Professional Documents
Culture Documents
Wd-P-O-2210-02276 - Stack Monitoring Report
Wd-P-O-2210-02276 - Stack Monitoring Report
Page1
TEST REPORT
PROJECT No.: WD-P-O-2210-02234
SUBMITTED TO
SUBMITTED BY
…………………………………………
Ishrar Hussain
Manager
Environment Division (UAE) Page2
TEST REPORT
PROJECT No.: WD-P-O-2210-02234
1.0 INTRODUCTION
Further to the request received from Visco Lubes LLC, Wimpey Laboratories LLC representatives
visited their site in Al Jarf -02 Area, Ajman and commenced testing of Stack Emission Monitoring based
on standard procedures as reflected in our proposal. The onsite evidences and results of analysis are
described in detail as follows.
2.0 OBJECTIVE
The Team of Wimpey Laboratories LLC had been on site for the collection of flue gas sample to
measurement of their Boiler Exhaust emission contamination from stack. Technical team of Wimpey fixes
a schedule of monitoring with the plant representative and conducts the monitoring as per the given
schedule.
LIMIT AS PER
PARAMETER METHOD UNIT RESULT
FEA*
TOTAL SUSPENDED PARTICULATE [TSP] USEPA 5: 2019 mg/Nm3 13.13 250 iii
SULPHUR DIOXIDE [SO2] USEPA 06: 2017 mg/Nm3 16.35 500 iii
OXIDES OF NITROGEN [NOX] USEPA 7E: 2018 mg/Nm3 142.37 500 iii
CARBON MONOXIDE [CO] USEPA 10: 2017 mg/Nm3 56.71 500 iii
# This parameter is not covered in EIAC scope
*Limit as per Cabinet Decree (12) of 2006, Federal Environmental Agency of UAE, Regarding Regulation Concerning Protection of Air from Pollution, Annexure – 02,
“Maximum Allowable Emission Limits of Air Pollutants Emitted from Hydrocarbon Fuel Combustion Sources”.
Page4