Any foreign matter which accidentally dropped into the
cabinet must be retrieved. Metallic dust in particular could cause malfunc-
tion and damage when the drive is energized.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 5-1 (4)
226
原図 3N4-S4293202
Chapter 5 - Mechanical installation ABB
Contact the ABB service organization if the condition of the installation site
is not within the specifications or if the transportation or the installation
require special measures.
See:
• Rating plate of the drive for the maximum ambient temperature
• Technical data for information on the climatic and environmental
conditions based on IEC 60721-3
Classification: 3K3 / 3B1 / 3C2 / 3S2 / 3M1
5-2 (4) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
227
原図 3N4-S4293202
ABB Chapter 5 - Mechanical installation
NOTICE
It is important that the cabinets are not buckled and the roof plates are
level. Otherwise the fan units cannot be installed properly. Improper
installation may affect the cooling.
Check the cabinets for misaligned doors and any gaps between cabinet
walls and cabinet frame. Use a spirit level to check the horizontal and
vertical position of the transport unit.
If the floor proves to be not level and the unevenness cannot be corrected,
place shims or leveling plates under the base frame to adjust the position
of the transport unit.
To fix the joining surfaces, remove the back walls of the adjoining transport
units. The doors can stay in place.
Connect the transport units with each other all around the joining surfaces
using the supplied M6 screws.
Table 5-1 Installation material
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 5-3 (4)
228
原図 3N4-S4293202
L-201 3BHB012376R0001 Montageband Double-side foam tape for mounting or assembly
L-202 3BHB020536R0001 Dach Verbindungsstuck Assembly plate
L-209 NB 312350P8018 SHR-6KT-ISO4017-M10x35-A2-70 Hex-scr. M10x35
L-210 NB 335050P0609 SCH-ZYL-DIN125A-10.5x20x2-A2 Washer 10.5/20x2
L-211 NB 335805P0512 HSPN-Fed,-Ring 10 ST-NR Spring washer 10 SST
L-216 9ABA450093R0261 SHR-KBS-M6x25-8.8-FLZNNC Hex socket head M6x25-8.8
The Assembly plates are mounted at the front and back of the roof and connect two joining drive
2)
unit.
item # L-202
Item # L-209, L-210, L-211
229
原図 3N4-S4293202
4) Cooling fans are mounted on the roof and screwed.
Bolts, Nuts and Washers are attached on the cooling fans.
230
原図 3N4-S4293202
Transformer panel Converter panel DWG. / Sheet No.
The name in the
Description Devise & Connector Devise & Connector
drawing Transformer Converter
designation designation
Power cable connection T1011.3U 31L1 A23.1L1 51 101
T1011.3V 31L2 A23.1L2 51 101
T1011.3W 31L3 A23.1L3 51 101
T1011.4U 21L1 A23.2L1 51 101
T1011.4V 21L2 A23.2L2 51 101
T1011.4W 21L3 A23.2L3 51 101
T1011.5U 11L1 A22.1L1 51 101
T1011.5V 11L2 A22.1L2 51 101
T1011.5W 11L3 A22.1L3 51 101
T1011.6U 32L1 A22.2L1 51 101
T1011.6V 32L2 A22.2L2 51 101
T1011.6W 32L3 A22.2L3 51 101
T1011.7U 22L1 A21.1L1 51 101
T1011.7V 22L2 A21.1L2 51 101
T1011.7W 22L3 A21.1L3 51 101
T1011.8U 12L1 A21.2L1 51 101
T1011.8V 12L2 A21.2L2 51 101
T1011.8W 12L3 A21.2L3 51 101
Door monitaring -X210 : 11 DL11 X101.4 281 181
-X210 : 15 DL13 X101.7 281 181
-X210 : 13 DL15 X101.10 281 181
-X210 : 12 DL12 X101.5 281 181
-X210 : 16 DL14 X101.8 281 181
-X210 : 14 DL16 X101.12 281 181
Cooloing fan (-E1700) -X211 : 1 coolingfan0_L1 K5470.2 501 170
-X211 : 2 coolingfan0_L2 K5470.4 501 170
-X211 : 3 coolingfan0_L3 K5470.6 501 170
-X211 : PE coolingfan0_PE PE2.14 501 170
Cooloing fan (-E1701) -X211 : 4 coolingfan1_L1 K5471.2 501 170
-X211 : 5 coolingfan1_L2 K5471.4 501 170
-X211 : 6 coolingfan1_L3 K5471.6 501 170
-X211 : PE coolingfan1_PE PE2.11 501 170
Cooloing fan (-E1702) -X211 : 7 coolingfan2_L1 K5472.2 501 170
-X211 : 8 coolingfan2_L2 K5472.4 501 170
-X211 : 9 coolingfan2_L3 K5472.6 501 170
-X211 : PE coolingfan2_PE PE2.12 501 170
Cooloing fan (-E1703) -X211 : 10 coolingfan3_L1 K5473.2 501 170
-X211 : 11 coolingfan3_L2 K5473.4 501 170
-X211 : 12 coolingfan3_L3 K5473.6 501 170
-X211 : PE coolingfan3_PE PE.13 501 170
Space heater (-E1704) -E1704 SP_H_L1 A12:XT.1 503 170
-E1704 SP_H_L2 A12:XT.2 503 170
24V contact interrogation voltage X210.1 24V_P1 X24_P1.7 551 175
X210.2 24V_N1 X24_N1.27 551 175
Transformer cooling diff pressure trip X210.5 DP_SIG1 A2551.B6 551 175
Transformer air filter alarm X210.6 FILT_SUP_2 A2551.B7 551 175
Transformer cubicle temperature high X210.7 TEMP_SUP A2551.B3 551 175
Transformer protection relay trip X210.4 PROT_REL_2 A2551.C4 551 151
Transformer temperature alarm X210.19 TRU_TEMP_AL A2551.C8 551 101
Transformer temperature trip X210.20 TRU_TEMP_TR A2551.B8 551 101
FE FE 51 100
PE PE 51 100
T1011_PE PE 51 101
231
原図 3N4-S4293202
Chapter 5 - Mechanical installation ABB
5.5 Fan installation
See Outline drawing in Appendix C - Mechanical drawings for information
on:
• the number of fan units to be installed and their location on the
cabinet roof
• dimensions and weight of the fan unit
Procedure
1 Lift the fan unit onto the roof by means of a crane.
Use the supplied lifting eyes to attach the lifting gear.
3 Fasten the fan unit to the roof using the supplied screws.
The four fastening holes are accessible through the cutouts in the
mounting plate (see arrows).
See section 6.8 Connecting the fan units for information on the electrical
installation.
5-4 (4) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
232
原図 3N4-S4293202
ABB
Chapter 6 - Electrical installation
6.1 Safety
WARNING
Hazardous voltage!
Improper work could lead to life-threatening injury or death.
The electrical installation must be carried out by qualified personnel
according to the site and equipment requirements, and the relevant
electrical codes.
When the electrical installation is completed, the main and auxiliary power
supply to the drive must not be switched on without the consent of the ABB
commissioning personnel.
Take appropriate measures to prevent main and auxiliary power supply
being switched on during installation.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 6-1 (20)
233
原図 3N4-S4293202
Chapter 6 - Electrical installation ABB
6.3.2 Ground cable
It is important that the drive is properly grounded to maintain safety and to
ensure smooth functioning of the equipment.
The ground cable must be securely tied to the ground system of the
installation site and to the ground bus of the drive. See section 6.4
Recommended grounding scheme for the drive system for further
information.
Cross-section The cross-section of the ground cable and the ground connection must be
in compliance with the electrical codes.
Cross-section The cross-section and ampacity rating of the conductor and the
connection must be in compliance with the electrical codes.
6-2 (20) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
234
原図 3N4-S4293202
ABB Chapter 6 - Electrical installation
Speed Twisted pair cable with separately shielded 0.5 mm2 / 4 x (2+1)
encoder pairs and overall shield
4 Earth electrode
5 Ground cable
5
6 Cable screen
6
7 Cable shield
7
8 Equipotential
bonding conductor 8
3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 5
2 FE PE
12 L3
12 L2
12 L1
11 L3
11 L2
11 L1
21 L3
21 L2
21 L1
22 L3
22 L2
22 L1
31 L3
31 L2
31 L1
32 L3
32 L2
32 L1
1L1
1L2
1L3
FE PE
1 2 3 1 2 3
5
6
8
7
5
1 2 3 1 2 3
3 U V W PE
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 6-3 (20)
235
原図 3N4-S4293202
Chapter 6 - Electrical installation ABB
6.5 Cabling between drive and transformer
1 2 3
Legend
1 Transformer
2 Terminal compartment
3 Drive
6-4 (20) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
236
原図 3N4-S4293202
ABB Chapter 6 - Electrical installation
Legend
1 Transformer
2 Terminal compartment
3 Drive
The following external cable connections between the two cabinets have
to be made, if the transformer is detached:
• Transformer secondary cables
• Cable from the PT100 temperature sensor in the transformer cabinet
• Cable for the start command of the transformer fan units. Cooling fan
configurations with a stand-by unit require a separate cable for the
stand-by unit.
• Cable for several alarm and trip signals from transformer protection
relays, cooling fans, air filter and air pressure monitoring
• Power supply cable for the heating cable of the transformer (option)
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 6-5 (20)
237
原図 3N4-S4293202
Chapter 6 - Electrical installation ABB
6.6 Feeder and motor cables
EMC entry plate The entry plate for ground cable, feeder and motor cables is made of 1.5
mm thick galvanized sheet metal. The entry holes are equipped with net-
like EMC sleeves (1 in Figure 6-4), and rubber grommets (2 in Figure 6-4)
for IP protection.
1 1 2
Figure 6-4 EMC entry plate
Roxtec cable transit The cable entry assembly consists of a galvanized entry frame (1 in Figure
6-5) which holds the adaptable EMC sealing modules (2 in Figure 6-5).
The modules can be adapted easily to the cable diameter by peeling off
the concentric layers of the module. Compression wedges (3 in Figure 6-
5) ensure that the conductive foil of the sealing modules tightly enclose the
cable armor or shield in the area of the cable transit.
6-6 (20) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
238
原図 3N4-S4293202
ABB Chapter 6 - Electrical installation
Note: The sealing modules and the installation accessories are not
supplied.
Undrilled cable entry The plate is provided for the use of cable glands. The aluminium plate has
plate a thickness of 5 mm.
All material for cable entry, EMC requirements and IP protection are to be
provided by the customer.
NOTICE
Waste inside the cabinet could cause damage or malfunction.
If possible, do not cut cables inside the terminal compartment. Retrieve
any waste which accidentally dropped into the cabinet.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 6-7 (20)
239
原図 3N4-S4293202
Chapter 6 - Electrical installation ABB
6.6.3.2 EMC entry plates
• Prepare the cable as illustrated in Figure 6-7 for top (A) or bottom (B)
entry.
• Remove the cable insulation at the point of entry (5 in Figure 6-7).
Tighten the EMC sleeve on the stripped part of the cable with cable
ties.
Legend A 1 B
1 Outer cable sheath
9
2
2 Rubber grommet
3 8
3 Entry plate
4 EMC sleeve 4
5 Cable sheath removed to expose cable
shield
6 Mounting bracket 5
7 Shrinkable sheath seal
8 Conductor screen extension to be 6
connected to the PE busbar 7
9 Heat-shrinkable termination 7
6
4
3
8
9 1
• Remove the rubber grommets (2 in Figure 6-7) from the entry plates
and cut them to the required diameter (A in Figure 6-8). To ensure
proper sealing, cut along the diameter marking that corresponds to
the cable diameter. Slide the grommet onto the cable. The grommet
must fit tightly to prevent water entering the cabinet.
1 2 3
6-8 (20) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
240
原図 3N4-S4293202
ABB Chapter 6 - Electrical installation
The rubber grommets can be discarded when the cables are entered
through the bottom of the cabinet.
• Fasten the entry plate after the ground connections have been made.
Legend
1
1 Outer cable sheath 2
2 Sealing module
3 Entry plate 3 5
4 Conductive foil of sealing module
5 Cable sheath removed to expose cable 4
shield 6
6 Mounting bracket
7 Shrinkable sheath seal 7
8
8 Shield extension to be connected to PE
busbar
9 Conductor screen extension to be
connected to the PE busbar
10 Heat-shrinkable termination
9
10
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 6-9 (20)
241
原図 3N4-S4293202
Chapter 6 - Electrical installation ABB
6.6.3.4 Undrilled cable entry plates
• Prepare the cable as illustrated in Figure 6-10.
1 Legend
NOTICE
High voltages will be present in the terminal compartment. High voltages
can cause a flashover between the electric potential of different phase
conductors, and the electric potential of a phase conductor and earth.
Therefore, a minimum clearance of 55 mm must be maintained between
a phase conductor and the terminals of any other phase conductor, and
between a phase conductor and earth.
6-10 (20) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
242
原図 3N4-S4293202
ABB Chapter 6 - Electrical installation
Transformer • Connect the primary and the secondary cables of the transformer to
their corresponding busbars.
• Connect the cables to the side of the busbars where the arrows point
to in Figure 6-12.
• Orientate the bolts as shown in Figure 6-12.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 6-11 (20)
243
原図 3N4-S4293202
Chapter 6 - Electrical installation ABB
Drive • Connect the secondary cables of the transformer, and the motor
cables to their corresponding busbars.
• Connect the secondary cables of the transformer to the side of the
busbars where the arrows point to in Figure 6-13.
• Orientate the bolts for the transformer primary cables as shown in
Figure 6-13.
6-12 (20) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
244
原図 3N4-S4293202
ABB Chapter 6 - Electrical installation
Cabinet back
Figure 6-14 Ground bus inside drive cabinet
Cabinet front
Material requirements • Use stainless steel bolts and nuts with the appropriate steel grade
and property class for the connection (recommended: A2-70
[designation according to ISO 3506]).
Nuts with bonded coating can be used as an alternative to uncoated
stainless steel nuts.
Connection type The following connection type is recommended when connecting a cable
lug (3 in Figure 6-16) to a busbar:
• Spring washer (1 in Figure 6-16) and flat washer (2 in Figure 6-16) on
each side of the busbar (4 in Figure 6-16).
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 6-13 (20)
245
原図 3N4-S4293202
Chapter 6 - Electrical installation ABB
1 2 4 3 2 1
• Other washers may be used, provided they can maintain the required
contact pressure.
Lubrication • If stainless steel bolts and nuts are used, lubricate the thread and
head contact surface of the bolt using recommended pasts, e.g.
Molykote D paste.
Note: If a coated nut (e.g. with bonded molybdenum-disulfide [MoS2]
coating) is used, the connection does not have to be lubricated.
Tightening torque • Tighten bolted connections with bolts of sizes M10 and greater with
the recommended nominal torque for the bolt size used.
6-14 (20) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
246
原図 3N4-S4293202
ABB Chapter 6 - Electrical installation
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 6-15 (20)
247
原図 3N4-S4293202
Chapter 6 - Electrical installation ABB
I/O stations • Connect the cables for the standard I/O station (1 in Figure 6-19) to
the intermediate terminals (2 in Figure 6-19).
• Connect the cables for the optional I/O station (3 in Figure 6-19)
directly to the terminals of the I/O modules.
6-16 (20) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
248
原図 3N4-S4293202
ABB Chapter 6 - Electrical installation
Fieldbus interface • Connect the serial communication cable directly to the fieldbus
(Option) interface.
If a twisted pair cable is used, leave the unscreened cable ends as
short as possible.
• Connect the individual cable screens to the PE terminals.
Encoder module • Connect the overall shield and the individual shields of the encoder
(Option) cable to the separate shield grounding point (2 in Figure 6-20). Do not
connect the cable directly to the encoder (1 in Figure 6-20).
The unshielded cable ends must be as short as possible. The shield
ends which are fixed to the grounding clamp must be not longer than
50 mm.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 6-17 (20)
249
原図 3N4-S4293202
Chapter 6 - Electrical installation ABB
SK 20
SK 14
SK 8
Terminal sizes The terminals are suitable for wires with a maximum cross-section of 0.2
to 2.5 mm2.
6-18 (20) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
250
原図 3N4-S4293202
ABB Chapter 6 - Electrical installation
• If EMC entry plates with rubber grommets are used, check that the
the grommets fit tightly. If necessary, seal the gaps with silicone
rubber.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 6-19 (20)
251
原図 3N4-S4293202
Chapter 6 - Electrical installation ABB
• Connect the two cables (1 and 2 in Figure 6-23) at the shipping split
of the two cabinets.
The connectors are accessible either from the back of the cabinets,
when the back walls have been removed (see Figure 6-23), or from
the front of the cabinets.
If only front access is possible, it is recommended to make the
connection before the power cables are installed.
1 2
6-20 (20) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
252
原図 3N4-S4293202
ABB
Chapter 7 - Commissioning
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 7-1 (2)
253
原図 3N4-S4293202
Chapter 7 - Commissioning ABB
7-2 (2) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
254
原図 3N4-S4293202
ABB
Commissioning check list
Mechanical installation
4 Visual inspection:
- no badly affixed or damaged components
- no foreign objects inside cabinet
- no dirt, dust and humidity inside cabinet
Electrical installation
1 Types and cross sections of control cables suitable for the signal type and signal level
2 Types and cross sections of power cables selected according to the ABB power cable
specification
3 Pulse encoder cable screens connected to screen grounding point and not
connected directly to the pulse encoder interface (only applicable for drives with pulse
encoder interface)
4 Cable entry made according to the instructions in the User’s manual
5 All control cable screens and conductors are connected according to the instructions of
the User’s manual, appropriately labelled, and the customer-side connections are
completed
6 Heating cable (if supplied) installed according to the instructions in the User’s manual
8 Input transformer and motor cables not connected at both ends (cables and drive must
be meggered before connection)
Motor
Insulation tests
1 All power cables to input transformer, between input transformer and drive, and from
drive to motor are meggered, and measured values are within the required limits.
Power supply
Miscellaneous
8.1 Overview
The chapter outlines the local operation of the drive. For local operation,
the CDP control panel and the control switches on the control
compartment door of the drive are used. See Figure 8-1 for illustration.
Control of the drive via a PLC or higher-level control systems is not
described in this chapter. If the drive is controlled from remote, see the
appropriate manuals for information.
Note: The panel messages and parameter settings used in this chapter
are typical examples to illustrate the related instructions and display
functions and may therefore differ from the actual messages and
parameter settings in your drive.
8.2 Safety
The drive system must only be operated by qualified and authorized
personnel, i.e. personnel who are familiar with the operation of the drive
system and the hazards involved.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 8-1 (12)
259
原図 3N4-S4293202
Chapter 8 - Local operation ABB
MAIN SUPPLY
OFF ON
2 3
ALARM EMERGENCY OFF
FAULT RESET
4 5
GROUND. SWITCH
UNLOCKED
EMERGENCY OFF
8-2 (12) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
260
原図 3N4-S4293202
ABB Chapter 8 - Local operation
Legend
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 8-3 (12)
261
原図 3N4-S4293202
Chapter 8 - Local operation ABB
8.4 Status messages
See the status words in the Signal and parameter table of the drive for
information on other status messages, such as fault status messages in
particular.
NotReadyOn means that the DC link cannot be charged and the drive
Not ready on cannot be connected to the main power supply, i.e. the main circuit
breaker cannot be closed. The status message is displayed, e.g. when the
doors of medium voltage compartments are still open, the grounding
switch of the drive is in the grounded position, or the motor starter of the
fan unit is switched off etc.
The status message signals that the drive is healthy and ready for the ON
Ready on command. The ON command initiates charging of the DC link capacitors
and closing of the main circuit breaker of the drive. Depending on the
control place, the command can either be sent from the higher-level
control system to the drive or be initiated by pressing the SUPPLY ON
pushbutton on the control compartment door.
The message ReadyRun tells the operator that the drive is energized and
Ready run ready for operation. As soon as the start command is initiated, the motor
is magnetized and the drive starts to modulate.
Stopping indicates that the drive has received a stop command and that
Stopping a ramp or coast stop has been initiated. The stopping mode depends on
the parameter setting. The status indication changes to ReadyRun when
the zero speed threshold is reached.
When a start command is given while the drive is stopping, the drive
resumes operation and the status indication changes to ReadyRef again.
The status message indicates that a fault condition has occurred that
Tripped requires a shutdown of the drive. The status message always alternates
8-4 (12) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
262
原図 3N4-S4293202
ABB Chapter 8 - Local operation
with the specific fault message. The type of shutdown depends on the fault
class the fault condition is assigned to in the drive software.
Not ready on
Ready-on conditions:
On command
Charging
DC link charges
Fan switches on
MCB closes
Ready run
Start command
Ready ref
Operation
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 8-5 (12)
263
原図 3N4-S4293202
Chapter 8 - Local operation ABB
8.4.3 Stop sequence
Operation
Ready ref
Stop command
Stopping
Ready run
Off command
MCB opens
DC link discharges
Fan switches off
after a delay
Ready on Actions:
Drive is grounded
Door with electro-mechanical lock
is released for opening
Auxiliary power supply is switched off
Not ready on
8-6 (12) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
264
原図 3N4-S4293202
ABB Chapter 8 - Local operation
Operation
Ready ref
Emergency-off command
MCB opens
INU stops to modulate
Speed coasts down
Not ready on
DANGER
Hazardous voltages!
All covers must be screwed in place to prevent unintentional contact with
energized components.
When the drive system is put into service after it has been commissioned,
or after it has been taken out of service for a longer period, check the drive
according to the following list:
• Check that no tools and foreign objects are left inside the cabinet.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 8-7 (12)
265
原図 3N4-S4293202
Chapter 8 - Local operation ABB
• Check that all auxiliary power supplies from external sources are
switched on.
• Check that all internal circuit breakers of the drive are closed.
• Check that all covers are mounted and the doors are closed, locked
and / or bolted.
• Check that the grounding switch is in position not grounded.
• Check that the MCB is in operating position.
• Check that there is no run interlock active.
8-8 (12) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
266
原図 3N4-S4293202
ABB Chapter 8 - Local operation
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 8-9 (12)
267
原図 3N4-S4293202
Chapter 8 - Local operation ABB
6 Start the motor.
When the motor has been magnetized, the motor speed ramps up to
the setpoint.
While the motor is accelerating, the run status indication on the
display blinks. When the motor speed has reached the setpoint, the
run status indication lights up permanently.
The display shows ReadyRef to indicate that the drive system is
operating:
8.6 Stopping
Press the stop key on the CDP control panel.
The motor stops according to the preset stop function and the drive stops
modulating. While the motor stops, the status line of the display shows
ReadyRef. The run status indication blinks during the stop sequence.
Just before the motor will come to a standstill, the CDP control panel
displays shortly the message Stopping.
8-10 (12) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
268
原図 3N4-S4293202
ABB Chapter 8 - Local operation
When the drive has stopped modulating, the CDP control panel displays
ReadyRun:
As long as the MCB has not been opened, the motor can be started again.
8.7 Emergency-off
8.7.1 Function
The drive is equipped with a hard-wired emergency-off circuit. When an
emergency situation occurs during operation, this safety feature ensures
that the drive system can be disconnected without delay from the main
power supply. When the emergency-off pushbutton has been pressed
while the drive is at standstill, the main power supply cannot be connected
to the drive, hence the drive cannot be started up.
The emergency-off pushbutton of the drive is part of the operator control
panel (see Figure 8-1) and features a latching switch action.
Note: Pressing the emergency-off pushbutton does not disconnect the
auxiliary power supply from the drive.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 8-11 (12)
269
原図 3N4-S4293202
Chapter 8 - Local operation ABB
• The drive system coasts down.
• The DC link of the drive discharges.
• The status line of the CDP control panel alternates between the
message EmergencyOff, NotReadyOn.
Now, the main power supply can be connected to the drive again and the
drive system can be started up.
8-12 (12) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
270
原図 3N4-S4293202
ABB
Chapter 9 - CDP control panel
9.1 Overview
Note: The panel messages and parameter settings used in this chapter
are typical examples to illustrate the related instructions and display
functions and may therefore differ from the actual messages and
parameter settings in your drive.
3
2 4
7
5 8
6
9 11
10
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 9-1 (22)
271
原図 3N4-S4293202
Chapter 9 - CDP control panel ABB
The CDP control panel can be attached to or detached from the drive
without having to switch off the auxiliary power supply first.
Using the CDP control panel it is possible to
• enter start-up data,
• control the drive with a reference value and start, stop and direction
commands,
• display actual values (three values can be read simultaneously),
• display and adjust parameters,
• display information on the most recent forty fault events,
• upload and download complete parameter sets from one drive to
another.
........
9-2 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
272
原図 3N4-S4293202
ABB Chapter 9 - CDP control panel
After 2-3 seconds, information on the drive (1, 2), the application software
in use (3), and the drive identification (4) is displayed.
After another few seconds, the display changes to the actual signal
display mode. The status line of the display alternates between DCGnd
NOpen, NotReadyOn.
9.5.1 Overview
Two kinds of displays can be selected in the actual signal display mode:
• Actual signal display
• Fault history display
The actual signal display appears first when the actual signal display
mode has been selected. However, when the drive is in a fault condition,
the fault display will be shown instead.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 9-3 (22)
273
原図 3N4-S4293202
Chapter 9 - CDP control panel ABB
The actual signal display is used to monitor the drive without interfering
its operation. Three selectable actual values are shown continuously on
the display.
The CDP control panel will automatically return to the actual signal
display mode from other modes within one minute when no keys are
pressed (exceptions: status display and common reference display
when in drive selection and fault display mode).
Actual values
See Signal and parameter table for the complete list of selectable actual
signals.
1 Status line
2 Actual signal names and values
3 Selects the function mode
4 Selects actual signals and faults
1 L -> 600.0 rpm 1
StateINU ReadyOn 5 Scrolls through signal and fault
MOTOR SP 0.00 rpm 2 messages
POWER 0.0 kW 6 Enters the selection mode
Acknowledges the selection
3
4
5
6
9-4 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
274
原図 3N4-S4293202
ABB Chapter 9 - CDP control panel
Fault memory The fault memory includes information on the 64 most recent fault events
that occurred in the drive. The name of the fault and the actual time are
displayed. The procedure for selecting and clearing the fault history is
described in section 9.5.5 Displaying and resetting an active fault.
When a fault or warning is generated in the drive, the message will be
displayed immediately, except when in drive selection mode.
Changing from the fault display mode to other display modes is possible
without resetting the fault first. When no keys are pressed, the fault or
warning text is displayed as long as the fault is pending.
Selecting the actual The actual signal display mode is selected by pressing the ACT key.
signal display
Toggle between actual When in actual signal display mode, the fast up/down keys allow to
signal display and fault toggle between actual signal display and fault history display.
history
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 9-5 (22)
275
原図 3N4-S4293202
Chapter 9 - CDP control panel ABB
9.5.2 Displaying three actual signals
1 To display the full name of three actual signals, press and hold the
ACT key:
3 To enter the actual signal selection function, press the ENTER key:
9-6 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
276
原図 3N4-S4293202
ABB Chapter 9 - CDP control panel
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 9-7 (22)
277
原図 3N4-S4293202
Chapter 9 - CDP control panel ABB
7 To cancel the selection and keep the original selection, press any of
the mode keys:
9-8 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
278
原図 3N4-S4293202
ABB Chapter 9 - CDP control panel
2 To enter the fault history display, press any of the fast navigation
keys:
H MIN S
5 To return to the actual signal display mode, press any of the fast
navigation keys:
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 9-9 (22)
279
原図 3N4-S4293202
Chapter 9 - CDP control panel ABB
9-10 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
280
原図 3N4-S4293202
ABB Chapter 9 - CDP control panel
NOTICE
Running the drive system with incorrect data can result in improper oper-
ation, reduction of control accuracy and damage of equipment. Do not
change any parameter, if the meaning of the parameter and the effects of
the change are not fully understood.
9.6.1 Overview
Parameters allow the drive to be configured and set-up specifically for an
application. Parameters are organized in functional groups. All control
functions are represented by a parameter group and can be activated and
set-up individually by the parameter mode.
Group 18 Utility .
Group 20 Limits .
See Signal and parameter table for further information on the parameters,
their settings and functions.
When the parameter mode is entered for the first time after the auxiliary
voltage of the drive has been switched on, the display will show the first
parameter of parameter group 11. The next time the parameter mode is
entered, the previously selected parameter is shown.
Some parameter values cannot be changed while the drive is running. If
tried, the following warning will be displayed:
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 9-11 (22)
281
原図 3N4-S4293202
Chapter 9 - CDP control panel ABB
** WARNING **
WRITE ACCESS DENIED
PARAMETER SETTING
NOT POSSIBLE
Legend
1 Status line
2 Group number and name
3 Parameter number and name
1 L -> 600.0 rpm 1 4 Parameter value
77 SYSTEM CONFIG 2 5 Selects the parameter mode
01 INU IdentifySel 3 6 Selects the parameter number
INU1 (MASTER) 4 and name
7 Selects the parameter value
5 8 Enters change mode
Acknowledges the selection
6
7
8
9.6.2 Procedure
1 To enter the parameter mode, press the PAR key:
9-12 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
282
原図 3N4-S4293202
ABB Chapter 9 - CDP control panel
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 9-13 (22)
283
原図 3N4-S4293202
Chapter 9 - CDP control panel ABB
7 To cancel the setting and keep the original selection, press any of the
mode keys. The selected CDP control panel mode is entered.
9-14 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
284
原図 3N4-S4293202
ABB Chapter 9 - CDP control panel
9.7.1 Overview
The function mode is used to set the display contrast.
Legend
1 Status line
2 Selectable functions
3 Selects the function mode
4 Selects the line
1 L -> 0.0 rpm 1
UPLOAD <= <= 5 Acknowledges the selection
DOWNLOAD => => 2
CONTRAST 4
4
5
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 9-15 (22)
285
原図 3N4-S4293202
Chapter 9 - CDP control panel ABB
9.7.2 Procedure
1 To enter the function mode, press the FUNC key:
9-16 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
286
原図 3N4-S4293202
ABB Chapter 9 - CDP control panel
6 To cancel the setting and keep the original selection, press any of the
mode keys. The selected CDP control panel mode is entered:
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 9-17 (22)
287
原図 3N4-S4293202
Chapter 9 - CDP control panel ABB
9.8 Operational commands
Local control When the CDP control panel is switched to local, operation via the
pushbuttons on the control compartment door and the CDP control panel
is possible. Control commands from remote have no effect.
Remote control When the CDP control panel is switched to remote, the pushbuttons on
the control compartment door and the operational keys of the CDP control
panel are disabled. Operational commands and reference value from a
remote control station are transmitted via fieldbus or remote I/O to the
drive.The CDP control panel can also be used as a remote control place
if selected (see section Selecting remote).
Selecting local To select local control, press the LOC / REM key. The local control location
is indicated by the letter L.
1 L 600.0 rpm 0
StateINU ReadyRun
MOTOR SP 0.00 rpm
POWER 0.0 kW
9-18 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
288
原図 3N4-S4293202
ABB Chapter 9 - CDP control panel
Selecting remote To select remote control, press the LOC / REM key. The remote control
mode is normally indicated by a blank (see arrow).
1 600.0 rpm 0
StateINU ReadyRun
MOTOR SP 0.00 rpm
POWER 0.0 kW
The letter R (see arrow) is indicated if the CDP control panel is used as a
remote control place. In this case parameter 11.01 or 11.02 or 12.03 or
12.06 is set to KEYPAD. The START/STOP command can then be given
and the reference value can be set from the CDP control panel.
1 R 600.0 rpm 0
StateINU ReadyRun
MOTOR SP 0.00 rpm
POWER 0.0 kW
Disable lock function The lock function is disabled if the parameter 16.04 is set to 1 (= OPEN).
Switching from local to remote and vice versa is possible.
Enable lock function The lock function is enabled if the parameter 16.04 is set to 2 (= LOCKED).
In this case local cannot be selected on the CDP control panel. However,
the CDP control panel or the DriveWindow PC remains in local mode if
they had already been in local mode when the parameter was set to
locked, until the CDP control panel is switched to remote.
The letter L remains on the display until the LOC / REM key has been
pressed.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 9-19 (22)
289
原図 3N4-S4293202
Chapter 9 - CDP control panel ABB
9.8.3 Setting the direction of rotation
The direction of rotation is selected using the forward (I) or reverse (0)
key of the CDP control panel. Both keys can be used if the CDP control
panel is in local mode. The function is released with parameter 11.03
DIRECTION (REQUEST).
9-20 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
290
原図 3N4-S4293202
ABB Chapter 9 - CDP control panel
4 To exit the setpoint setting mode, press any of the mode keys:
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 9-21 (22)
291
原図 3N4-S4293202
Chapter 9 - CDP control panel ABB
9.8.5 Run status indication
The run status indication on the display (see arrows) changes depending
on the state the INU is in:
9-22 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
292
原図 3N4-S4293202
ABB
Chapter 10 - Troubleshooting and maintenance
10.1.5 Logbook
It is recommended to record all troubleshooting and maintenance work in
a logbook including:
• Date and time
• Detailed description
See Spare parts list for information on types and identification codes.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 10-1 (22)
293
原図 3N4-S4293202
Chapter 10 - Troubleshooting and maintenance ABB
10.2 Identifying electrical equipment
10-2 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
294
原図 3N4-S4293202
ABB Chapter 10 - Troubleshooting and maintenance
10.3 Troubleshooting
MAIN SUPPLY
OFF ON
The display message can be saved and viewed in the fault logger of the
drive when a PC with the DriveWindow, DriveDebug or DriveMonitorTM
tool is connected to the drive. The fault logger can also be called up on the
CDP control panel.
Alarm / warning An alarm does not shut down the drive. However, a persisting alarm
condition can often lead to a fault if the condition causing the alarm is not
corrected. An alarm cannot be reset manually. The alarm message will be
deleted from the display as soon as the alarm condition has been
corrected.
Fault A fault always shuts down the drive. The type of shutdown depends on the
origin of the fault.
Depending on the type of fault, the MCB is opened by the drive or stays
closed:
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 10-3 (22)
295
原図 3N4-S4293202
Chapter 10 - Troubleshooting and maintenance ABB
• Class 1 faults (FC 1) open the MCB
• Class 2 faults (FC 2) do not open the MCB
Since the MCB is controlled and monitored entirely by the drive, no
external opening command must be given to the MCB when a fault
condition occurs.
In general, a fault condition must be corrected and the fault be manually
reset before the drive can be started again.
Alarm / fault handling In the event of an alarm or a fault, a specific message is saved in the fault
logger of the drive. Information on the 64 most recent fault and alarm
events are saved.
The faults are entered into the fault buffer as they occur and are
numbered; the last fault entered always has number 1 assigned to it and
the first fault always has the highest number in the fault buffer.
Information of the fault classification (e.g. FC 1 or FC 2) is also saved
when the first fault of the fault class is active. Date and time stamps
facilitate fault tracing, especially when a fault leads to several subsequent
faults.
Example:
1. +Fault AMC: Fault Class 2 2008-01-08 16:58:24.3770
2. +Fault PPCS Communication 2008-01-08 16:58:24.3760
3. +Fault AMC: Fault Class 1 2008-01-08 16:56:02.1170
4. +Fault DC Undervoltage 2008-01-08 16:56:02.1170
In the above example:
• 4. +Fault DC Undervoltage is the reason for the failure of the drive,
as it occurred first.
• The message 3. +Fault AMC: Fault Class 1 classifies the fault.
• The message 2. +Fault PPCS Communication occurred 2 min 22
sec later than the first fault due to another fault in the drive.
• The message 1. +Fault AMC: Fault Class 2 informs about the
pending fault class.
See Signal and parameter table for further information on alarms and
faults.
10-4 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
296
原図 3N4-S4293202
ABB Chapter 10 - Troubleshooting and maintenance
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 10-5 (22)
297
原図 3N4-S4293202
Chapter 10 - Troubleshooting and maintenance ABB
10.4 Malfunctioning grounding switch
CAUTION
If the control circuit of the grounding switch malfunctions, it is possible that
the grounding switch can be closed while the DC link is still charged.
Closing the switch will short-circuit the DC capacitors. The short-circuit will
manifest itself in a loud bang. To prevent temporary minor hearing impair-
ment, follow the instructions below.
When the DC link of the drive has been de-energized, the lamp
GROUNDING SWITCH UNLOCKED lights up to indicate that the
grounding switch is released and can be turned to the grounded position.
If the lamp does not light up or there is reason to assume that the
grounding circuit is malfunctioning, proceed as follows:
1 Do not try with force to turn the grounding switch in any direction.
The handle and / or the switch could be damaged if tried.
2 Verify that the MCB is in the open position.
3 Check the drive status on the CDP control panel.
The message ReadyOn is displayed when the DC link of the drive
has been discharged.
7 Call ABB service if the cause for the malfunctioning grounding switch
cannot be rectified.
See section General information on manual and equipment for
address.
10-6 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
298
原図 3N4-S4293202
ABB Chapter 10 - Troubleshooting and maintenance
1 2 3
Meaning of the LEDs The green LED (see arrow in 3) is illuminated when the control voltage has
been switched on.
The red LED is not used.
Weight 0.2 kg
Communication with The CDP control panel (1) is connected to the AMC circuit board via an
AMC circuit board RS485-Interface.
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 10-7 (22)
299
原図 3N4-S4293202
Chapter 10 - Troubleshooting and maintenance ABB
10-8 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
300
原図 3N4-S4293202
ABB Chapter 10 - Troubleshooting and maintenance
F R
M P
T1 T2
S3 S1
S4 S0
P green Supply OK
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 10-9 (22)
301
原図 3N4-S4293202
Chapter 10 - Troubleshooting and maintenance ABB
10.6.2 S800 I/O - TB820 bus modem
Modem address The TB820 bus modem has a unique cluster address that identifies the
module in the software and links it to a parameter.
The address is set with the rotary switch on the module (see arrow in
Figure 10-2). The factory set value must not be changed.
10-10 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
302
原図 3N4-S4293202
ABB Chapter 10 - Troubleshooting and maintenance
See the Appendix D - Wiring diagrams or the Parts list to identify the serial
communication interface in your drive and select the appropriate manual
from the list below for further information:
• AF 100 fieldbus - NAFA-01 installation and start-up guide
• Ethernet - user’s manual ethernet adapter module NETA-01
• Modbus - NMBA-01 installation and start-up guide
• Profibus - NPBA-12 installation and start-up guide
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 10-11 (22)
303
原図 3N4-S4293202
Chapter 10 - Troubleshooting and maintenance ABB
10.7 Maintenance
10.7.2 Safety
DANGER
Hazardous voltages!
Before starting to work on the drive, make sure that:
• the main and auxiliary power supply to the drive is switched off,
locked out, and tagged out,
• the drive is dead,
• safety ground connections are in place,
• personal protective equipment is provided and used when required,
• everyone involved is informed.
Before energizing the drive again, make sure that:
• all foreign objects are removed from the drive,
• all internal and external covers are securely fastened and all doors
are closed, locked and / or bolted.
10-12 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
304
原図 3N4-S4293202
ABB Chapter 10 - Troubleshooting and maintenance
DANGER
Hazardous voltages!
When maintenance on the drive is carried out that includes the removal of
phase cells, the connection of grounding equipment at the appropriate
locations is a must. The grounding equipment ensures that hazardous
voltages cannot be fed into the drive neither from the main power supply
nor the motor.
NOTICE
When working on the drive ensure that foreign matter cannot enter the
cabinet. Close the doors and cover openings completely when work is
discontinued. Any foreign matter which accidentally dropped into the
cabinet must be retrieved. Metallic dust in particular could cause malfunc-
tion and damage when the drive is energized.
Procedure 1 Check that the CDP control panel is connected to the INU.
2 Set the CDP control panel to LOCAL mode.
4 Press the SUPPLY OFF pushbutton to disconnect the drive from the
main power supply. The following takes place:
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 10-13 (22)
305
原図 3N4-S4293202
Chapter 10 - Troubleshooting and maintenance ABB
• The MCB opens.
• The DC link discharges.
While the DC link discharges, the display shows OffSeqOn:
10-14 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
306
原図 3N4-S4293202
ABB Chapter 10 - Troubleshooting and maintenance
7 Switch off and lockout all auxiliary voltages from external sources.
8 Verify that the drive system is de-energized.
9 Ground the drive.
Depending on the delivery, the cabinet is equipped with ground ball
studs for the connection of grounding sets.
Legend
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 10-15 (22)
307
原図 3N4-S4293202
Chapter 10 - Troubleshooting and maintenance ABB
10 Connect the clamps of the grounding set in the following sequence:
1 Connect the enclosure grounding clamp (2 in Figure 10-4) to the
ground ball stud of the cabinet’s grounding frame.
2 Use the telescopic insulating pole to connect the busbar
grounding clamps (see 3 in Figure 10-4) to the ground ball studs
of the busbars, and to tighten each connection.
The drive is now dead, and safe access is possible.
See Rating label of the drive for information on the permitted air
temperature range.
• Dust built-up inside the drive room and inside the drive
• Signs for overheated components, wires, cables or busbars
• Corrosion on circuit boards, connectors or busbars
• Appropriate fastening of cables and wires and connections of cable
shields and screens
See Chapter 6 - Electrical installation if further information is required.
• Integrity of cable insulation
The outer cable sheath must not be damaged.
• Correct type of signal and power cables
See applicable cable specifications for reference.
10.7.5 Cleaning
Dust on electrical components and wiring can cause malfunction and
damage the components. Dust and moisture can build up in loose
connections and cause loss of low-level signals.
For these reasons, the cabinet should be checked regularly and cleaned
if necessary.
When cleaning the drive cabinet, mind the following:
• Cover equipment or assemblies to prevent dirt falling into them.
• The drive contains components which are sensitive to electrostatic
discharge. Therefore, take electrostatic-sensitive precautions and
use suitable tools when cleaning circuit boards and assemblies that
are sensitive to electrostatic discharge.
10-16 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
308
原図 3N4-S4293202
ABB Chapter 10 - Troubleshooting and maintenance
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 10-17 (22)
309
原図 3N4-S4293202
Chapter 10 - Troubleshooting and maintenance ABB
10.7.7 Filter mats
Location The filter mats are located behind all air intake panels of the drive and the
integrated transformer.
Checking, Check the filter mats regularly. The intervals in which the mats are
replacement checked depend on the cleanliness of the cooling air.
indications The filter mats are monitored by pressure sensors. When the mats are
clogging and the pressure drop reaches the specified final pressure loss,
the message Conv1CoolAirFilter comes up on the CDP control panel
and the alarm/fault lamp lights up on the control compartment door.
Removing a filter mat When a filter mat has been removed, do not discontinue work for a longer
period to prevent foreign matter entering the cabinet.
To remove a filter mat (1), remove the louvered panel (2) of the
corresponding door. The panels are secured to the cabinet by Phillips-
head screws(3).
.
1 3
When removing a filter mat, roll down the filter mat beginning at the top.
Cleaning The filter mats can be cleaned using compressed air or a vacuum cleaner.
Cleaning should always be carried out away from the converter to prevent
dust entering the cabinet.
10-18 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
310
原図 3N4-S4293202
ABB Chapter 10 - Troubleshooting and maintenance
Filter class Use only replacement filter mats of the same filter class as the original
filter mat:
• G3 (EN779)
B C D
Drive power A B C D
3.5 MVA 230 x 738 1839 x 648 1839 x 698 1839 x 277
A B C
Transformer power A B C
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 10-19 (22)
311
原図 3N4-S4293202
Chapter 10 - Troubleshooting and maintenance ABB
10.7.8 Replacing a fan
Legend
1 Fine-meshed screen
2 Mounting plate 1
3 Impeller and motor
4 Nozzle
5 Fan housing
6 Motor cable connector
2
Procedure 1 Disconnect all power supplies to the drive and ground the drive.
See section 10.7.3 De-energizing the drive if further information is
required.
Switch off the motor starter of the fan unit to isolate the fan unit from
the auxiliary power supply.
10-20 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
312
原図 3N4-S4293202
ABB Chapter 10 - Troubleshooting and maintenance
4 Disconnect the power supply cable inside the terminal box of the fan
motor (see arrow).
ACS 5000 A User’s manual 3BHS221906 ZAB E01 Rev. B 10-21 (22)
313
原図 3N4-S4293202
Chapter 10 - Troubleshooting and maintenance ABB
5 Unscrew the locknut of the cable gland and pull the power supply
cable through the cable gland (see arrow).
6 Lift off the mounting plate with the impeller and the motor attached to
it.
7 Remove the eight fixing screws of the motor to separate the motor-
impeller-assembly from the mounting plate.
8 Replace the motor with the impeller and continue in reverse order of
removal to assemble the unit again.
10-22 (22) 3BHS221906 ZAB E01 Rev. B ACS 5000 A User’s manual
314
原図 3N4-S4293202
ABB
Maintenance schedule
The maintenance schedule applies to all air-cooled and water-cooled medium voltage drives. Please
note the maintenance items in the schedule which only apply to particular drives.
The recommended intervals for maintenance and component replacement are based on the normal
operational conditions of the drive. The drive should be checked at least every two years by qualified
personnel whose recommendations should be followed. Depending on the actual condition of the
drive, the maintenance work can be carried out before or after the recommended interval.
A Applies to ACS 1000i, ACS 1000A, ACS 1000W, ACS 2000, ACS 5000A, ACS 5000W, ACS 6000, MEGADRIVE-LCI
B Applies to ACS 1000i, ACS 1000A, ACS 1000W, ACS 2000, ACS 5000A, ACS 5000W
C Applies to all water-cooled drives
D Applies only to ACS 1000i, ACS 1000A, ACS 1000W
1 Air filters can be replaced or cleaned. The decision to replace or clean a filter depends on the condition of the filter.
© Copyright 2009 ABB. All rights reserved. Specifications subject to change without notice. 3BHS221906 ZAB E01 Rev. B.
ABB Switzerland Ltd
Medium Voltage Drives
CH-5300 Turgi
Phone: +41 58 589 27 95
Fax: +41 58 589 29 84
E-Mail: mvdrives@ch.abb.com
www.abb.com/drives
318
原図 3N4-S4293202